HomeMy WebLinkAboutE60-6FEEDER AND BRANCH CIRCUIT
SCHEDULE
NOTE: SEE DRAWINGS FOR NUMBER OF WIRES IN HOMERUN
FEEDER/BRANCH CIRCUIT
DESIGNATION
CONDUCTOR SIZE TYPE CABLE CONDUIT
PHASE & NEUTRAL EQUIPMENT
GROUND ALUMINUM COPPER
F20 12 12 X NM
F30 10 10 X NM
F40-50 8 10 X NM
F60 6 10 X MC
F70-80 4 8 X MC
F90 3 8 X MC
F100 3 8 X MC
F125 1/0 4 X MC
F150 3/0 4 X 2-1/2"
F175 4/0 4 X 2-1/2"
F200 250 4 X 3"
F225 300 2 X 3"
F250 350 2 X 3"
F300 500 2 X 3-1/2"
F350 2 RUNS OF 4/0 1 X 2-1/2"
F400 2 RUNS OF 250 1 X 3" EACH
F600 2 RUNS OF 500 2/0 X 3-1/2" EACH
F800 3 RUNS OF 400 3/0 X 3-1/2" EACH
F1000 3 RUNS OF 600 4/0 X 4" EACH
F1200 4 RUNS OF 500 250 X 3-1/2" EACH
F1600 5 RUNS OF 600 350 X 4" EACH
F2000 6 RUNS OF 600 400 X 4" EACH
F2500 7 RUNS OF 750 600 X 5" EACH
F3000 8 RUNS OF 750 600 X 5" EACH
NOTES:
1. 20 A BRANCH CIRCUITS SHALL BE SIZED FOR VOLTAGE DROP. WIRE SIZES ARE NOT INDICATED ON THE DRAWINGS TO
COMPENSATE FOR VOLTAGE DROP. FOR THESE CIRCUITS, CONTRACTOR SHALL UTILIZE WIRE SIZE SHOWN ABOVE FOR
DISTANCES LISTED ABOVE.
2. VOLTAGE DROP WIRE SIZES WILL BE STRICTLY ENFORCED. CONTRACTOR SHALL SUBMIT A LIST OF CIRCUITS THAT WILL
EXCEED THE DISTANCES ALLOWED AND INDICATE WIRE SIZE TO BE USED PRIOR TO ANY WIRE BEING INSTALLED.
3. DO NOT SHARE NEUTRAL CONDUCTORS FOR ANY BRANCH CIRCUITS. ALL BRANCH CIRCUIT SHALL HAVE SEPARATE,
INDEPENDENT NEUTRAL CONDUCTORS.
4. ALL BRANCH CIRCUIT WIRING SHALL BE NM AND MC CABLE WITH THE FOLLOWING EXCEPTIONS:
a. ALL WIRING THAT IS INSTALLED IN AREAS THAT DO NOT HAVE CEILINGS OR WHERE WIRING WOULD BE EXPOSED
SHALL BE INSTALLED IN CONDUIT COMPLETE.
5. ALL CONDUIT PENETRATIONS THRU THE FLOOR SLAB SHALL BE MADE WITH CAUTION. CONTRACTOR SHALL
COORDINATE ALL HOLE LOCATIONS WITH STRUCTURAL ENGINEER PRIOR TO CUTTING ANY NEW HOLES. NEW HOLES
SHALL BE ADJUSTED AS REQUIRED TO MISS REBAR AS DETERMINED BY THE STRUCTURAL ENGINEER.
200A
MLO
LOT60B
1P -3W
120/240
F200
SECOND FLOOR
FIRST FLOOR
THIRD FLOOR
FOURTH FLOOR
BUILDING EXTERIOR
120/240V, 1P, 3W
UTILITY
RISER DIAGRAM NOTE:
UNIT PANEL FEEDERS TO BE ROUTED UNDERGROUND INTO BUILDING FROM
METER CENTER AND UP THROUGH WALLS TO PANELS.
TOWNHOME METER CENTER
1600A, 120/240V, 1 PHASE, 3 WIRE METER CENTER WITH 1600A MAIN
CIRCUIT BREAKER AND FOUR 2-SOCKET, 1PH -IN / 1PH -OUT BRANCH
UNITS WITH 400A/2P CIRCUIT BREAKER PER METER SOCKET. LABEL
METER BREAKERS PER UTILITY COMPANY REQUIREMENTS
BASEMENT
400A
MCB
LOT60A
1P -3W
120/240
F400
ARCHITECT
BLACKLINE
1 N MERIDIAN ST, SUITE 400
INDIANAPOLIS, INDIANA 46204
BLACKLINESTUDIO.NET
317.803.790
M.E.P.
GENESIS ENGINEERING GROUP
91 SOUTH MAIN STREET, SUITE 200
ZIONSVILLE, IN 46077
GENESIS-ENGINEERING.COM
317.927.8307
STRUCTURAL
SCHWARZ ENGINEERING GROUP
WWW.SCHWARZINC.COM
317.850.5133
-
-
ALL INFORMATION CONTAINED IN THIS DOCUMENT IS
CONSIDERED TO BE BOTH CONFIDENTIAL AND
PROPRIETARY INTELLECTUAL PROPERTY OF BLACKLINE
STUDIO AND SHALL NOT BE COPIED, REPRODUCED,
DISTRIBUTED OR ASSIGNED TO A THIRD PARTY WITHOUT
PRIOR WRITTEN CONSENT OF BLACKLINE STUDIO.
UNAUTHORIZED USE OF THESE DOCUMENTS IS NOT
PERMITTED.
CERTIFICATION:
CHECKED:DRAWN: C:\Users\jfakes\Documents\Custom Living Monon on Main Town Homes GEG R18_jfakes.rvt
4/29/2019 5:56:52 PM E60-6COPYRIGHT 2018 ELECTRICAL SCHEDULESMonon & Main Brownstones
Monon & Main St., Carmel INJAWJAW
Monon and Main Brownstone
Interior Remodel – Unit 60
04/29/2019 Lot 60 -HANNUM RESIDENCE# REVISION Date
Remarks:
Total Est. Demand Current: 0 A
Total Conn. Current: 0 A
Total Est. Demand: 0 VA
Total Conn. Load: 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Load Sumamry:
Total Load: 0.0 kVA 0.0 kVA
0LOT60B (SUB FEED)0
59 SPARE (GFCI / AFCI) 20 A 1 0 0 1 20 A SPARE (GFCI / AFCI) 60
57 SPARE (GFCI / AFCI) 20 A 1 0 0 1 20 A SPARE (GFCI / AFCI) 58
55 SPARE (GFCI / AFCI) 20 A 1 0 0 1 20 A SPARE (GFCI / AFCI) 56
53 SPARE (GFCI / AFCI) 20 A 1 0 0 1 20 A SPARE (AFCI) 54
51 SPARE (GFCI / AFCI) 20 A 1 0 0 1 20 A SPARE (AFCI) 52
49 2ND FLOOR LIVING ROOM RECS (AFCI) 20 A 1 0 0 1 20 A SPARE (AFCI) 50
47 2ND FLOOR LIVING ROOM RECS (AFCI) 20 A 1 0 0 1 20 A SPARE (AFCI) 48
45 2ND FLOOR DINING RECS (AFCI) 20 A 1 0 0 1 20 A SPARE (AFCI) 46
432ND FLOOR BATHROOM (GFCI / AFCI) 20 A 1 0 0 1 20 A SPARE (AFCI) 44
41 2ND FLOOR KITCHEN RECS (GFCI / AFCI) 20 A 1 0 0 1 20 A SPARE (AFCI) 42
39 2ND FLOOR KITCHEN RECS (GFCI / AFCI) 20 A 1 0 0 1 20 A 1-3 FRONT EXTERIOR RECEPTACLES (GFCI / AFCI) 40
37 2ND FLOOR KITCHEN RECS (GFCI / AFCI) 20 A 1 0 0 1 20 A 1ST FLOOR HALL RECS (AFCI) 38
35 2ND FLOOR ISLAND RECS (GFCI / AFCI) 20 A 1 0 0 1 20 A 1ST FLOOR BEDROOM RECS (AFCI) 36
33 2ND FLOOR GARBAGE DISPOSAL (GFCI / AFCI) 20 A 1 0 0 1 20 A 1ST FLOOR BEDROOM RECS (AFCI) 34
31 2ND FLOOR DISHWASHER (GFCI / AFCI) 20 A 1 0 0 1 20 A 1ST FLOOR BATH (GFCI / AFCI) 32
29 2ND FLOOR HOOD (AFCI) 20 A 1 0 0 1 20 A 1ST FLOOR WASHER (GFCI / AFCI) 30
27 2ND FLOOR REFRIGERATOR (AFCI) 20 A 1 0 0 28
25 0 0 2 30 A 1ST FLOOR DRYER 26
23 OVEN 30 A 2 0 0 1 20 A GARAGE RECEPTACLES (GFCI / AFCI) 24
21 0 0 1 20 A GARAGE DOOR OPENER (GFCI / AFCI) 22
19 RANGE 50 A 2 0 0 1 20 A BASEMENT FURNACE (AFCI) 20
17 0 0 1 20 A BASEMENT MECHANICAL RECS (AFCI) 18
15 SPARE 20 A 2 0 0 1 20 A DATA RACK (AFCI) 16
13 SUMP PUMP (GFCI / AFCI) 20 A 1 0 0 1 20 A DATA RACK (AFCI) 14
11 SUMP PUMP (GFCI / AFCI) 20 A 1 0 0 1 20 A LOW VOLTAGE PANEL (AFCI) 12
9 0 0 1 20 A ALARM PANEL (AFCI) 10
7 SPARE 20 A 2 0 0 1 20 A WATER HEATER (GFCI / AFCI) 8
5 LIFT LIGHTING AND CONTROLS (AFCI / GFCI) 20 A 1 0 0 1 20 A 2ND FLOOR LIGHTING (AFCI) 6
3 0 0 1 20 A 1ST FLOOR LIGHTING (AFCI) 4
1 LIFT (SHUNT TRIP) 30 A 2 0 0 1 20 A BASEMENT LIGHTING (AFCI) 2
Circuit
Number Circuit Description Trip Poles A B Poles Trip Circuit Description
Circuit
Number
General Panel Comments:
Enclosure Type: Type 1 Ground: YES Main Rating: 400A
Mounting: Recessed Wire: 3 Main Type: MCB
Supplied From: Phase: 1 A.I.C. Rating: TBD
Location: GARAGE 107 Voltage: 120/240 Single Branch: NORMAL
Branch Panel: LOT60A
Remarks:
Total Est. Demand Current: 0 A
Total Conn. Current: 0 A
Total Est. Demand: 0 VA
Total Conn. Load: 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Load Sumamry:
Total Load: 0.0 kVA 0.0 kVA
41 PROVISION -- -- 0 0 -- -- PROVISION 42
39 PROVISION -- -- 0 0 -- -- PROVISION 40
37 PROVISION -- -- 0 0 -- -- PROVISION 38
35 SPARE (GFCI / AFCI) 20 A 1 0 0 1 20 A SPARE (GFCI / AFCI) 36
33 SPARE (GFCI / AFCI) 20 A 1 0 0 1 20 A SPARE (GFCI / AFCI) 34
31 SPARE (GFCI / AFCI) 20 A 1 0 0 1 20 A SPARE (GFCI / AFCI) 32
29 SPARE (AFCI) 20 A 1 0 0 1 20 A 4TH FLOOR MECHANICAL RECS (AFCI) 30
27 SPARE (AFCI) 20 A 1 0 0 1 20 A 4TH FLOOR BATHROOM (GFCI / AFCI) 28
25 SPARE (AFCI) 20 A 1 0 0 1 20 A 4TH FLOOR U/C REFRIGERATOR (AFCI) 26
23SPARE (AFCI) 20 A 1 0 0 1 20 A 4TH FLOOR GAME ROOM RECS (AFCI) 24
21 4TH FLOOR FURNACE (AFCI) 20 A 1 0 0 1 20 A 4TH FLOOR GAME ROOM RECS (AFCI) 22
19 0 0 1 20 A 4TH FLOOR DECK RECS (GFCI / AFCI) 20
17 SPARE 20 A 2 0 0 1 20 A 3RD FLOOR HALL RECS (AFCI) 18
15 0 0 1 20 A 3RD FLOOR WASHER (GFCI / AFCI) 16
13 SPARE 20 A 2 0 0 1 20 A 3RD FLOOR BATHROOM (GFCI / AFCI) 14
11 0 0 1 20 A 3RD FLOOR BATHROOM (GFCI / AFCI) 12
9 3RD FLOOR DRYER 30 A 2 0 0 1 20 A 3RD FLOOR BATHROOM (GFCI / AFCI) 10
7 0 0 1 20 A 3RD FLOOR BEDROOM RECS (AFCI) 8
5 4TH FLOOR CONDENSER 40 A 2
0 0 1 20 A 3RD FLOOR BEDROOM RECS (AFCI) 6
3 0 0 1 20 A 4TH FLOOR LIGHTING (AFCI) 4
1 4TH FLOOR CONDENSER 40 A 2
0 0 1 20 A 3RD FLOOR LIGHTING (AFCI) 2
Circuit
Number Circuit Description Trip Poles A B Poles Trip Circuit Description
Circuit
Number
General Panel Comments:
Enclosure Type: Type 1 Ground: YES Main Rating: 200A
Mounting: Surface Wire: 3 Main Type: MLO
Supplied From: Phase: 1 A.I.C. Rating: TBD
Location: MECH 2 400 Voltage: 120/240 Single Branch: NORMAL
Branch Panel: LOT60B
06/12/19
Mike Sheeks