HomeMy WebLinkAboutLEGACY RIDGE 101 - LR101 (AS DESIGNED)IECC 2009 Performance Compliance
Property
6707 PULASKI LN
CARMEL, IN 46033
Model: SOUTHILL (B)
Community: LEGACY RIDGE 101
LR101 (AS DESIGNED)
LEGACY RIDGE 101
Organization
TSI Energy Solutions
Matthew Timmons
Builder
LENNAR HOMES
Design
Heating
Cooling
Water Heating
SubTotal - Used to determine compliance
Lights & Appliances
Onsite generation
Total
Inspection Status
Results are projected
Annual Energy Cost
IECC 2009 Performance
$1,758
$281
$416
$2,455
$957
$0
$3,412
Requirements
C-M,
Energy Solutions
As Designed
51,767
S270
S416
$2,453
S957
S0
$3,410
C4405.3 Performance-based compliance passes by 0.1%
402.4.12 Air Leakage Testing Air sealing is 6.DD ACH at 5D Pa. It must not exceed 7 -DD ACH at 50 Pa.
C4402.5 Area -weighted average fenestration SHGG
402.5 Area -weighted average fenestration 11 -11 -Factor
40322 Duct Testing
Mandatory Checklist Mandatory code requirements that are not
checked by Ekotrope must be met.
R4052 Duct Insulation
Design exceeds requirements for IECC 2009 Performance compliance by 0.1%.
As a 3rd party extension of the code jurisdiction utilizing these reports, I certify that this energy code compliance document has been created in accordance with the requirements of
Chapter 4 of the adopted International Energy Conservation Code based on Climate Zone 5. If rating is Projected, I certify that the building design described herein is consistent with
the building plans, specifications, and other calculations submitted with the permit application. If rating is Confirmed, I certify that the address referenced above has been
inspected/tested and that the mandatory provisions of the IECC have been installed to meet or exceed the intent of the IECC orwill be verified as such by another party.
Name: Matthew Timmons
Organization: TSI Energy Solutions
Signature:
Date:
411119 at 10:49 AM
Ekotrope RATER - Version 3.1.0.2142
IECC 2009 Performance compliance results calculated using Ekotrope RATER's energy and code compliance algorithm.
Ekotrope RATER is a RESIN ET Accredited HERS Rating Tool. All results are based on data entered by Ekotrope users.
Ekotrope disclaims all liability for the information shown on this report.
6707 PULASKI LN
I�,FTM
CARMEL, IN 46033
Builder: LENNAR HOMES
Ceiling Attic, R-38
Above Grade Walls R-16
Foundation Walls R-11
Framed Floor R-38
Slab R-0.0 Perimeter, R-0.0 Under
Infiltration 6 ACH50
Window U -Value: 0.31, SHGC: 0.32
Building Features
Duct Supply R-30.0, Return R-30.0
Duct Leakage to Outside 327.0 CFM @ 25Pa
Total Duct Leakage 436.0 CFM @ 25Pa
Heating Furnace • Natural Gas • 95.5 AFUE
Cooling Air Conditioner • Electric • 13 SEER
Water Heating Water Heater • Electric • 0.93 Energy Factor
As a 3rd party extension of the code jurisdiction utilizing these reports, I certify that this energy code compliance document has been created in accordance with the requirements of
Chapter 4 of the adopted International Energy Conservation Code based on Climate Zone 5. It rating is Projected, I certify that the building design described herein is consistent with the
building plans, specifications. and other calculations submitted with the permit application. If rating is Confirmed, I certify that the address referenced above has been inspected/tested and
that the mandatory provisions of the I ECC have been installed to meet or exceed the intent of the IECC or will be verified as such by another party.
Name: Matthew Timmons
Organization: TSI Energy Solutions
Signature:
Date: 411119 at 10:49 AM
Ekotrope RATER - Version 3.1.0.2142
20091ECC compliance results calculated using Ekotrope RATER's energy and code compliance algorithm.
Ekotrope RATER is a RESIN ETAccredited HERS Rating Tool. All results are based on data entered by Ekotrope users.
Ekotrope disclaims all liability for the information sh own on this report.
Energy Code Inspection Checklist
Property Organization
6707 PULASKI LN TSI Energy Solutions
CARMEL, IN 46033 Matthew Timmons
Model: SOUTHILL (B)
Community: LEGACY RIDGE 101 Builder
LENNAR HOMES
LR101 (AS DESIGNED)
LEGACY RIDGE 101
General Building Information
Conditioned Area (sq ft) 5,454
Conditioned Volume (cubic ft) 51,120
Insulated Shell Area (sq ft) 9,401
Inspection Status
Results are projected
C-M,
Energy Solutions
The building energy model in Ekotrope reflects the building assemblies and energy features listed below. Sometimes energy
features will change in the field from what has been modeled. The inspection process should identity any changes and ensure
that the home continues to meet the applicable energy code.
Slab
] Name: BSMT (1,872 s.f.)
R-0 perimeter insulation, R-0 under slab insulation.
Framed Floor
El Name: OVER GAR (70 s.f.)
R-0 continuous insulation, R-38 cavity insulation
Insulation Grade: I
Foundation Wall
] Name: CONDIAMB (Exterior Perimeter [ft]: 168, Height Above Grade [ft]: 1, Depth Below Grade [ft]: 8)
R: 11.00
Feet from top of wall to top of insulation: 0, Feet from top of wall to bottom of insulation: 4
] Name: CONDIGAR (Exterior Perimeter [ft]: 31, Height Above Grade [ft]: 1, Depth Below Grade [ft]: 7)
R: 11.00
Feet from top of wall to top of insulation: 0, Feet from top of wall to bottom of insulation: 4
Above Grade Wall
El Name: CONDIAMB (2,397 s.f.)
R-3 continuous insulation, R-13 cavity insulation
Insulation Grade: I
El Name: CONDIAMB 2X6 (468 s.f.) 1
R-3 continuous insulation, R-19 cavity insulation
Insulation Grade: I
Energy Code Inspection Checklist
Property Organization
6707 PULASKI LN TSI Energy Solutions
CARMEL, IN 46033 Matthew Timmons
Model: SOLITHILL (B)
Community: LEGACY RIDGE 101 Builder
LENNAR HOMES
LR101 (AS DESIGNED)
LEGACY RIDGE 101
Name: CONDIGAR (279 s.f.)
R-0 continuous insulation, R-13 cavity insulation
Insulation Grade: I
Name: CONDIATTIC (248 s.f.)
R-3 continuous insulation, R-13 cavity insulation
Insulation Grade: I
Rim Joist
Name: CONDIAMB (303 s.f.)
R: 13.575
Name: CONDIGAR (31 s.f.)
R: 10.876
El Name: CONDIATTIC (31 s.f.)
R: 13.575
Roof
El Name: MAIN (1,942 s.f.)
R-27.55 continuous insulation, R-10.15 cavity insulation
Insulation Grade: I
Opaque Door
J --G Name: FRONT (20 s.f.)
U: 0.182
Name: GARAGE (18 s.f.)
U: 0.182
Glazing
Inspection Status
Results are projected
El Name: FRONT (184 s.f.), U:0.310, SHGC: 0.29, Orientation: EAST
El Name: BACK (228 s.f.), U:0.310, SHGC: 0.32, Orientation: WEST
C-M,
Energy Solutions
2
Energy Code Inspection Checklist
C-M
Energy Solutions
Property Organization Inspection Status
6707 PULASKI LN TSI Energy Solutions Results are projected
CARMEL, IN 46033 Matthew Timmons
Model: SOUTHILL (B)
Community: LEGACY RIDGE 101 Builder
LENNAR HOMES
LR101 (AS DESIGNED)
LEGACY RIDGE 101
E] Name: BACK BSMT (11 s.f.), U:0.320, SHGC: 0.31, Orientation: WEST
E] Name: SLIDER (40 s.f.), U:0.290, SHGC: 0.33, Orientation: WEST
El !Name: RIGHT SIDE (52 s.f.), U:0.310, SHGC: 0.32, Orientation: NORTH
El Name: LEFT SIDE (106 s.f.), U:0.310, SHGC: 0.32, Orientation: SOUTH
Skylight
None Present
Mechanical Ventilation
None Present
Mechanical Equipment
0 Fuel -fired air distribution (1) • Natural Gas • 100% Heating Load @ 95.5 AFUE
Air conditioner (2) • Electric • 100% Cooling Load @ 13 SEER
E] Water Heating (3) • Electric • 100% Hot Water Load @ 0.93 Energy Factor
Air Leakage Control
ElTest Status: Blower -door tested
House is air -sealed as to achieve 5,112 CFM50 (6.00 ACH50) or less at final blower -door test.
Infiltration Requirements for IECC in Climate Zone 5
2009 IECC Infiltration limit for the design home is 7 ACH50.
2012 IECC Infiltration limit for the design home is 3 ACH50.
2015 IECC Infiltration limit for the design home is 3 ACH50.
3
Energy Code Inspection Checklist
Property
6707 PULASKI LN
CARMEL, IN 46033
Model: SOUTHILL (13)
Community: LEGACY RIDGE 101
LR101 (AS DESIGNED)
LEGACY RI DG E 101
Duct Leakage
Duct System 1
Organization
TSI Energy Solutions
Matthew Timmons
Builder
LENNAR HOMES
Inspection Status
Results are projected
NOT entirely within conditioned space, testing required
Tested Post -Construction
Leakage to Outdoors is specified in Ekotrope at 327.0 CFM @ 25 Pa
Total Duct Leakage is specified in Ekotrope at 436.0 CFM @ 25Pa
Duct Leakage Code Requirements for IECC
2009 IECC:
Postconstruction Leakage Test: Duct Leakage to Outdoors <= 8 CFM25 / 100 sq ft CFA.
Rough in Test with AHU: Total Duct Leakage <= 6 CFM25 / 100 sq ft CFA.
Rough in Test without AHU: Total Duct Leakage <= 4 CFM25 / 100 sq ft CFA.
2012 IECC and 2015 IECC Prescriptive Path:
Postconstruction Leakage Test: Total Duct Leakage <= 4 CFM25 / 100 sq ft CFA.
Rough in Test with AHU: Total Duct Leakage <= 4 CFM25 / 100 sq ft CFA.
Rough in Test without AHU: Total Duct Leakage <= 3 CFM25 / 100 sq ft CFA.
2015 Performance Path (Cost Compliance):
C",
Energy Solutions
Leakage testing is required UNLESS all ducts and air handlers are located entirely within the thermal envelope.
There is no pass/fail threshold for duct leakage on the performance path.
Project Notes
4
Building Summary
C-M
Energy Solutions
Property Organization Inspection Status
6707 PULASKI LN TSI Energy Solutions Results are projected
CARMEL, IN 46033 Matthew Timmons
Model: SOUTHILL (B)
Community: LEGACY RIDGE 10 I Builder
LENNAR HOMES
-R1 01 (AS DESIGNED)
LEGACY RIDGE 101
I
enerAuilding Informationmber Of Bedrooms 4
mber Of Floors 2
nditioned Floor Area [sq_ ft.] 5;454
conditioned, attached garage? Yes
nditioned Volume [Cu. ft.] 51;120
tal Units in Building 1
sidence Type Single family detached
adel SOUTHILL (B)
mmunity LEGACY RIDGE 101
mate Zone 5A
Basement Wall
d6
Name Library Type Height Above Grade Depth Below Grade Perimeter Location Enclosing
CONDIAMB R-11 Draped, Oft 1 8 168 Exposed Exterior Conditioned Space
CONDIGAR R-11 Draped, Oft 1 7 31 Exposed Exterior Conditioned Space
Basement Wall Library List
Name Feet From Wall Tap To In suIation Feet From Wall Top Tb Insulation Is Fully Insulated Effective Insulation R -value
Top Bottom
R-11 Draped, 4ft 0 4 No 11.00
Slab
BSMT Uninsulated 1 Below Grade ❑ 0 1,872.0 sq. R. Exposed Exterior Conditioned
Space
Slab Library List
Name Wall C
Uninsulated Woad Frame / Other
Na ❑ 0 D 0.00
1
Building Summary
Property
Organization
6707 PULASKI LN
TSI Energy Solutions
CARMEL, IN 46033
Matthew Timmons
Model: SOUTHILL (B)
Surface Calor
Community: LEGACY RIDGE 101
Builder
CONDIAMB
LENNAR HOMES
-R1 01 (AS DESIGNED)
2,397.0 sq. ft.
LEGACY RIDGE 101
CONDIAMB 2X6
ramed Floor
Medium
Name Library Type
Ca
OVER GAR R-38, GRi
G1 R-13 BATT, R-3.0
Medium
248.0 sq. ft.
Framed Floor Library List
Name
Effective R -value
R-38, GRi
2
33.825
Rim Joist
Name Library Type
CONDIAMB G1 R-13, R-3.0
CONDIATTIC G1 R-13, R-3.0
CONDIGAR G1 R-13, OSB
Rim Joist Library List
Name Effective Insulation R -value
G1 R-13, OSB 10.876
G1 R-13. R-3.0 13.575
C-M
Energy Solutions
Inspection Status
Results are projected
e Surface Area Location
1.23 Above Grade 70.0 sq. ft Unconditioned, attached
garage
303.0 sq. ft.
Exposed Exterior
31.0 sq. 11 Attic
31.0 sq. ft. Unconditioned, attached garage
ali
Name
Library Type
Surface Calor
Surface Area
Location
CONDIAMB
G1 R-13 BATT, R-3.0
Medium
2,397.0 sq. ft.
Exposed Exterior
CONDIAMB 2X6
G1 R-19, R-3.0 2X6
Medium
468.0 sq. ft.
Exposed Exterior
CONDIATTIC
G1 R-13 BATT, R-3.0
Medium
248.0 sq. ft.
Attic
2
Building Summary
Property
6707 PULASKI LN
CARMEL, IN 46033
Model: SOUTHILL (B)
Community: LEGACY RIDGE 101
LR101 (AS DESIGNED)
LEGACY RIDGE 101
Name
Organization
TSI Energy Solutions
Matthew Timmons
Builder
LENNAR HOMES
Library Type
Inspection Status
Results are projected
Surface Calor
Surface Area
C-MEnergy Solutions
Location
CONDIGAR G1 R-13 Gar Walls
Medium
279.0 sq. ft.
Unconditioned, attached garage
Wall Library List
Name
Effective R -value
G1 R-13 BATT, R-3.0
15.12
G1 R-13 Gar Walls
11.141
G1 R-19, R-3.0 2X6
20217
Glazing
Name Library Type Wall
Assignment Basement Wall
Assignment
Overhang Depth Overhang Ft
Top
To Overhang Ft To
Bottom
Orientation
Surface Area
BACK U-.31, 3HGC-.32
CONDIAMB
0
0 0
West
228.0 sq. ft.
BACK BSMT U-.32, SHGC-.31
CONDIAMB
0
0 0
West
11.0 sq. ft.
FRONT U-.31, SHGG29
CONDIAMB
0
0 ❑
East
184.0 sq. ft.
LEFT SIDE U-.31, SHGG.32
CONDIAMB
0
0 ❑
South
106.0 sq. ft.
RIGHT SIDE U-.31, SHGG.32
CONDIAMB
0
0 ❑
North
52.0 sq. ft
SLIDER U-29, SHGG.33
CONDIAMB
0
0 ❑
West
40.0 sq. ft
Glazing Library List
Name
Shg c
U factor
U-29, SHGC-.33
0.33
0290
U-.31, SHGC-29
029
0.310
U-.31, SHGC-.32
0.32
0.310
U-.32, SHGC-.31
0.31
0.320
Building Summary
Property
6707 PULASKI LN
CARMEL, IN 46033
Model: SOUTHILL (B)
Community: LEGACY RIDGE 101
-R1 01 (AS DESIGNED)
LEGACY RIDGE 101
kyligh
Skylight Library List
Opaque Door
Organization
TSI Energy Solutions
Matthew Timmons
Builder
LENNAR HOMES
Inspection Status
Results are projected
C-M,
Energy Solutions
Name Library Type Wall Assignment Basement Wall Emittance Solar Surface Color Surface Area Location
Assignment Ab sorpta nce
FRONT Steel Door CONDIAMB 0.9 0.75 Medium 20.0 sq. ft Exposed Exterior
GARAGE Steel Door CONDIGAR 0.9 0.75 Medium 18.0 sq- ft Exposed Exterior
Opaque Door Library List
Name Effective U -factor
0.182
Roof Insulation
Name
Library Type
MAIN
R-38 Blown. GR1
krea Clay or Concrete Root
P.f.] Tiles
7,942 No
Roof Insulation Library List
Name Has Radiant Barrier Effective R -value
'•3 �- -I :a l No 38268
n
Medium 1,942.0 sq. ft Attic
4
Building Summary
Property
6707 PULASKI LN
CARMEL, IN 46033
Model: SOUTHILL (B)
Community: LEGACY RIDGE 10 I
LR101 (AS DESIGNED)
LEGACY RIDGE 101
loWhole House Infiltration
Infiltration
6 ACH at 50 Pa
Mechanical Ventilation
Lighting ,
°I Interior Fitiorescent
Lighting
Onsite Generation
Organization Inspection Status
TSI Energy Solutions Results are projected
Matthew Timmons
Builder
LENNAR HOMES
Blower -door tested 4
rang Y. txsenor rmorescem
Lighting
10❑ o
None Present
Onsite Generation Library List
None Present
Solar Generation
Solar Generation Library List
C-M,
Energy Solutions
Lighting
1❑0
Building Summary
Property
Organization
Inspection Status
6707 PULASKI LN
TSI Energy Solutions
Results are projected
CARMEL, IN 46033
Matthew Timmons
PSG (Single Speed)
Model: SOUTHILL (B)
95.5 AFUE
Heating Capacity [kBtulh]
Community: LEGACY RIDGE 11-) I
Builder
No
EAE [kWh]
LENNAR HOMES
Equipment Type: CA13NA042
-R1 01 (AS DESIGNED)
Fuel Type
Electric
LEGACY RIDGE 101
Forced Air
Motor Type
onditioning Equipment
Cooling Efficiency
13 SEER
Name
Library Type
Heating Percent Load Co(
Air conditioner (2)
Equipment Type: RE350*
CA13NA042
0%
C-M,
Energy Solutions
g Percent Load Hot Water
100%
0%
Fuel4red air 915SA4808OS17 100% 0% 0%
distribution (1)
Water Heating (3) RE350" 0% 0% 100%
1
Equipment Type: 915SA4808OS17
Fuel Type
Natural Gas
Distribution Type
Forced Air
Motor Type
PSG (Single Speed)
Heating Efficiency
95.5 AFUE
Heating Capacity [kBtulh]
78
Use default EAE
No
EAE [kWh]
946
Equipment Type: CA13NA042
Fuel Type
Electric
Distribution Type
Forced Air
Motor Type
PSG (Single Speed)
Cooling Efficiency
13 SEER
Cooling Capacity [kBtulh]
46
Equipment Type: RE350*
Fuel Type
Electric
Distribution Type
Hydronic Delivery
Hot Water Efficiency
0.93 Energy Factor
Tank Capacity (gal.)
50
Hot Water Capacity [kBtulh]
15.4
Recovery Efficiency
0.98
Building Summary
Property
6707 PULASKI LN
CARMEL, IN 46033
Model: SOUTHILL (B)
Community: LEGACY RIDGE 10 I
LR101 (AS DESIGNED)
LEGACY RIDGE 101
1butivn System
tion Type
Equipment
Equipment
t Served
i Grilles
Xct R Value
]uct R Value
Xct Area [sq. ft.]
]uct Area [sq. ft_]
akage to Outdoors (CFM25)
akage
akage Duct Test Conditions
fault Flow Rate
cation
Supply Area
Return Area
cation
Supply Area
Return Area
cation
Supply Area
Return Area
cation
Supply Area
Return Area
cation
Supply Area
Return Area
cation
Supply Area
Return Area
rCeiling Fan
Has Ceiling Fan
Ctm Per Watt
Organization Inspection Status
TSI Energy Solutions Results are projected
Matthew Timmons
Builder
LENNAR HOMES
Forced Air
Fuel -fired air distribution (1)
Air conditioner (2)
5454
6
3❑
3❑
1041.7
964.5
327
436
Post -Construction
Yes
Conditioned Space
7❑
70
Attic (well vented; under insulation)
3❑
3❑
Conditioned Space
0
0
Conditioned Space
Conditioned Space
Conditioned Space
No
C-M,
Energy Solutions
7
Building Summary
Property
6707 PULASKI LN
CARMEL, IN 46033
Model: SOUTHILL (B)
Community: LEGACY RIDGE 101
-R1 01 (AS DESIGNED)
LEGACY RIDGE 101
ater Distribution
I
ter Fixture Type
e Default Hot Water Pipe Length
t Water Pipe Length [ft]
Least R3 Pipe Insulation?
t Water Recirculation System?
circulation System Pipe Loop Length [ft]
in Water Heat Recovery?
Clothes Dryer
Fuel Type
Cef
Field utilization
Clothes Washer
Label Energy Rating
Electric Rate
Annual Gas Cost
Gas Rate
Capacity
I met
Appliances and Controls
Programmable thermostat?
Dishwasher Size
Dishwasher Efficiency
Range/Oven Fuel
Convection Oven?
Induction Range?
Refrigerator Consumption
Organization Inspection Status
TSI Energy Solutions Results are projected
Matthew Timmons
Builder
LENNAR HOMES
Standard
No
134
No
No
30
No
Electric
Timer Controls
glow
704 kWh/Year
$0.081kWh
$23.00
$0.581Therm
2.847
❑.331
Yes
Standard
270 kWh
Electric
No
No
709 kWh/Year
"M �
C-M,
Energy Solutions
,�