HomeMy WebLinkAboutSHEET E001- Shoppes on Main Retail Center (Carmel, IN)ELECTRICAL
SYMBOLS
8 p
EXIT SIGNAGE WITH EMERGENCY HEADS p
EMERGENCY EXIT EGRESS LIGHT 8
SUSPENDED STRIP LIGHT I
LIGHT FIXTURE - WALL SCONCE
OUTLET-4 WAY
OUTLET -DUPLEX
1mP
OUTLET- GROUND FAULT INTERRUPT
n
OUTLET- GROUND FAULT INTERRUPT WEATHERPROOF q Wp
TIME CLOCK
TC
SWITCH WITH OCCUPANCY SENSOR 4 $OS
PANEL DESIGATION-i
� CIRCUIT BREAKER NUMBERS
X:
XX,XX,XX
PANELBOARD SCHEDULE
ABBREVIATIONS
L
LIGHTING
R
RECEPTACLE
PN
POWER NON -SEASONAL
PW
POWER WINTER
MN
MOTOR NON -SEASONAL
MNI
MOTOR NON -SEASONAL INTERMITTENT
MS
MOTORSUMMER
MW
MOTOR WINTER
KT
KITCHEN
ELECTRICAL ABBREVIATIONS
A
AMPS
AFF
ABOVE FINISHED FLOOR
CO
COMPANY
CONTR
CONTRACTOR
DIN
DOWN
DWG(S)
DRAWING(S)
EC
ELECTRIC CONTRACTOR
EDC
ELECTRICAL DISTRIBUTION CENTER
EM
EMERGENCY
EQUIP
EQUIPMENT
ETR
EXISTING TO REMAIN
EWC
ELECTRIC WATER COOLER
EX
EXISTING
FLA
FULL LOAD AMPS
FS
FLOW SWITCH
GC
GENERALCONTRACTOR
HP
HORSEPOWER
MAX
MAXIMUM
MB
MAIN BREAKER
MC
MECHANICAL CONTRACTOR
MCA
MINIMUM CIRCUITAMPS
MFR
MANUFACTURER
MIN
MOUNTING HEIGHT
MIN
MINIMUM
MLO
MAIN LUG ONLY
MOCP
MAXIMUM OVER CURRENT PROTECTION
MOD
MOTOR OPERATED DAMPER
MTD
MOUNTED
NIC
NOT IN CONTRACT
NTS
NOT TO SCALE
OC
ON CENTER
PC
PLUMBING CONTRACTOR
PSI
POUNDS PER SQUARE INCH
RLA
RUNNING LOAD AMPS
RPM
REVOLUTIONS PER MINUTE
V
VOLTS
JOIN
UNLESS OTHERWISE NOTED
RELEASED FOR CONSTRUCTION
Subject to compliance with all regulations
of State and Local Codes
City of Camel
DATE: 07/03/19
ELECTRICAL SPECIFICATIONS
BID INSTRUCTIONS: CONTRACTORS SHALL PROVIDE BASE
BID IN STRICT ACCORDANCE WITH DESIGN BASIS
EQUIPMENTAND MATERIALS. PROJECT DOES ENCOURAGE
COMPETITIVE PRICING AND ALLOWS FOR SUBSTITUTIONS
OF EQUAL EQUIPMENT AND MATERIALS AGAINST THE BASIS
OF DESIGN. SUBSTITUTE ITEMS WILL BE COMPARED
AGAINST DESIGN BASIS DURING SUBMITTAL PROCESS.
ENGINEER RESERVES THE RIGHT TO REJECT
SUBSTITUTIONS FOUND NOT TO BE EQUAL TO ITEMS
LISTED IN DESIGN BASIS..
PRIOR TO PROCUREMENT CONTRACTOR SHALL SUBMIT TO
ARCHITECT FULL SUBMITTALS FOR ALL ENERGY
CONSUMING OR PRODUCING ITEMS AND FOR ALL SWITCH
GEAR, LOAD CENTERS AND PANEL BOARDS. SUBMITTALS
SHALL BE DELINEATED WITH TAGS INDICATED ON PRINTS,
CONTRACTORS NAME AND PROJECT NAME. CLEARLY
INDICATE ALL MODEL NUMBERS AND ALL ACCESSORIES
AND OPTIONS BEING PROVIDED. SUBMISSIONS SHALL BE IN
PDF FORMAT. ALL EQUIPMENT AND ITEMS SHALL BE PER
DESIGN BASIS OR APPROVED EQUAL. ENGINEER RESERVES
THE RIGHT TO REJECT ANY SUBSTITUTE ITEM FOUND NOT
EQUAL TO THE SPECIFIED ITEM AS DESIGNED.
3. CONTRACTOR SHALL FURNISH A TEMPORARY SERVICE FOR
THE USE OF ALL TRADES DURING CONSTRUCTION AS
REQUIRED BY THE GENERAL CONTRACTOR. REMOVEALL
TEMPORARY EQUIPMENT AS PERMANENT SERVICES
BECOME AVAILABLE.
4. THE DRAWINGS IN THIS SECTION ARE DIAGRAMMATIC AND
ARE NOT INTENDED TO DEFINE EXACT QUANTITIES,
LOCATIONS OR CODIFIED REQUIREMENTS. DRAWINGS
SHOW GENERAL INTENT OF SYSTEMS. MODIFICATIONS IN
ELECTRICAL SYSTEM ROUTING AND LOCATIONS AS
REQUIRED TO MEET THE INTENT, SHALL BE PERFORMED
WITHOUT ADDITIONAL COST TO OWNER. SECURE AND PAY
FOR ALL REQUIRED PERMITS.
THE ELECTRICAL CONTRACTOR IS TO PROVIDE ALL
REQUIRED LABOR, MATERIALS, EQUIPMENT, AND
CONTRACTOR'S SERVICES NECESSARY TO COMPLETE THE
INSTALLATION OF SYSTEMS REQUIRED IN FULL
CONFORMITY WITH APPLICABLE CODES AND ORDINANCES.
THE FINISHED JOB SHALL BE FUNCTIONAL AND COMPLETE
IN EVERY DETAIL INCLUDING ANY AND ALL SUCH ITEMS FOR
A COMPLETE SYSTEM. CONTRACTOR SHALL GUARANTEE
ALL LABOR AND MATERIALS ENTERING INTO CONTRACT
FOR A PERIOD OF ONE (1) YEAR FROM DATE OF
ACCEPTANCE.
6. ALL WORK SHALL IN BE IN FULL ACCORDANCE WITH 2O09
INDIANA ELECTRICAL CODE (2008 NFPA 70), 2010 INDIANA
ENERGY CODE (ASHRAE 90.1-2007), PERTINENT STATE,
COUNTY, CODES AND ORDINANCE AND INDIANA
AMENDMENTS. COORDINATE WORK WITH OTHER TRADES.
ELECTRICAL CONTRACTOR SHALL BEAR ALL COSTS
RESULTING FROM ANY NON COMPLIANCE WITH CODE
REQUIREMENTS
7. MATERIALS AND EQUIPMENT SHALL BE NEW UNLESS
INDICATED OTHERWISE. MATERIAL SHALL BEAR U.L. LABEL
WHERE SUCH STANDARDS HAVE BEEN ESTABLISHED AND
LISTEDBYU.L. MATERIALS AND EQUIPMENT SHALL
CONFORM WITH THE LATEST ISSUES OF APPLICABLE
TECHNICAL STANDARDS.
8. THE ELECTRICAL CONTRACTOR IS TO PROVIDE A
COMPLETE SYSTEM OF LIGHTING, RECEPTACLES, AND
POWER AS REQUIRED.
9. ALL CONDUIT COUPLINGS AND CONNECTIONS SHALL BE
MADE TO ENSURE POSITIVE GROUNDING CONTINUITY.
MAKE CONNECTIONS TO EQUIPMENT SUBJECT TO
VIBRATION WITH 18 INCHES OF FLEXIBLE WATERTIGHT
CONDUIT WITH WATERTIGHT FITTINGS. PROVIDE FOR
SUPPORT AND SECURING OF ALL CONDU IT AND
EQUIPMENT. CONNECTIONS TO LIGHTING FIXTURES SHALL
BE MADE WITH SIX (6) FEET OF FLEXIBLE CONDUIT FROM A
BOX WITHIN TWO (2) FEET OF THE FIXTURE. SPLICE ALL
WIRES ONLY IN ACCESSIBLE BOXES. ALL FIXTURE WHIPS
TO BE FLEXIBLE METAL CONDUIT 1/2" MINIMUM SIZE WITH
COMPRESSION CONNECTORS WITH INSULATED THROATS.
WHIPS SHALL NOT EXCEED 6'. FIXTURE WHIPS TO BE
SUPPORTED FROM BUILDING STRUCTURE.
10. ALL LIGHTING AND BRANCH CIRCUIT WIRING SHALL BE
SOLID COPPER MINIMUM SIZE #12 AWG. 600V INSULATION,
75 DEG. C., TYPE THW OR THW N, NOT LESS THAN #12 AWG.
ALL WIRE SERVING AS FEEDS TO DISTRIBUTION PANEL
BOARDS OR INTEGRAL HORSEPOWER MOTORS SHALL BE
EITHER STRANDED COPPER CONDUCTOR OR ASTM B800
ALUMINUM AA-8000 SERIES. THESE SHALL BE SIZED NOT
LESS THAN #10 AWG FOR COPPER AND NOT LESS THAN #8
AWG FOR ALUMINUM. EACH WITH MINIMUM 600V THW OR
THWN INSULATION, 75 DEG. C. ALL FEEDER SHALL BE
SIZED IN ACCORDANCE WITH NEC 310.15.
11. PANELBOARDS SHALL BE A DEAD -LOCK SAFETY TYPE,
SURFACE OR RECESSED MOUNTED AS SHOWN, EQUIPPED
WITH THERMAL -MAGNETIC MOLDED CASE CIRCUIT
BREAKERS WITH FRAME AND TRIP RATINGS AS REQUIRED.
TERMINALS FOR FEEDER CONDUCTORS TO THE
PANELBOARD MAINS AND NEUTRAL SHALL BE U.L. LISTED
AS SUITABLE FOR THE TYPE OF CONDUCTOR SPECIFIED.
TERMINALS FOR BRANCH CIRCUIT WIRING, BOTH BREAKER
AND NEUTRAL, SHALL BE U.L. LISTED AND CONNECTORS
SHALL BE OF THE FULL COMPRESSION TYPE.THE
PANELBOARD BUS ASSEMBLY SHALL BE ENCLOSED IN A
STEEL CABINET. THE SIZE OF THE WIRING GUTTERS AND
GAUGE OF STEEL SHALL BE IN ACCORDANCE WITH NEMA
STANDARD PUBLICATION NO. PB-1971 AND U.L.
STANDARDS NO. 67 FOR PANELBOARDS. CABINET SHALL
BE FABRICATED FROM GALVANIZED STEEL OR EQUIVALENT
RUST -RESISTANT STEEL. FRONTS SHALL INCLUDE DOORS
AND HAVE FLUSH, BRUSHED STAINLESS STEEL, CYLINDER
TUMBLER -TYPE LOCKS WITH CATCHES AND SPRING
ELECTRICAL SPECIFICATIONS
LOADED DOOR PULLS. THE FLUSH LOCK SHALL NOT
PROTRUDE BEYOND THE FRONT DOOR. ALL PANELBOARD
LOCKS SHALL BE KEYED ALIKE. FRONTS SHALL HAVE
ADJUSTABLE INDICATING TRIP CLAMPS WHICH SHALL BE
CONCEALED WHEN THE DOORS ARE CLOSED. DOORS
SHALL BE MOUNTED BY COMPLETELY CONCEALED STEEL
HINGES. FRONTS SHALL NOT BE REMOVABLE WITH DOOR
IN THE LOCATED POSITION. A CIRCUIT DIRECTORY FRAME
AND TYPE WRITTEN CARD WITH A CLEAR PLASTIC
COVERING SHALL BE PROVIDED ON THE INSIDE OF THE
DOOR. THE DIRECTORY CARD SHALL PROVIDE A SPACE AT
LEAST 1/4" HIGH X 3" LONG OR EQUIVALENT FOR EACH
CIRCUIT. FRONTS SHALL BE OF CODE GAUGE, FULL
FINISHED STEEL WITH RUST -INHIBITING PRIMER FACTORY
FINISHED ENAMEL PAINT.
12. CIRCU IT BREAKERS SHALL BE QUICK -MAKE, QU ICK-BREAK,
THERMAL -MAGNETIC, TRIP INDICATING AND HAVE COMMON
TRIP ON ALL MULTI -POLE BREAKERS. BRANCH CIRCUIT
BREAKERS FEEDING CONVENIENCE OUTLETS SHALL HAVE
SENSITIVE INSTANTANEOUS TRIP SETTINGS OF NOT MORE
THAN 10 TIMES THE TRIP RATING OF BREAKER TO PREVENT
REPEATED ARCING SHORTS RESULTING FROM FRAYED
APPLIANCE CORDS. CONNECTION TO BUS SHALL BE BOLT
ON.
13. CONTRACTOR TO OBTAIN MAXIMUM FAULT CURRENT
AVAILABLE FROM THE UTILITY. CALCULATE THE FAULT
CURRENT AVAILABLE AT THE PANELS. ALL
PANELS/BREAKERSISW ITCHES ARE TO BE BRACED TO
EXCEED MAXIMUM AVAILABLE FAULT CURRENT AND
CIRCU IT BREAKERS ARE TO BE CAPABLE OF INTERRUPTING
FAULT CURRENT. MANUFACTURER SHALL PROVIDE ALL
REQUIRED FAULT CURRENT AND ARC -FLASH LABELING PER
110.16 AND 110.24.
14. MAXIMUM LOADING OF 20 AMP CIRCUITS SHALL NOT
EXCEED 175D WATTS. VOLTAGE DROP OF BRANCH
CIRCUITS SHALL NOT EXCEED 3%AND FEEDER CIRCUITS
SHALL NOT EXCEED 2%. SEAL ALL PENETRATIONS
THROUGH WALLS, CEILINGS AND FLOORS AIR AND WATER
TIGHT. FIRE STOP WHERE REQUIRED.
15. CONTRACTOR SHALL PROVIDE ENGRAVED BAKELITE
NAMEPLATES FOR ALL ELECTRICAL PANELS,
DISCONNECTS, TRANSFORMERS AND MOTORS OVER 1 NO
FURNISH TYPEWRITTEN PANEL DIRECTORIES TO IDENTIFY
ALL ELECTRICAL CIRCUITS BOTH NEW AND EXISTING.
16. VERIFY EXACT LOCATION, COLOR AND HEIGHTS OF ALL
OUTLETS, RECEPTACLES, LIGHT FIXTURES AND EQUIPMENT
WITH OWNER'S REPRESENTATIVE PRIOR TO START OF
WORK. FURNISH GENERAL SERVICE DUPLEX'S, 15 AMP
SWITCHES, 15/20 AMP GFICS, HEAVY DUTY DISCONNECTS,
HVAC SSU SWITCHES, PANEL BOARDS, LOAD CENTERS,
DISTRIBUTION PANELS ETC. AS REQUIRED.
17. DISCONNECT SWITCHES SHALL BE GENERAL DUTY, NEMA
TYPE 1 FOR INDOOR SERVICE AND NEMA TYPE 3R FOR
OUTDOOR SERVICE, SUITABLE FOR PADLOCKING, NUMBER
OF POLES, RATINGS, FUSES (IF REQUIRED) SHALL BE AS
INDICATED ON THE DRAWINGS.
18. DEVICES:
A. CONVENIENCE RECEPTACLES SHALL BE MOUNTED 18'
ABOVE FINISHED FLOOR (A.F.F.) TO BOTTOM UNLESS
NOTED OTHERWISE, SWITCHES AND PUSHBUTTONS SHALL
BE 420 A.F.F. TO BOTTOM UNLESS SPECIFIED OTHERWISE
ON THE DRAWINGS.
B. PRIOR TO ROUGH -IN E.C. SHALL VERIFY FINAL LOCATIONS
AND COLORS OF ALL DEVICES WITH OWNER.
C. INSTALL ALL DEVICES PARALLEL AND PERPENDICULAR TO
ADJACENT WALL AND CEILING, FLUSH WITH SURROUNDING
SURFACES AND FREE FROM ALL OBSTRUCTIONS.
REWORKING OF EQUIPMENT INSTALLED IMPROPERLY
SHALL BE AT THE CONTRACTOR'S EXPENSE.
D. SWITCHES, BOXES, ETC., SHALL BE NEMA TYPE 1
CONSTRUCTION FOR INDOOR APPLICATIONS AND NEMA
TYPE 3R CONSTRUCTION FOR OUTDOOR APPLICATIONS.
E. SWITCHES SHALL MEET NEMA STANDARDS, COLOR SHALL
BE BY ARCHITECT. SWITCHES SHALL BE EQUAL TO
HUBBELL COMMERCIAL SPECIFICATION GRADE 20/15
AMPERES, SINGLE POLE, 125I277V. MULTI -POLE OR
SPECIAL SWITCHING SHALL BE AS NOTED ON THE
DRAWINGS.
F. RECEPTACLES SHALL BE 125 VOLT, 15/20 AMPERES,
DUPLEX, GROUNDED HUBBELL COMMERCIAL
SPECIFICATION GRADE. SPECIAL RECEPTACLES SHALL BE
AS NOTED ON THE DRAWINGS.
G. MATCHING COVER PLATES SHALL BE PROVIDED FOR ALL
RECEPTACLES AND SWITCHES.
23. LIGHTING FIXTURES:
A. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING
FIXTURES- MODEL NUMBERS, QUANTITY AND DISTANCE
BETWEEN LIGHTING FIXTURE PER FLOOR PLANS.
B. PRIOR TO ROUGH -IN E.C. SHALL VERIFY FIXTURE
QUANTITY, MODELS, STYLE, TRIM, LENS, ETC. WITH OWNER
FOR ALL FIXTURES.
C. PROVIDE LIGHTING FIXTURES COMPLETE WITH, BUT NOT
NECESSARILY LIMITED TO, HOUSINGS, LAMPS, LAMP
HOLDERS, REFLECTORS, BALLASTS, STARTERS AND
WIRING
PHOTOCELL
NEMA
;EM�TC��3R
F
PBX
PHONE
JUNCTION BOX
4"CTO
SERVICES
Ni 12" X 12"NEMA 3R WIRE WAY
HOUSE
PANEL
H'
3PH4W I i I I( I I/ I( I
24C I �i I I I I I
METER LMETERA LMETERL LM ETER� LMETERL
BRANCH CIRCUITS TO MONUMENT
SIGN AND PARKING LOT LIGHTING. SEE
SHEET E050 PLAN FOR LOCATIONS
DUKE ENERGY
TAP BOX FOR
SERVICE
ENTRY
(3) 4" C TO DUKE
TRANSFORMER
10200395 _{�=
Q% ' snm of s
�=
muuunrunnuN
O7
L
L
Z
cQ
G
Q
Z
Q
W
1
Y
O
znn
V
LL
0
Q
U
J
JO
_W
� /^'
w.w !
Cl)
13.
�_^'
v!
w
Z
O
l
Ly
O
(n
J
^�
U
DATE
ISSUE
5/19/19
PERMIT
ELECTRICAL
ABBREVIATIONS, SYMBOLS,
& SPECIFICATIONS
E001