HomeMy WebLinkAboutE06.01 Elec SpecsSECTION 2E0000 - BASIC ELECTNLCAL REC MEMBITS A. NOTE 1. THE ABBREVIATION LSD&C WHEREVER IT APPEARS IN THESE ELECTRICAL DRAWINGS AND/OR SPECIFICATIONS SHALL REFER TO "UNITED STORE DESIGN AND CONSTRUCTION". ANY REFERENCE TO TENANT'S PROJECT MANAGER OR FURNISHED BY ANY OF THE ABOVE REFERS TO LSD&C. 23RAWINGS AND GENERAL PROVISIONS OF CONTRACT, INCLUDING GENERAL AND SUPPLEMENTARY CONDITIONS AND ALL OTHER SPECIFICATION SECTIONS, APPLY TO THIS AND THE OTHER SECTIONS OF DIVISION 26. &THE CONTRACTOR FOR THIS DIVISION OF WORK IS REQUIRED TO READ THE SPECIFICATIONS AND REVIEW DRAWINGS FOR ALL DIVISIONS OF WORK AND IS RESPONSIBLE FOR THE COORDINATION OF THIS WORK AND THE WORK OF HIS OR HER SUBCONTRACTORS WITH ALL DIVISIONS OF WORK. IT IS THIS CONTRACTOR'S RESPONSIBILITY TO PROVIDE HIS OR HER SUBCONTRACTORS WITH A COMPLETE SET OF BID DOCUMENTS. 4.THIS ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR SCHEDULING THE COMPLETION AND INSPECTION OF THIS WORK TO COMPLY WITH THE LSD&C SCHEDULE AND THE PROJECT COMPLETION DATE. S. 6. REFER TO RESPONSIBILITY SCHEDULE ON SHEET E01.01 OF THIS SET FOR INFORMATION IN REGARD TO RESPONSIBILITY OF WORK OR ITEMS WHICH MAY AFFECT BID. IL GENERAL REQUIREMENTS 1. THIS CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS, EQUIPMENT, SERVICES, TOOLS, TRANSPORTATION, INCIDENTALS AND DETAILS NECESSARY TO PROVIDE A COMPLETE ELECTRICAL SYSTEM AS SHOWN ON THE DRAWINGS, CALLED FOR IN THE SPECIFICATIONS, AND AS REQUIRED BY JOB CONDITIONS. ALL WORK NOT SPECIFICALLY NOTED AS BEING BY THE LANDLORD OR LSD&C SHALL BE PROVIDED BY THIS CONTRACTOR. CLOSELY COORDINATE THE ENTIRE INSTALLATION WITH THE LANDLORD AND THE LSD&C PROJECT MANAGER, AS REQUIRED. 2.THE DRAWINGS AND SPECIFICATIONS ARE INTENDED TO SUPPLEMENT EACH OTHER AND ANY MATERIAL OR LABOR CALLED FOR IN ONE SHALL BE FURNISHED AND INSTALLED EVEN THOUGH NOT SPECIFICALLY MENTIONED IN BOTH. ANY MATERIAL OR LABOR WHICH IS NEITHER SHOWN ON THE DRAWINGS NOR CALLED FOR IN THE SPECIFICATIONS BUT WHICH IS OBVIOUSLY NECESSARY TO COMPLETE THE WORK AND WHICH IS USUALLY INCLUDED IN WORK OF SIMILAR CHARACTER SHALL BE FURNISHED AND INSTALLED AS PART OF CONTRACT. & WHERE THE DRAWINGS OR SPECIFICATIONS CALL FOR ITEMS WHICH EXCEED CODES OR THE LANDLORD'S TENANT CRITERIA, THE CONTRACTOR IS RESPONSIBLE FOR FURNISHING AND INSTALLING THE SYSTEM WITH THE MORE STRINGENT REQUIREMENTS AS DESIGNED AND DESCRIBED ON THESE DRAWINGS UNLESS SPECIFICALLY NOTED OTHERWISE. CALL WORK IN THIS SECTION SMALL BE INSTALLED SO AS TO BE READILY ACCESSIBLE FOR OPERATING SERVICING MAINTAINING AND REPAIRING. THIS CONTRACTOR IS RESPONSIBLE FOR PROVIDING SUFFICIENT SERVICE ACCESS TO ALL EQUIPMENT. 5. ALL WORK SHALL BE PERFORMED IN A NUT PROFESSIONAL MANNER USING GOOD CONSTRUCTION PRACTICES. 6. UNLESS SPECIFICALLY NOTED OTHERWISE MATERIALS PRODUCTS AND EQUIPMENT, INCLUDING ALL COMPONENTS THEREOF SHALL BE NEW UNDERWRITERS LABORATORIES LISTED AND LIBELED AND SIZED IN CONFORMITY WITH REQUIREMENTS OF STATE AND LOCAL CODES, WHICHEVER IS MORE STRINGENT. 7.THIS CONTRACTOR SHALL DO ALL CUTTING CHASING AND CHANNELING REQUIRED FOR ANY WORK UNDER THIS DIVISION. CUTTING SHALL HAVE PRIOR APPROVAL BY LSD&C PROJECT MANAGER AND THE LANDLORD. ALL PATCHING SHALL BE BY G.C. AND SHALL MATCH THE SURROUNDING SURFACES. & THE ELECTRICAL CONTRACTOR SHALL MAKE ALL FINAL ELECTRICAL CONNECTIONS AS REQUIRED FOR A COMPLETE AND OPERATING SYSTEM. C. TEMPORARY LIGHT AM POWER 1. THIS CONTRACTOR SHALL FURNISH AND INSTALL ALL TEMPORARY WIRING AND RELATED GROUND FAULT INTERRUPTION PROTECTION FOR LIGHT AND POWER FOR ALL CONTRACTORS AND IS RESPONSIBLE FOR ITS REMOVAL 2.AL1 TEMPORARY LIGHTING WILL CONFORM WITH OSHA STANDARDS. 3.THE GENERAL CONTRACTOR SETS UP ALL ELECTRICAL UTILITIES IN THE NAME OF UNITED BRANDS. LIMITED BRANDS PAYS FOR ALL UTILITIES THROUGHOUT CONSTRUCTION. a 00010 L ALL WORK SHALL CONFORM TO THE LANDLORDS' CRITERIA, THE STATES, COUNTYS, CITY'S, PROVINCE AND LOCAL CODES AND ORDINANCES, SAFETY AND HEALTH CODES, NFPA/NFPAC CODES, ENERGY CODES AND ALL OTHER APPLICABLE CODES AND REQUIREMENTS. THIS CONTRACTOR SHALL INQUIRE INTO AND COMPLY WITH ALL APPLICABLE CODES, ORDINANCES, AND REGULATIONS. THIS CONTRACTOR SMALL INCLUDE ANY CHANGES REQUIRED BY CODES IN THE BID AND IF THESE CHANGES ARE NOT INCLUDED IN THE BID, THEY SHALL E QUALIFIED AS A SEPARATE LINE REM IN THE BID. AFTER CONTRACT IS AWARDED. CHANGE ORDERS FOR INCREASED COSTS DUE TO CODE ISSUES WILL NOT E ACCEPTED BY LSD&C, UNLESS ALLOWANCES HAVE PREVIOUSLY BEEN AGREED UPON. E LICENSES, PWMTB, NMECTMM & FEES I. THIS CONTRACTOR SHALL OBTAIN AND PAY FOR ALL LICENSES, PERMITS, INSPECTIONS, AND FEES REQUIRED OR RELATED TO HIS OR HER WORK. 2.FURNISH TO THE LSD&C'S PROJECT MANAGER ALL CERTIFICATES OF INSPECTION AND FINAL INSPECTION APPROVAL AT COMPLETION OF PROJECT. F. TRADE MALES, MANUFACTURERS AND SHOP DRAWINGS 1. WHERE TRADE NAMES AND MANUFACTURERS ARE USED ON THE DRAWINGS OR IN THE SPECIFICATIONS, THE EXACT EQUIPMENT SHALL BE USED AS A MINIMUM FOR THE BASE BID. MANUFACTURERS CONSIDERED AS AN EQUAL OR BETTER IN ALL ASPECTS TO THAT SPECIFIED WILL BE SUBJECT TO APPROVAL IN WRITING BY LSD&C'S PROJECT MANAGER THROUGH SHOP DRAWING SUBMITTAL PROCESS FOR ACCEPTANCE PRIOR TO INSTALLATIONS. THE USE OF ANY UNAUTHORIZED EQUIPMENT SHALL BE REPLACED AT THE CONTRACTOR'S EXPENSE. 2. GENERAL CONTRACTOR SHALL SUBMIT ONLY SUBSIIMION REQUESTS TO LSD&C PROJECT MANAGER FOR APPROVAL. SUBMISSIONS SHALL BE MADE EARLY ENOUGH IN PROJECT TO ALLOW FOUR (4) WORKING DAYS FOR LSD&C PROJECT MANAGER'S REVIEW WITHOUT CAUSING DELAYS OR CONFLICTS TO THE JOB'S PROGRESS. SUBMITTALS SHALL BEAR THE STAMP OF THE GENERAL CONTRACTOR AND THE SUBCONTRACTOR SHOWING THAT HE HAS REVIEWED AND CONFIRMED THAT THE SUBMITTALS ARE IN CONFORMANCE WITH THE CONTRACT DRAWINGS AND SPECIFICATIONS OR INDICATE WHERE EXCEPTIONS HAVE BEEN TAKEN. 0. GUARANTEE L THIS CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORK PROVIDED UNDER HIS OR HER CONTRACT AND SHALL MAKE GOOD, REPAIR OR REPLACE AT HIS OR HER OWN EXPENSE, ANY DEFECTIVE WORK, MATERIAL, OR EQUIPMENT WHICH MAY BE DISCOVERED WITHIN A PERIOD OF 12 MONTHS FROM THE DATE OF ACCEPTANCE OF THE INSTALLATION BY LSD&C'S PROJECT MANAGER (IN WRITING). EXTENDED WARRANTIES ARE AS SPECIFIED WITH INDIVIDUAL EQUIPMENT. 2.THE EQUIPMENT MANUFACTURER SHALL GUARANTEE AND PROVIDE A 12 MONTH GUARANTEE TO LSD&C FROM THE DATE OF ACCEPTANCE. THE CONTRACTOR SHALL WARRANT THE INSTALLATION OF THIS EQUIPMENT AND WILL BE RESPONSIBLE FOR ANY DAMAGE AND/OR MALFUNCTION CAUSED BY THE INSTALLATION. THIS CONTRACTOR SHALL NOT BUR ADDITIONAL WARRANTIES BEYOND A COMPLETE WORKING SYSTEM. IL RECORD DRAWINGS 1. THIS CONTRACTOR SHALL MAINTAIN ONE SET OF DRAWINGS ON THE JOB SITE UPDATED WEEKLY TO RECORD ALL DEVIATIONS FROM CONTRACT DRAWINGS, SUCH AS: o. LOCATION OF CONCEALED PULLBOXES. '.. b. REVISIONS, ADDENDUMS, AND CHANGE ORDERS.. c. SIGNIFICANT DEVIATIONS MADE NECESSARY BY FIELD CONDITIONS, APPROVED EQUIPMENT SUBSTITUTIONS, AND CONTRACTOR'S COORDINATION WITH OTHER TRADES. 2. AT COMPLETION OF THE PROJECT AND BEFORE FINAL APPROVAL THIS CONTRACTOR SMALL MAKE ANY FINAL CORRECTIONS TO DRAWINGS AND CERTIFY THE ACCURACY OF EACH PRINT BY SIGNATURE THEREON. FAILURE TO KEEP THESE RECORDS WILL ALLOW LSD&C TO DIRECT THE GENERAL CONTRACTOR TO PROVIDE THESE RECORDS AT HIS OR HER EXPENSE PRIOR TO FINAL PAYMENT. L DDCEPAHM IN DOOINENTB 1. DRAWINGS (PLANS, SPECIFICATIONS, AND DETAILS) ARE DIAGRAMMATIC AND INDICATE THE GENERAL LOCATION AND INTENT OF THE MECHANICAL SYSTEMS. WHERE DRAWINGS, EXISTING SITE CONDITIONS, SPECIFICATIONS OR OTHER TRADES CONFLICT OR ARE UNCLEAR, ADVISES THE GENERAL CONTRACTOR IN WRITING, PRIOR TO SUBMITTAL OF BID. THE GENERAL CONTRACTOR IS RESPONSIBLE TO ADVISE LSD&C'S PROJECT MANAGER, IN WRITING, OF VARIATIONS TO CONTRACT DOCUMENTS PRIOR TO SUBMISSION OF BID. OTHERWISE, ESD&C PROJECT MANAGER'S INTERPRETATION OF CONTRACT DOCUMENTS OR CONDITIONS SHALL BE FINAL WITH NO ADDITIONAL COMPENSATION PERMITTED. J. PHASING EOU REMEM 1. THIS CONTRACTOR IS TO INCLUDE IN HIS OR HER BID ALL NECESSARY SERVICE REQUIRED TO KEEP THE OPERATING PHASE OF THE STORE'S HVAC, ELECTRICAL, PLUMBING AND SPRINKLER SERVICE IN OPERATION. CONTRACTOR SHALL SCHEDULE IN WRITING WITH LSD&C'S PROJECT MANAGER AND THE LANDLORD ONE WEEK PRIOR TO ANY SHUT DOWN OF THE HVAC, PLUMBING OR FIRE PROTECTION SYSTEMS. K. EIWLITION 1. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF THE DEMOLITION OF EXISTING WORK AND THE DEMOLITION PROVIDED BY THE GENERAL CONTRACTOR. COORDINATE WITH THE GENERAL CONTRACTOR ANY EXISTING EQUIPMENT REQUIRED TO BE LEFT INTACT. 2.THIS CONTRACTOR SHALL INCLUDE, AND WILL BE HELD RESPONSIBLE FOR, THE REMOVAL OF ALL EXISTING CONDUIT, FIRE ALARM SYSTEM, SWITCH GEAR, PITCH POCKETS AND EQUIPMENT ETC.. UNLESS SPECIFICALLY NOTED OTHERWISE. CONTRACTOR SHALL VERIFY WITH THE LANDLORD ALL PRESUMED ARANDONED EQUIPMENT, CONDUIT AND SWITCH GEAR PRIOR TO REMOVAL PITCH POCKETS SHALL BE REMOVED AND THE ROOF PATCHED, AS REQUIRED BY THE LANDLORD. ALL EXTRANEOUS ITEMS IN THE SPACE OR ON THE ROOF NOT APPLICABLE TO THE NEW WORK SHALL BE REMOVED AND ROOF/WALL/FLOOR PATCHED/REPAIRED TO LIKE NEW CONDITION. EXISTING ABANDONED CONDUIT OR EQUIPMENT IN THE FLOOR, EMBEDDED IN CONCRETE, OR OTHERWISE INACCESSIBLE, ARE TO BE CUT OFF AND SEALED BELOW OR WITHIN FLOOR OR WALL LEVEL WHEN THEY ARE NOT TO BE REUSED IN THIS PROJECT. IF REQUIRED BY LANDLORD OR CODES, ABANDONED CONDUIT SHALL BE REMOVED TO POINT OF ORIGINATION. CONFIRM EXTENT OF DEMOLITION PRIOR TO BID AND INCLUDE IN PROPOSAL. & ALL UNUSED COMMUNICATION, DATA, AND LOW VOLTAGE CABLING IS TO BE REMOVED IN ACCORDANCE WITH N.E.C. 725.(3)B AND 760.3(A). L SLEMBS 1. THIS CONTRACTOR SHALL PROVIDE SLEEVES TO PROTECT EOUIPMENT OR FACILITIES IN THE INSTALLATION. EACH SLEEVE SHALL EXTEND THROUGH ITS RESPECTIVE FLOOR, WALL OR PARTITION AND SHALL BE CUT FLUSH WITH EACH SURFACE EXCEPT SLEEVES THAT PENETRATE THE FLOOR, WHICH SHALL EXTEND 2" ABOVE THE FLOOR. CONTRACTOR SHALL COORDINATE THROUGH THE LANDLORD ANY CORE DRIVING OR CUTTING OF OPENINGS IN MASONRY FLOORS OR WALLS. 2. ALL SLEEVES AND OPENINGS THROUGH FIRE RATED WALLS AND/OR FLOORS SHALL BE FIRE SEALED WITH CALCIUM SILICATE, SILICONE "RIV" FOAM, "311' FIRE RATED SEALANTS OR EQUAL, SO AS TO RETAIN THEIR FIRE RATING. 3.SLEEVES IN BEARING AND MASONRY WALLS, FLOORS, AND PARTITIONS SHALL BE STANDARD WEIGHT STEEL PIPE FINISHED WITH SMOOTH EDGES FOR OTHER THAN MASONRY PARTITIONS, THROUGH SUSPENDED CEILINGS, OR FOR CONCEALED VERTICAL PIPING, SLEEVES SHALL BE NO. 22 U.S.G. GALVANIZED STEEL MINIMUM. IS MAMONN 1. HANGERS SHALL INCLUDE ALL MISCELLANEOUS STEEL SUCH AS ANGLE IRON, BANDS, C-CLAMPS WITH RETAINING CLIPS, CHANNELS, HANGER RODS, ETC., NECESSARY FOR THE INSTALLATION OF WORK. 2.RANGERS SHALL BE FASTENED TO BUILDING STEEL, CONCRETE, OR MASONRY, BUT NOT TO PIPING. HANGING FROM METAL DECK IS NOT PERMITTED. HANGERS SHALL BE ATTACHED TO UPPER CHORD OF BAR JOIST. WHERE INTERFERENCES OCCUR, AND IN ORDER TO SUPPORT DUCTWORK OR PIPING, THE CONTRACTOR SHALL INSTALL TRAPEZE TYPE HANGERS OR SUPPORTS WHICH SHALL BE LOCATED WHERE THEY DO NOT INTERFERE WITH ACCESS TO FIRE DAMPERS, VALVES, AND OTHER EQUIPMENT. HANGER TYPES AND INSTALLATION METHODS ARE ALSO SUBJECT TO LANDLORD CRITERIA. 3.HANGERS FOR ALL INSULATED PIPING SHALL BE SIZED AND INSTALLED FOR THE OUTER DIAMETER OF INSULATION. INSTALL 6" LONG SPLIT CIRCLE GALVANIZED SADDLE BETWEEN THE RANGER AND THE PIPE INSULATION. 4.HANGERS AND PIPING OF DISSIMILAR METALS SHALL BE DI -ELECTRICALLY SEPARATED. FL FINAL ELECTRICAL BISPECTI01 1. ASIDE FROM NORMAL INTERIM INSPECTIONS OF WORK IN PLACE, LSD&C MAY HAVE AN INDEPENDENT ELECTRICAL CONTRACTOR INSPECT THE FINISHED ELECTRICAL INSTALLATION UPON COMPLETION FOR COMPLIANCE WITH THE PLANS, SPECIFICATIONS AND CODES. THE INSTALLING CONTRACTOR WILL BE RESPONSIBLE TO BRING ALL ITEMS REPORTED BY THE INDEPENDENT ELECTRICAL CONTRACTOR UP TO PUNS AND SPECIFICATION REQUIREMENTS. 0. SCOPE OP WINK 1. THIS CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, EQUIPMENT, SERVICES, TOOLS, TRANSPORTATION, AND FACILITIES NECESSARY FOR, --'--' -"' "'-"'- "'- "'-'-------- -"--"-NISHING, INSTALLATION, COMPLETION AND TESTING OF ALL THE WORK FOR THE ELECTRICAL RELEASED FOR CONSTRUCTION OR IN THE SPECIFICATIONS, AND AS REQUIRED BY JOB CONDITIONS, TO INCLUDE, BUT NOT BE Subject to compliance with all regulations of State and Racal Codes City of Carmel 1"ATIONS a.A COMPLETE ELECTRICAL DISTRIBUTION SYSTEM INCLUDING THE INSTALLATION OF LSD&C FURNISHED POWER DISTRIBUTION SYSTEM UNIT, SAFETY SWITCHES, DISCONNECT SWITCHES AND MOTOR STARTERS (SOMETIMES FURNISHED AND INSTALLED BY CONTRACTOR), AND LIGHTING. IT IS THE ELECTRICAL CONTRACTOR'S RESPONSIBILITY TO INCLUDE IN HIS OR HER BID FOR PROVIDING SERVICE EQUIPMENT NECESSARY FOR TIE-IN TO LANDLORD'S DISTRIBUTION EQUIPMENT OR TO OBTAIN SERVICE FROM LOCAL UTILITY COMPANY. REFER TO ELECTRICAL RESPONSIBILITY SCHEDULE AND ELECTRICAL POWER RISER DIAGRAM FOR ADDITIONAL INFORMATION. b.CONTRACTOR SHALL INCLUDE IN BID ALL NECESSARY MATERIALS REQUIRED TO COMPLETE THE SYSTEM INCLUDING, BUT NOT UNITED T09 FEEDERS, BRANCH CIRCUITS, JUNCTION BOXES, OUTLET BOXES, WIRING DEVICES, COVERPLATES, CONDUITS, MOTOR STARTERS, DISCONNECTS, ETC. a.METERING AND CURRENT TRANSFORMERS AS REQUIRED BY DRAWINGS, LSDAC, UTILITY COMPANY, AND/OR LANDLORD. d.THE WIRING OF MECHANICAL EQUIPMENT AS OUTLINED ON THE BID SET DRAWINGS AND IN THE SPECIFICATIONS. WORK SHALL INCLUDE WIRING OF ALL STARTERS, DISCONNECTS, AND POWER WIRING OF MECHANICAL EQUIPMENT EXCEPT AS SPECIFICALLY NOTED OTHERWISE. ALL LOW VOLTAGE (24 VOLT) EMS TEMPERATURE CONTROL WIRING SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR UNLESS NOTED SPECIFICALLY ON DRAWING. e.INSTALLATION OF LIGHT FIXTURES AND LAMPS AS SHOWN ON THE DRAWINGS INCLUDING ALL DEVICES, EQUIPMENT, ETC. REQUIRED FOR MOUNTING. f. A COMPLETE CONDUIT SYSTEM FOR TELEPHONE/DATA AND TRAFFIC COUNTER INCLUDING BRANCH CONDUITS, OUTLET BOXES, PULL WIRES,. GROUND CONDUCTORS, COVER PLATES, ETC. OR AS SPECIFICALLY NOTED OTHERWISE ON THE DRAWINGS. g.A COMPLETE EMERGENCY AND EDT UGHTING SYSTEM AS SHOWN ON THE DRAWINGS h.TEMPORARY SERVICE AS INDICATED IN THE SPECIFICATIONS, INCLUDING ITS REMOVAL I. FINAL CONNECTIONS TO ALL SIGNS, CORNICE LIGHTING, CASE LIGHTING, ETC. AS SHOWN ON DRAWINGS. (.INSTALLATION AND WIRING OF SPEAKERS, AMPLIFIERS, CONDUIT AND FINAL CONNECTIONS FOR SOUND SYSTEM AS SHOWN. k. SMOKE/FIRE ALARM WIRING, DEVICES AND CONDUIT, AS SHOWN OR DESCRIBED ON DRAWINGS OR AS NECESSARY TO MEET LANDLORD, STATE, LOCAL INSURANCE AND FIRE DEPARTMENT REQUIREMENTS. I. INSTALLATION OF CONDUITS STUBBED TO ABOVE CEILING FOR HVAC. ALSO, ANY ADDITIONAL CONDUIT FOR HVAC CONTROL EQUIPMENT WHERE PLENUM RATED CABLES ARE NOT PERMITTED. m2ALANCING LOADS. n.AS-BUILT, PANEL DESCRIPTION AND CIRCUIT BREAKER SPECIFIC LABELING. 2.WORK NOT INCLUDED: THE FOLLOWING ITEMS OF ELECTRICAL CONSTRUCTION ARE NOT INCLUDED IN THIS CONTRACT: a.TELEPHONE INSTRUMENTS AND WIRING UNLESS NOTED OTHERWISE. b.DATA CABLE WIRING UNLESS NOTED OTHERWISE. 3.BEFORE STARTING WORK THIS CONTRACTOR SHALL EXAMINE THE ARCHITECTURAL STRUCTURAL FIRE PROTECTION MECHANICAL AND PLUMBING PLANS SHOP DRAWINGS AND SPECIFICATIONS TO SEQUENCE, COORDINATE AND INTEGRATE THE VARIOUS ELEMENTS OF THE ELECTRICAL SYSTEM MATERIALS AND EQUIPMENT WITH OTHER CONTRACTORS TO AVOID INTERFERENCES AND CONFRONTATIONS. P. CLEANING I. AT THE END OF THE PROJECT THIS CONTRACTOR SHALL CLEAN ALL EQUIPMENT, INCLUDING UGHT FIXTURES TO THE SATISFACTION OF LSD&C. ALL DUST, DIRT, DEBRIS, AND FOREIGN MATTER SHALL BE REMOVED FROM ALL EQUIPMENT. SECTION 26012/ - MADTENANCE TESTING OF ELECTRICAL SYSTEMS A ALL CONNECTIONS AT PANELS, UGHTING CONTACTORS AND SWITCHES ARE TO BE MADE, ALL SPLICES COMPLETE. ALL FUSES IN PLACE, AND ALL CIRCUITS CONTINUOUS FROM POINT OF SERVICE CONNECTION TO ITS FINAL DESTINATION AND ALL COVERS AND PLATES INSTALLED PRIOR TO THE TIME OF FINAL INSPECTION BY LSO&C'S PROJECT MANAGER. B. UPON COMPLETION OF THE WORK, ALL PARTS OF THE ELECTRICAL INSTALLATION SHALL E TESTED AND PROVED FREE OF UNWANTED GROUNDS AND OTHER DEFECTS. C. ALL OVERLOAD DEVICES INCLUDING EQUIPMENT FURNISHED UNDER OTHER CONTRACTS E SHALL SET AND ADJUSTED TO SUIT THE LOAD CONDITIONS. D. TEST AND MAKE CORRECTIONS/ADJUSTMENTS FOR PHASE BALANCING. E. THIS CONTRACTOR IS TO BALANCE THE VOLTAGE LEAVING THE STEP-DOWN TRANSFORMER TO PROVIDE A SECONDARY VOLTAGE OF 120 MINIMUM TO 125 VOLTS MAXIMUM BY ADJUSTING THE TRANSFORMER TAPS ONCE ALL THE FINAL CONNECTIONS HAVE BEEN MADE TO THE LOW VOLTAGE PANELBOARD. INCLUDE FINAL BALANCE REPORT WITH AS -BUILT DRAWINGS. SECTION 260818 - ELECTRICAL POWER CONDUCTORS AM CABLES A. CONDUCTORS FOR FEEDERS AND BRANCH CIRCUITS SHALL BE COPPER AND THE AWG SIZE AND TYPE AS SHOWN ON DRAWINGS. MINIMUM WIRE SIZE SHALL BE #12 AND THE CONDUCTORS SHALL BE 60D VOLT INSULATION TYPE THW, THWN, THHN, OR RW90(CANADA). B. MINIMUM WIRE SIZE - 20 AMP BRANCH CIRCUIT SHALL BE AWG LISTED, SIZE PER DISTANCE SHOWN BELOW. DISTANCE SHALL BE MEASURED FROM THE PANELBOARD CIRCUIT BREAKER TO THE FARTHEST OUTLET. 1./12 LESS THAN 100 FEET 2.g110 BETWEEN 100 - 150 FEET 3./8 BETWEEN 150 - 250 FEET 4. /6 OVER 250 FEET C. ON ALL 20 AMP BRANCH CIRCUITS, CONDUCTORS LARGER THAN /10 AWG SHALL BE REDUCED TO /10 AMID WITHIN 10 FEET OF PANELBOARD AND DEVICE IN JUNCTION BOXES ON RATED TERMINAL STRIPS. D. CONDUCTORS MAY BE STRANDED FOR SIZES /10 AWG AND LARGER. CONDUCTORS' SIZE /12 SHALL BE SOLID. E. ALUMINUM CONDUCTORS ARE NOT PERMITTED, EXCEPT AT SERVICE ENTRANCE, WHERE REQUIRED BY LANDLORD. CONDUCTOR CONNECTION SHALL BE PER MANUFACTURER'S REQUIREMENTS. CONTRACTOR SHALL OBTAIN WRITTEN PERMISSION FROM GENERAL CONTRACTOR AND LSD&C'S PROJECT MANAGER WHEN USED. F. ALL WIRING SHALL BE IN CONDUIT, UNLESS SPECIFICALLY NOTED OTHERWISE (I.E. LOW VOLTAGE PLENUM RATED WIRE). G. THE USE OF ROMEX OR BX CABLE IS NOT PERMITTED. THE USE OF MC CABLE IS NOT PERMITTED IN CANADA. H. WIRE CONNECTORS SHALL BE EQUAL TO "SCOTCH LOCK" FOR i8 AWG WIRE AND SMALLER AND EQUAL TO T & B "LOCKTIGHT" FOR 16 AWG AND LARGER. SECTION 280823 - CONTROL VOLTAGE ELECTRICAL POWER CABLES A. MUTED STATES 1. FURNISH AND INSTALL A SYSTEM OF CONDUIT RACEWAYS, OUTLET BOXES AND PULL WIRES AS SHOWN ON THE DRAWINGS UNLESS OTHERWISE NOTED ON PLANS. TELEPHONE SWITCHING APPARATUS, CONDUCTORS, INSTRUMENTS, MISCELLANEOUS EQUIPMENT AND APPURTENANCES ARE NOT PART OF THIS CONTRACT AND WILL BE PROVIDED AND INSTALLED BY LSD&C. 2.GUTLET BOXES TO BE 4" SQUARE MINIMUM WITH SINGLE DEVICE COVER AND TELEPHONE PLATE. 3.CONDUIT RUNS FROM ITS ENCLOSURE OR MANAGER'S OFFICE FOR TELEPHONE AND DATA LINES TO CASHWRAPS ARE TO BE CONTINUOUS WITH NO JUNCTION BOXES EXCEPT AS NOTED OTHERWISE ON DRAWINGS. 4.ALL PULL WIRES ARE TO BE LABELED FOR PURPOSE DESIGNATED. S.ELECTRICAL CONTRACTOR SHALL REFER TO MECHANICAL DRAWINGS FOR ADDITIONAL ELECTRICAL WORK TO BE INCLUDED IN HIS OR HER BID. & ELECTRICAL CONTRACTOR SHALL DO ALL POWER WIRINGS, LINE VOLTAGE WIRINGS, AND LINE VOLTAGE CONTROL WIRING INDICATED UNDER THE HEATING, VENTILATION AND AIR CONDITIONING, PLUMBING AND FIRE PROTECTION SPECIFICATIONS AND DRAWINGS. THIS CONTRACTOR SHALL ALSO DO ALL INTERCONNECTING LINE VOLTAGE WIRINGS BETWEEN RELAYS AND SWITCHES AS REQUIRED. 7.ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR FURNISHING AND INSTALLING CONDUIT FOR HVAC CONTROL WIRING WHERE REQUIRED BY CODE OR SHOWN ON PRINTS TO BE IN CONDUIT. REFER TO PLANS FOR REQUIREMENTS AND SIZE. B.FIRE AND/OR SMOKE DAMPERS SHALL BE WIRED BY ELECTRICAL CONTRACTOR. COORDINATE WITH HVAC CONTRACTOR FOR POWER REQUIREMENTS. 9.REFER TO MECHANICAL DRAWINGS FOR AVAILABLE SCHEMATIC WIRING DIAGRAMS OF EQUIPMENT. I. CANADA 1. ALL CCTV CABLES TO BE CAT5E TYPE AND WHITE IN COLOR. V-0" LOOP OF CABLE TO BE LEFT AT DVR AND 10'-O" LOOP OF CABLE TO BE LEFT AT EQUIPMENT LOCATION END COILED UP IN CEILING. 2. ALL SECURITY/ADT CABUNG TO BE 22/4 NON -SHIELDED FEB TYPE, NO CONDUIT REQUIRED IF RUN WITHIN THE PLENUM. 5'-0" LOOP OF CABLE TO BE LEFT AT THE CONTROL PANEL END AND 5'-0" TO BE LEFT AT THE EQUIPMENT LOCATION COILED IN CEILING. SECTION 260528.OROUNDM AM BONDING FOR ELE07MAL SYSTEMS A. FURNISH AND INSTALL COMPLETE WIRED GROUNDING CONDUCTOR SYSTEM, j12 AWG MINIMUM, SIZED AND INSTALLED IN ACCORDANCE WITH THE LATEST ADOPTED EDITION OF THE NATIONAL ELECTRICAL CODE, STATE AND LOCAL CODES, THE LANDLORD'S TENANT CRITERIA, AS NOTED IN THE SPECIFICATIONS, AND AS INDICATED ON THE DRAWINGS. B. ALL CONDUITS, INCLUDING FLEXIBLE METAL CONDUIT, SHALL BE GROUNDED WITH A GREEN GROUNDING CONDUCTOR. C. GROUNDING CONNECTIONS MADE TO THE WATER PIPING SYSTEM SHALL BE COORDINATED WITH THE PLUMBING CONTRACTOR AND A BONDING JUMPER INSTALLED AROUND WATER METER PER CODES AND AS INDICATED ON DRAWINGS. D. ALL DEVICES SHALL BE BONDED TO THE CONDUIT SYSTEM. USE A BONDING JUMPER BETWEEN THE OUTLET BOX AND THE DEVICE GROUNDING TERMINAL METAL -TO -METAL CONTACT BETWEEN THE DEVICE YOKE AND THE OUTLET BOX IS NOT ACCEPTABLE AS A BOND FOR EITHER SURFACE MOUNTED BOXES OR FLUSH TYPE BOXES. ALL JUNCTION BOXES, OUTLET BOXES, AND PULL BOXES SHALL BE BONDED TO THE CONDUIT SYSTEM. E. ALL ENCLOSURES AND NON -CURRENT CARRYING METAL PARTS ARE TO BE GROUNDED. CONDUIT SYSTEM IS TO BE ELECTRICALLY CONTINUOUS. ALL LOCKNUTS SHALL CUT THROUGH ENAMELED OR PAINTED SURFACES ON ENCLOSURES WHERE ENCLOSURES AND NON -CURRENT CARRYING METAL PARTS ARE ISOLATED FROM THE CONDUIT SYSTEM, USE BONDING JUMPERS WITH APPROVED CLAMPS. ALL GROUND CLAMPS SHALL BE "PENN-UNION" OR EQUAL, SIMILAR TO NOTE" TYPE. SECTION 200533-RACEWAY AM BOXES FOR ELECTRICAL SYSTEMS A. THIS CONTRACTOR SHALL FURNISH AND INSTALL ALL CONDUITS SERVING ALL EQUIPMENT, INCLUDING BUT NOT LIMITED TO, UGHTING, RECEPTACLES, HEATING, AIR CONDITIONING, PLUMBING EQUIPMENT, TELEPHONE, DATA, SPEAKERS, SECURITY, PAGER, TRAFFIC COUNTING SYSTEM AND ELECTRICAL EQUIPMENT. B. ALL CONDUITS SHALL BE GALVANIZED INC OR EMT UNLESS OTHERWISE SPECIFIED IN SPECIFICATIONS OR ON DRAWINGS. ALL CONDUIT IS TO BE UL/ULC LABELED. EMT CONNECTORS SHALL BE STEEL COMPRESSION OR SET SCREW TYPE. CONDUIT UNDER SLAB ON GRADE SHALL BE RIGID STEEL, OR SCHEDULE 40 PVC WITH RIGID STEEL ELLS WHERE PERMITTED BY LANDLORD OR CODE. C. MINIMUM SIZE OF CONDUIT SHALL BE: 1. MAIN FEEDER CONDUIT TO 2" OR LARGER FOR ALL APPLICATIONS. 2.1/2" MINIMUM FOR ALL LOCATIONS (IF ACCEPTABLE BY THE LANDLORD AND LOCAL CODE OFFICIALS), UNLESS NOTED OTHERWISE IN PLANS, SPECIFICATIONS, OR DRAWINGS. 3.I17 HVAC CONTROL WIRING IS REQUIRED TO BE RUN IN CONDUIT, IT SHALL BE A MINIMUM OF 3/4", UNLESS NOTED OTHERWISE ON DRAWINGS. CALL IN/UNDER FLOOR CONDUIT SHALL BE OF MINIMUM 3/4" SIZE. $.ALL FIRE ALARM CONDUIT SHALL BE OF MINIMUM 3/4" SIZE. D. SUPPORT ALL CONDUIT, INCLUDING SEISMIC AND SWAY BRACING, IN ACCORDANCE WITH THE LOCALLY ADAPTED CODES, E. GENERALLY, ALL CONDUIT SHALL BE CONCEALED EXCEPT FOR UNFINISHED AREAS, SUCH AS EQUIPMENT ROOMS EXPOSED CONDUIT SHALL BE ALLOWED ONLY AS NOTED ON PUN AND AS APPROVED BY LSD&C'S PROJECT MANAGER. PAINTING OF CONDUITS, NOTED ON DRAWINGS OR SPECIFICATIONS WILL BE BY GENERAL CONTRACTOR. F. FLEXIBLE METAL CONDUIT, MC TYPE CABLE OR AC90(CANADA). PROVIDE RIGID CONDUITT THE SALES ROOMS, ONCE IN THE SALES RQQM5. MQ CABLE IS ACCEPTABLE IF INSTALLED IN A NEAL WORKMANLIKE MANNER 1. ADDITIONALLY, FLEXIBLE METAL CONDUIT, MC TYPE CABLE OR AC90(CANADA) SHALL BE USED FOR THE FOLLOWING APPLICATIONS: a. FINAL CONNECTIONS TO MOTORS. b. FINAL CONNECTIONS INTO AND OUT OF THE TRANSFORMER. a. FINAL CONNECTIONS TO VIBRATING EQUIPMENT. d.INTER-CONNECTIONS BETWEEN ALL RECESSED LIGHT FIXTURES AND JUNCTION BOXES. e. FINAL CONNECTIONS WHERE RIGID CONDUIT IS NOT PRACTICAL I. IN WALLS (FOR LIGHT SWITCHES AND 120 VOLT POWER RECEPTACLES AND HVAC CONTROL EQUIPMENT). 2.FLEXIBLE METAL CONDUIT OR AC90 (CANADA) SHALL BE THE SAME SIZE AS THE INC OR EMT CONDUIT TO WHICH IT IS CONNECTED. BOTH THE FLEXIBLE METAL CONDUIT, OR AC90 (CANADA) AND ITS FITTINGS ARE TO BE USTED FOR GROUNDING. A GREEN GROUNDING CONDUCTOR SHALL BE INSTALLED. ALL CONNECTORS ARE TO BE OF A MENA APPROVED TYPE. 3.IENGTH OF FLEXIBLE METAL CONDUIT, MC TYPE CABLE, OR AC90 (CANADA) IS ALLOWED TO EXCEED 6'-O" PER LINE F OF THIS SECTION. 4. THE USE OF ROMEX OR FIX CABLE IS NOT PERMITTED. G. CONNECTION TO ANY OUTDOOR EQUIPMENT SHALL BE MADE WITH LIQUIDTIGHT FLEXIBLE METAL CONDUIT OR AC90 (CANADA). H. PROVIDE PULL -WIRE IN ALL EMPTY CONDUITS EXCEPT AS NOTED OTHERWISE ON DRAWINGS. I. HOME RUNS AND MAIN CONDUIT RUNS ARE TO BE HELD TIGHT TO STRUCTURE ABOVE OR AS REQUIRED TO ALLOW PROPER SERVICE ACCESS AND OTHER TRADES WORK. CONDUIT SHALL BE TRAPEZED TO ALLOW 3 FEET MINIMUM CLEARANCE ABOVE CEILING. J. ALL CONDUITS SHALL BE SIZED PER LOCALLY ADOPTED CODES. K. ALL SENSORMATIC WIRING SHALL BE PLACED IN EMT, IMC, OR RMC CONDUIT. PVC IS NOT ALLOWED. L PRESSED STEEL STANDARD KNOCKOUT TYPE. NO ROUND OUTLET BOXES SHALL BE PERMITTED ALL OUTLET BOXES SHALL R GALVANIZED TEE OF THE UNLESS INDICATED AND FOR LIGHTING THAT REWIRE SUCH CONFIGURATION. CONCEALED BOXES SHALL NOT BE LESS THAN SINGLE GANG AND 1-1/2' DEEP, WITH PLASTER RINGS. M. ALL KNOCKOUT BOXES, UPON WHICH LIGHTING FIXTURES ARE TO E INSTALLED, SHALL BE EQUIPPED WITH 3/8" FIXTURE STUDS. N. EXTERIOR BOXES SHALL BE CAST RUST -RESISTING METAL WITH GASKETED COVERS. 0. INSTALL BOXES RIGIDLY FROM BUILDING STRUCTURE AND SUPPORT INDEPENDENTLY OF THE CONDUIT SYSTEM. ALSO PROVIDE SUITABLE BOX EXTENSIONS TO EXTEND BOXES TO FINISHED FACES OF FLOORS, CEILINGS, WALLS EFC. ALL OUTLET BOXES TO E PROVIDED WITH CADDY "QUICK -MOUNT BOX SUPPORT" TO MINIMIZE THE DEFLECTION THAT OCCURS WHEN PLUGGING/UNPLUGGING INTO THESE DEVICES. P. UNLESS OTHERWISE NOTED ON DRAWINGS OR OTHERWISE REQUIRED BY THE NATIONAL ELECTRICAL CODE ACCESSIBILITY CODES OR LOCAL CODES OUTLET HEIGHTS SHALL BE AS FOLLOWS: I. SWITCH HEIGNT 42' FROM FINISHED FLOOR TO CENTERLINE OF OUTLET. 2.CONVENIENCE OUTLETS: a.SALES AREAS: MOUNTED ON THE WALL 15" AFF UNLESS INDICATED OR HORIZONTALLY MOUNTED IN BASEBOARD BENEATH CABINETS, AS SHOWN ON DRAWINGS, OR AS REQUIRED BY LOCAL CODES. SEE DRAWINGS. b.NON-SALES AREA: 15" FROM FINISHED FLOOR TO CENTERLINE OF OUTLET. & TELEPHONE OUTLETS SHALL BE LOCATED AS NOTED ON DRAWINGS. Q THE PLANS INDICATE ONLY SCHEMATIC ROUTINGS FOR CONDUIT RUNS. THIS CONTRACTOR SHALL FURNISH AND INSTALL ADDITIONAL BOXES WHERE REQUIRED BY FIELD CONDITIONS OR BY CODE. R. BOXES AND COVERS SHALL BE GALVANIZED STEEL OF CODE GAUGE SIZE S. ARRANGE CIRCUITS TO AVOID THE USE OF JUNCTION BOXES IN INACCESSIBLE LOCATIONS. THE USE Of JUNCTION BOXES ABOVE DRYWALL CEILINGS SHOULD BE LIMITED TO LOCATIONS NEAR ACCESS FRAMES USED FOR DIFFUSERS AND RETURN AIR GRILLES OR ACCESS PANELS AS LOCATED ON PLANS. SECTION 280E684DEKTOWATION FOR ELECTRICAL SYSTMM A. FOR ALL U.S PROJECTS ALL WIRING SHALL BE COLOR -CODED AS FOLLOWS: 1. 120/208 VOLT SYSTEM o.NEUTRAL - WHITE b.PHASE A OR L1 - BLACK c. PHASE B OR L2 - RED d.PHASE C OR L3 - BLUE e. GROUND - GREEN 2.277/480 VOLT SYSTEM a.NEUTRAL - GRAY It. PHASE A OR LI - BROWN c. PHASE B OR L2 - ORANGE d. PHASE C OR L3 - YELLOW e.GROUND - GREEN B. FOR CANADIAN PROJECT ALL WIRING SHALL BE OOLOR-CODED AS FOLLOWS: 1. 120/208 VOLT SYSTEM a. NEUTRAL - WHITE b. PHASE A OR L1 - RED c. PHASE B OR L2 - BUCK d.PHASE C OR L3 - BLUE e.GROUND - GREEN 2.347/600 VOLT SYSTEM a.NEUTRAL - GRAY b.PHASE A OR LI - RED c.PHASE B OR L2 - BUCK d.PHASE C OR LT - BLUE e.GROUND - GREEN C. JUNCTION AND PULL BOXES SHALL BE LIBELED WITH CIRCUIT NUMBER IDENTIFICATION AND SYSTEM TYPE ON COVER. SECTION 2609234JOHMO CONTROL ECIISYl f A. LIGHTING CONTROL PANEL WILL BE PROVIDED BY LSD&C THROUGH CONTROL MANUFACTURER, MOUNTED IN ITS PANEL WITH CONDUIT, INSTALLED BY THE ELECTRICAL CONTRACTOR. THE CONTROL PANEL SHALL BE PROGRAMMED AND COMPLETE WHEN SHIPPED TO THE JOB SITE. THE ELECTRICAL CONTRACTOR WILL BE RESPONSIBLE TO PULL ALL WIRES AS DETAILED ON THESE DRAWINGS AND CIRCUITED EXACTLY AS DIAGRAMMED ON THE ELECTRICAL PLAN DRAWINGS. NO VARIATIONS TO THE CIRCUITING ARE ALLOWED WITHOUT PRIOR WRITTEN APPROVAL BY LSD&C'S PROJECT MANAGER. B. DIMMING SYSTEM WILL BE PROVIDED BY THE ELECTRICAL CONTRACTOR, INSTALLED BY THE ELECTRICAL CONTRACTOR. THE ELECTRICAL CONTRACTOR WILL BE RESPONSIBLE TO PULL ALL WIRES AS DETAILED ON THESE DRAWINGS AND CIRCUIT EXACTLY AS DIAGRAMMED ON THE ELECTRICAL PLAN DRAWINGS. NO VARIATIONS TO THE CIRCUITING ARE ALLOWED WITHOUT PRIOR WRITTEN APPROVAL BY USDMVS PROJECT MANAGER. SECTION 20221S4)RY TYPE TRANSFORMERS A. TRANSFORMERS ARE GENERALLY INCLUDED IN THE ITS SWITCHGEAR. IF NOT, TRANSFORMER SHALL BE PAD MOUNTED OR SHALL BE SECURELY MOUNTED FROM THE BUILDING STRUCTURE, REINFORCED WALLS OR AS NOTED ON DRAWINGS. USE ADDITIONAL VIBRATION ISOLATORS AT POINTS OF MOUNTING TO CUT VIBRATION NOISES. USE FLEXIBLE METALLIC CONDUIT WITH GROUNDING BUSHING FOR PRIMARY AND SECONDARY CONNECTIONS TO TRANSFORMER. TRANSFORMERS SHALL BE LOCATED, SET, MOUNTED AND CONNECTED IN SUCH A MANNER AS TO KEEP NOISE LEVELS WITHIN THE SURROUNDING AMBIENT NOISE LEVELS AND MAINTAIN ALL CODE REQUIRED CLEARANCES. B. TRANSFORMER SHALL BE QUIET TYPE CONSTRUCTION AND HAVE SIX (6) 2-1/2% TAPS, TWO (2) TAPS ABOVE AND FOUR (4) TAPS BELOW NORMAL PRIMARY RATING. C. ALL DRY TYPE TRANSFORMERS PROVIDED SHALL MEET THE DOE 2016 EFFICIENCY REQUIREMENT. SECTION 20241"ANELBOARDS A. ALL PANELBOARDS SHALL BE FACTORY ASSEMBLED OF THE BOLTED CIRCUIT BREAKER TYPE WITH SOLID COPPER BUSSING, FULL SIZED COPPER NEUTRAL, 100% GROUND BUSHING, AND OVERALL HINGED/LOCKABLE DOOR. ALL CIRCUIT BREAKERS SHALL BE OF THE QUICK -MAKE AND QUICK -BREAK DESIGN, THERMAL -MAGNETIC TYPE, TRIP FREE AND TRIP -INDICATING. ALL PANELS SHALL BE DEAD FRONT AND RUSH OR SURFACE MOUNTED AS SHOWN. B. CONTRACTOR SHALL FURNISH AND INSTALL A TYPEWRITTEN DIRECTORY CARD OF THE CIRCUITS AND PUCE IN PANEL DOOR. THE DIRECTORY SHALL IDENTIFY THE SPECIFIC ROOM LOCATION FOR EACH CIRCUIT. C. ALL PANELBOARDS PHASE AMPERAGE SHALL BE BALANCED TO WITHIN 7 PERCENT MAX. TO MIN. REARRANGE NON-UGHTING BRANCH CIRCUITS AS REQUIRED AND NOTE CHANGES ON RECORD DRAWINGS. LIGHTING PANEL CIRCUIT BREAKERS SHALL BE INSTALLED AND WIRED EXACTLY AS SHOWN ON DRAWINGS. D. IF LOOSE PANELBOARDS ARE USED, PANELBOARDS SHALL BE MOUNTED ON MINIMUM 3/4" A/D PLYWOOD AND PAINTED IN A COLOR TO MATCH THE SURROUNDING WALLS OR A COLOR AS REQUIRED BY LOCAL CODE. PLYWOOD SHALL EXTEND 1 FOOT MINIMUM BEYOND EDGE OF EQUIPMENT. E. PANELBOARDS SHALL HAVE A MINIMUM SHORT CIRCUIT CURRENT RATING AND LUG CONNECTIONS AS FOLLOWS. 1.120/208 VOLT PANELBOARDS: 10,000 A.I.C. 2.277/480 VOLT PANELBOARDS: 14,0DO A.I.C. 3.347/600 VOLT PANELROARDS: KOOO A.I.C. 4.VERIFY ACTUAL A.I.C. SHORT CIRCUIT CURRENT REQUIREMENTS WITH THE LANDLORD OR UTILITY COMPANY AND VERIFY SWITCHGEAR COMPLIANCE PRIOR TO INSTALLING EQUIPMENT. ALL LUG CONNECTIONS TO BE 75C RATED. F. ITS ENCLOSURE FURNISHED BY LSD&C AND INSTALLED BY ELECTRICAL CONTRACTOR IS HEREIN DESCRIBED: 1. UNIT WILL BE SHIPPED TO THE PROJECT IN MULTIPLE SECTIONS AND THE ELECTRICAL CONTRACTOR WILL BE RESPONSIBLE FOR OFF-LOADING OF EQUIPMENT, INSPECTION OF EQUIPMENT FOR DAMAGES, VERIFICATION OF EQUIPMENT RECEIVED, ENSURING THAT THE EQUIPMENT RECEIVED IS COMPLETE AND MEETS THE SCHEDULED PANELS FOR THE PROJECT, MOVING AND MOUNTING OF SECTIONS AS WELL AS REASSEMBLING OF SAME INTO ONE COMPLETE UNIT PER MANUFACTURER'S REQUIREMENTS. 2.ELECTRICAL CONTRACTOR IS TO CONNECT ALL PROVIDED INTERCONNECTING CABLES BETWEEN SECTIONS AND TORQUE CONNECTIONS PER MANUFACTURER'S REQUIREMENTS. CONTRACTOR IS TO ANCHOR PANEL SYSTEM IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS AND LOCAL CODES IN SEISMIC ZONES 3. ELECTRICAL CONTRACTOR IS TO CONNECT LIGHTING BRANCH CIRCUITS TO APPROPRIATE LOAD TERMINALS OR PRC LIMITER PANEL PROVIDED WITHIN ITS ENCLOSURE PER UGHTING ZONES INDICATED IN THE PANEL SCHEDULE (I.E.: ZONE A, B. C. OR D)AN) CURRENT UNITING BREAKER SCHEDULE. UNE SIDE WIRING AND LIGHTING CONTROL WIRING WILL BE PREWIRED BY MANUFACTURER AT FACTORY. COORDINATE EXACT TERMINAL NUMBER FOR EACH CIRCUIT CONNECTION WITH MANUFACTURER'S DRAWINGS. 4. ALL LIGHTING, RECEPTACLE AND MISCELLANEOUS BRANCH CIRCUITS NOT SPECIFIED AS BEING CONTROLLED, ARE TO BE WIRED DIRECTLY TO THE CORRESPONDING BRANCH BREAKER IN THE DESIGNATED PANEL. 5.ALL CONNECTIONS WITHIN THE TELEPHONE/DATA SECTION AND HVAC CONTROL SECTION OF THE ITS ENCLOSURE ARE TO HE PERFORMED BY OTHERS. 6. ELECTRICAL CONTRACTOR WILL ONLY BE RESPONSIBLE FOR INSTALLATION OF THE CONDUIT SYSTEM INTO THE LOW VOLTAGE SECTION OF THE ITS PANEL 7. PRC UMITER PANEL IS COMPLIANT WITH CALIFORNIA TITLE 24, SECT. 130 C(3) AND ASHRAE. SECTION 202720-MITRING DEVICES A. THIS CONTRACTOR SHALL FURNISH AND INSTALL SWITCHES AND RECEPTACLES, UNLESS NOTED OTHERWISE, AS NECESSARY FOR A COMPLETE INSTALLATION. COLOR OF DEVICES AND PLATES SHALL BE SELECTED BY LSD&C. THE DEVICES SHALL BE OF THE TYPES AND RATINGS LISTED, OR EQUALS BY ARROW -HART, HUBBELL OR PASS & SEYMOUR. WEATHERPROOF GFI RECEPTACLES SHALL BE INSTALLED WHERE SHOWN ON DRAWINGS OR AS REQUIRED BY CODE. 1. SEE "SECTION 269000-ELECTRICAL CONTRACTOR PROVIDED DEVICE SCHEDULE" BELOW FOR EQUIPMENT TO BE PROVIDED. B. ALL DEVICE COVERPLATES SHALL BE PASS AND SEYMOUR SERIES "TP" OR EQUAL. SECTION 202B'I84MMOSED SWITCHES AM CIRCUIT BREAKERS A. SAFETY AND DISCONNECT SWITCHES SHALL BE HEAVY DUTY TYPE, QUICK -MAKE, QUICK -BREAK FUSED OR NON -FUSIBLE WITH RATINGS AND SIZES AS NOTED ON PUNS AND REQUIRED BY CODES. B. SWITCHES SHALL BE WEATHERPROOF IN OUTDOOR LOCATIONS OR AS REQUIRED BY LOCAL CODES. C. AT SERVICE ENTRANCE, DISCONNECT SHALL BEAR THE MANUFACTURER'S LABEL INDICATING THE EQUIPMENT IS UL/ULC RATED FOR APPLICATION IN ACCORDANCE WITH ALL CODES, D. CUTLER HAMMER ORE UAL MANUAL MOTOR STARTERS LESS OVERLOAD PROTECTION HEATERS ARE TO BE USED AS A DISCONNECTING MEANS Q ONLYWHERE INDICATED ON DRAWINGS FOR MOTORS ABOVE 1 1 2 HP AT 120 VOLTS AND 2 HP AT 240 VOLTS THAT DO NOT RE UIRE AUXILIARY / Q CONTROL MOTORS THAT ARE BELOW THE 1 1/2 HP AT ITT VOLTS, 2 HIP AT 240 VOLTS, WATER HEATER AND ROVING GRILLE ARE TO BE PROVIDED WITH HUBBELL "HBL-1221, OR 1222" AC SWITCH. E. MAGNETIC MOTOR STARTERS SHALL BE PROVIDED WITH RESET TYPE OVERLOADS THAT CLOSELY MATCH MOTOR NAMEPLATE RATING AND SHALL BE ELECTRICALLY HELD (MINIMUM SIZE jt IN A MENA I ENCLOSURE) AND BE USED FOR ALL SINGLE PHASE AND THREE PHASE MOTORS RATED ABOVE 1/2 HP THAT REQUIRE AUXILIARY CONTROL PROVIDE CONTROL DEVICES (AUXILIARY CONTACTS, TRANSFORMERS, H-O-A, ETC.) IN STARTERS AS REQUIRED FOR INTERLOCKS. COORDINATE ALL CONTROL DEVICES WITH MECHANICAL CONTRACTOR. COMBINATION STARTER/ DISCONNECT SWITCHES SHALL CONTAIN FUSIBLE SWITCHES AND ONLY USED WHERE INDICATED ON DRAWINGS. SECTION 2651004RflWOR LIGHTING A. THIS CONTRACTOR SHALL INSTALL ALL UGHTING FIXTURES AND LAMPS AS SHOWN ON THE FIXTURE SCHEDULE. LIGHTING FIXTURES AND LAMPS ARE SUPPLIED BY LSD&C, UNLESS NOTED OTHERWISE. CONTRACTOR IS TO REPLACE ALL NON -WORKING LAMPS PRIOR TO MERCHANDISE DATE AND IS TO INCLUDE COST IN BID. B. ALL RECESSED INCANDESCENT FIXTURES SHALL BE PROVIDED WITH APPUCABLE THERMAL PROTECTION. C. WHERE FLUORESCENT FIXTURES ARE SPECIFIED, THEY SHALL BE PROVIDED WITH HIGH POWER FACTOR RAPID START BALLASTS, U.L/U.LC LISTED, C.B.N. CERTIFIED AND E.T.L. APPROVED WITH EFFICIENCY FACTORS IN ACCORDANCE WITH "THE ENERGY POLICY ACT OF 1992" AND ITS AMENDMENTS AS A MINIMUM. D. THIS CONTRACTOR SHALL FURNISH ADDITIONAL AUXILIARY SUPPORT STEEL HANGER WIRES ADEQUATELY SIZED TO SUPPORT THE WEIGHT OF THE FIXTURE FASTENED TO THE BUILDING STRUCTURE (MINIMUM TWO PER FIXTURE) FOR ALL FIXTURES IN LAY -IN CEILINGS AND OTHER FIXTURES AS REQUIRED BY THE LANDLORD AND LOCAL CODE OFFICIALS. E. FURNISH AND INSTALL APPLICABLE FIRE RATED DRYWALL BOXES OVER RECESSED FIXTURES IN FIRE RATED CEILINGS AS REQUIRED BY CODES. FIELD COORDINATE AS REQUIRED TO AVOID CONFLICTS. SEC= 2090004LECTWCAL COKIMCTOR PROVDED DEVICE SCHEDULE A. DELIVERY BUZZER SYSTEM I. TRANSFORMER PLATE - EDWARDS NA593 2. TRANSFORMER - EDWARDS W99 3.PUSH BUTTON - EDWARDS NA603 4.ADAPT-A-BUZZER - EDWARDS NA34OA-G5 5.STRAP MOUNTED BUZZER - EDWARDS NA1D64-G5 B. FLOOR BOXES 1. 4" DIAMETER PVC FLOOR BOX ADJUSTABLE MOUNTING CUP - HUBBELL CFBSIR4CUP 2.4' DIAMETER VC RECESSED FLOOR BOX (FOR ON GRADE USE) - CFB51R4PFB 3.4" DIAMETER FIRE RATED POKE THRU FLOOR BOX BRASS COVER - HUBBELL SITFCBRS 4.4" FIRE RATED POKE -THROUGH W/ JUNCTION BOX - HUBBELL S1R4PTFIT SIC DIAMETER FIRE RATED POKE THOU BRASS COVERPUTE - HUBBELL SIR4CVRBRS 6.4" DIAMETER FLOOR BOX 2X2 SUB -PLATE - HUBBELL SIR4SP2X2DUPLEX 7. AV DIAMETER RECESSED FLOOR BOX BRASS COVER - HUBBELL CFBSIR4CVRBRS C. RECEPTACLES 1.20 AMP WHITE USB CHARGER DUPLEX RECEPTACLE - HUBBELL USB2OX2W 2.15 AMP IVORY CLOCK OUTLET - MULBERRY METAL PRODUCTS 40585 3.20 AMP RED DUPLEX RECEPTACLE - PASS AND SEYMOUR CR95362RED 4.20 AMP ORANGE ISOLATED GROUND DUPLEX RECEPTACLE - PASS AND SEYMOUR 165362 5.20 AMP WHITE SELF TESTING GFI DUPLEX RECEPTACLE - PASS AND SEYMOUR 2095W 6.20 AMP WHITE DUPLEX RECEPTACLE - PASS AND SEYMOUR 5362W 7.20 AMP BACK DUPLEX RECEPTACLE - PASS AND SEYMOUR 53628K 8.20 AMP GRAY SELF TESTING GFI DECDRA DUPLEX RECEPTACLE - HUBBELL GFRST2DGY 9.20 AMP GRAY DUPLEX RECEPTACLE - PASS AND SEYMOUR 5362GRY D. SWITCHES 1.20 AMP WHITE SPST SWITCH - PASS AND SEYMOUR PS20ACIW 2.20 AMP WHITE 3-WAY SWITCH - PASS AND SEYMOUR PS20ACS 3.20 AMP WHITE 4-WAY SWITCH - PASS AND SEYMOUR PS20AC4W C DOUBLE POLE WHITE PASSIVE INFRARED OCCUPANCY SENSOR - HUBBELL AP2000W22 E. OOVERPLATES 1.1-GANG STAINLESS STEEL LOUVERED PLATE - HUBBELL SS771 2.1-GANG WHITE DUPLEX RECEPTACLE THERMOPLASTIC NYLON - PASS AND SEYMOUR TP8-W 3.1-GANG BLACK DUPLEX RECEPTACLE THERMOPLASTIC NYLON - PASS AND SEYMOUR TPB-BK 4.2-GANG WHITE DUPLEX RECEPTACLE THERMOPLASTIC NYLON - PASS AND SEYMOUR TP82-W 5.2-GANG BLACK DUPLEX RECEPTACLE NYLON - HUBBELL NPB2BK 6.1-GANG WHITE TOGGLE SWITCH THERMOPLASTIC NYLON - PASS AND SEYMOUR TPl-W 7.1-GANG GRAY DUPLEX RECEPTACLE THERMOPLASTIC NYLON - PASS AND SEYMOUR TP8-GRY 8.2-GANG GRAY DUPLEX RECEPTACLE THERMOPLASTIC NYLON - PASS AND SEYMOUR TP82-GRY F. LIGHTING CONTROL DEVICES 1.CEILING POWER BASE ADAPTOR - LEVITON OP815-ODW 2.SUPER DUTY LOW VOLTAGE POWER PACK - LEVITON OPP20-OD1 3.CE1UNG MOUNT LOW VOLTAGE WHITE OCCUPANCY SENSOR - LEVITON OSC10-MOW 4.1-ZONE GRARK T DIMMER - LUTRON GTJ-25OM-SC 5.120 VOLT PHASE ADAPTER POWER MODULE INTERFACE MODULE - LUTRON PHPM-PA-120-WH G. MISCELLANEOUS DEVICES 1. MAGNETIC SENSOR SWITCH (SLIDING DOOR) - C&K COMPONENTS MPS45WGW 2.12OV-24V STEP-DOWN TRANSFORMER (SOLENOID VALVE)- TA00 569 NTS A 0004 I-AO04DEn /1 11 M-Engineering 750 Brooksedge BIM. WeslerWlle, OW 43081 phune:514.839.4639 1ex: 614.839.2222 www ngineering.as.wm ..G Ia.:P,t i �J ,..� MAY 3 1 201S Z W U D fy �0 �_ U) z (C: O U 06 Z y U V) LU 0 LU Ly (n O CD c`O V N M M Re Ui _ a L 44 O r V7 v X CO LL o ' 00 a O 3 n Y Lri <`D a IL v MCI Q0 E c J O L N CL W 0a L N F- I - a M 3 >" e5o n�$�a- sa Mull 9 a-e M a Maw `e.oH W e a gSu .2e �a ,X f=IMe? ojgoaL9<oe gRw cBe � ak"4 �e 0iEed 5;=go am�. $5a.: , C_ Wi 20 Matz �Bg'�e Ek�FI FIX? Sk»gso '&5 2 vi r �o ap,g-Y I. es: 19.19 FY2 IaaE}ee saagP r 0 a // V� I 11 r T""a 0 qe 0 T 0 r ME O z U W C3 i VJ � Me 1 {m 0 J >00 0 0 0 M J Do W U0 06 Q < N CC CC W O a Th i IQr� J O FEIN } U QC) 4hw QMWi m U�tn0 RFeu e;e BY: REVISIONS: N KIM O X 0n a IH) 0, V 0 ..OU - W H o aka Y W UMW iUa J � N W Z3 M 0 " I n O N DU E U O x;0 � U J V J W � 3 m U W � Wz a W=Q o_ 2 .adt o vI o vacs DAM DATE ISSUED: 05/31/2019 DESIGNED BY: RH DRAWN BY: RH CHECKED BY: DFG ELECTRICAL SPECIFICATIONS I•• DATE: 07/16/19