HomeMy WebLinkAboutG-2TO ANTENNA COAX
COPPER/GALVANIZED GROUND BAR
O
O
TWO HOLE LONG BARREL
COMPRESSION LUG (TYR)
NOTES:
1. DOUBLING UP "OR STACKING" OF CONNECTIONS IS NOT PERMITTED.
2. EXTERIOR ANTIOXIDANT JOINT COMPOUND TO BE USED ON ALL EXTERIOR CONNECTIONS.
3. GROUND BAR SHALL NOT BE ISOLATED FROM TOWER. MOUNT DIRECTLY TO TOWER STEEL.
ANTENNA GROUND BAR DETAIL
#6 MIN. FROM ANTENNA
CABLE GROUND KIT
GROUND BAR ON SHELTER. ICE
BRIDGE, OR ON ANTENNA TOWER
TWO HOLE LUG, OR
EXOTHERMIC WELD TO BE
USED WITH #2 BARE
CONDUCTOR WIRE TO
BUILDING SERVICE GROUND
OR GROUND RING
GROUNDWIRE INSTALLATION
SGALL: NUI IU SCALE
GROUNDING SHALL BE
ELIMINATED WHEN GROUND
BAR IS ELECTRICALLY BONDED
TO METAL TOWER
(TYPICALLY) WEATHERPROOFING KIT
12" TO 24" (SEE NOTE 3)
ANTENNA CABLE 120" MAX. COAX JUMPER NOTE: MINIMUM OF
3 THREADS TO BE
VISIBLE
TO ANTENNA (TYR)
CABLE 2 HOLE LONG
CONNECTOR BARREL TINNED
SOLID COPPER
WEATHERPROOFING KIT LUG
#6 STRANDED COPPER (SEE NOTE 3) (TYR)
GROUND WIRE
(GROUND TO GROUND BAR) CABLE GROUND KIT
SEE NOTES 1 & 2
NOTES:
1. DO NOT INSTALL CABLE GROUND KIT AT A BEND AND ALWAYS DIRECT GROUND
WIRE DOWN TO GROUND BAR.
2, GROU NS II CT SHALL BE TYPE AND PART NUMBER AS SUPPLIED OR
RECOMI.'I 5 BY CABLE MANUFACTURER.
3. WEATHE9 - -FING SHALL BE TWO—PART TAPE KIT, COLD SHRINK SHALL NOT BE
RELEASED FOR CONSTRUCTION
Subject to compliance with all regulation;
Of State and Local Codes ; d
e City of Camel ('�
gUrthGl9wldApA�.
DATE: \ 06/25/19
TO ANTENNA COAX
COPPER/GALVANIZED GROUND BAR
N
N
•
N
• N •
•
O 1
#2 SOLID TINNED COPPER
CONDUCTOR TO TOWER/SHELTER
TWO HOLE LONG BARREL COMPRESSION LUG GROUND RING (2 TYR. FOR
(TYR) BOTTOM GROUND BAR ONLY)
NOTES:
1. EXTERIOR ANTIOXIDANT JOINT COMPOUND TO BE USED ON ALL EXTERIOR CONNECTIONS.
2. GROUND BAR SHALL NOT BE ISOLATED FROM TOWER. MOUNT DIRECTLY TO TOWER STEEL (TOWER ONLY).
3. GROUND BAR SHALL BE ISOLATED FROM BUILDING OR SHELTER.
TOWER/SHELTER GROUND BAR DETAIL
SCALE: NOT TO SCALE
3/8-11x1" TAMPER
RESISTANT BOLT
(TYR)
INSULATORS
SEE NOTE 2.
(TYR)
WALL BRACKET
(TYR)
® o
0 0
0 0
o
0
LOCK WASHER
P/N MID
(TYR) /
TWO —HOLE
COMPRESSION LUG
11111111110
UNIVERSAL COPPER
GROUND BAR (4"x20")
1. DOWN LEAD (HOME RUN) CONDUCTORS ARE NOT TO BE INSTALLED ON CROWN CASTLE
USA INC. TOWER, PER THE GROUNDING DOWN CONDUCTOR POLICY QAS—STD-10091, NO
MODIFICATION OR DRILLING TO TOWER STEEL IS ALLOWED IN ANY FORM OR FASHION,
CAD —WELDING ON THE TOWER Al IN THE AIR ARE NOT PERMITTED.
2. OMIT INSULATOR WHEN MOUNTING TO TOWER STEEL OR PLATFORM STEEL
USE INSULATORS WHEN ATTACHING TO BUILDING OR SHELTERS.
GROUND BAR DETAIL
SGALL: NUI IU SGALL
S/S NUT
(TYR)
S/S SPLIT
WASHER
(TYR)
S/S FLAT
WASHER
(TYR)
TIN COATED SOLID
COPPER BUS BAR S/S FLAT
WASHER
CHERRY INSULATOR (TYR)
INSTALLED IF REQUIRED S/S BOLT
(TYR)
Ear
7 LUG DETAIL
SCALE: NOT TO SCALE
#2 TINNED SOLID IN 3/4" LIQUID
CONDUIT FROM 24" BELOW GRA1
WITHIN 3" TO 6" OF CAD —
TERMINATION POINT. EXPOSED EN
THE LIQUID TIGHT CONDUIT MU!
SEALED WITH SILICONE C
CADWELD
(TYR)
TIE INTO EXISTING GROUND RINC
8 TRANSITIONING GROUND DETAIL
SCALE: NOT TO SCALE
WIRE SIZE
BURNDY LUG
BOLT SIZE
#6 GREEN INSULATED
YA6C-2TC38
3/8"
— 16
NO
SS
2
BOLT
#2 SOLID TINNED
YA3C-2TC38
3/8"
— 16
NO
SS
2
BOLT
#2 STRANDED
YA2C-2TC38
3/8"
— 16
NO
SS
2
BOLT
#2/0 STRANDED
YA26-2TC38
3/8"
— 16
NC
SS
2
BOLT
#4/0 STRANDED
YA28-2N
1/2"
— 16
NO
SS
2
BOLT
BURNDY GROUND LUG W/ LONG BARREL HEAT SHRINK
(SEE CHART) (CLEAR)
NUT (TYP)
LOCK WASHER (TYP)awl Am 7-
GROUND
CONDUCTOR
GROUND BAR
BOLT (SEE CHART)
BURNDY TWO HOLE LUG (TYR)
W/ LONG BARREL
(SEE CHART)
BARE WIRE TO BE TREATED
WITH NO—OX AT BOTH ENDS
N9SE:
STRANDED ALL GROUNDING LUGS ARE TO BE
(SEE CHART) INSTALLED PER MANUFACTURER'S
SPECIFICATIONS. ALL HARDWARE
BOLTS, NUTS, LOCK WASHERS SHALL
BE STAINLESS STEEL. ALL HARDWARE
ARE TO BE AS FOLLOWS: BOLT, FLAT
WASHER, GROUND BAR, GROUND
LUG, FLAT WASHER AND NUT.
MECHANICAL LUG CONNECTION
SCALE: NUI IU SCALE
2—HOLE CRIMP/
COMPRESSION
CONNECTOR
STAINLESS STEEL BOLT
(TYR)
STAINLESS STEEL
FLAT WASHER
(TYR)
GROUND
BAR
STAINLESS STEEL
FLAT WASHER
STAINLESS STEEL (TYR)
BELLVILLE WASHER STAINLESS STEEL NUT
(TYR) (TYR)
SINGLE CONNECTOR AT GROUND BARS
STAINLESS STEEL BOLT
DRAGON TOOTH WASHER
(TYR)
2—HOLE CRIMP/
COMPRESSION
CONNECTOR
STAINLESS STEEL
FLAT WASHER
STEEL
STAINLESS STEEL
FLAT WASHER
(TYR)
STAINLESS STEEL NUT
STAINLESS STEEL
BELLVILLE WASHER (TYR)
(TYR)
SINGLE CONNECTOR AT STEEL OBJECTS
STAINLESS STEEL
SELF —DRILLING
METAL SCREW
(TYR)
2—HOLE CRIMP/
COMPRESSION
CONNECTOR
STAINLESS STEEL
FLAT WASHER
(TYR)
DRAGON TOOTH METALLIC OBJECT
WASHER
(TYR)
SINGLE CONNECTOR AT METALLIC/STEEL OBJECTS
9 HARDWARE DETAIL FOR EXTERIOR CONNECTIONS
SCALE: NOT TO SCALE
41••Mobile••1
12920 SE 38TH STREET
BELLEV UE, WA 98006
CCCROWN
CASTLE
9045 RIVER ROAD, SUITE 425
INDIANAPOLIS, IN 46240
ILEAoF
944 CALLS AMANECER, SUITE E
SAN CLEMENTE, CA 92673
N .LEAFCOMM.COM
TEL: (949)38&0192
T-MOBILE SITE NUMBER:
MW07146A
BU #: 818988
12900 HAZEL DELL PKWAY
12900 HAZEL DELL PKWAY
CARMEL. IN 46033
EXISTING TBD OTHER
ISSUED FOR:
REV
DATE
DAWN
DESCRIPTION
DES./Q
0
03/21/2019
SD
PRELIMINARY
L.QN
03/22/2019
IT IS A VIOLATION OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL ENGINEER,
TO ALTER THIS DOCUMENT.
SHEET NUMBER: G-2 0 REVISION: