HomeMy WebLinkAboutE8-1 - Electrical Details2 BEAM CLAMP 0 BEAM CLAMP / CON UITCLAMPOR o EQUIVALENTSIZE STEEL CABLE AS REQUIRED AIRCRAFT NOTE', HANGERWIRE 1. FOR STEEL STRUCTURAL SYSTEM. 2. PROM DE SEISMI C BRACING MI NI MUM 40' ON CENTER WHEN THE CONDUITS SUPPORT IS BELOW 12' FROM STRUCTURE. r-4-) 2-12" AND LARGER CONDUIT SUPPORT DETAIL �J NOSCALE STEEL CABLE AIRCRAFT HANGERWIRE THREADED ROD SIZE AS REQUIRED STRUTCIAMP OR EQUIVALENT UNISTRUT CHANNEL OR EQUIVALENT COMBINATION BEA CONDUIT HANGER OR "Mvivm""11 NOTE'. FOR STEEL STRUCTURAL SYSTEM %2 2" AND SMALLER CONDUITSUPPORTDETAIL NO SCALE 12 GAUGE HANGER WIRE OR CHAIN FOR FIXTURE SUPPORT CONNECTED TO STRUCTURE ABOVE JUNCTION BOX FLEXIBLE CONDUIT 0�0 WIp12 WIRE(6'MAX.) / LAY -IN CEILING LAY -IN CEILING LAY IN LIGHT FIXTURE DETAIL J NO SCALE LAY -IN CEILING LAY -IN CEILING SEISMIC CLIP 4-11116' x 441116' SQUARE BOX 2-718' DEEP S8 DATA OUTLETS � RUSH MOUNTED DATA OUTLET J NO SCALE tunas FACE PLATE (1)1-1I4'EMT CONWIT CONFIGURATION WITH NYLON BUSHING STUBBED TO ACCESSIBLE CEILING AW EMT CONDUITS WITH NYLON RING STUBBED TO ACCESSIBLE .ING 411116' x411116' SQUARE BOX 2-718' DEEP O 12'DEEP TILE RING DATA 2-GANG TILE RING 10 DEEP 14 DATA FLI 1. SUPPORTS FOR CABLE SHALL BE INDEPENDENTLY SUPPORTED. CABLE SHALL NOT LAY OVER CONDUIT, DUCTWORK, PIPING, STRUCTURAL SUPPORT MEMBERS, ETC. CABLE SHALL BE NEATLY INSTALLED AT RIGHT ANGLES TO THE BUILDING LINES. ENGINEER WILL REQUIRE CABLE TO BE REMOVED AND REINSTALLED IF IT IS NOT INSTALLED IN AN ACCEPTABLE MANNER. 2. REFER TO FLOOR PLANS FOR DEVICE LOCATIONS AND QUANTITY 4 3. PROVIDE ALL REQUIRED EQUIPMENT REQUIRED FOR A COMPLETE SYSTEM PER NEW DEVICE QUANTITIES AND LOCATIONS. 3. WIRING INSTALLATION: CADDY SCREW GUN BRACKET A. WIRING INSTALLED ABOVE ACCESSIBLE CEILINGS MAY BE EXPOSED CABLE. B. WIRING INSTALLED IN WALLS, ABOVE INACCESSIBLE CEILINGS, OR AREAS WITH EXPOSED CEILINGS SHALL BE BOX MOUNTING INSTALLED IN CONDUIT COMPLETE. METAL STUDS BRACKET CONDUIT ,A �1 INFORMATION PLATE P SQUARE BOX LAMACOID PLATE PANEL 1LN1- EQUIPMENTSERVED 120/208V 3P 4W — — VOLTAGE FED FROM MDP SOURCE OF POWER NOTE: PROVIDE I. D. PLATE LABEL FOR ELECTRICAL EQUIPMENT SUCH AS MAIN SWITCHGEAR, SWITCHBOARD PANELBOARDS, NOTE. FOR METAL STUD WALL CONSTRUCTION ONLY. AND TRANSFORMERS WALL BOX INSTALLATION DETAIL �� ELECTRICAL EQUIPMENT I.D. LABELING DETAIL NO SCALE NO SCALE TYPICAL EMERGENCY PAGESPEAKER 2 f TYPICAL GENERAL PAGE SPEAKER SECOND FLOOR T I— I NOTES: 1. SUPPORTS FOR CABLE SHALL BE INDEPENDENTLY SUPPORTED. CABLE SHALL NOT LAY OVER CONDUIT, TT I DUCTWORK, PIPING, STRUCTURAL SUPPORT MEMBERS, ETC. CABLE SHALL BE NEATLY INSTALLED AT RIGHT ANGLES TO THE BUILDING LINES. ENGINEER WILL REQUIRE CABLE TO BE REMOVED AND REINSTALLED IF IT IS NOT INSTALLED IN AN ACCEPTABLE MANNER. EXISTING 2, REFER TO FLOOR PLANS FOR DEVICE LOCATIONS AND QUANTITY, AUDIO PAGING RACK 3. PROVIDE ALL REQUIRED EQUIPMENT AND MODIFICATIONS REQUIRED FOR A COMPLETE SYSTEM PER NEW DEVICE QUANTITIES AND LOCATIONS. I4. WIRING INSTALLATION. A. WIRING INSTALLED ABOVE ACCESSIBLE CEILINGS MAY BE IXPOSEDCABLE. COMPUTER 7006 B, WIRING INSTALLED IN WALLS, ABOVE INACCESSIBLE CEILINGS, ORAREAS WITH EXPOSEDCEILINGS SHALL BE INSTALLED IN CONDUIT COMPLETE. RELEASED FOR CONSTRUCTION Subject to compliance with all regulations of State and Local Codes City of Carmel ��1A�lt _ Arc Flash Hazard Appropriate PPE Required Equipment Type 480V Switchgear Grounding Grounded Work Distance 11 inches (300 PIT) Availiable 3-Ph Baited Current 25 kA Flash Protection Boundary 27 inches Incident Energy at 11 inches 4.39 colI Risk Category 2 Equipment Name: Switchboard NOTE: PROVIDE WARNING LABEL FOR ALL ELECTRICAL EOUI PMENT SUCH AS MAIN SWITCHGEEAR, SWITCHBOARDS, PANELBOARDS, AND TRANSFORMERS. %,1 ELECTRICAL EQUIPMENT WARNING LABEL DETAIL NOS CALE NOTES: 1, SUPPORTS FOR CABLESHALL BE INDEPENDENTLY SUPPORTED, CABLE SHALL NOT LAY OVER CONDUIT, DUCTWORK, PIPING,STRUCTURAL SUPPORT MEMBERS, ETC. CABLE SHALL BE NEATLY INSTALLED AT RIGHT ANGLES TO THE BUILDING LINES. ENGINEER WILL REQUIRE CABLE TO BE REMOVED AND REINSTALLED IF IT IS NOT INSTALLED IN AN ACCEPTABLE MANNER. 2. REFER TO FLOOR PLANS FOR DEVICE LOCATIONS AND QUANTITY. 3. PROVIDE PLENUM RATED WIRE I CABLE AS REQUIRED. 4. PROVIDE ALL REQUIRED EQUIPMENT AND MODIFICATIONS REQUIRED FOR A COMPLETE SYSTEM PER NEW DEVICE QUANTITIES AND LOCATIONS. — NEW CABLE TRAY _ CAT 6A CABLE F ELECOMMUNICATIONS-j BLE TOBE TERMINATED IDF BV CONTRACTOR. TELECOM I EQUIPMENT PROVIDEDBY OWNERAS REQUIREDED F7-Mr CONDUIT TO CABLE - TRAY. TERMINATE CONDUITS WITH BUSHING (TYPICAL) I LI O I ES QUANTITY OFT CABLES I BE INSTALLED EXISTING I REFER TO DETAIL ON THIS SHEE DATA IN CK FOR ADDITIONAL INFORMATION. LOCATEDAS SHOWN ON DRAWINGS. COMPUTER 7006 _ SECOND FLOOR TELECOM SYSTEM DETAIL U NO SCALE TYPICAL I ` TYPICAL DOME DOME LIGHT LIGHT NURSE CALL SYSTEM CABINET MASTER EMERGENCYCALL TYPICAL TYPICAL TYPICAL DUTY TYPICAL STATION STAULLTION WITH PATIENT NWITH STATIONLOCATOR CORD AND STATION CODE STATION ELEC. 1359 RESET BUTTON. BLUE (ALTERNATE) SECOND FLOOR %01 NURSE CALL DETAIL NO SCALE ADDRESSABLE RELAY FOR CONTROL PROVIDE ONE TO OTHER DEVICES AT EACH HUE/SMOKANDRET AND NFAT r SEE STARTERS,AT EACH AHU SUPPLY AND REr AN FAT FLOOR PLANS EACH DOOR HOLD RELEASE DEVICE PROVIDE SPARE CAPACITY J s TOADD20% FUTUREDEVICESON EACH INITIATION LOOP TVPICALSMOKE TYPICAL TYPICAL DOOR DETECTORWITH FIRESMOKE HOLDIRELEASE SOUNDERBASE DAMPER DEVICE NOTES, 1. ALL FIREALARM SYSTEM WIRING SHALL BE INSTALLED IN CONDUIT COMPLETE. 2. REFER TO FLOOR PLANS FOR DEVICE LOCATIONS AND QUANTITIES. 3. EXISTING FIRE ALARM PANELWORKSHALL INCLUDE ALL NEW CARDS, EQUIPMENT AND PROGRAMMING NECESSARY TO SUPPORT THE NEW DEVICES AS INDICATED. 4. LABELALL FIRE ALARM DEVICES AS DIRECTED BV THE OWNER WITH EXTERNAL TAGS AND LABELS ON DEVICE MSES. I 71:1�:1I:1:IL56`P691gL56YNag151:11[N L IN CONDUIT AS REQUIRED TYPICAL HVAC UNIT STARTER — PROVIDE SPARE CAPACITY TO ADD (2) SIGNAL DEVICES (TYP, OF EACH SIGNAL CIRCUIT) __E;� I PROVIDESIGNAL IXPANDERIAMPLIFIER POWER SUPPLY ON EACH FLOOR FOR SIGNAL DEVICES. LOCATE EQUIPMENT IN ELECTRICAL ROOM, TYPICAL FOR EACH FLOOR IXISTI NG FIREALARM CONTROL PANEL ELECTRICAL1012 MSKTD & Associates Architecture I Engineering I Interior Design 1715 Magnavox Way 930 North Mendian Fort Wayne, IN 46804 Indianapolis, IN 46204 260432.9337 317.917.1190 w .msktd.cwm PE10708732 STATE 9 W � E W _O 4—a O VJ 0 Al �^'`) an ^^L\\ ) r "' W� L/ \ L / O /� ..l O w+mmi mmmmmmmo LL Z M O O L V M C:) �� VJ C0 PROJECT NO. DATE 7335 05-07-19 REV. DATE SET DESCRIPTION FOR CONSTRUCTION SET SHEET TITLE Electrical Details DATE: V//L)U/-IU SHEET NUMBER E8-1 C