HomeMy WebLinkAboutE60-6FEEDER AND BRANCH CIRCUIT SCHEDULE NOTE: SEE DRAWINGS FOR NUMBER OF WIRES IN HOMERUN FEEDER/BRANCH CIRCUIT DESIGNATION CONDUCTOR SIZE TYPE CABLE CONDUIT PHASE & NEUTRAL EQUIPMENT GROUND ALUMINUM COPPER F20 12 12 X NM F30 10 10 X NM F40-50 8 10 X NM F60 6 10 X MC F70-80 4 8 X MC F90 3 8 X MC F100 3 8 X MC F125 1/0 4 X MC F150 3/0 4 X 2-1/2" F175 4/0 4 X 2-1/2" F200 250 4 X 3" F225 300 2 X 3" F250 350 2 X 3" F300 500 2 X 3-1/2" F350 2 RUNS OF 4/0 1 X 2-1/2" F400 2 RUNS OF 250 1 X 3" EACH F600 2 RUNS OF 500 2/0 X 3-1/2" EACH F800 3 RUNS OF 400 3/0 X 3-1/2" EACH F1000 3 RUNS OF 600 4/0 X 4" EACH F1200 4 RUNS OF 500 250 X 3-1/2" EACH F1600 5 RUNS OF 600 350 X 4" EACH F2000 6 RUNS OF 600 400 X 4" EACH F2500 7 RUNS OF 750 600 X 5" EACH F3000 8 RUNS OF 750 600 X 5" EACH NOTES: 1. 20 A BRANCH CIRCUITS SHALL BE SIZED FOR VOLTAGE DROP. WIRE SIZES ARE NOT INDICATED ON THE DRAWINGS TO COMPENSATE FOR VOLTAGE DROP. FOR THESE CIRCUITS, CONTRACTOR SHALL UTILIZE WIRE SIZE SHOWN ABOVE FOR DISTANCES LISTED ABOVE. 2. VOLTAGE DROP WIRE SIZES WILL BE STRICTLY ENFORCED. CONTRACTOR SHALL SUBMIT A LIST OF CIRCUITS THAT WILL EXCEED THE DISTANCES ALLOWED AND INDICATE WIRE SIZE TO BE USED PRIOR TO ANY WIRE BEING INSTALLED. 3. DO NOT SHARE NEUTRAL CONDUCTORS FOR ANY BRANCH CIRCUITS. ALL BRANCH CIRCUIT SHALL HAVE SEPARATE, INDEPENDENT NEUTRAL CONDUCTORS. 4. ALL BRANCH CIRCUIT WIRING SHALL BE NM AND MC CABLE WITH THE FOLLOWING EXCEPTIONS: a. ALL WIRING THAT IS INSTALLED IN AREAS THAT DO NOT HAVE CEILINGS OR WHERE WIRING WOULD BE EXPOSED SHALL BE INSTALLED IN CONDUIT COMPLETE. 5. ALL CONDUIT PENETRATIONS THRU THE FLOOR SLAB SHALL BE MADE WITH CAUTION. CONTRACTOR SHALL COORDINATE ALL HOLE LOCATIONS WITH STRUCTURAL ENGINEER PRIOR TO CUTTING ANY NEW HOLES. NEW HOLES SHALL BE ADJUSTED AS REQUIRED TO MISS REBAR AS DETERMINED BY THE STRUCTURAL ENGINEER. 200A MLO LOT60B 1P -3W 120/240 F200 SECOND FLOOR FIRST FLOOR THIRD FLOOR FOURTH FLOOR BUILDING EXTERIOR 120/240V, 1P, 3W UTILITY RISER DIAGRAM NOTE: UNIT PANEL FEEDERS TO BE ROUTED UNDERGROUND INTO BUILDING FROM METER CENTER AND UP THROUGH WALLS TO PANELS. TOWNHOME METER CENTER 1600A, 120/240V, 1 PHASE, 3 WIRE METER CENTER WITH 1600A MAIN CIRCUIT BREAKER AND FOUR 2-SOCKET, 1PH -IN / 1PH -OUT BRANCH UNITS WITH 400A/2P CIRCUIT BREAKER PER METER SOCKET. LABEL METER BREAKERS PER UTILITY COMPANY REQUIREMENTS BASEMENT 400A MCB LOT60A 1P -3W 120/240 F400 ARCHITECT BLACKLINE 1 N MERIDIAN ST, SUITE 400 INDIANAPOLIS, INDIANA 46204 BLACKLINESTUDIO.NET 317.803.790 M.E.P. GENESIS ENGINEERING GROUP 91 SOUTH MAIN STREET, SUITE 200 ZIONSVILLE, IN 46077 GENESIS-ENGINEERING.COM 317.927.8307 STRUCTURAL SCHWARZ ENGINEERING GROUP WWW.SCHWARZINC.COM 317.850.5133 - - ALL INFORMATION CONTAINED IN THIS DOCUMENT IS CONSIDERED TO BE BOTH CONFIDENTIAL AND PROPRIETARY INTELLECTUAL PROPERTY OF BLACKLINE STUDIO AND SHALL NOT BE COPIED, REPRODUCED, DISTRIBUTED OR ASSIGNED TO A THIRD PARTY WITHOUT PRIOR WRITTEN CONSENT OF BLACKLINE STUDIO. UNAUTHORIZED USE OF THESE DOCUMENTS IS NOT PERMITTED. CERTIFICATION: CHECKED:DRAWN: C:\Users\jfakes\Documents\Custom Living Monon on Main Town Homes GEG R18_jfakes.rvt 4/29/2019 5:56:52 PM E60-6COPYRIGHT 2018 ELECTRICAL SCHEDULESMonon & Main Brownstones Monon & Main St., Carmel INJAWJAW Monon and Main Brownstone Interior Remodel – Unit 60 04/29/2019 Lot 60 -HANNUM RESIDENCE# REVISION Date Remarks: Total Est. Demand Current: 0 A Total Conn. Current: 0 A Total Est. Demand: 0 VA Total Conn. Load: 0 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals Load Sumamry: Total Load: 0.0 kVA 0.0 kVA 0LOT60B (SUB FEED)0 59 SPARE (GFCI / AFCI) 20 A 1 0 0 1 20 A SPARE (GFCI / AFCI) 60 57 SPARE (GFCI / AFCI) 20 A 1 0 0 1 20 A SPARE (GFCI / AFCI) 58 55 SPARE (GFCI / AFCI) 20 A 1 0 0 1 20 A SPARE (GFCI / AFCI) 56 53 SPARE (GFCI / AFCI) 20 A 1 0 0 1 20 A SPARE (AFCI) 54 51 SPARE (GFCI / AFCI) 20 A 1 0 0 1 20 A SPARE (AFCI) 52 49 2ND FLOOR LIVING ROOM RECS (AFCI) 20 A 1 0 0 1 20 A SPARE (AFCI) 50 47 2ND FLOOR LIVING ROOM RECS (AFCI) 20 A 1 0 0 1 20 A SPARE (AFCI) 48 45 2ND FLOOR DINING RECS (AFCI) 20 A 1 0 0 1 20 A SPARE (AFCI) 46 432ND FLOOR BATHROOM (GFCI / AFCI) 20 A 1 0 0 1 20 A SPARE (AFCI) 44 41 2ND FLOOR KITCHEN RECS (GFCI / AFCI) 20 A 1 0 0 1 20 A SPARE (AFCI) 42 39 2ND FLOOR KITCHEN RECS (GFCI / AFCI) 20 A 1 0 0 1 20 A 1-3 FRONT EXTERIOR RECEPTACLES (GFCI / AFCI) 40 37 2ND FLOOR KITCHEN RECS (GFCI / AFCI) 20 A 1 0 0 1 20 A 1ST FLOOR HALL RECS (AFCI) 38 35 2ND FLOOR ISLAND RECS (GFCI / AFCI) 20 A 1 0 0 1 20 A 1ST FLOOR BEDROOM RECS (AFCI) 36 33 2ND FLOOR GARBAGE DISPOSAL (GFCI / AFCI) 20 A 1 0 0 1 20 A 1ST FLOOR BEDROOM RECS (AFCI) 34 31 2ND FLOOR DISHWASHER (GFCI / AFCI) 20 A 1 0 0 1 20 A 1ST FLOOR BATH (GFCI / AFCI) 32 29 2ND FLOOR HOOD (AFCI) 20 A 1 0 0 1 20 A 1ST FLOOR WASHER (GFCI / AFCI) 30 27 2ND FLOOR REFRIGERATOR (AFCI) 20 A 1 0 0 28 25 0 0 2 30 A 1ST FLOOR DRYER 26 23 OVEN 30 A 2 0 0 1 20 A GARAGE RECEPTACLES (GFCI / AFCI) 24 21 0 0 1 20 A GARAGE DOOR OPENER (GFCI / AFCI) 22 19 RANGE 50 A 2 0 0 1 20 A BASEMENT FURNACE (AFCI) 20 17 0 0 1 20 A BASEMENT MECHANICAL RECS (AFCI) 18 15 SPARE 20 A 2 0 0 1 20 A DATA RACK (AFCI) 16 13 SUMP PUMP (GFCI / AFCI) 20 A 1 0 0 1 20 A DATA RACK (AFCI) 14 11 SUMP PUMP (GFCI / AFCI) 20 A 1 0 0 1 20 A LOW VOLTAGE PANEL (AFCI) 12 9 0 0 1 20 A ALARM PANEL (AFCI) 10 7 SPARE 20 A 2 0 0 1 20 A WATER HEATER (GFCI / AFCI) 8 5 LIFT LIGHTING AND CONTROLS (AFCI / GFCI) 20 A 1 0 0 1 20 A 2ND FLOOR LIGHTING (AFCI) 6 3 0 0 1 20 A 1ST FLOOR LIGHTING (AFCI) 4 1 LIFT (SHUNT TRIP) 30 A 2 0 0 1 20 A BASEMENT LIGHTING (AFCI) 2 Circuit Number Circuit Description Trip Poles A B Poles Trip Circuit Description Circuit Number General Panel Comments: Enclosure Type: Type 1 Ground: YES Main Rating: 400A Mounting: Recessed Wire: 3 Main Type: MCB Supplied From: Phase: 1 A.I.C. Rating: TBD Location: GARAGE 107 Voltage: 120/240 Single Branch: NORMAL Branch Panel: LOT60A Remarks: Total Est. Demand Current: 0 A Total Conn. Current: 0 A Total Est. Demand: 0 VA Total Conn. Load: 0 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals Load Sumamry: Total Load: 0.0 kVA 0.0 kVA 41 PROVISION -- -- 0 0 -- -- PROVISION 42 39 PROVISION -- -- 0 0 -- -- PROVISION 40 37 PROVISION -- -- 0 0 -- -- PROVISION 38 35 SPARE (GFCI / AFCI) 20 A 1 0 0 1 20 A SPARE (GFCI / AFCI) 36 33 SPARE (GFCI / AFCI) 20 A 1 0 0 1 20 A SPARE (GFCI / AFCI) 34 31 SPARE (GFCI / AFCI) 20 A 1 0 0 1 20 A SPARE (GFCI / AFCI) 32 29 SPARE (AFCI) 20 A 1 0 0 1 20 A 4TH FLOOR MECHANICAL RECS (AFCI) 30 27 SPARE (AFCI) 20 A 1 0 0 1 20 A 4TH FLOOR BATHROOM (GFCI / AFCI) 28 25 SPARE (AFCI) 20 A 1 0 0 1 20 A 4TH FLOOR U/C REFRIGERATOR (AFCI) 26 23SPARE (AFCI) 20 A 1 0 0 1 20 A 4TH FLOOR GAME ROOM RECS (AFCI) 24 21 4TH FLOOR FURNACE (AFCI) 20 A 1 0 0 1 20 A 4TH FLOOR GAME ROOM RECS (AFCI) 22 19 0 0 1 20 A 4TH FLOOR DECK RECS (GFCI / AFCI) 20 17 SPARE 20 A 2 0 0 1 20 A 3RD FLOOR HALL RECS (AFCI) 18 15 0 0 1 20 A 3RD FLOOR WASHER (GFCI / AFCI) 16 13 SPARE 20 A 2 0 0 1 20 A 3RD FLOOR BATHROOM (GFCI / AFCI) 14 11 0 0 1 20 A 3RD FLOOR BATHROOM (GFCI / AFCI) 12 9 3RD FLOOR DRYER 30 A 2 0 0 1 20 A 3RD FLOOR BATHROOM (GFCI / AFCI) 10 7 0 0 1 20 A 3RD FLOOR BEDROOM RECS (AFCI) 8 5 4TH FLOOR CONDENSER 40 A 2 0 0 1 20 A 3RD FLOOR BEDROOM RECS (AFCI) 6 3 0 0 1 20 A 4TH FLOOR LIGHTING (AFCI) 4 1 4TH FLOOR CONDENSER 40 A 2 0 0 1 20 A 3RD FLOOR LIGHTING (AFCI) 2 Circuit Number Circuit Description Trip Poles A B Poles Trip Circuit Description Circuit Number General Panel Comments: Enclosure Type: Type 1 Ground: YES Main Rating: 200A Mounting: Surface Wire: 3 Main Type: MLO Supplied From: Phase: 1 A.I.C. Rating: TBD Location: MECH 2 400 Voltage: 120/240 Single Branch: NORMAL Branch Panel: LOT60B 06/12/19 Mike Sheeks