RELEASED FOR CONSTRUCTION
MECHANICAL AND PLUMBING ABBREVIATIONS
ABBREV.
DESCRIPTION
ABBREV.
DESCRIPTION
ABBREV.
DESCRIPTION
NE
ARCHITECT AND END IN EER
FHC
FIRE HOSE CABINET
OC
ON CENTER
AC OR ACU
AI R CONDITION NG UNIT OR Al R CO MPRESSOR
FIN
FINISH
OD
OUTSIDE DIAMETER
ACCU
AIR COOLED CONDENSING UNIT
FLA
FULL LOAD AMPS
OFCI
OWNER FURNISHED/CONTRACTOR INSTALLED
ADD
AIR CONDITIONING CONDENSATE DRAIN
FLR
FLOOR
OFOI
OWNER FURNISHEDIOWNER INSTALLED
AD
ACCESS DOOR
FODT
FUEL OIL DAY TANK
OM
OXYGEN MANIFOLD
ADJ
ADJUSTABLE ORADJACENT
FOP
FUEL OIL PUMP
OPER
OPERATOR
AFCV
AIRFLOWCONTROL VALVE
FOR
FUEL OIL RETURN
OPNG
OPENING
AFF
ABOVE FINISHED FLOOR
FOS
FUEL OIL SUPPLY
OSD
OPEN SITE DRAIN
AFMS
AIR FLOW MEASURING STATION
POST
FUEL OIL STORAGE TANK
AHU
AIR HANDLING UNIT
FOV
FUEL OIL VENT
P
PUMP, PNEUMATIC OR PRESSURE
ADD
AIR PRESSURE DROP
FP
FIRE PROTECTION
PC
PLUMBING CONTRACTOR
APPROX
APPROXIMATE
FPB
FAN POWERED BOX
PC
PRESSURE DROP OR PERFORATED DIFFUSER
AR
AIR RECEIVER
FPC
FIRE PROTECTION CONTRACTOR
PE
PNEUMATIC ELECTRIC
ARCH
ARCHITECT
FPM
FEET PER MINUTE
PF
PREFILTERS
AS
AIR SEPARATOR
FPS
FEET PER SECOND
PG
PROPYLENE GLYCOL
ATM
ATMOSPHERE
FPST
FIRE PROTECTION STORAGE TANK
PHC
PREHEAT COIL
AV
ACID VENT
FS
FLOWSWITCH
PIV
POST INDICATOR VALVE
AVMS
AIR VOLUME MEASURING STATION
FT
FEET OR FLASH TANK
PLT
PLASTERTRAP
AW
ACID WASTE
FTG
FOOTING OR FITTING
POC
POINT OF CONNECTION
FTR
FIN TUBE RADIATION
PPH
POUNDS PER HOUR
B
BOILER
PPM
PARTS PER MILLION
BCU
BLOWER COIL UNIT
G
GAS,NATURAL
PRO
PRESSURE RELIEF DOOR
BOD
BACKDRAFT DAMPER
GA
GAUGE
PREFAB
PREFABRICATED
BHP
BRAKE HORSEPOWER
GAL
GALLON
PRIES
PRESSURE
BI
BACKWARD INCLINED
BALM
GALVANIZED
FIRM
PRESSURE REDUCING VALVE
BLDG
BUILDING
GC
GENERAL CONTRACTOR
PSI
POUNDS PER SQUARE INCH
BOT
BOTTOM
GH
GRAVITY HOOD
PSIG
POUNDS PER SQUARE INCH GAUGE
BP
BRINE PUMP
GPH
GALLONS PER HOUR
PVC
POLYVINYL CHLORIDE
BST
BULK SALT STORAGE
GPM
GALLONS PER MINUTE
BTU
BRITISH THERMAL UNIT
TV
GAS NATURAL VENT
RA
RETURN AIR OR RELIEF AIR
BTUH
BTU PER HOUR
RA
RADIATED
H
HUMIDIFIER, HUMIDITY OR HEIGHT
RAT
RETURN AIR TEMPERATURE
CA
COMPRESSED AIR
HC
HEATING COIL
RIH
REHEAT
CAP
CAPACITY
HCP
HEATING COIL PUMP (HOT WATER)
RD
ROOF DRAIN
CAV
CONSTANT AIR VOLUME
HD
HEAD
RED
RECEIVER
CC
COOLING COIL
HE
HEAT EXCHANGER
RECIR
RECIRCULATING
CCP
COOLING COIL PUMP
HGT
HEIGHT
REF
REFRIGERATOR
CDS
CONDENSATE PUMP DISCHARGE
HO
HUB OUTLET
RF
RETURN AIR FAN
CENTRIF
CENTRIFUGAL
HOA
HAND -OFF -AUTOMATIC
RG
RETURN GRILLE
CFM
CUBIC FEET PER MINUTE
HORZ
HORIZONTAL
RH
RELIEF HOOD OR RELATIVE HUMIDITY
CFOI
CONTRACTOR FURNISHEDIOWNER INSTALLED
HOSP
HOSPITAL
RFC
REHEAT COIL
CH
CHILLER
HP
HORSEPOWER OR HEATPUMP
RLA
RUNNING LOAD AMPS
Cl
CASTIRON
HPR
HI GH PRESSURE CONDENSATE RETURN
RM
ROOM
CO
CLEAN OUT
FPS
HIGH PRESSURE STEAM
ROM
REVERSE OSMOSIS VENT
CO2
CARBON DIOXIDE
HR
HOUR
ROP
REVERSE OSMOSIS PUMP
COL
COLUMN
HRC
HEAT RECOVERY COIL
ROST
REVERSE OSMOSIS STORAGE TANK
COM
CARBON DIOXIDE MANIFOLD
HTR
HEATER
RP
RADIANT PANELS
COMP
COMPRESSOR
HVAC
HEATING, VENTILATION AND AIR CONDITIONING
RPG
RETURN PERFORATED GRILLE
CONIC
CONCRETE
HW
DOMESTIC HOT WATER
RPM
REVOLUTIONS PER MINUTE
CONN
CONNECTION
HAD
DOMESTIC HOT WATER RECIRC
RPZ
REDUCED PRESSURE BACKFLOW
CONST
CONSTRUCTION
HWCP
HOT WATER CIRCULATING PUMP
REDD
REQUIRED
CONT
CONTINUOUS
HAP
HEATING HOTWATERPUMP
RV
ROOFVENTILATOR
CP
CONDENSATE PUMP
HAIR
HEATING HOTWATER RETURN
CPD
CONDENSATE PUMP DISCHARGE
HWS
HEATING HOTWATERSUPPLY
S
SANITARYORSEWER
DUN
CABINET UNIT HEATER
HX
HEAT EXCHANGER
SA
SUPPLY AIR OR SOUND ATTENUATOR
CV
CENTRALVACUUM
HZ
HERTZ
SB
STEAM BOILER
CW
COLD WATER
SC
STEAM COIL
CWM
COLD WATER MAKE-UP
IA
INSTRUMENT AIR
SCC
STEAM CONDENSATE COOLER
CWP
CHILLED WATER PUMP
LAC
INSTRUMENT AIR COMPRESSOR
SCCH
SUBCOOLED CHILLER
CAR
CHILLED WATER RETURN
LAD
INSTRUMENT AIR DRYER, EQAD
SCFM
STANDARD CUBIC FEET PER MINUTE
CWS
CHILLED WATER SUPPLY
ID
INSIDE DIAMETER OR DIMENSION
SCH
SCHEDULE
IFB
INTEGRAL FACE AND BYPASS
SCW
SOFT COLD WATER (DOMESTIC)
D
DIFFUSER OR DAMPER
IHOM
IN-HOUSE OXYGEN MANIFOLD
SO
SUPPLY DIFFUSER OR SMOKE DAMPER
DB
DECIBELS OR DRY BULB
IN
INCHES
SEC
SECTION
DC
DUCT COIL
INCL
INCLUDE
SENS
SENSIBLE
DCV
DOUBLE CHECK VALVE
INSUL
INSULATED
SEP
SEWAGE EJECTOR PUMP
DCWBP
DOMESTIC COLD WATER BOOSTER PUMP
INT
INTERIOR
SF
SUPPLY AIR FAN
DID
DUAL DUCT
INV
INVERT
SG
SUPPLY GRILLE
CDC
DIRECT DIGITAL CONTROL
P.S.
INTERNATIONAL PIPE SIZING
SHT
SHEET
DE
DEAERATOR
ISOL
ISOLATION
SHIN
SOFT HOTWATER
DEFL
DEFLECTION
SK
SINK
DEG
DEGREE
JT
JOINT
SMBH
SENSIBLE MBH
DEPT
DEPARTMENT
SMC
SHEET METAL CONTRACTOR
DHWBP
DOMESTIC HOTWATER BOOSTER PUMP
KAIC
SHORT CIRCUIT RATING
SP
STATIC PRESSURE OR STORM PUMP
DI
DEIONIZED WATER
KEC
KITCHEN EQUIPMENT CONTRACTOR
SPEC
SPECIFICATIONS
CIA
DIAMETER
KW
KILOWATTS
SQ
SQUARE
DISC
DISCONNECT
SOFT
SQUARE FEET
TISCH
DISCHARGE
L
LENGTH
SRV
SAFETY RELIEF VALVE
CIS
DOWNSPOUT
LAC
LAB AIR COMPRESSOR
ST
STEAM TRAP
DSWBP
DOMESTIC SOFT WATER BOOSTER PUMP
LAD
LAB AIR DRYER
STD
STANDARD
DUC
DOOR UNDER CUT
LAN
LOCAL AREA NETWORK
STM
STORM
DWG
DRAWING
LAT
LEAVING AIR TEMPERATURE
STIR
STARTER
DIN
DISTILLED WATER
LAV
LAVATORY
STRUCT
STRUCTURAL
DWBP
DOMESTIC WATER BOOSTER PUMP
LBD
LINEARBAR DIFFUSER
SV
STEAM VENT
DWH
DOMESTIC WATER HEATER
LBS
POUNDS
SW
SWITCH
LD
LINEAR DIFFUSER
SYS
SYSTEM
EA
EXHAUST AIR
LF
LINEAR FOOT
SZ
SPRINKLERZONE
EAT
ENTERING AIR TEMPERATURE
LFD
LAMINAR FLOW DIFFUSER
EBH
ELECTRIC BASEBOARD HEATER
LFT
LEAVING FLUID TEMPERATURE
T
THERMOSTAT
EC
ELECTRICAL CONTRACTOR
LOC
LOCATION
TB
TERMINAL BOX
ECC
ENVIRONMENTAL CONTROL CONTRACTOR
LPR
LOW PRESSURE CONDENSATE RETURN
TCC
TEMPERATURE CONTROL CONTRACTOR
ECG
EGG CRATE GRILLE
LPS
LOW PRESSURE STEAM
TDH
TOTAL DISCHARGE HEAD
ED
EXHAUST DIFFUSER
_VG
LEAVING
TDV
TRIPLE DUTY VALVE
EDC
ELECTRIC DUCT COIL
LVP
LAB VACUUM PUMP
TEMP
TEMPERATURE
EER
ENERGY EFFICIENCY RATIO
LWT
LEAVING WATERTEMPERATURE
THW
TEMPERED HOT WATER
EF
EXHAUST AIR FAN
TILL
TEMPERATURE LOW LIMIT
EFT
ENTERING FLUID TEMPERATURE
MA
MEDICAL AIR
TMV
THERMOSTAT MIXING VALVE
EG
EXHAUST GRILLE OR ETHYLENE GLYCOL
MAC
MEDICAL AIR COMPRESSOR
TMBH
TOTAL MBH
ELEC
ELECTRIC
MAD
MEDICAL AIR DRYER
TSP
TOTAL STATIC PRESSURE
ELEV
ELEVATION
MAI
MEDICAL AIR INTAKE
TW
TEMPERED WATER
EVER
EMERGENCY
MAT
MIXED AIRTEMPERATURE
TYP
TYPICAL
EMG
EXTRUDED METAL GRILLE
MAX
MAXIMUM
ENCL
ENCLOSURE
MB
MOP BASIN
UH
UNIT HEATER
ENTR
ENTERING
MBH
BTUIHRX 1000
UNO
UNLESS NOTED OTHERWISE
EOM
END OF MAIN DRIP
MC
MECHANICAL CONTRACTOR
UR
URINAL
EQA
EQUIPMENTAIR
MCA
MINIMUM CIRCUIT AMPACITY
UVL
ULTRA VIOLET LIGHT
EQAC
EQUIPMENTAIR COMPRESSOR
MCC
MOTOR CONTROL CENTER
EQAI
EQUIPMENTAIR INTAKE
MD
MOTORIZED DAMPER
V
VENT
EQUIP
EQUIPMENT
MECH
MECHANICAL
VAC
VACUUM
EQV
EQUIPMENTVACUUM
MFR
MANUFACTURER
VAV
VARIABLE AIR VOLUME
EQVP
EQUIPMENT VACUUM PUMP
MH
MANHOLE
VB
VACUUM BREAKER
EQVV
EQUIPMENT VACUUM VENT
MIN
MINIMUM
VD
VOLUME DAMPER (MANUAL)
ERP
ELECTRIC RADIANT PANEL
MISC
MISCELLANEOUS
VEL
VELOCITY
ES
EMERGENCY SHOWER
MOCP
MAXIMUM OVERCURRENT PROTECTION
VSC
VARIABLE SPEED CONTROLLER
ESP
EXTERNAL STATIC PRESSURE OR ELEVATOR SUMP PUMP
MPSR
MEDIUM PRESSURE CONDENSATE RETURN
VTR
VENT THROUGH ROOF
ET
EXPANSION TANK
MPS
MEDIUM PRESSURE STEAM
VV
VACUUM VENT
EUH
ELECTRIC UNIT HEATER
MTD
MOUNTED
EW
EMERGENCY EYEWASH
MV
MEDICAL VACUUM
W
WASTE, WATTS OR WIDTH
EWC
ELECTRIC WATER COOLER
MVP
MEDICAL VACUUM PUMP
WAGD
WASTE ANESTHESIA GAS DISPOSAL PUMP
EAT
ENTERING WATER TEMPERATURE
WB
WET BULB
EXH
EXHAUST
N
NORTH OR NITROGEN
WI
WITH
EXIST
EXISTING
NA
NOT APPLICABLE
WIO
WITHOUT
EXT
EXTERIOR
INC
NORMALLY CLOSED OR NOISE CRITERIA
WC
WATER CLOSET OR WATER COLUMN
NIC
NOT IN CONTRACT
ACID
WALL CLEAN OUT
F
DEGREES FAHRENHEIT
NM
NITROGEN MANIFOLD
WFMD
WATER FLOWMEASURING DEVICE
F&B
FACE B BYPASS
NO
NORMALLY OPEN, NITROUS OXIDE, OR NUMBER
WG
WATER GAUGE
F&T
FLOAT AND THERMOSTATIC TRAP
NOM
NOMINAL OR NITROUS OXIDE MANIFOLD
ACT
WEIGHT
FIA
FIRE ALARM
NTS
NOT TO SCALE
Witt
WALL HYDRANT
FISD
FIRE AND SMOKE DAMPER
AM
WATER METER
FC
FLEXIBLE CONNECTION
0
OXYGEN
WP
WEATHERPROOF
FCU
FAN COIL UNIT
CA
OUTSIDE AIR
APT
WATER PRESSURE DROP
FD
FLOOR DRAIN OR FIRE DAMPER
OAT
OUTSIDE AIR TEMPERATURE
WS
WATER SOFTENER
FH
FIRE HOSE OR FUME HOOD
a
POUND
VALVE AND FITTING SYMBOLS
TAGS
PLAN VI EWS
DETAIL
V1
E
CALIBRATED BALANCE VALVE
V2
-D<a
PIPING FLEXIBLE CONNECTION
V3
--0
PIPE TURNED UP (UNLESS NOTED OTHERWISE)
V4
D
PIPE TURNED DOWN
V5
PIPE OUT TOP
V6
PIPE OUT BOTTOM
V7
THREADED N I PPLE WICAP
VB
—iI
PI PE WITH BLIND FLANGE
V9
CONCENTRIC REDUCER
MID
ALL-
ECCENTRIC REDUCER
V11
�b
CHECK VALVE
V12
��
UNION
V13
HHyy
N.1Dd
GATEVALVE
V14
I Cl
BALL VALVE
V15
a^fi}
M M
GLOBE VALVE
V16
�0
BUTTERFLY VALVE
V17
TEMPERATURE CONTROL- 2 WAY MODULATING VALVE
MIS
TEMPERATURE CONTROL 2 WAY 2 POSITION MODULATING VALVE
V19
0
TEMPERATURE CONTROL- 3 WAY MODULATING VALVE
TEMPERATURE CONTROL- 3 WAY 2 POSITION MODULATING VALVE
V20
C
0
V21
0
�
SAFETY RELIEF VALVE
V22
m
STRAINER
V23
-V -
FLOW METER
V24
0 S
0
FLOOR DRAIN
V25
I
I -J),
ZONE CONTROL VALVE(OS&Y)
V26
-EAr
AUTOMATIC FLOW CONTROL VALVE
V27
-0-
FLOW MEASURING DEVICE
V28
MANUAL AIR RELIEF VENT
V29
AUTOMATIC AIR RELIEF VENT
V30
-7EP-
LUBRICATED PLUG VALVE
V31
1�
STEAM PRESSU RE REDUCING VALVE
V32
ANGLEVALVE
V33
GAS PRESSURE RELIEF VALVE
V34
REFRIGERANT HOT GAS BY-PASS VALVE
V35
SHUT-OFF COCK(HYDRONICS)
V36
SOLENOIDVALVE
V37
41-
REFRIGERANT EXPANSION VALVE
V38
a
WATER PRESSURE REDUCINGREGULATING VALVE
V39
- (D�-
COMBINATION WATER PRESSURE RELIEF AND REDUCING VALVE
V40
0
-{Tr
STEAM TRAP
V41
DIELECTRIC UNION BETWEEN STEEL AND COPPER
V42
T1
STMIINER(STEAM)
V43
P
PRESSURE AND TEMPERATURE PLUG
V44
REFRIGERANT SIGHT GLASS
V45
THERMOMETER
V46
(PEPRESS V=VAC T=TEMP) GAUGE
V47
T
SENSOR(T-TEMP HFH UMIDITY)
V48
FLOW SWITCH
V49
CLEAN OUT
V51)
.
WATER HAMMER ARRESTOR OR ALARM PRESSURENACUUM SWITCH
V51
INDICATED EXPANSION LOOP (COLD SPRUNG)
V52—
ANCHOR
V53
—
GUIDE
V54
REDUCED PRESSURE BACIffLOW PREVENTER
V55
ATMOSPHERIC VACUUM BREAKER
V56
PRESSURE VACUUM BREAKER
V57
REFRIGERANT SHUT-OFF VALVE
V58
DOMESTIC WATER TEMPERATURE REGULATING VALVE
V59
EXPANSION JOINT
VBD
L'-1
DIFFERENTIAL SWITCH
V61
0
CENTRAL VACUUM OUTLET
PLUMBING PIPING SYMBOLS
6'DCW, —
��j DOMESTIC COLD WATER
_.. SIR 1 .
DOMESTIC HOTWATER
6' DHW R
- - - DOMESTIC HOT WATER RETURN
FIRE PROTECTION
6' NG�
NATURAL GAS
6'S�
SANITARY
—----6V�----—
VENT
6' SCW
— - - -
- DOMESTIC SOFT COLD WATER
GENERAL NOTES
(REQUIRED TO COMPLETE THE SCOPE OF WORK)
1. ALL CONTRACT DOCUMENTS(SPECI FICATI ONS AND D RAWI NGS) ARE COMPLI MENTARY AND
MUST BE USED IN COMBINATION TO OBTAIN COMPLETE CONSTRUCTION INFORMATION.
2. ALL CONFLI CTS SHALL BE BROUGHT TO THE ARCHITECTS OR ENGI NEERS ATTENTI ON IN
ORDER TO ALLOW A CLARIFICATION TO BE ISSUED. ANY WORK COMPLETED WITHOUT THE
CLARIFYING INFORMATION IS AT THE CONTRACTORS FINANCIAL RISK.
3. THE CONTRACTOR SHALL PROVIDE AND FURNISH ALL MATERIALS AND ACCESSORIES TO
CREATE A FULLY OPERATIONAL, CODE COMPLIANT AND TESTED SYSTEM. ALL MATERIALS
AND ACCESSORIES REQUIRED TO CREATE THE FULLY OPERATIONAL SYSTEM SHALL BE
INCLUDED IN THE COST OF THIS PROJECT.
4, THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE. THE CONTRACTOR MAY AT THEIR
OPTION MODIFY THE PIPE ROUTING IN ORDER TO CREATE A SYSTEM THAT MEETS THE
INTENT OF THIS SET OF CONSTRUCTION DOCUMENTS.
5. THE CONTRACTOR SHALL INCLUDE ALL ITEMS THAT ARE REQUIRED TO ENSURE THAT THE
ENTIRE SYSTEM IS FUNCTIONING IN COMPLIANCE WITH THE APPLICABLE CODES, AND
MANUFACTURES INSTALLATION RECOMMENDATIONS AND OR REQUIREMENTS.
6. ALL CUTTING, DRILLING AND PATCHING OF WALLS, FLOORS ANDIOR STRUCTURAL
MEMBERS FOR THE INSTALLATION OF THE PLUMBING AND FIRE PROTECTION SYSTEMS
SHALL BE PROVIDED AS PART OF THE SCOPE OF THIS PROJECT.
7. STRUCTURAL COMPONENTS SHALL NOT BE CUT, DRILLED OR MODIFIED IN ANY WAY
WITHOUT THE STRUCTURAL ENGINEERS REVIEW AND PRIOR WRITTEN APPROVAL.
B. PROVIDE FIRE STOPPING WHERE PIPES PENETRATE FIRE RATED FLOORS AND WALLS.
FIRE STOPPING MATERIALS AND METHODS SHALL BE PER LOCAL AND STATE CODES AND
REQUIREMENTS.
9. ALL PLUMBING SYSTEMS SHALL BE INSTALLED PER THE CURRENT PLUMBING CODE FOR
THE LOCATION OF THE WORK BEING INSTALLED.
10. ALL PLUMBING EQUIPMENT, PIPING, FIXTURES, AND PIPE ACCESSORIES SHALL BE NSF 61,
ANNEX G COMPLIANT.
11. ALL PIPING LOCATED WITHIN A RETURN AIR PLENUM SHALL COMPLY WITH A 25150 FLAME
SMOKE RATING. ANY EXISTING PIPING DISCOVERED WITHIN A RETURN AIR PLENUM THAT
DOES NOT COMPLY WITH THIS REQUIREMENT SHALL BE BROUGHT TO THE ATTENTION OF
THE ARCHITECT FOR FURTHER CLARIFICATION.
12. ALL EXTERIOR WALL PENETRATIONS SHALL BE SEALED WATER AND WEATHER TIGHT BY
THE APPROPRIATE TRADE COMPETENT IN COMPLETING THIS WORK. THE COST OF THIS
WORK SHALL BE INCLUDED IN THE SCOPE OF THIS PROJECT.
13. ALL VENT THROUGH ROOF VTR) LOCATIONS SHALL BE FIELD VERIFIED IN REGARDS TO
ANY OUTDOOR INTAKE. LOCATION OF VTR SHALL BE NO LESS THAN AS REQUIRED BY THE
LOCAL OR STATE CODES.
14. DO NOT ATTACH ANY CONSTRUCTION TO THE ROOF DECK JOIST BRIDGING, JOIST CROSS
BRACING, PIPING, CONDUIT, DUCTWORK OR ANY OTHER NON-STRUCTURAL ITEM.
15. DO NOT WELDOR DRILL INTO STRUCTURAL STEEL OR JOIST; INSTEAD USE CLAMPS, TIE
WIRE, THRU-BOLTS WITH WASHERS
16. DO NOT USE ANY PVC,PLASTIC,ETC. IN PLENUM OR DEMISING WALLS UNLESS FIRE
WRAPPED. ALL WOOD BLOCKING AND NAILERS, CONCEALED OR NOT SHALL BE FIRE
RETARDANT TREATED.
17. DO NOT PENETRATE BUILDING WALLS FOR ANY DUCTING OR VENTING; ROUTE THROUGH
ROOF USING OWNERS ROOFING CONTRACTOR.
18. VENT THROUGH ROOF INSTALLATION; ALL ROOFING WORK SHALL BE COMPLETED BY THE
OWNERS ROOFING CONTRACTOR. THE COST SHALL BE INCLUDED IN THE SCOPE OF THIS
PROJECT.
19. PIPING BELOW GROUND SHALL BE SERVICE -WEIGHT CAST IRON OR SCHEDULE 4D PVC. NO
HUB PIPING OR FERNCO CONNECTIONS ARE NOT PERMITTED BELOW GRADE.
20 DOMESTIC WATER PIPING ABOVE GRADE SHALL BE TYPE T'WATER TUBE.
21. ALL PIPING SHALL BE PROPERLY SUSPENDED BY THE STRUCTURE PER THE LOCAL CODES.
24. GAS PIPING SUPPORTED ON THE ROOF SHALL BE PROVIDED FREE FLOATING
PREFABRICATED SUPPORTS OR EQUIPMENT SUPPORTS WITH ROLLER ASSEMBLIES. WOOD
SUPPORTS ALL NOT BE PERMITTED.
25. ALL GAS PIPING SHALL BE PROVIDED PIPE LABELS IDENTIFYING THE GAS PRESSURE.
26. ALL GAS PIPING SHALL BE INSTALLED PER THE LOCAL CODES FOR MATERIALS AND
INSTALLATIONS REQUIREMENTS.
27. ALL SHUT -DOWN OF UTILITIES AND FIRE PROTECTION SYSTEMS SHALL BE ARRANGED WITH
NO LESS THAN SEVEN(7) DAYS NOTICE TO THE OWNER. WORK MAY NOT COMMENCE
UNLESS WRITTEN APPROVAL IS PROVIDED BY THE OWNER.
28, ALL DOMESTIC WATER BRANCH PIPES SERVING FIXTURES OR EQUIPMENT WITH FAST
ACTING OR ELECTRONIC VALVES SHALL BE PROVIDED WATER HAMMER ARRESTORS.
29. ALL BRANCH PIPES FROM DOMESTIC WATER MAINS SHALL BE PROVIDED QUARTER TURN
FULL PORT BALL VALVES ON THE BRANCH PIPE JUST ADJACENT TO THE MAIN.
FLOOR PLAN SYMBOLS
TYP
1 SECTION WITH TOP NUMBER INDICATING
SECTION DESIGNATION AND BOTTOM
A101 NUMBER
INDICATING DRAWING THAT SECTION IS CUT
ON
1 TYP DETAIL WITH TOP LETTER INDICATING DETAIL
A101 DESIGNATION
AND BOTTOM NUMBER INDICATING DRAWING THAT DETAIL
IS REFERENCED ON OR DRAWING THAT DETAIL IS DRAWN
ON
7O PLAN NOTE
(�
UN THERMOSTAT -'N' INDICATING NIGHT SETBACK THERMOSTAT
O HUMIDISTAT
A. GENERAL NOTEHAT SECTION IS DRAWN ON
1. PLAN NOTE LIST
4%ir CONNECTION OF NEWWORK TOEXISTING
H
V
^W
NO
W
am
IM
2
Z
O
0
LLI
C /
MSKTD
& Associates
Architecture I Engineering I Interior Design
1715 Magnavox Way 930 North Meridian
Fort Wayne, IN 46804 Indianapolis, IN 46204
260.432.9337 1 317.917.1190
w .msktd.cwm
Opnn4U1p
`��ANN A. � 4oe
g PE10708732
3z _
P�tL STATE 9 A ?
W
TOT
V!
E
W
co
Q
}r
O
^�
W
0
0
CIO
W
Vi
V/
W
VJ
i
0
O
LL
Z
V/
`V
Cc:
O
0
O
(`)
O
U)
VJ
PROJECT NO. DATE
7335 05-07-19
REV. DATE
SET DESCRIPTION
SHEET TITLE
Plumbing Symbols and
General Notes
Subject to compliance with all regulations
of State and Local Codes
City of Cannel
1�01AG19
DATE: V//V`U/-IU
SHEET NUMBER
P0.1