HomeMy WebLinkAboutE3-2 - Second Floor Power Plan -Area B2
T
WORKSPACE CORRIDOR
0
I D IF
Imo,
DECONTAMINATION
HP4, F50 2236 175
❑ O
❑ I
rcY 7t L
WAVE
Phase 2 - Enlarged Decontamination 236 & Central Sterile 233 Power Plan
\--J 114,E =1,-0,�
4.3 45. 4.7 5.1
— — —I — — — —
WAITING
202
I I I I I
STAIR
O REG1 REG2
CORRIDOR
201
..�,. n 240 ,.,.,.,
CORRIDOR
63
STAFF LOUNGE
2d2 ���iii III III
ME LOCKER ROC
� 2d4
RELEASED FOR CONSTRUCTION
Subject to compliance with all regulations
of State and Local Codes
City of Cannel
�VI(AW \tPrv:4VM/�L
DATE: Vf/V`J/-IU
I 11 MECH CHASISj
N 204
CORRIDOR
205
239
=&RIOR
z3e
6
7 8
9
9.3
4
OINSULT
WATER SOFTENS
—
—
— —
——
—
262
(D
R-TVACMP--�
STORAGE
FAN ROOM
26d
—
—
— —
RECEIPT
15
20,T2,
p
OFFICE W
HP4
J
7 w
219
O
CORRIDOR
LRP6C
-7 TRANSFOR
R
SFORMER
CONSULT M3
213A
LASER R OM L HP3
LS
WILLS
CR
MLCRA
211
231 HP2 9
EL TOR
1 CORRIDOR
WORK SPAC
210
In HAZARD
CORRIDOR
218
■
SOONTAMINATIO� pap CONSU OFFICE
O OFFI O
SEE DETAIL CENTRAL STERILE 221A
ON SHEET E3-2C ❑ 233
SEE DETAIL 4
ON SHEET Eb2C CORRIDOR !1 pREIPOST OP R00 REIPOST OP ROOK
PREIPOST OP RO M
222 223 224
Q M 234
CORRIDOR I WAVE71 23] CORRIDOR �\ CORRIDOR
228
JAN EpUIPMENTSTORAGE
216 220
PREIPOST OR ROO PREIPOST OR ROO
U U=a SOILED ICI YI 2 4
��
MEDS R00 BIOHAZARD 1
253 1 0 REIPOST P ROOM PREMOST OR ROOM TOILET
ESH-284 SH-282 25 260 _ ORK STATION
27]
OR#2 TYPE — — —OR#1 TYPE _ .. �1P4TF90 'F90 — — — — O 268
4 245 Eal a a El16 RP3q'.a �- ¢'cd CORRIDOR
ryP src a � STO GE PREMOST OR 279 ADA TOILET
3 �7 2]6 M� 261
ww�
10 _ m° PATIENT RC OM ou 7MENURSE STATION
HORRID C 75 8 PM€N — ORRIDOR +I — — — —
9 286 66 26V 11 280 O
ORKAREA TOILET
SUB STERILE 246 CORRIDOR m 4 MLC .41 18 - 270
267 ILE SCRUB AREA
250 10 EMLC 3:41 p3B: 331 ELI 281 WORK S ATION
ED SEE DETAIL 22 TOILET
5 75 75 . n E3e� -3
�] RECOVERY 2]f
290 Q LINEN
J EM CRA 3 EM RA 3 EMLCRA II P3 :41 2 2
/-EMLCRA:7 12 EMLC
$ N 1
RP3B: 29 13 rc . 10 17 10 17 PATIENT RECOVERY
OR A3 TYPE OR d4 TYPE RP3B'. 31� J s 274
MLCRA:S �l w w 12
240 2a9 `I II RP3B:
" 0' EMLCRA. 70 = RECOVERY
RP3B 29
RP3B'. 39 m J EMI•CRA: 13
� 209
q ®Ea l®� ® ® ®¢ ®15 RP3B:41
3.�
Phase 2 - Second Floor Power Plan - Area B
9.8
-�� A.3
www
I
B.2
STAIR
B.6
—41 B.9
NURSE MANAGE
)RRIDO 267
266
OFFICE
263
PLAN NOTES
1 CONNECT NEW NORMAL POWER RECEPTACLETOEXISPNG120V,20A, IF NORMAL CIRCUIT THAT WAS
MAINTAINED DURING DEMOLITION. EXTEND I MODIFY EXISTING WIRINGI CONDUIT AS REQUIRED.
2 RECEPTACLES FOR OR VIDEO INTEGRATION DATA RACK. COORDINATE LOCATION AND MOUNTING HEIGHT WITH
OWNERS VENDOR.
3 CONNECT COMPLETE NEW ELECTRIC STEAM HUMIDIFIER VIA CIRCUIT INDICATED. PROVIDE 3P-60A, 460V, FUSIBLE
DISCONNECT. FUSE PER MANUFACTURERS RECOMMENDATIONS. PROVIDE ADDITIONAL SUPPORT STRUCTURE
AS REQUIRED. COORDINATE EXACT LOCATION PRIOR TO INSTALLATION.
4 RECEPTACLE FOR WALL MOUNTED PATIENT TRACKING TELEVISION. COORDINATE LOCATION AND MOUNTING
HEIGHT WITH ARCHITECT.
5 CONNECT COMPLETE NEW STERILIZERMACIRCUIT INDICATED. PROMDE3P-6K HEIN. FUSIBLE DISCONNECT.
FUSE PER MANUFACTURERS RECOMMENDATIONS. PROVIDE ADDITIONAL SUPPORT STRUCTURE AS REQUIRED.
COORDINATE EXACT LOCATION PRIOR TO INSTALLATION.
6 CONNECT AUTO OPERATORS COMPLETE TO 121V,21A, 1 P LIFE SAFETY CIRCUIT FROM PANEL'EMLS'LOCATED IN
SECOND FLOOR ELECTRICAL ROOM 221. PROVIDE PUSH PLATES AND ALL ASSOCIATED ROUGH -INS AND
CONTROL WIRING IN CONDUIT AS REQUIRED. PROVIDE TOGGLE DISCONNECT SWITCH.
7 PROVIDE SINGLE CHANNEL SURFACE MOUNTED MULTI -OUTLET ASSEMBLY AS REQUIRED. MOUNT AT t42' A.F.F.
8 CONNECT COMPLETE NEW WASHER VIA CIRCUIT INDICATED. PROVIDE 3P-60A, 400V, FUSIBLE DISCONNECT. FUSE
PER MANUFACTURERS RECOMMENDATIONS. PROVIDE ADDITIONAL SUPPORT STRUCTURE AS REQUIRED.
COORDINATE EXACT LOCATION PRIOR TO INSTALLATION.
9 PROM DE NEW,ADDITIONAL, RECEPTACLE AT WORK AREA. CONNECT COMPLETE VIA EXISTING RECEPTACLE
CIRCUIT OF ADJACENT RECEPTACLE.
10 RECEPTACLES WITHIN OR SHALL BE MOUNTED AT +44" UNLESS SPECIFICALLY NOTED OTHERWISE.
11 CONNECT EXISTING FIRE I SMOKE DAMPER COMPLETE TO CIRCUIT MAINTAINED DURING DEMOLITION. PROVIDE
WIRING IN CONDUIT AS REQUIRED. PROVIDE TOGGLE DISCONNECT SWITCH.
12 RECEPTACLE FOR WALL MOUNTED MON TOR. COORDINATE LOCATION AND MOUNTING HEIGHT WITH ARCHITECT.
13 RECEPTACLE FOR OR SURGICAL LIGHT POWER SUPPLY ON SHELF. COORDINATE LOCATION AND MOUNTING
HEIGHT WITH ARCHITECT.
14 PROVIDE 8"%8PBACK BOX FLUSH IN WALL FOR MICROSCOPE CONTROL PANEL. PROVIDE (2)2"CONDUITS FROM
CONTROL PANEL TO MICROSCOPE BOOM BASE. PROVIDE CONDUTS WITH BUSHINGAS REQUIRED. PROVIDE
RELAY AS REQUIRED FOR FOOT PEDAL CONTROL OF ROOM LIGHT FIXTURES. CONTRACTOR SHALL VERIFY ALL
MICROSCOPE REQUIREMENTS WITH SUPPLIER AND OWNER PRIOR TO INSTALLATION.
15 CONNECT COMPLETE TO SPARE 120V, M BREAKER MADE AVAILABLE BY DEMOLITION.
16 CONNECT COMPLETE TO SPARE 120V, 20A BREAKER IN PANEL INDICATED.
17 CONNECT COMPLETE CIRCU ITS INDICATED WTHI N THIS ROOM VIA SPARE 120V, 20A BREAKERS MADE AVAILABLE
BY DEMOLITION.
10 PROVIDE NEW 120V, 20A BREAKERWITHIN EXISTING SPACE OF PANEL INDICATED AND CONNECT COMPLETE.
19 CONNECT RELOCATED EXISTING EQUIPMENT VACUUM PUMP INSTALLED IN PHASE ONE OF THIS PROJECT TO
CIRCUIT THAT IS CURRENTLY SERVING THE VACUUM PUMP. PROVIDE TOGGLE SWITCH DISCONNECT.
20 PROVIDE NEW DUPLEX RECEPTACLE SAME HEIGHT AS EXISTING RECEPTACLE SERVING DI WATER SYSTEM.
CONNECT TO EXISTING CIRCUIT COMPLETE.
21 PROVIDE 480V3P 130q FUSIBLE DISCONNECT. FUSE PER MANUFACTURER'S RECCOMENDATION. PROVIDE
ADDITIONAL SUPPORT STRUCTURE AS REQUIRED.
CORRIDOR
f
�1 Phase 2 -Enlarged Sub Sterile 250 Power Plan
11 =1'-0"
CORRIDOR
280
SUB STERILE HP4, F50
81
5
Phase 2 - Enlarged Sub Sterile 281 Power Plan
KEY PLAN
MSKTD
& Associates
Architecture I Engineering I Interior Design
1715 Magnavmx Way 930 North Meridian
Fort Wayne, IN 46804 Indianapolis, IN 46204
260.432.9337 1 317.917.1190
v .msktd.cwm
PE10708732
STALE 9
l�^
i
CD
l^'E
W
i
O
Co
f rO
NW
W
W W
LU
� � L
_O
C LL
v! + vi
PROJECT NO.
733505-07-19
REV. DATE