MECHANICAL ABBREVIATIONS
ABBREVIATION
DESCRIPTION
ABBREVIATION
DESCRIPTION
A
AMPS
LDB
LEAVING DRY BULB
AC
AIR CONDITIONER
IPs
LITERS PER SECOND
AMB
AMBIENT
LVG
LEAVING
APO
AIR PRESSURE DROP
LWB
LEAVING WET BULB TEMPERATURE
APPROX.
APPROXIMATE
LW/
LEAVING WATER TEMPERATURE
ATFP
ANTI TERRORISM FORCE PROTECTION
MAX
MAXIMUM
BTUH
BRITISH THERMAL UNITS PER HOUR
MBH
1,000 BRITISH THERMAL UNITS PER HOUR
C
CENTIGRADE
MCA
MAXIMUM CURRENT AMPS
CAP
CAPACITY
MERV
MINIMUM EFFICIENCY REPORTING VALUE
CC
COOLING COIL
MFG
MANUFACTURER
CFM
CUBIC FEET PER MINUTE
MIN
MINIMUM
CHW
CHILLED WATER
min
MILLIMETER
CHWR
CHILLED WATER RETURN
MOCP
MAXIMUM OVERCURRENT PROTECTION
CHWS
CHILLED WATER SUPPLY
MPS
MEDIUM PRESSURE STEAM
COP
COEFFICIENT OF PERFORMANCE
MTD
MOUNTED
CR
CONDENSATE RETURN
MU
MAKE-UP
CU
CONDENSING UNIT
NC
NOISE CRITERION
CW
COLD WATER
NEMA
NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
DOC
DIRECT DIGITAL CONTROL
NFPA
NATIONAL FIRE PROTECTION
ASSOCIATION
D/L
DOOR LOUVER
NMCI
NAVY MARINE CORPS INTRANET
DSD
DUCT SMOKE DETECTOR
0 & M
OPERATION AND MAINTENANCE
DX
DIRECT EXPANSION
OBD
OPPOSED BLADE DAMPER
(E)
EXISTING
OSA
OUTSIDE AIR
EA
EXHAUSTAIR
Pa
PASCALS
EAT
ENTERING AIR TEMPERATURE
PD
PRESSURE DROP
EDB
ENTERING DRY BULB TEMPERATURE
PH
PHASE
EER
ENERGY EFFICIENCY RATIO
PRV
PRESSURE REDUCING / RELIEF VALVE
EF
EXHAUST FAN
PSI
POUNDS PER SQUARE INCH
EL
EXPANSION LOOP
QTY
QUANTITY
ENT
ENTERING
RA
RETURN AIR
EQUIP
EQUIPMENT
REF
REFERENCE
ESP
EXTERNAL STATIC PRESSURE
REO'D
REQUIRED
EWB
ENTERING WET BULB TEMPERATURE
RF
RETURN FAN
ENIT
ENTERING WATER TEMPERATURE
RLA
RUNNING LOAD AMPS
F
FAHRENHEIT
RP
RECIRCULATING PUMP
FC
FAN COIL
RPM
REVOLUTIONS PER MINUTE
FLA
FULL LOAD AMPS
SA
SUPPLY AIR
FT HD
FOOT HEAD
SEER
SEASONAL ENERGY EFFICIENCY RATIO
GAL
GALLON
SF
SUPPLY FAN
GALV
GALVANIZED
Si
SEISMIC JOINT
GLYR
GLYCOL RETURN
SMACNA
SHEET METAL AND AIR CONDITIONING
CONTRACTORS' NATIONAL ASSOCIATION
GLYS
GLYCOLSUPPLY
SO FT
SQUAREFOOT
GPM
GALLONS PER MINUTE
T
TRAP
HHW
HEATING HOT WATER
TAB
TEST AND BALANCE
HHWM2
HEATING HOT WATER RETURN
TSP
TOTAL STATIC PRESSURE.
HHWS
HEATING HOT WATER SUPPLY
TSTAT
THERMOSTAT
HP
HEAT PUMP
TYP
TYPICAL
HP
HORSEPOWER
U/C
UNDERCUT
HR
HOUR
U/G
UNDERGROUND
HSPF
HEATING SEASONAL PERFORMANCE FACTOR
UPC
UNIFIED FACILITIES CRITERIA
HV
HEAT VENTILATOR
UON
UNLESS OTHERWISE NOTED
HW
HOTWATER
V
VOLTAGE/VOLTS
HX
HEAT EXCHANGER
VAV
VARIABLE AIR VOLUME
Hz
HERTZ
VE
VEHICLE EXHAUST SYSTEM
in-wg
INCHES WATER GAUGE
VFD
VARIABLE FREQUENCY DRIVE
in('
INCHES
W/
WITH
IPLV
INTEGRATED PART LOAD VALUE
WB
WET BULB
IRH
INFARED HEATER
WPD
WATER PRESSURE DROP
LAT
LEAVING AIR TEMPERATURE
LBS
IPOUNDS
MECHANICAL LEGEND
®
SUPPLYDIFFUSER
RETURN/EXHAUST REGISTER
1i
200 CFM
XXX
DIFFUSER/REGISTER TAG
BALANCE DAMPER
®
FIRE DAMPER
®
ROUND SUPPLY DUCT RISER
®
RECTANGULAR SUPPLY DUCT RISER
MECHANICAL GENERAL NOTES
NOTE NUMBER
NOTE
1
DUCT FABRICATION AND INSTALLATION SHALL CONFORM TO THE "HVACDUCT CONSTRUCTION STANDARDS AS PUBLISHED BYS.M.AC.N.A.LATEST EDITION.
2
ALL BRANCHED TO DIFFUSERS AND REGISTERS SHALL BE SUPPLIED WITH MANUAL VOLUME DAMPERS. ALL DAMPERS THATARE INACCESSIBLE SHALL BE PROVIDED WITH
REMOTE OPERATORS SIMILAR TO VENTLOK677-PLAIN FINISH
3
ALL MISCELLANEOUS METAL, ANGLES, BRACING OR SUPPORTS EXPOSED TO THE WEATHER SHALL BE GALVANIZED IRON OR BLACK IRON PAINTED WITH ONE COAT OF
RUST INHIBITING PAINTAND ONE COAT OF GRAY PRIMER.
4
PENETRATIONS IN FIRE -RESISTIVE WALLS, PARTITIONSAND FLOORS WHERE PROTECTED OPENINGS ARE REQUIRED SHALL BE FIRE STOPPED USING APPROVED
MATERIALS, INTEGRITY AND PREVENTING THE MOVEMENT OF HOT FLAMES OR GASES THROUGH THE VOID SPACES BETWEEN PENETRATING MATERIALS AND WALLS,
PARTITIONS AND FLOORS WHEN TESTED IN ACCORDANCE WITH ASTM STANDARD E-814 OR U.L. STANDARD 1479.
5
ALL SUPPLY AND RETURN DUCTWORK AND PIPING SHALL BE INSULATED. INSULATION SHALL HAVE A FLAME SPREAD OF NOT MORE THAN 25 AND A SMOKE DEVELOPED
RATING OF NOT MORE THAN 50 WHEN TESTED AS A COMPOSITE INSTALLATION INCLUDING INSULATION FACING MATERIALS, TAPE, AND ADHESIVE.
6
FLEXIBLE DUCTS SHALL BE SUPPORTED AT OR NEAR MID -LENGTH WITH T WIDE 28 GUAGE STEEL HANGER COLLAR ATTACHED TO THE STRUCTURE WITH AN APPROVED
DUCT HANGER. INSTALLATION SHALL MINIMIZE SHARP RADIUS TURNS OR OFFSETS. THE MAXIMUM LENGTH CONNECTING TO TERMINAL OUTLETS SHALL BE G-0".
7
CONSTRUCTION PRESSURE CLASSIFICATION: SUPPLY AND RETURN DUCT TO BE 1" STATIC PRESSURE CONSTRUCTION. DUCT LEAKAGE TEST NOT REQUIRED. RETURN AND
EXHAUST DUCT TO BE 1" STATIC PRESSURE CONSTRUCTION, UNLESS OTHERWISE NOTED. DUCT LEAKAGE TEST NOT REQUIRED UNLESS OTHERWISE NOTED.
8
DIMENSIONS SHOWN ON DRAWINGS ARE CLEAR INSIDE DIMENSIONS.
9
FOR AV ROOMS THE REFRIGERANT SUPPLY AND SUCTION LINES, THE POWER AND CONTROL CABLES AND THE CONDENSATE DRAIN PIPING SHALL BE CONTAINED IN A
SINGLE CONDUIT PENETRATION.
10
CONTRACTOR SHALL COORDINATE ACTUAL LOCATIONS OF EQUIPMENT, STRUCTURAL BRACING, AND UTILITY REQUIREMENTS WITH OTHER TRADES.
11
ALL EQUIPMENT SHALL BE PROVIDED WITH MANUFACTURER'S HIGHEST EFFICIENCY MOTOR OPTION.
12
ROUND DUCT MAY BE USED IN PLACE OF SQUARE OR RECTANGULAR DUCT. ROUND DUCT SHALL BE SIZED USING A DUCTULATOR WITH FRICTION LOSS OF 0.08" TO CAW
PER 100 FEET OF DUCT.
13
ALL WORK SHALL CONFORM TO THE APPLICABLE FEDERAL, STATE, AND LOCAL CODES.
EXHAUST FAN
SCHEDULE
APPROX REMARKS
WEIGHT
DESCRIPTION
ELECTRICAL DATA
CAPACITIES
ESP
SYMBOL
EQUIPMENT
WATTS
VOLTS
PHASE
CFM
(Wffi)
EF-1
EXHAUST FAN - CEILING
5
115
1
100
025
30
PROVIDE WITH BACKDRAFT DAMPER, DISCONNECT,
GREENHECK: SP-A125
.
POTENTIOMETER MOUNTED ON FAN AND ROOF CAP
AIR DISTRIBUTION SCHEDULE
SYMBOL
MAKE & MODEL
AIRFLOW
SIZE
REMARKS
(CFM)
(IN)
A
KRUEGER
100-175
8x8
STEEL SUPPLY DIFFUSER WITH WHITE FINISH, NO OBDs,
SERIES 1240
24x24 FILLER PANEL FOR T-BAR MOUNTING (WHERE REQUIRED)
B
KRUEGER
10x10
STEEL SUPPLY DIFFUSER WITH WHITE FINISH, NO OBDs,
SERIES 1240-
24x24 FILLER PANEL FOR T-BAR MOUNTING (WHERE REQUIRED)
AA
KRUEGER
�
18x18
STEEL RETURN REGISTER WITH WHITE FINISH, NO OBDs, PLENUM RETURN
SERIES SBOH
24x24 FILLER PANEL FORT -BAR MOUNTING (WHERE REQUIRED)
BB
KRUEGER
800 1100
24x24
STEEL RETURN REGISTER WITH WHITE FINISH, NO OBDs, PLENUM RETURN
SERIES SBOH
2424 FILLER PANEL FORT -BAR MOUNTING (WHERE REQUIRED)
CC
KRUEGER
1000-1400
24x24
STEEL RETURN REGISTER WITH WHITE FINISH, NO OBDs,
SERIES SBOH
PROVIDE SECURITY BAR BEHIND REGISTER
0
_ U
m
m z
o
ail
Q��
z
a��
o
��E
a
0
a
0
U
QµOFESS�Q
4� N9l
NO. PE10910442 c
m
0 Y. A
r P
STH F OF �NO� �P
�t Eoonooa=°
°o0 -sea„„o_da Ea
a e Deb - 38e�ro=3-�€
a a�omva020 cc �Uizuom roEE�vo
e W 2;z De FEcvg5E°`2
8 vEov ' _; eeoaosm
o® fa��o3rs of°-vuUzo
a"-m
bsum
& ° PEa °usuo➢6-
a`o"u 86 ss „
0
0
.N
y
E
0
U
w
75
U
L
J
`o
0
�
�
0
J
`0�
m
Q
> >
QN
I..I..I
Cc Q
n
N
Nz
ca C
f
L
cc0
2
4 N N
w m
E
D
'D 'O Now
a S2
"NU
# Date
Pp0JE7 STATUS
STATE SUBMITTAL
PROJECT#
PROJEMMUEDATE'
19149
20190507
DRAWNBr
REVEWED or
KAC
LLA
saEaTTLE,
MECHANICAL LEGEND
RELEASED FOR CONSTRUCTION
Subject to compliance with all regulations
of State and meal Codes
City of Cannel
DATE: 06/27/19
5HETNUMBER