HomeMy WebLinkAboutM101 MECHANICAL SHEETTWO-PIECE
COUNTER FLASHING
BASE FLASHING
60 MIL MEMBRANE
(INSTALLED PER
MFR.) ON 3" RIGID
INSULATION, ON
METAL DECK SEE
STRUCT.
WOOD NAILER THRU
BOLT TO DECK WITH
3/8" DIA. BOLTS AT
STRUCTURAL
FRAMING
WOOD NAILER
PREFABRICATED
ROOF CURB W/
INTEGRAL FIBER
GLASS INSULATION
CANT STRIP
PROVIDE WELL LINER
OR DUCT
CONNECTION
WHERE REQ'D.
FASTEN TO METAL.
CURB 8 WELD TO
STRUCTURAL
FRAMING
TYP. ROOF CURB DTL.
M 101 SCALE: 1" = 1'-0"
MC6K15.3
C/L OF BAR JOIST
II II II K�OUTUINIE
��2 C6X6.2 OF MECH. UNIT
I I
I II II I
I II II I
MQ6%15.3
/'6� TYP. ROOF CURB PLAN
M101 SCALE: 1/2"=1'-0"
GIST SPACING, SEE PLAN
RqPF OPENIUG L6x4x3/8x6" LG.
STRUCTURAL STEEL:
(LLV) - TYP
C SHAPES: ASTM A36 UNO
PLATE, ANGLES ASTM A36 UNO
L6x4x5/16
TUBES" ASTM A500 GRADE B(Fy = 46 KSI)
(LLR) TYP.
EACH SIDE OF
DETAILING, FABRICATION, AND ERECTION SHALL
CONFORM TO THE LATEST AISC SPECIFICATIONS.
/1 P.
ALL WELDING SHALL BE DONE USING E-70XX
*FOR ALL ROOF OPENINGS 12" OR
ELECTRODES IN ACCORDANCE WITH THE LATEST AWS
MORE.
SPECIFICATIONS.
COORDINATE OPENING SIZES AND
PRIMEA ALL STEEL NOT IN CONTACT WITH CONCRETE.
LOCATIONS WITH ARCHITECT AND
M.C.
j:) TYP. ROOF
OPENING DETAIL
M101 SCALE: 1/2"=1'-0"
STEEL SHIMS O 2'-0"
MECH. UNIT
O.C. (NOTE REQ'D IF
TAPERED CURBS ARE
PROVIDED)
MECH. CURB
�CONT. MC605.3
L REINFORCEMENT
TYP WHEN GREATER THANAN 6" 6"
/8 L7 3x1 JxA EA SIDE
/71 TYP. RTU SUPPORT
M101/ SCALE: 1/2"=1'-0"
RELEASED FOR CONSTRUCTION
Subject to compliance with all regulations
of State and Local Codes
City of Camel
DATE: 06/19/19
MECHANI
SCALE: 1 /4" = 1'-0"
DUCTWORK & AIR DISTRIBUTION NOTES
1. ALL DUCTWORK SHALL BE INSTALLED STRAIGHTAND TRUE IN A QUALITY
WORKMANLIKE FASHION.
2. ALL DUCTWORK SHALL CONFORM TO ASHRAE AND SMACNA STANDARDS
WITH REGARDS TO DUCT GAUGES, TURNING VANES, THE INSTALLATION OF
THE TURNING VANES AND/OR EXTRACTORS, AND MOUNTED AND BRACING.
3. RECTANGULAR DUCT CONSTRUCTION
4. GALVANIZED IRON PER SMACNA
5. DUCT WIDTH U.S. STD BRACING INCHES
6. IN INCHES GAUGE GALV.ANGLE SPACING
1-12 26 Ga. - -
13-24 24 Ga. - -
25-30 24 Ga. 1X 1 X 1/8 48
31-40 22 Ga. 1X1X1/8 48
41-60 22 Ga. 11/4 x 11/4 x 1/8 24
61-90 20 Ga. 11/2 x 11/2 x 1/8 24
91-OVER 18 Ga. 11/2x 11/2x 1/8 24
7. STEEL OR ALUMINUM DUCTWORK SHALL CONFORM WITH DEPT.OF
COMMERCE CHAPTER 63.29(3) AND 64.34(184), AS WELL AS SMACNA SEAL
CLASS'C'. FRESH AIR DUCTWORK, AND ANY DUCTWORK EXTERIOR OF TH E
BUILDING SHALL BE INSULATED WITH MATERIAL NO LESS THAN R-9.
SUPPLY -AIR DUCTWORK NOT IN THE CONDITIONED SPACE SHALL BE
INSULATED WITH MATERIAL NO LESS THAN R-5.
8. TH E HVAC CONTRACTOR SHALL CONSULT WITH THE GENERAL CONTRACTOR
AND/ OR THE BUILDING OWNER(S) TO DETERMINE THE EXACT LOCATION OF
REGISTERS, GRILLES, AND DIFFUSERS. HVAC DRAWINGS INDICATE
QUANTITIES AND AIR FLOW SPECIFICATIONS, HOWEVER, LOCATIONS ARE
DIAGRAMMATIC.
9. THE HVAC CONTRACTOR SHALL BE RESPONSIBLE FOR BALANCING THE
ENTIRE SYSTEM SO THAT TH E SUPPLY AIR, RETURN AIR, EXHAUST AIR, AND
FRESH AIR ARE WITH IN +/-5% OF THE AIR QUANTITIES SHOWN ON TH E PLAN.
THE HVAC CONTRACTOR SHALL FURNISH THE HVAC DESIGNER WITH TWO
COPIES OF THE BALANCE DATA.
10. INSULATED FLEXIBLE SUPPLY AIR DUCT RUNS SHALL NOT EXCEED FIVE (5)
FEET IN LENGTH.
11. HVAC CONTRACTOR SHALL FURNISH AND INSTALL PLEATED FILTERS WITH
AN AVERAGE ARRESTANCE OF 85% OR GREATER, OR HIGHER EFFICIENT
FILTER MEDIA TYPES. FILTERS SHALL BE EASILY ACCESSIBLE IN FILTER RACK
OR FILTER GRILLES.
12. HVAC CONTRACTOR SHALL FIELD ROUTE DUCTWORK AS REQUIRED TO
AVOID INTERFERENCE WITH SUSPENDED ACOUSTICAL CEILING HEIGHT.
COORDINATE WITH GENERAL CONTRACTOR.
13. ALL ELECTRICAL FIXTURES SHALL BE PROVIDED BY THE ELECTRICIAN, AND
INSTALLED BY THE ELECTRICAL CONTRACTOR, UNLESS OTHERWISE NOTED,
SEE E101.
14. FOR SYMBOLS SHOWN IN LEGEND, BUT NOT ON THE PLAN, REFER TO THE
MECH. AND ELEC. DRAWINGS.
15. EACH UNIT SHALL PROVIDE IONIZATION TYPE RETURN AIR DUCT SMOKE
DETECTION.
16. SMOKE DETECTION SYSTEM WILL CONSIST OF IONIZATION TYPE SAMPLING
TUBE, SMOKE DETECTOR WITH AUDIBLE ALARM, LED INDICATOR, AND
MANUAL TESTRRIP KEY.
GAS PIPING NOTES;
17. ALL GAS PIPING SHALL BE RUN STRAIGHTAND TRUE AND BE INSTALLED IN A
QUALITY WORKMANLIKE FASHION.
18. GAS PIPING SHALL CONFORM TO ALL STATE AND LOCAL CODES, AS WELL AS
NATIONAL FUEL GAS CODE RECOMMENDATIONS.
19. PLUMBING CONTRACTOR SHALL FURNISH AND INSTALL SCHEDULE 40 STEEL
GAS PIPING AND FITTINGS. HVAC CONTRACTOR SHALL INSTALL ALL
NECESSARY VALVES, FITTINGS, REGULATORS, AND SAFETY AND OPERATING
DEVICES.
VENTING NOTES:
20. ALL GAS FIRED APPLIANCE VENTING SHALL COMPLY WITH STATE AND LOCAL
CODES AND BE DONE IN A QUALITY WORKMANLIKE FASHION.
21. ALL VENTING SHALL STRICTLY COMPLY WITH MANUFACTURER'S
RECOMMENDATIONS AND INSTRUCTIONS.
22. ALL FRESH AIR INTAKES SHALL BE A MINIMUM OF 10' AWAY FROM ANY
EXHAUST VENT, SOIL VENT PIPE, OR GAS METER.
23. ALL GAS FIRED APPLIANCE VENTS SHALL BE A MINIMUM OF 1 O'-0" AWAY FROM
ANY WINDOW, DOOR, OR BUILDING ENTRANCE.AND MANUAL TEST/TRIP KEY.
MECHANICAL NOTES
1. AFIELD VISIT IS REQUIRED TO THE SITE TO VERIFY THE FIELD
CONDITIONSAND LAYOUTOF EXISTING DUCTWORK. ALL WORK
REQUIRED TO COMPLETE THE REWORK OF DUCTWORK IN THE SPACE
SHALL BE INCLUDED IN THE BASE BID FOR THE PROJECT.
2. ALL WORK AND MATERIALS SHALL COMPLY WITH GOVERNING CODES,
SAFETY ORDERS AND REGULATIONS.
3. OBTAIN AND PAY FOR ALL NECESSARY PERMITS, FEES AND
INSPECTIONS REQUIRED BY GOVERNING AUTHORITIES.
4. ALL FLEX DUCT SHALL BE UL 181 LISTED.
5, ALL BRANCH DUCTS FEEDING INDIVIDUAL DIFFUSERS SHALL HAVE
DAMPERS AT TAKEOFFS FOR AIR BALANCING. PROVIDE ACCESS
PANELS TO DAMPERS AS MAY BE REQUIRED BY THE GENERAL
TRADES CONSTRUCTION, SEE ARCHITECTURAL PLANS.
6. ALL OUTSIDE AIR INTAKES SHALL BE MINIMUM OF 1O'-0" FROM
EXHAUST FANS AND / OR VENTS.
7, FINAL HVAC BALANCING SHALL BE PERFORMED BY THE HVAC
CONTRACTOR AS A PART OF H IS BASE BID FOR THE PROJECT. IN
WHEN REMOVING DIFFUSERS AND SHORTENING EXISTING DUCTING,
MECHANICAL CONTRACTOR IS RESPONSIBLE FOR RE -BALANCING
HVAC SYSTEM.
8. MECHANICAL CONTRACTOR TO INSTALL DUCT WORK TO EF-1 AS
SHOWN UNLESS APPROVED BY ARCHITECT AHEAD OF TIME.
9. SEE SHEET M102 FOR HOOD, WELDED DUCT, FIRE WRAP AND
EXHAUST FAN. THE HOOD AND EF-1 ARE PROVIDED BY THE OWNER
INSTALLATION AND CONNECTION FOR PROPER OPERATION ARE BY
THIS CONTRACTOR.
10. EF-1 IS TO BE INSTALLED ON THE ROOF. PROVIDE A ROOF CURB
DESIGNED FOR THE SLOPED ROOF. VERIFY ROOF PITCH AT ALL
LOCATIONS.
11. ALL EXHAUST AND VENTS SHALL BEA MINIMUM OF IO'TO PROPERTY
LINES.
DIFFUSER AND GRILLE SCHEDULE
SYMBOL MAKE BOOT NEC,
MODEL NO.
PRICE POE
PERFORATED W/
INSULATED BOOT 8 AS STATED
2-WAY BLADES
9:i [6>!:i>r Oli 9 C115
MODEL BOFF W/ AS STATED
INSULATED BOOT 8
REMOVABLE FILTER
181:14111MMIM 011 W IMMA1*41�.
v
EXHAUST FAN NUMBER
e
DIFFUSER TYPE
INDICATES GEM QUANTITY
V AFF) NUMBER I NDICATES HVAC NUMBER
O SMOKE D ETE CT
OR MOUNTED IN THE RETURN
PLENUMS OF HVAC UNITS.
�TTIIII
CONTROL DAMPER
FLEXIBLE DUCT WITH INSULATION
�P
NUMBER DENOTES INSIDE DIAMETER
EMERSON 1F97-1277 or EQUIVALENT HONEYW ELL
O
EQUIVALENT AUTOMATIC CHANGEOVER THERMOSTAT
(r@ 54' A.F.F. NUMBER INDICATES HVAC NUMBER.)
J
C
(73
U)
CC:
C
C
C
U,
a
C
0)
(i
758048th Street, S.E.
Grand Rapids, Mi. 49512
P. 616.634.2253
Glenn@rdc-Ilc.com
a
W=
L
a)0 M
Q
a)Ev
f6 (� Z
u .J U
EE
L O L
Df Lid M
C.) (o U
DATE ISSUED FOR
03/15/2019 REVIEW
04/01/H019 Construction
04/23Y2019 Per State Rev.
omaoolNN IR nn� biyi�ix�
goo• ............. "..,
i Na. AR110001fi] `:
gRaCHITEn�1
THIS DRAWING IS THE
SOLE PROPERTY OF
RETAIL DESIGN
CONSULTANTS LLC AND IS
A COPYRIGHTED
DOCUMENT AND IS NOT
TO BE USED OR
REPRODUCED WITHOUT
WRITTEN CONSENT.
101