CODE SUMMARY
SCOPE OF WORK
PREVIOUS USE OF SPACE
OFFICE REMODEL OF PREVIOUSLY BUILT -OUT OFFICE SPACE
BUSINESS)
OCCUPANCY CLASSIFICATION
BUSINESS)
CHANGE OF OCCUPANCY CLASS?
NO
TOTAL BUILDING AREA
33,419 SF/FLOOR
X
1 6 STORIES
=
200,516 SF
TOTAL PROJECT AREA
7,747 SF
OCCUPANCY CALCULATIONS
SPACE TYPE
AREA
SF PER OCCUPANT
OCS f LOAD
GEN. OFFICE
6,664 SF
100
67
TRAINING ROOM
1,083 SF
1 IS
1 73
TOTAL OCCUPANTS IN PROJECTAREA 140
NUMBER OF EXITS
REQUIRED:2 PROVIDED:2
SPRINKLER SYSTEM(YES/NO)
YES- EXISTING TO REMAIN
TOTAL AREA OF ACCESSORY USES
0 SF
TOTAL AREA ON THE FLOOR
33,419 SF
ACCESSORY AREA EXCEEDS 10%
NO
FIRE WALLS, AND/OR OCCUPANCY
SEPARATIONS (IF REQUIRED)
N/A
ASHRAE 90.1 SUMMARY
EXEMPT (SEE REFLECTED CEILING PLAN)
BUILT BEFORE 19782
NO
BUILDING CONSTRUCTION TYPE
III (ORIGINAL TYPE II-FR J
LEGEND
EP EXISTING ELECTRICAL PANEL LOCATION
EJ( EXISTING EXIT
FE FIRE EXTINGUISHER
0 EXITSIGN
EMERGENCY LIGHT
— — — TRAVEL DISTANCE
RELEASED FOR CONSTRUCTION
Subject to compliance with all regulations
of State and Local Codes
City d Carmel
DATE: 06/17/19
AREA NOT IN CONTRACT
❑ AREA OF WORK
LIFE SAFETY NOTES
I. PROVIDE EMERGENCY LIGHTING IN TENANT SPACE AS REQUIRED PER
NEMA AND IBC. EMERGENCY BATTERY PACKS OR LIGHTS
CONNECTED TO AN EMERGENCY POWER SOURCE ARE REQUIRED IF
THE SPACE CONTAINS 50 PERSONS OR MORE. FIXTURES SHOWN ON
PLAN ARE FOR REFERENCE ONLY.
2. PROVIDE ALARM NOTIFICATION APPLIANCES HORNS/STROBES),
EMERGENCY SPEAKERS, SMOKE DETECTORS, FIRE PULLS, AND ANY
OTHER REQUIRED ALARM & DETECTION SYSTEMS AS NECESSARY TO
MEET ALL APPLICABLE CODES (INTERNATIONAL BUILDING CODE,
INTERNATIONAL FIRE CODE, NFPA). IN RECEPTION AREAS,
CONFERENCE ROOMS AND OTHER HIGH PROFILE AREAS WITHIN SURE,
ALL LOCATIONS OF SUCH DEVICES MUST BE APPROVED BY SDI OR
TENANT PRIOR TO INSTALLATION. FAILURE TO DO SO MAY RESULT IN
CONTRACTOR RELOCATING THESE ITEMS ATTHEIR EXPENSE.
3. FIRE EXTINGUISHERS: CONTRACTOR TO ENSURE ALL NEW AND
EXISTING FIRE EXTINGUISHERS ARE INSTALLED ACCORDING TO NFPA
10. COORDINATE WITH OWNER/LANDLORD ON EXTINGUISHER TYPE
AND HOUSING. MAXIMUM TRAVEL DISTANCE OF 75 FEET FROM ANY
POINT TO A VISIBLE EXTINGUISHER.
THE FOLLOWING NOTES APPLY ONLY IN EXISTING SPRINKLERED FACILITIES.
4. FIRE PROTECTION WORK IS TO BE PROVIDED BY DESIGN/BUILD
SERVICES UNDER THE GENERAL CONTRACT, PROVIDE A COMPLETE,
WORKING SYSTEM. SCHOTT DESIGN, INC., IS NOT RESPONSIBLE FOR
THE DESIGN, INSTALLATION, OR RENOVATION OF THE FIRE SPRINKLER
SYSTEM.
5. THE FIRE PROTECTION CONTRACTOR SHALL GENERATE ALL REQUIRED
DRAWINGS, AND SHALL FILE THOSE DRAWINGS, AND RELATED
DOCUMENTS, WITH THE STATE AND LOCAL AUTHORITIES HAVING
JURISDICTION OVER THE PROJECT.
GENERAL NOTES
H. REFER TO ARCHITECTURAL PLAN FOR WALL TYPE AND CONSTRUCTION
DEFAILS.
L2. EXISTING COMMON CORRIDOR TO REMAIN. EXISTING EXIT SIGNS, FIRE
PULLS, FIRE EXTINGUISHERS, ALARM NOTIFICATION APPLIANCES TO
REMAIN. RELOCATE EXISTING EXITSIGNS, FIRE PULLS, FIRE
EXTINGUISHERS AND ALARM NOTIFICATIONS AS REQUIRED TO MEET
ALL LOCAL AND STATE CODES.
LIFE SAFETY PLAN N
THIS DRAWING, AND THE IDEAS,
DESIGNS AND CONCEPTS CONTAINED
HEREIN, ARE THE EXCLUSIVE
INTELLECTUAL PROPERTY OF SCH07
DESIGN, INC., AND ARE NOT TO BE
USED OR REPRODUCED IN WHOLE, OR
IN PART, WITHOUTTHE WRITTEN
CONSENT OF SCHOTT DESIGN.
N
C/)
�oJ
Wog0
ZWQ
Q
N
Z
0
O
F-
ELLI
t/7
OO
LLJ
7
I—
aaaaaa�
SC
�
=
Z
Q
�
�0
O
a
�
w
O
O
ISSUE
DATE
DESCRIPTION
03,04.19
REVIEW SET
03.13,19
CHECKSET
03.19.19
BID SET
04.21.19
CONSTRUCTION SET
EVISIONS
ARK
DATE
DB
DESCRIPTION
iiiiiiiim
PROJECT NUMBER
2019.049
PROD. MGR DRAWN BY
SDH JJ
4TH FLOOR
LIFE SAFETY
L100