HomeMy WebLinkAboutP-701-SCHEDULES---PLUMBING-Rev.0PLUMBING SYMBOLS
ALL SYMBOLS SHOWN MAY NOT APPEAR IN ALL DRAWINGS
SYMBOLS ARE SHOWN SCHEMATIC AND MAY NOT BE TO SCALE.
SYMBOL
DESCRIPTION
EXISTING PIPING/FIXTURES/EQUIPMENT TO REMAIN
EXISTING PIPING/FIXTURES)EQUIPMENT TO BE REMOVED
-.-
DOMESTIC COLD WATER PIPING
DOMESTIC HOT WATER PIPING
--
DOMESTIC HOT WATER RETURN PIPING
-RCW-
RELOCATED DOMESTIC COLD WATER PIPING
SCW-
SOFTENED DOMESTIC COLDWATER PIPING
PIPING UP
PIPING DOWN
F
WET -PIPE FIRE PROTECTION PIPING
DF
DRY -PIPE FIRE PROTECTION PIPING
- G -
NATURAL GAS PIPING
LPG
LIQUEFIED PETROLEUM GAS
VV
WATER SERVICE
DIRECTION OF FLOW
GATE VALVE
a
BUTTERFLVVALVE
BALL VALVE
GLOBAL VALVE
TEMPERATURE AND PRESSURE RELEIF VALVE
(
GAS COCK
PRESSURE REGULATING VALVE
t8w
-
CHECKVALVE
HYDRAULIC SHOCK ARRESTOR
UNION
HOSE BIBB OR HYDRANT
OH
THERMOMETER
-D-
INDIRECT WASTE PIPING
-SS-
SANITARY SEWER PIPING
SANITARY VENT PIPING
-Rn
PRIMARY ROOF DRAIN LEADER
OD
OVERFLOW ROOF DRAIN LEADER
-SD
STORM DRAIN PIPING BELOW GRADE
-SSD-
SUBSOIL DRAIN PIPING
-AW-
ACIDWASTEPIPING
----AV----
ACID VENT PIPING
GW
GREASE WASTE PIPING
P-TRAP
FLOOR DRAIN WITH P-TRAP
FLOOR SINK WITH P-TRAP
HUB DRAIN WITH P-TRAP
HCUI
FLOOR CLEANOUT OR GRADE CLEANOUT
TI uwoCLEANOUT
WCO
OR WALL CLEANOUT
-TP-
TRAP PRIMER SUPPLY
-MC
MEDICAL GAS PIPING
-MO-
MEDICAL OXYGEN PIPING
®
MEDICAL GAS VALVE BOX OR MEDICAL GAS OUTLET
MEDICAL GAS PIPING DOWN IN WALL
MEDICAL GAS RISERS OR PIPING UP IN WALL
B
CONNECT TO EXISTING
PLUMBING ABBREVIATIONS
AFF ABOVE FINISHED FLOOR Hi HOT WATER RETURN
AFG ABOVE FINISHED GRADE OD OVERFLOW DRAIN
A/C ABOVE CEILING CON OVERFLOW DOWNSPOUT NOZZLE
B/F BELOW FLOOR FIRM PRESSURE REDUCING VALVE
BFF BELOW FINISHED FLOOR RD ROOF DRAIN
BIG BELOW GRADE SO STORM DRAIN
BRF BELOW RAISED FLOOR SS SANITARVSEWER
CO CLEANOUT SV SANITARVVENT
CW COLD WATER TP TRAP PRIMER
DCO DOUBLE CLEANOUT VTR VENT THRU ROOF
DS DOWNSPOUT (E) EXISTING TO REMAIN
FCO FLOOR CLEANOUT (D) EXISTING TO BE RELOCATED
FD FLOOR DRAIN (R) RELOCATED FROM EXISTING
FDC FIRE DEPARTMENT CONNECTION
FS FLOOR SINK
GCO GRADE CLEANOUT
GC GENERAL CONTRACTOR
GW GREASE WASTE
HW HOT WATER
RELEASED FOR CONSTRUCTION
Subject to compliance with all regulations
of State and meal Codes
City of Camel
DATE: 06/07/19
PLUMBING FIXTURE SCHEDULE
WC1
WATER CLOSET (ACCESSIBLEH PUBLIC & STAFF RESTROOMS(FLOOR MOUNTED FLUSH VALVE)
PROFLO MODEL #PF1723WH HIGH EFFICIENCY FLUSH VALVE W/ SIPHON JET FLUSHING, 17" HIGH ADA BOWL, 1-12" TOP
INLET SPUD AND 11-1)2" X 13" WATER SURFACE. ZURN MODEL Z6000 MODEL FLUSH VALVE W/ 1.6 GALLON LOW
CONSUMPTION FLUSH, SWEAT SOLDER KIT AND VAST WALL FLANGE. BEMIS COMMERCIAL EXTRA HEAVY DUTY PLASTIC
TOILET SEAT MODEL #1655CT(WHITE), OPEN FRONT LESS COVER. PROFLOW PFWR HEAVY DUTY WAX BOWL RING.
PROFLO PFC2110RWLA CLOSET BOLT KIT.
LI
WALL HUNG LAVATORY ADA (PATIENT)
PROFLO MODEL #PF541419"X17" WALL HUNG LAVATORY, ADA COMPLIANT, ANTI SPLASH RIM, WALL MOUNT BRACKET
INCLUDED, CONCEALED FRONT OVERFLOW, WITH 3 FAUCET HOLES, 4" CENTERSET LAVATORV(WHITE). CHICAGO MODEL #
895S17GNBAE29VAB DECK MOUNTER LAVATORY FAUCET W/ 4" FIXED CENTERS AND 4"WRIST BLADES. INCLUDE OFFSET
LAVATORY GRID DRAIN ANGLE STOPS, LEAD FREE FLEXIBLE CONNECTORS, ESCUTCHEONS, WATER SAVER TRAP PRIMER
AND TRAP COVER.
L2
WALL HUNG LAVATORY (PUBLIC)
PROFLO MODEL #PF5414 19"X17" WALL HUNG LAVATORY, ADA COMPLIANT, ANTI SPLASH RIM, WALL MOUNT BRACKET
INCLUDED, CONCEALED FRONT OVERFLOW, WITH 1 FAUCET HOLE, 4" CENTERSET LAVATORV(WHITE). SLOAN MODEL #SF-
2150 ELECTRONIC SENSOR FAUCET, BATTERY OPERATED, 0.5GPM W/ MECHANICAL MIXING VALVE. INCLUDE OFFSET
LAVATORY GRID DRAIN, ANGLE STOPS, FLEXIBLE CONNECTORS, ESCUTCHEONS, WATER SAVER TRAP PRIMER AND TRAP
COVER.
S1
(EXAM SINKS, EMERGENCY TREATMENT SINK, NOURISHMENT SINK, SUPPLIES SINK)
PROFLO MODEL #PFSR171963 STAINLESS STEEL SINK W/ 3 FAUCET HOLES, 4" CENTERS' CHICAGO MODEL #786E29-
245ABCP DECK MOUNTED FAUCET WITH 2.2 GPM NONAERATING OUTLET WITH 4" VANDAL PROOF WRISTBLADES'
MCGUIRE 8912C P-TRAP AND MCGUIRE BV2165 SUPPLIES INCLUDE FLEXIBLE CONNECTORS.
82
(LAB SINK, SOILED UTILITY SINK)
PROFORM PFS42521553C STAINLES STEEL SINK W/ 3 FAUCET HOLES, 4" CENTERS ° CHICAGO MODEL #786E29-245ABCP
DECK MOUNTED FAUCET WITH 2.2 GPM NON -AERATING OUTLET WITH 4" VANDAL PROOF WRISTBLADES'MCGUIRE 8912C
P-TRAP, MCGUIRE BV2165 SUPPLIES. INCLUDE FLEXIBLE CONNECTORS.
S3
(BREAK ROOM SINK)
ELKAY #LRADQ19196519"X19", 18 GAUGE STAINLESS STEEL SINGLE COMPARTMENT SINK DRAIN CENTERED IN REAR, 8"
CENTERS, 3 HOLE PUNCH *PROFLO MODEL #PFXC4111 SINGLE HANDLE KITCHEN FAUCET W/ SPRAYER, 1.5 GPM.
MCGUIRE MODEL#H-2165 SUPPLY KIT WITH CHROME PLATED ANGLE STOP WITH ROUND W HEEL HANDLES, TWO 12"
FLEXIBLE RISERS AND TWO CRHOME PLATED WALL ESCUTCHEONS
McGUIRE MODEL#8912 ADJUSTABLE CHROME PLATED P-TRAP WITH SET SCREW, ESCUTCHEON AND CLEANOUT PLUG,
MCGUIRE MODEL #151 BRASS BASKET STRAINER.
S4
(POC LAB)
ELKAY #DLR19191 OPD 18 GAUGE STAINLESS STEEL SINGLE COMPARTMENT SINK DRAIN CENTERED IN REAR, 8" CENTERS,
3 HOLE PUNCH' CHICAGO MODEL #786-E29-245ABCP DECK MOUNTED FAUCET WITH 2.2 GPM NON -AERATING OUTLET
WITH 4" 4" VANDAL PROOF WRISTBLADES' MCGUIRE HD1151 W C GRID STRAINER, MCGUIRE 8912C P-TRAP, MCGUIRE
BV2165 SUPPLIES.
SHi
REFER ARCHITECTURAL DRAWINGS FOR SHOWER ENCLOSURE SPECIFICATIONS' DELTA MODEL#DT13H3331.5GPM
SHOWER HEAD, SUPPLY ELBOW WITH WALL FLANGE, 24" SLIDE BAR AND 60" HOSE WITH HAND HELD SHOWER.' JAY R
SMITH 2705AO5NB DRAIN'
CSS1
KOHLER "CAMERTON"K-12867 WALL HUNG CLINICAL SERVICE SINK, 21-1/2"Lx25"W,1-1/2" TOP SPUD, VITREOUS CHINA,
WHITE BLOW-OUT ACTION FLUSHING RIM, KOHLER K-13W LOOSE SINK STRAINER, KOHLER K-8935 STAINLESS STEEL RIM
GUARD. PROVIDE ZURN Z1217 SERVICE SINK SUPPORT SYSTEM WITH FITTING.. ZURN Z6017 MODEL EXPOSED AQUAFLUSH,
WITH HANDLE ON FRONT OF FLUSH VALVE. ZURN Z843D4LVB-PESX7-FT-YJ SERVICE SINK FAUCET, POLISHED CHROME -
PLATED CAST BRASS 8" SINK FAUCET WITH QUARTER -TURN CERAMIC DISC CARTRIDGES, 3/8" SHORT SWIVEL INLETS
PROVIDING ADJUSTABLE CENTERS FROM 7-1/4" TO 8-3/4", INTEGRAL SERVICE STOPS AND A 6" CENTERLINE CAST BRASS
PLAIN END SPOUT, PAIL HOOK, A FLUSH TUBE SPOUT BRACE AND WALL BRACE. UNIT SHALL BE FURNISHED WITH 4"
VANDAL -RESISTANT COLOR -CODED METAL WRIST BLADE HANDLES. BEDPAN WASHER: BURN Z877P2-LKS-HK3H2
POLISHED CHROME PLATED CAST BRASS WASHER WITH A QUARTER TURN CERAMIC DISC CARTRIDGE, A LOOSE KEY
STOP WITH A REMOVABLE BRASS TEE HANDLE AND AVANDAL RESISTANT COLOR -CODED METAL FOUR ARM HANDLE,
WITH VACUUM BREAKER, A HAND-HELD 4' VINYL SPRAY HOSE W ITH AN ANGLED INSULATED 6" HANDLE AND HOOK.
MS1
PROFLO MODEL PFMB 242424"X24" MOP SERVICE BASIN WITH INTEGRAL MOLDED DRAIN, ZURN MODEL#7843M1-RC
SERVICE FAUCET. PROVIDE WITH CHECKSTOP AND SERVICE STOPS, VACUUM BREAKER, LEVER HANDLES, WALL BRACE
AND AT GARDEN HOSE OUTLET, PROFLO MODEL #PF245 MOP HANGER, T&S B-0654 STAINLESS STEEL HOSE BRACKET AND
HOSE.
NFWH
ZURN Z1305 NON -FREE WALL HYDRANT WITH HOSE CONN ECTION, INTEGRAL VACU UM BREAKER, "IT HANDLE KEY AND
STAINLESS STEEL BOX WITH FULL 180 DEGREE COVER OPENING. INSTALL AT 24" AFF, UNLESS NOTED OTHERWISE.
FD1
JAY R SMITH"2005L-AOIBNB CAST IRON FLOOR DRAIN, TWO PIECE BODY WITH FLANGE, BOTTOM OUTLET, 6°ROUND NICKEL
BRONZE STRAINER AND TRAP PRIMER CONNECTION IN COMPLIANCE WITH ASSE 1072.
SH-2
DECONTAMINATION SHOWER(ADA COMPLAINT)
SHOWER VALVE WITH PRESSURE AND TEMPERATURE MIXING VALVE "POWERS ES♦'-F727 C727' VISGUARD' COMBINATION
VALVE W ITH BATTERY OPERATED LCD TEMPERATURE READOUT. 4 GPM CAPACITY WITH HIGH TEMP LIMIT STOP,
SPEAKMAN VS 123014 CHROME COMBINATION FIXED AND HAND-HELD SHOWER HEADS WITH VS-111 DIVERTER AND VS153
ADA SLIDE BAR, 60" CHROME HOSE. ASSE 1016 LISTED.
FS
WATTS DRAINAGE MODEL #FS-740 12"X8" SQUARE DEEP SANITARY FLOOR SINK WITH WHITE PROCELAIN ENAMEL COATED
INTERIOR, LOOSE SET PORCELAIN ENAMEL COATED CAST IRON GRATE, ALUMINUM DOME BOTTOM STRAINER, AND NO
HUB OUTLET, HALF GRATE UNLESS NOTED OTHERWISE.
TO
WATTS DEAD LEVEL DX PRE SLOPED TRENCH DRAIN SYSTEM WITH 12" WIDE X BY LONG DUCTILE IRON FRAME. LIVE
STABILIZED CHANNELS WITH 4" NO HUB OUTLET. SYSTEM SHALL BE FRAMED -ANCHORED, TO INCLUDED FRAME
CONNECTORS, GRATE LOCKDOWNS AND CONSTRUCTION COVERS. PROVIDE DUCTILE IRON GRATE.
EW
DECK MOUNTED EYE WASH. BRADLEY S19465EFW EYEWASH/DRENCH HOSE UNIT. DECK MOUNTED WITH UNDER
COUNTER HOSE GUIDE BRACKET. TMV MODEL BS19-200 THERMOSTATIC MIXING VALVE TO DELIVER TEPID WATER AS
PROVIDED BY ANSI Z358.1-2014 W/ WALL MOUNT BRACKET.
SS-1
ADVANCED TABCO MODEL#7-PS-62 HANDS FREE HAND SINK W ITH KNEE OPERATED VALVE. 18 GAUGE 304 STAIN LESS
STEEL WITH NO DROP COUNTERTOP EDGE, SINGLE KNEE VALVE AND LEAD FREE FAUCET INCLUDED. 31/2" BASKET
DRAIN INCLUDED.
WE-1
GUY GRAY GALVANIZED OUTLET BOX MODEL NO. FBI RECESSED IN WALL.
IMCB-1
GUY GRAV#MIEIAB ICE MAKER CONNECTION BOX.
CO
JR SMITH#4472-U STAINLESS STEEL CLEANOUTS, THREADED PLUG WITH COVER, VANDAL PROOF SCREWS.
SA
JAY R SMITH-5OOO SERIES HYDROTROL ALL STAINLESS STEEL SHOCK ABSORBERS INSTALLED AT ALL SOLENOID,
REMOTE OPERATED OR QUICK CLOSING VALVES AND AT EACH PLUMBING FIXTURE OR BATTERY OF PLUMBING
FIXTURES. INSTALL ON BOTH HOT AND COLD WATER BRANCH LINES IN AN UPRIGHT POSITION AS CLOSE AS POSSIBLE TO
THE VALVE OR VALVES BEING SERVED. SIZES AND LOCATIONS AS INDICATED ON DRAWINGS.
TP
J.R. SMITH PRIME-EZE#2698 WATER SAVER P-TRAP WITH TRAP PRIMER.
TG
J.R. SMITH TRAP GUARD#2692 QUAD CLOSE"STINK STOPPER"TRAP SEAL DEVICE.COMPLIANCE WITH ASSE 1072.
GENERAL NOTES:
1. VERIFY ALL MOUNTING HEIGHTS WITH ARCHITECTURAL DRAWINGS.
2. ALL LAVATORY P-TRAPS SHALL HAVE CLEANOUT PLUGS.
3. ALL PLUMBING FIXTURES MUST CONFORM TO CURRENT WATER CONSERVATION REGULATIONS.
4. ALL FIXTURES SHALL HAVE STANDARD FINISHES, UNLESS NOTED OTHERWISE.
5. PROVIDE TRAP PRIMERS FOR ALL FLOOR DRAINS, FLOOR SINKS AND INDIRECT CONNECTIONS UNLESS NOTED OTHERWISE.
6. PROVIDE ALL DRAIN COVERS, ESCUTCHEONS, AND MISCELLANEOUS TRIM ITEMS FORA NEAT APPEARANCE.
7. ALL MOUNTED HEIGHTS SHALL BE VERIFIED WITH THE ELEVATIONS SHOWN ON THE ARCHITECTURAL DRAWINGS.
8. ALL PLUMBING FIXTURES MUST MEET ADA REQUIREMENTS.
9. ALL FAUCETS WITH WRIST BLADE HANDLES SHALL BE INSTALLED SUCH THAT THE BLADE HANDLES ARE PARALLEL TO THE BACK
LEDGE OF THE SINK OR LAVATORY WHEN IN "OFF" POSITION.
ELECTRIC WATER HEATER SCHEDULE
SYMBOL
LOCATION
SERVES
STORAGE
STORAGE
TANK
PH RECOVERYVOLT/PHASE
ANUFACTURE
OPERATING WEIGHT
GALLONS
TEMP
DIMENSIONS
� 100°F. RISE
KW
MODEL N0.
48OVGP
WHi
HK
BUILDING
BO
740
24"DX
49
12 KW TOTAL
AO SMITH
211 LBS
142
593/8"H.
SIMULTANEO
DEN-80
US
OPERATION
' MAINTAIN PROPER CLEARANCE AROUND UNIT TO COMPLY WITH APPLICABLE CODES AND MANUFACTURER'S RECOMMENDATIONS FOR SERVICE ACCESS.
° COORDINATE ELECTRICAL REQUIREMENTS WITH ELECTRICAL CONTRACTOR PRIOR TO ORDERING AND INSTALLATION.
CIRCULATION PUMP SCHEDULE
SYMBOL
LOCATION
SERVES
TYPE
GPM
TDH HP
RPM
VOLTS/PHASE
MANUFACTURER
(FT)
MODEL NO.
CP1
HK
142
WATER
IN -LINE
6
15 1/12
2750
120/1
GRUNDFOS
HEATER
UP26-96BF
EXPANSION TANK SCHEDULE
SYMBOL
LOCATION
TANK
TOREDWATER
PRE -CHARGE
INSTALLATION
TANK PRESSURE MANUFACTURER
CAPACITY
TEMP ('F)
PRESSURE(PSI)
CONFIGURATION
RATING (PSI) MODEL NO.
ET -I
2.1
140 F
55
SUSPENDED
150 A TTSROOL
742
THERMOSTATIC MIXING VALVE SCHEDULE
HOTWATER I
LENDEDWATEF
PRESSURE
SENSING
MANUFACTURER
SYMBOL
LOCATION
NLET TEMP. (°F)
TEMP.(OF)
DROPTHRU
RANGE
MODEL N0.
REMARKS
SYSTEM
(GPM)
LEONARD
-HIGH LOW THERMOSTATIC MIXING VALVE, LOCKING TEMP REGULATOR,
Tel
HK
140
110
20
29
#TM-18652OB-LF
OUTLET BALL VALVE WITH THERMOMETER/PRESSURE GAUGE, 3/4"RETURN
&
142
LOOPITHERMOMETER AND BALL VALVE, INTEGRAL COMBO CHECK STOPS
TMV2
-
LOCKING TEMP REGULATOR, SWARM, MOUNTED ON UN ISTRUT
MIXING VALVE MUST CONFORM TO ASSET 017.
-INSTALL BOTH TMV-1 AND TMI IN PARALLEL ON WALL FOR REDUNDANCY
AND SERVICING. PROVIDE SHUT-OFF VALVES ON INLET FOR BOTH COLD
AND HOT WATER ON EACH TMV AND ON BLENDED WATER OUTLET FOR
EACH TMV. REFER TO DETAIL 08/P-801 FOR PIPING DIAGRAM,
TMI
L2
110
105
20
0.5-7.0
LEONARD
-PROVIDE CHECKS ON HOT AND COLD WATER SIDE OF VALVE. MIXING VALV
-
#Z70
MUST CONFORM TO ASSE 1070
MEDICAL VACUUM PUMP SCHEDULE
NFPA SYSTEM ON
TANK
SYSTEM
SYSTEM
SYMBOL
LOCATION
PUMP SCFM
STANDBY PUMP
WEIGHT
SQ. FT.
HP
SIZE
F.L.A
VOLTAGE/ BTUH
SOUND
MANUFACTURER
@ 19'HG
SCFM @ 19"HG
LBS.
REQUIRED
GAL,
46D V
PHASE
LEVEL DBA
MODEL NO.
VACUUM
BEACON MEDAS
BEACONVEDAS
All
PUMPROOM
5
5
348
6.3
1.5
30
3.1
4W/3 3,054
67
VDVOl
WATER DEMAND SCHEDULE
FIXTURE TYPE
QUANTITY
WSFU VALV
TOTAL
WSFU VALUE
WATER CLOSET (FLUSH VALVE TYPE)
7
10
70.0
LAVATORY
8
2.0
16.0
SINK
18
2.0
36.0
MOP SINK
1
3.0
3.0
SHOWER
1
3.0
3.0
CLINICAL SERVICE SINK
1
10.0
10.0
(FLUSH VALVE)
136.00 WSFU= 77 GPM
TOTAL =2"CW SERVICE
@ <8FT./SEC MAX
ZONE VALVE BOX SCHEDULE
ZONE VALVE BOX
SERVING
OXYGEN
AIR
VACUUM
NB-1
CT & PAID
12"
12"
314"
NB-2
TREATMENTEXAM
314"
314"
1-114"
NB3
FT EXAM
3/4"
314"
1-114"
PLUMBING FIXTURE
CONNECTION SCHEDULE
FIXTURE TYPE WASTE TVENT CW HW
WATER CLOSET
4"
2"
1"
-
LAVATORY
2"
2"
1124
1Q"
ELEC. WATER COOLER
2"
2"
1/Z'
'
CLINICAL SERVICE SINK
4"
2"
1-1/4"
3M"
SHOWER
2"
MOPSINK
3"
2"
3/4"
314"
SW ASSOCIATES
Tn
GonsWfing Engineers
l- LU
Z
E
1700 Pacific Avelac
Z
W
e
S
s
Darts, TX 75201
Tel: 214.397.0211
mrww.Swamgmars.min-
w
d
=
PRDJECT#18209
�wH
PLUMBING GENERAL NOTES:ZJ
;:=V
12
ZOO
F
PIP
-
A PROVIDE COMPLETE PLUMBING SYSTEM AS REQUIRED FOR THE SCOPE OF
LLJ L.LQ
THIS CONTRACT. FINAL SYSTEM DESIGN SHALL BE BUILT TO COMPLY WITH
o
CURRENT PLUMBING, LOCAL CODE DEPARTMENT OF HEALTH, NFPA, AND
t
OSHA REQUIREMENTS.
B. ALL CONSTRUCTION DEBRIS BY THE
c
�'
z
y
o
RWISE.OSEDOF
EDSHALL
CONTRACTOR,UNLESS NOTED OTHERWISE.
OTHERWISE.
r
g
C. THERE SHALL BE NOTHING ABANDONED IN PLACE, UNLESS SPECIFICALLY
-
0
E
E
2
IDENTIFIED AS SUCH.
-
D. THESE PLANS ARE DIAGRAMMATIC IN NATURE, CONTRACTORS SHALL
m
O
e
INCLUDE APPROPRIATE ALLOWANCES FOR OFFSETS AS REQUIRED TO
m
ACCOMMODATE VERTICAL AND HORIZONTAL VARIATIONS IN THE LOCATIONS
AND ELEVATIONS OF DUCTWORK, PIPING AND EXISTING CONDITIONS.
H0101"Ii
E. EACH TRADE SHALL COORDINATE THE ROUTING AND INSTALLATION OF HIS
tYaN G. PIq�'%.
IIS Pill,
.%e
0;.I
WORK WITH THAT OF ALL OTHER TRADES THROUGH THE GENERAL
`3-'i2• f0 •-1
CONTRACTOR. IN ANY INSTANCES OF CONFLICT, SYSTEMS REQUIRING
3 '
% =
"GRADE"OR"SLOPE"FOR DRAINAGE (SANITARY SEWER, SANITARY VENT,
= 1NO.PE10403225
EQUIPMENT DRAINS, ETC...) SHALL HAVE PRIORITY.
ea STATE OF ;_
c
F. PENETRATIONS OF WALLS OR FLOORS FOR THE PASSAGE OF PIPING, OR
OTHER EQUIPMENT SHALL BE PROPERLY SEALED AFTER INSTALLATION OF
EQUIPMENT. FIELD VERIFY EXISTING WALL PENETRATIONS AND PROPERLY
SEAL AS REQUIRED TO MAINTAIN WALL OR FLOOR RATING.
/I
G. PROVIDE ALL EQUIPMENT,MATERIAL, LABOR, SUPERVISION, COSTS AND
SERVICES REQUIRED TO INSTALL COMPLETE AND WORKING
Seals
SVSTEMSINCLUDING ALL ITEMS AND APPURTENANCES NECESSARY,
REASONABLE, INCIDENTAL OR CUSTOMARILY INCLUDED, EVEN THOUGH EACH
AND EVERY ITEM IS NOT SPECIFIED OR SHOWN ON DRAWINGS.
H. ALL WOW DOCUMENTS, INC UDNGADDENDA,ANDAPPLICABLECCODESANDLL COMPLY WITH THE REQUIREMENTS OF THE TRACT ISSUED FOR BID &
STANDARDS.PERMIT
I. PROVIDE ACCESS TO ALL CONCEALED EQUIPMENT AND VALVES.
COORDINATE LOCATION OF ACCESS PANELS WITH ARCHITECT.
J. ALL FLOOR DRAINS, FLOOR SIN KS, H UB DRAINS, OR INDIRECT CONNECTIONS
SHALL BE PROVIDED WITH JR SMITH QUAD CLOSE IN LIEU OF TRAP PRIMER.
K. VENT STACK SHALL BE LOCATED A MINIMUM OF 25'-0" AWAY FROM ANY HVAC
OUTSIDE AIR INTAKE. (HOSPITAL)
L. PROVIDE PVC SLEEVE FOR ANY PORTION OF THE GAS PIPING THAT IS ROUTED
CD
IN BUILDING, UNDER CONCRETE SLAB OR WALKWAY (TYPICAL)
O
M. EXTEND SANITARY SEWER, DOMESTIC WATER, FIRE, STORM AND GAS PIPING
AS REQUIRED IN ORDER TO CONNECT TO STUB -OUT PROVIDED BY CIVIL.
T
C)
N. UTILITIES OR SHALL BE INSTALLED PER THE
MANUFACTURERS RECOMMENDATIONS.
O.J
>CD)
0. COORDINATE ALL FLOOR DRAIN, FLOOR SINK, HUB DRAIN, WALL AND FLOOR
CLEANOUT LOCATIONS WITH ARHICTECT/OWNER AND EQUIPMENT VENDOR
NC
BOOK PRIOR TO INSTALLATION.
C
L.I..I
P. PROVIDE AND INSTALL BACKFLOW PREVENTERS ON SUPPLY LINES SERVING
OWNER FURNISHED EQUIPMENT IN ACCORDANCE WITH LOCAL AND STATE
p46
CODES. REFER TO SPECIFICATIONS. ROUTE DRAIN LINE FROM RPZ TO AN
APPROVED LOCATION.
a�D
0. DURING INSTALLATION FIELD MODIFICATIONS TO ROUTING MAY BE REQUIRED.
U
R. CONTRACTOR TO VERIFY ALL INVERT ELEVATIONS FOR NEW PIPING
a--�
CONNECTING TO CIVIL. NOTIFY ENGINEER OF ANY DISCREPANCIES.
N
S. NO PIPING SHALL RUN EXPOSED IN FINISHED AREAS.
T. PROVIDE WALL CLEANOUTS ON ALL FLOOR DRAINS, FLOOR SINKS, HUB
J
DRAINS, FIXTURES, AND AT THE BASE OF ALL RISERS. MOUNT MINIMUM 12"
-
A.F.F. TO KEEP WALL CLEANOUT OUT OF BASEBOARDS.
aD
U. PROVIDE CHECK VALVES ON HOT AND COLD WATER SIDE BEFORE ALL
THERMOSTATIC MIXING VALVES.
V. PROVIDE SHOCK ARRESTOR'S AT ALL QUICK CLOSING VALVES PE R PLUMBINGCz
CODE AND LOCAL CODE.
C
W. ANY PIPING LOCATED IN RETURN AIR PLENUM SHALL BE PLENUM RATED PER
TDH, PLUMBING AND LOCAL CODE.
X VERIFY FINAL VENDOR EQUIPMENT DRAWINGS WITH OWNER PRIOR TO
INSTALLATION.
Z. PROVIDE FUNNEL DRAINS ON BACKFLOW DEVICES.
GENERAL FIRE PROTECTION NOTES:
A. PROVIDE A COMPLETE AUTOMATIC WET PIPE FI RE SPRINKLER SYSTEM AS REQUIRED TO
PROVIDE FULL COVERAGE FOR THE SCOPE OF THIS CONTRACT. FINAL SYSTEM DESIGN
SHALL BE HYDRAULICALLY CALCULATED TO COMPLY WITH CURRENT NFPA 13,
INTERNATIONAL FIRE CODE. LOCAL CODE/AMMENDMENTS AND INDIANA DEPARTMENT OF
HEALTH FREESTANDING EMERGENCY MEDICAL CARE FACILITY LICENSING RULES.
B. SHOP DRAWINGS SHALL BE SUBMITTED TO AND APPROVED BY THEARCHRECT PRIOR TO
ORDERING, PURCHASING, OR FABRICATION OF ANY FIRE PROTECTION EQUIPMENT. SHOP
DRAWINGS SHALL INCLUDE: SPRINKLER DRAWINGS AND CALCULATIONS BEARING THE
SEAL OF AREGISTERED PRD ESSIONAL ENGINER OR EQUIVALENT CONTRACTORS FIRE
SPRINKLER CERTIFICATE SEAL AND APPROVAL STAMP OF LOCAL CODE AUTHORITY;
SPRINKLER PIPING. SPRINKLER HEADS VAViEB; AND ACCESSORIES. SHOP DRAWINGS
SWILL BE SUBMITTED TO AND APPROVED BY THE OWNERS INSURANCE UNDERWRITER
PRIOR TO BEING SUBMITTED TO THE ARCHITECT.
C. CONTRACTOR SHALL COORDINATE THE ELECTRICAL CHARACTERISTICS AND
REQUIREMENTS OF All FIRE PROTECTION EQUIPMENT WITH THE ELECTRICAL DRAWINGS
AND SHALL FURNISH EQUIPMENTWTRED FOR THEVOLTAGESSHOWN THEREIN.
D. All FIRE PROTECTION EQUIPMENT AND SYSTEMS SHAL BE GUARANTEED FOR A PERIOD
OF ONE YEAR AFTER FINAL ACCEPTANCE.
41
E. ALL PIPING ABOVE GRADE SHALL BE SUPPORTED BY THE BUILDING STRUCTURE AND
Z
SHALL NOT REST ON CEILING TILES OR CEILING STRUCTURE. PIPING HUNG FROM JOBTS
SWILL BE HUNG FROM THE TOP CHORDS OF THE JOBTS.
F. COORDINATE SPRINKLER TYPES WITH ARCHITECT PRIOR TO INSTALLMION.
G. PROVIDE CONCEALED SPRINILERB CENTERED IN CEILING TILE.
Project Number: 3018082
H. PROVIDE SIDEWALL SPRINKLERS INKRAY ROOM.
Date: 02/262019
I. PROJIDEDRKPIPE SYSTEM FOR EXTERIOR CANOPIESAS REQUIRED.
Sheet Title and Number'.
P-701
SCHEDULES - PLUMBING