HomeMy WebLinkAboutE8-1 - Electrical Details2
BEAM CLAMP
0
BEAM CLAMP
/ CON UITCLAMPOR
o EQUIVALENTSIZE
STEEL CABLE AS REQUIRED
AIRCRAFT NOTE',
HANGERWIRE 1. FOR STEEL STRUCTURAL SYSTEM.
2. PROM DE SEISMI C BRACING MI NI MUM 40'
ON CENTER WHEN THE CONDUITS
SUPPORT IS BELOW 12' FROM
STRUCTURE.
r-4-) 2-12" AND LARGER CONDUIT SUPPORT DETAIL
�J NOSCALE
STEEL CABLE
AIRCRAFT
HANGERWIRE
THREADED ROD
SIZE AS REQUIRED
STRUTCIAMP
OR EQUIVALENT
UNISTRUT CHANNEL
OR EQUIVALENT
COMBINATION BEA
CONDUIT HANGER OR "Mvivm""11
NOTE'. FOR STEEL STRUCTURAL SYSTEM
%2 2" AND SMALLER CONDUITSUPPORTDETAIL
NO SCALE
12 GAUGE HANGER WIRE OR CHAIN FOR FIXTURE
SUPPORT CONNECTED TO STRUCTURE ABOVE
JUNCTION BOX
FLEXIBLE CONDUIT
0�0 WIp12 WIRE(6'MAX.) /
LAY -IN CEILING
LAY -IN CEILING
LAY IN LIGHT FIXTURE DETAIL
J NO SCALE
LAY -IN CEILING
LAY -IN CEILING
SEISMIC
CLIP
4-11116' x 441116'
SQUARE BOX
2-718' DEEP
S8 DATA
OUTLETS
� RUSH MOUNTED DATA OUTLET
J NO SCALE
tunas
FACE PLATE
(1)1-1I4'EMT CONWIT
CONFIGURATION
WITH NYLON BUSHING
STUBBED TO ACCESSIBLE
CEILING
AW EMT CONDUITS WITH NYLON
RING STUBBED TO ACCESSIBLE
.ING
411116' x411116'
SQUARE BOX
2-718' DEEP
O
12'DEEP
TILE RING
DATA
2-GANG TILE
RING 10 DEEP
14 DATA
FLI
1. SUPPORTS FOR CABLE SHALL BE INDEPENDENTLY SUPPORTED. CABLE SHALL NOT LAY OVER CONDUIT, DUCTWORK, PIPING, STRUCTURAL SUPPORT
MEMBERS, ETC. CABLE SHALL BE NEATLY INSTALLED AT RIGHT ANGLES TO THE BUILDING LINES. ENGINEER WILL REQUIRE CABLE TO BE REMOVED AND
REINSTALLED IF IT IS NOT INSTALLED IN AN ACCEPTABLE MANNER.
2. REFER TO FLOOR PLANS FOR DEVICE LOCATIONS AND QUANTITY
4 3. PROVIDE ALL REQUIRED EQUIPMENT REQUIRED FOR A COMPLETE SYSTEM PER NEW DEVICE QUANTITIES AND LOCATIONS.
3. WIRING INSTALLATION:
CADDY SCREW
GUN BRACKET A. WIRING INSTALLED ABOVE ACCESSIBLE CEILINGS MAY BE EXPOSED CABLE.
B. WIRING INSTALLED IN WALLS, ABOVE INACCESSIBLE CEILINGS, OR AREAS WITH EXPOSED CEILINGS SHALL BE
BOX MOUNTING INSTALLED IN CONDUIT COMPLETE.
METAL STUDS BRACKET
CONDUIT
,A
�1 INFORMATION PLATE
P SQUARE BOX LAMACOID PLATE
PANEL 1LN1- EQUIPMENTSERVED
120/208V 3P 4W — — VOLTAGE
FED FROM MDP SOURCE OF POWER
NOTE: PROVIDE I. D. PLATE LABEL FOR
ELECTRICAL EQUIPMENT SUCH AS MAIN
SWITCHGEAR, SWITCHBOARD PANELBOARDS,
NOTE. FOR METAL STUD WALL CONSTRUCTION ONLY. AND TRANSFORMERS
WALL BOX INSTALLATION DETAIL �� ELECTRICAL EQUIPMENT I.D. LABELING DETAIL
NO SCALE NO SCALE
TYPICAL EMERGENCY
PAGESPEAKER
2 f TYPICAL GENERAL PAGE
SPEAKER
SECOND FLOOR
T
I— I NOTES:
1. SUPPORTS FOR CABLE SHALL BE INDEPENDENTLY SUPPORTED. CABLE SHALL NOT LAY OVER CONDUIT,
TT I
DUCTWORK, PIPING, STRUCTURAL SUPPORT MEMBERS, ETC. CABLE SHALL BE NEATLY INSTALLED AT RIGHT
ANGLES TO THE BUILDING LINES. ENGINEER WILL REQUIRE CABLE TO BE REMOVED AND REINSTALLED IF IT IS
NOT INSTALLED IN AN ACCEPTABLE MANNER.
EXISTING 2, REFER TO FLOOR PLANS FOR DEVICE LOCATIONS AND QUANTITY,
AUDIO PAGING
RACK 3. PROVIDE ALL REQUIRED EQUIPMENT AND MODIFICATIONS REQUIRED FOR A COMPLETE SYSTEM PER NEW
DEVICE QUANTITIES AND LOCATIONS.
I4. WIRING INSTALLATION.
A. WIRING INSTALLED ABOVE ACCESSIBLE CEILINGS MAY BE IXPOSEDCABLE.
COMPUTER 7006
B, WIRING INSTALLED IN WALLS, ABOVE INACCESSIBLE CEILINGS, ORAREAS WITH EXPOSEDCEILINGS SHALL
BE INSTALLED IN CONDUIT COMPLETE.
RELEASED FOR CONSTRUCTION
Subject to compliance with all regulations
of State and Local Codes
City of Carmel
��1A�lt _
Arc Flash Hazard
Appropriate PPE Required
Equipment Type
480V Switchgear
Grounding
Grounded
Work Distance
11 inches (300 PIT)
Availiable 3-Ph Baited Current
25 kA
Flash Protection Boundary
27 inches
Incident Energy at 11 inches
4.39 colI
Risk Category
2
Equipment Name:
Switchboard
NOTE: PROVIDE WARNING LABEL FOR ALL ELECTRICAL
EOUI PMENT SUCH AS MAIN SWITCHGEEAR, SWITCHBOARDS,
PANELBOARDS, AND TRANSFORMERS.
%,1 ELECTRICAL EQUIPMENT WARNING LABEL DETAIL
NOS
CALE
NOTES:
1, SUPPORTS FOR CABLESHALL BE INDEPENDENTLY SUPPORTED, CABLE SHALL NOT LAY OVER CONDUIT,
DUCTWORK, PIPING,STRUCTURAL SUPPORT MEMBERS, ETC. CABLE SHALL BE NEATLY INSTALLED AT RIGHT
ANGLES TO THE BUILDING LINES. ENGINEER WILL REQUIRE CABLE TO BE REMOVED AND REINSTALLED IF IT
IS NOT INSTALLED IN AN ACCEPTABLE MANNER.
2. REFER TO FLOOR PLANS FOR DEVICE LOCATIONS AND QUANTITY.
3. PROVIDE PLENUM RATED WIRE I CABLE AS REQUIRED.
4. PROVIDE ALL REQUIRED EQUIPMENT AND MODIFICATIONS REQUIRED FOR A COMPLETE SYSTEM PER NEW
DEVICE QUANTITIES AND LOCATIONS. —
NEW CABLE TRAY _
CAT 6A CABLE
F
ELECOMMUNICATIONS-j
BLE TOBE TERMINATED IDF BV CONTRACTOR.
TELECOM I
EQUIPMENT
PROVIDEDBY
OWNERAS
REQUIREDED
F7-Mr CONDUIT TO CABLE -
TRAY. TERMINATE CONDUITS
WITH BUSHING (TYPICAL)
I
LI
O I ES
QUANTITY OFT CABLES I
BE INSTALLED
EXISTING I REFER TO DETAIL ON THIS SHEE
DATA IN
CK FOR ADDITIONAL INFORMATION.
LOCATEDAS SHOWN ON
DRAWINGS.
COMPUTER 7006 _ SECOND FLOOR
TELECOM SYSTEM DETAIL
U NO SCALE
TYPICAL I ` TYPICAL
DOME DOME
LIGHT LIGHT
NURSE CALL
SYSTEM
CABINET
MASTER
EMERGENCYCALL
TYPICAL
TYPICAL
TYPICAL DUTY TYPICAL
STATION
STAULLTION WITH
PATIENT
NWITH
STATIONLOCATOR
CORD AND
STATION
CODE
STATION
ELEC. 1359
RESET BUTTON.
BLUE
(ALTERNATE)
SECOND FLOOR
%01 NURSE CALL DETAIL
NO SCALE
ADDRESSABLE RELAY FOR CONTROL PROVIDE ONE TO OTHER DEVICES
AT EACH HUE/SMOKANDRET AND
NFAT r SEE
STARTERS,AT EACH AHU SUPPLY AND
REr AN FAT FLOOR PLANS
EACH DOOR HOLD RELEASE DEVICE
PROVIDE SPARE CAPACITY J s
TOADD20% FUTUREDEVICESON
EACH INITIATION LOOP
TVPICALSMOKE TYPICAL TYPICAL DOOR
DETECTORWITH FIRESMOKE HOLDIRELEASE
SOUNDERBASE DAMPER DEVICE
NOTES,
1. ALL FIREALARM SYSTEM WIRING SHALL BE INSTALLED IN CONDUIT
COMPLETE.
2. REFER TO FLOOR PLANS FOR DEVICE LOCATIONS AND QUANTITIES.
3. EXISTING FIRE ALARM PANELWORKSHALL INCLUDE ALL NEW CARDS,
EQUIPMENT AND PROGRAMMING NECESSARY TO SUPPORT THE NEW
DEVICES AS INDICATED.
4. LABELALL FIRE ALARM DEVICES AS DIRECTED BV THE OWNER WITH
EXTERNAL TAGS AND LABELS ON DEVICE MSES.
I
71:1�:1I:1:IL56`P691gL56YNag151:11[N
L
IN CONDUIT AS REQUIRED
TYPICAL
HVAC UNIT
STARTER
— PROVIDE SPARE CAPACITY TO
ADD (2) SIGNAL DEVICES (TYP,
OF EACH SIGNAL CIRCUIT)
__E;� I
PROVIDESIGNAL
IXPANDERIAMPLIFIER POWER
SUPPLY ON EACH FLOOR FOR
SIGNAL DEVICES. LOCATE
EQUIPMENT IN ELECTRICAL
ROOM,
TYPICAL FOR EACH FLOOR
IXISTI NG
FIREALARM
CONTROL
PANEL
ELECTRICAL1012
MSKTD
& Associates
Architecture I Engineering I Interior Design
1715 Magnavox Way 930 North Mendian
Fort Wayne, IN 46804 Indianapolis, IN 46204
260432.9337 317.917.1190
w .msktd.cwm
PE10708732
STATE 9
W
�
E
W
_O
4—a
O
VJ
0
Al
�^'`)
an
^^L\\
)
r
"'
W�
L/
\
L
/
O
/�
..l
O
w+mmi
mmmmmmmo
LL
Z
M
O
O
L
V
M
C:)
��
VJ
C0
PROJECT NO.
DATE
7335
05-07-19
REV.
DATE
SET DESCRIPTION
FOR CONSTRUCTION
SET
SHEET TITLE
Electrical Details
DATE: V//L)U/-IU
SHEET NUMBER
E8-1 C