HomeMy WebLinkAboutM04.01 Mech Respons Schedule1. Summary
Ventilation Sizing Method ... ........ ..:........................
ASHRAE Sea 62142013
Design Condition ._......: .............. ....................
....... ...__. Headng operation
Creamer Diversity (D)........................................................................
1.DDO
Uncensored! OUMar Air Irtalae(you)....................................................
an CFM
System Wetilatlan Elements (Ev) ...................x.................................
O.ae7
Outdoor Arhnake(Vol).....................................-................................
1001 DIM
9 onu Van+llaann aaaleele
'
SupplySpamFlarAreaOutdoor
Air
CFM
Area
IP
Air Rate
CFN )
Time
Averaged
Occupancy
Occu Ms
People
Outdoor Air
luster
CFMI rson
--
Air
[ventilation
Enectiveness
Space
Outdoor Air
CFM
- arerthlrg
Zone
Outdoors
FM
-
Space
VentllMon
EMatene
Zone Name l Space Notes
Meg.
IVpxI
(Az)
(Ra)
(Pz)
(Rp)
(Ezl
[Fox)
DxD
(Evy
Zone1
BOH
1
637
637.0
0.12
32
7%
0.8
126
lIXi
1.077
surest
1
1707
1425.0
0.12
285
7SO
0.8
b1
385
0.992
Sueea2
1
1203
11680
0.12
23.4
7.50
0.8
]p4
3f5
0.897
Caahwrap
1
4%
309.0
0.12
6.0
7.50
0.8
121
47
0.958
Tetels(inel. Space Wituraparni
4004
898
0.897
OUTSIDE AIR CALCULATIONS
DESIGN WEATHER PARAMETERS
Design Parameters
City Name
Location
Latitude
Longitude
Elevation
Summer Design Dry -Bulb
Summer Coincident Wet -Bulb
Summer Daily Range
Winter Design Dry -Bulb
Winter Design Wet -Bulb
Atmospheric Clearness Number
Average Ground Reflectance
Sol Conductivity
Local Time Zone (GMT +/- N hours)
Consider Daylight Savings Time
Simulation Weather Data
Current Data Is
Design Cooling Months
Indianapolis
Indiana
39.7 Deg.
86.3 Deg.
807.0 It
91.0 OF
75.0 OF
18.9 OF
.3.0 OF
4.4 OF
1.00
0.20
0.800 BTU/(hrN `F)
5.0 hours
No
N/A
2001 ASHRAE Handbook
January to December
NTS
VARIABLE AIR VOLUME (VAV) AND
FAN -POWERED VARIABLE AIR VOLUME
(FPVAVI NETWORK WIRING AND SEQUENCE
18/2 COMMUNICATION CABLE ) CMDNUD ON E/110e.01
FPVAV N
SUPPLY
AIR
SENSOR
POWER
BY OTHERS
HEATING/
COOLING
CHANGEOVER
SENSOR
18/3 CABLE
L
HVAC
LOAD
CALCULATIONS
SENSOR
NOTES:
(1) PROVIDE 18" SERVICE LOOP FOR CONTROL WIRE AT UNIT.
Project Name: 1943073-BBW Clay Terrace, IN
05/22/2019
Prepared by: MEngineerng
10:2aAM
FAN POWERED VAV (FPVAV) SEQUENCE OF OPERATIONS
Air SysteminformaBon
Air Syslem Name_ ............................
Split System
Number of zones ................................
_......._..._.....,....1
Equipment Class ...................................
SPLTAHU
Floor Area...........................................................
3539.0 B2
MANUFACTURER SHALL FURNISH AND/OR INSTALL ALL NECESSARY CONTROL DEVICES ACCOMPLISH THE FOLLOWING SEQUENCE OF
Air System Type ..............................................
SZCAV
Location ... .............................
..... .. Indianapolis, Indiana
OPERATION (REFER TO RESPONSIBILITY SCHEDULE FOR FIELD INSTALLATION REQUIREMENTS):
DURING OCCUPIED HOURS THE VARIABLE AIR VOLUME TERMINAL UNIT FAN SHALL BE ENERGIZED AND DAMPER SHALL MODULATE TO MAINTAIN
Sizing Calculation Information
THE SPACE TEMPERATURE. FOR UNITS WITH NEAT/COOL CHANGEOVER CONTROL, THE DAMPER SHALL MODULATE TO MAINTAIN THE SPACE
TEMPERATURE, REVERSING DAMPER OPERATION AS REQUIRED BASED ON ZONE DEMAND AND THE TEMPERATURE OF THE PRIMARY SUPPLY AIR.
Calculation Months ....................................
Jan to Doe
Zone CFM Sizing ................
Sum of space airflow rates
Shag Data ................................................
Calculated
Space CFM Sizing ............
Individual peak space bads
IF THE SPACE TEMPERATURE DROPS ONE DEGREE BELOW SETPOINT AND THE DAMPER IS AT MINIMUM POSITION, THE UNIT'S ELECTRIC HEAT
SHALL ENERGIZE. THE HEAT WILL REMAIN ON UNTIL THE SPACE TEMPERATURE IS SATISFIED.
Central Cooling Coll Sizing Data
THE TERMINAL UNIT DAMPER SHALL FULLY CLOSE AND THE FAN SHALL DEENERGIZE UPON A SIGNAL FROM THE FIRE ALARM SYSTEM.
DURING THE UNOCCUPIED SCHEDULE, THE DAMPER SHALL CLOSE AND FAN/HEATER WILL DEENERGIZE. THE DAMPER SHALL OPEN AND THE
Total call load .................................................
........ 9.2
Tons
Load ocws at ..............
'--..--..-...--.-- .... Jul 17DO
FAN SHALL ENERGIZE IF UNOCCUPIED COOLING SETPOINT IS REACHED. THE FAN AND HEATER SHALL ENABLE IF UNOCCUPIED TEMPERATURE
Totalcallload..................................................
t70A
MBH
OA DB/DUB...IS...........................................
89.1 /74.5
°F
IS ZF BELOW UNOCCUPIED SETPOINT. FAN AND HEATER SHALL STOP WHEN SETPOINT IS REACHED.
Sensible ail load00............................................
MBH
DB/DUB...........................................
77.2/672
°F
Coil CFM at Jul 1700...........................................
004
4004
CFM
LeavEnteing
Leaving DB /DUB ...........................................
59... / 57.3
°F
SETPOINTS:
Max block CFO ...................................................
4004
CFM
Coll ADP..................................................................
57.2
°F
Sum of peak zone CFM.......................................
4004
CFM
Bypass Factor........................................................
0.10D
Sensible heat ratio ..............................................
0.691
Resulting RH................................
.............................. 62
%
OCCUPIED HEATING: 70°F COOLING: 746F
CFM/Ton............................................................
435.1
Design supplytemp.................................................
57.0
OF
UNOCCUPIED HEATING: 60'F COOLING: 85'F
R/FEm .................................................................
384.5
Zone T-stat Check .................................................
1 of 1
ON
( j
Max ne temperatuaeYietion........:....................... 0.0
zone
OF
WaterRow@10.0°F rise ......................................
WA
NON -FAN POWERED VARIABLE AIR VOLUME (VAV) SEQUENCE OF OPERATIONS
ND/OR
MANUFACTURER SHALL FURNISH AlLL ALL NECESSARY CONTROL DEVICES TO ACCOMPLISH THE FOLLOWING SEQUENCE OF
Central Heating Coil Sizing Data
OPERATION (REFER TO RESPONSIBRTIY SCHEDULE FOR FIELD INSTALLATION REQUIREMENTS):
Max ail load ........................................................
92.2
MEN
Load oecvs at...................................................
Des Ht g
DURING OCCUPIED HOURS THE VARIABLE AIR VOLUME TERMINAL UNIT DAMPER MODULATE T MAINTAIN T
SHALL LA E O MAI N HE SPACE TEMPERATURE. FOR
Coil CFM at Des HUB ...........................................
4004
CFM
BTU ..CIS..............................................51.6
UNITS WITH HEAT/COOL CHANGEOVER CONTROL THE DAMPER SHALL MODULATE TO MAINTAIN THE SPACE TEMPERATURE, REVERSING DAMPER
Max all CFM.....................................
CFM
CIS/ L)
Ent. DB / Lvg FIB ............................................
730
51.6 173.5
°F
OPERATION AS REQUIRED BASED ON ZONE DEMAND AND THE TEMPERATURE OF THE PRIMARY SUPPLY AIR.
0.........deal
Water flow @ 20.0 OF dnap..........................J........
NVA
WA
THE TERMINAL UNIT DAMPER SHALL FULLY CLOSE UPON A SIGNAL FROM THE FIRE ALARM SYSTEM.
Supply Fan Sizing Data
-
-
DURING THE UNOCCUPIED SCHEDULE, THE DAMPER SHALL CLOSE. THE DAMPER SHALL OPEN IF UNOCCUPIED COOUNG SETPOINT IS REACHED.:.
SETPOINTS:
Actual max CFM.................................................
4004
CFM
Fan motor BHP........................................................
0.70
BHP
Standard CFM.....................................................
3889
CFM
Fan motor kW..........................................................
0.55
kW
OCCUPIED HEATING: 70°F COOLING: 747
Actual max CIRAW...............................................
1.13
CFMI
Fan static.... ...............
............. ................................ . 1.00
in wg
UNOCCUPIED HEATING: 6C'F COOLING: 85°F
Outdoor Ventilation Air Data
Design siraow CFM...............................................
1001 CFM CFM/pereon................................
........................... 1&88 CFMWpelaon
CRAI.................................................................
0.26 CFMm2
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1700
HEATING DATA AT DES HTG
COOLINGOADB/WB 89.1°F/74.5°F
HEATINGOADB/WS-3.OF/4.4•F
Sensible Latent
Sensible Latent
ZONE LOADS
Details (BTUIhr) (BTURV)
Details (BTUIhr) (BTUIhr)
Window & Skylight Solar Loads
190 flat 3188 -
190 112 - -
Wall Transmission
354 R2 2530 -
354 112 5825 -
Roof Transmission
0 ft2 0 -
0 fY 0
Window Transmission
190 tie 1286
190 IF 6366
Skylight Transmission
00' 0 -
002 0
Door Loads
082 0
0a2 0 -
Floor Transmission
3539 82
0
-
3639 a2
1642
-
PadMons
0IP
0
-
002
0
-
Ceiling
0IP
0 -
-
ow
0
-
Overhead Lighting
450 W
968
-
0
0
-
Task Lighting
8389 W
24610
-
0
0
-
Electric Equipment
2700W
8636
-
0
0
-
Paople
63
12578
12924
0
0
0
Infiltration
-
0
0
-
0
0
Miscellaneous
-
0
0
-
0
0
Safety Factor
10%/10%
5377
1292
25%
3458
0
Total Zone Loads
-
59143
14217
-
17292
0
Zone Conditioning
-
57634
14217
-
17635
0
Plenum Wall Load
0%
0
-
0
0
-
Plenum Roof Load
70%
0
-
0
0
-
Plenum Lighting Load
30%
461
-
0
0
-
Retum Fan Load
4004 CFM
0
-
4004 CFM
0
-
VerNlation Load
1001 CFM
16370
19876
loot CFM
76423
0
Supply Fan Load
4004 CFM
1886
-
4004 CFM
-1886
-
Spam Fan Coll Fens
-
0
-
-
0
-
Duct Heat rain / Loss
0%
0
-
0%
0
-
>> Total 9vxtwm Lode
-
76351
34093
-
92173
0
RELEASED FDR CDNSTRUCTIDN -
7635
34194
o
0
0
0
92173
Subject to compliance with all regulations
76351
34094
92173
0
of State and Local Codes
Positive values
are clg loads
Positive values are hill loads
FAN POWERED VARIABLE AIR VOLUME (FPVAV) III VARIABLE AIR VOLUME (VAV)
BOX RESPONSIBILITY SCHEDULE
FURNISHED BY
INSTALLED OR PERFORMED BY
RE -USE
ITEM
DXSTING
N/A
REMARKS
LSD@C
LANDLORD
CON1R.
LANDLORD
CONTR.
OTHER
SENT] ARRANGEMENT FAN PO M VAV
AC
MC
BOX (WITH HUT AND NO HUT OPTIONS)
NON -FAN POWERED VAV BOX
•
FAN POWERED BOX ELECTRICAL
AC
AC
DISCONNECT
NON -FAN POWERED BOX
•
ELECTRICAL DISCONNECT
BAS CONTROLLER WITH
AC
AC
INTEGRATED ACTUATOR
SUPPLY MR TEMPERATURE
AC
NC
SENSOR
HEATING/COOUNG CHANGEOVER
AC
MC
TEMPERATURE SENSOR
SPACE TEMPERATURE/HUMIDITY
AC
MC
SENSORS
TERMINAL UNIT COMMISSIONING
AC
AC
CALL HVAC EQUIPMENT
SUPPLIER
CONTROL SYSTEM WIRE FOR
AC
MC
FINAL CONN. BY MC
SYSTEM COMPONENTS
City of Carmel ( Negative values am hig bads Negative values are ctg loads
NFT�lIlndDoA� I T I O N S NTS
N NETWORK WIRING AND SEQUENCE
DATE: 07/16/19 OOD-MO4101-MOO-LOAD 10/31/2014
SPLIT DX AIR HANDLING UNIT WITH ELECTRIC HEAT
NETWORK WIRING AND SEQUENCE
18/3
COMMUNICATION FRONT END
TERMINATE NETWORK WIRES ON THE
LIGHTING CONTROLLER NETWORK
TERMINALS LOCATED IN THE ITS
ELECTRICAL PANEL SYSTEM
CABLE
COMMUNICATION CABLE
OUTSIDE AIR CO2
SENSOR SENSOR
(DUCT MOUNTED)
18/3
24Y
MONITORING
CONTROLLER
AT IFS
COMMUNICATION CABLE
' i b
BUr
TYPE ONE
NOTES: SENSOR
(1) ALL WIRE SHALL BE 18/3 UNLESS OTHERWISE INDICATED. (CASHWRAP)
(2) NUMBER OF CABLES FURNISHED BY HVAC SUPPLIER IS INDICATED BY NUMBER OF TICK MARKS ACROSS THE LINE.
(3) PURPLE 18/2 WIRE IS FURNISHED BY III SUPPLIER AND IS PLENUM RATED.
(4) SCHEMATIC IS FOR REFERENCE ONLY. AT TIME OF CONSTRUCTION, THE HVAC SUPPLIER WILL PROVIDE A COMPLETE DIAGRAM FOR
INSTALLATION. SEE RESPONSIBILITY SCHEDULES, THIS SHEET, FOR A LIST OF ALL COMPONENTS AND SENSORS REQUIRING FIELD
INSTALLATION.
(5) PROVIDE 182 SERVICE LOOP FOR CONTROL WIRE AT UNIT.
SPLIT DX AIR HANDLING UNIT (AHU) SEQUENCE OF OPERATIONS
MANUFACTURER SHALL FURNISH AND/OR INSTALL ALL NECESSARY CONTROL DEVICES TO ACCOMPLISH THE FOLLOWING SEQUENCE OF
OPERATION (REFER TO RESPONSIBILITY SCHEDULE FOR FIELD INSTALLATION REQUIREMENTS):
DURING OCCUPIED HOURS THE SUPPLY FANS SHALL OPERATE CONTINUOUSLY, AND THE OUTSIDE AIR DAMPER SHALL OPEN TO THE MINIMUM
SCHEDULED POSITION (ADJUSTABLE). WHEN THE OUTDOOR TEMPERATURE IS ABOVE 55 DEGREES FAHRENHEIT (ADJUSTABLE), AND THE SPACE
TEMPERATURE IS 1•F ABOVE COOLING SETPOINT, COOLING SHALL BE ENERGIZED IN STAGES (WHERE APPLICABLE) UNTIL I•F BELOW SETPOINT
IS ACHIEVED. WHEN THE OUTDOOR TEMPERATURE IS BELOW 55 DEGREES FAHRENHEIT (ADJUSTABLE), AND SPACE TEMPERATURE IS ABOVE
COOUNG SETPOINT, COOLING SHALL DEENERGIZE, AND OUTSIDE AIR DAMPERS AND RETURN AIR DAMPERS SHALL MODULATE TO PROVIDE A
SUPPLY AIR TEMPERATURE TO SATISFY THE DEMAND FOR COOLING. IF THE SPACE TEMPERATURE FALLS 1°F BELOW THE HEATING SETPOINT,
AND THE OUTDOOR DAMPER IS AT THE MINIMUM POSITION, ELECTRIC HEAT SHALL BE ENERGIZED IN STAGES (WHERE APPLICABLE) UNTIL 1°F
ABOVE SETPOINT IS ACHIEVED.
DURING UNOCCUPIED HOURS, THE SUPPLY FANS SHALL DEENERGIZE AND THE OUTDOOR DAMPER SHALL CLOSE. IF THE SPACE TEMPERATURE
RISES 1°F ABOVE THE COOLING SETPOINT, THE FANS SHALL ENERGIZE, AND THE OUTSIDE AIR DAMPERS SHALL REMAIN CLOSED. COOLING
SHALL BE ENERGIZED IN STAGES (WHERE APPLICABLE). WHEN THE SPACE TEMPERATURE FALLS BELOW COOLING SETPOINT, COOLING AND
FANS SHALL DEENERGIZE. IF THE SPACE TEMPERATURE FALLS BELOW THE HEATING SETPOINT, THE FANS SHALL ENERGIZE, AND THE OUTSIDE
AIR DAMPERS SHALL REMAIN CLOSED. ELECTRIC HEAT SHALL BE ENERGIZED IN STAGES WHERE APPLICABLE) . WHEN THE SPACE
TEMPERATURE RISES ABOVE THE HEATING SEPOINT, ELECTRIC HEAT AND FANS SHALL BE DEENERGIZED.
REUEF FAN (WHERE APPLICABLE) SHALL BE ENERGIZED WHENEVER THE SUPPLY FANS ARE OPERATING, AND THE UNIT IS IN THE
ECONOMIZER MODE OF OPERATION. THE RELIEF FAN SPEED SHALL BE VARIED THROUGH A VARIABLE FREQUENCY DRIVE CONTROLLED BY
SPACE PRESSURE DIFFERENTIAL RELATIVE TO OUTDOOR PRESSURE. FAN SPEED SHALL MODULATE TO MAINTAIN A SPACE PRESSURE OF 0.05"
POSITIVE RELATIVE TO OUTDOOR PRESSURE. REUEF DAMPER SHALL OPEN WHENEVER RELIEF FAN IS ENERGIZED.
A MANUFACTURER PROVIDED OR FIELD INSTALLED PAN OVERFLOW SWITCH WILL DISABLE ALL FANS, COOLING, HEATING, AND CLOSE OUTDOOR
AIR DAMPER IF HIGH WATER IS SENSED IN THE PAN.
A FIELD INSTALLED CO2 SENSOR SHALL MODULATE THE OUTDOOR AIR DAMPER DURING OCCUPIED OPERATION BETWEEN SCHEDULED CA FLAW
CFM AND MIN SCHEDULED CA FLOW TO MAINTAIN A 002 CONCENTRATION BETWEEN IOOOPPM AND 50OPPM.
A DUCT MOUNTED SMOKE DETECTOR SHALL DEENERGIZE THE SUPPLY AND RELIEF FAN, AND CLOSE THE OUTDOOR AIR DAMPER WHEN
ACTIVATED.
SETPOINTS:
OCCUPIED HEATING: 70•F COOLING: 74'F
UNOCCUPIED HEATING: SOT COOLING: BSF
SPLIT DX AIR HANDLING UNIT WITH
CONDENSING UNIT RESPONSIBILITY SCHEDULE
FURNISHED BY
INSTALLED OR PERFORMED BY
RE -USE
ITEM
EXISTING
N A
REMARKS
LSDAC
LANDLORD
CONTR.
LANDLORD
CONTR.
OTHER
AIR HANDLING UNIT
AC
MC
MR HANDLING UNIT
DISCONNECT/FAN CONTACTOR
AC
AC
HIGH AND LOW PRESSURE
FACTORY
SWITCHES (FACTORY INSTALLED)
AC
AC
INSTALLED
ELECTRIC HEATER WITH SINGLE
AC
MC
POINT CONNECTION AND CONTACTOR
CONDENSATE DRAIN LINES
MC
MC
VERIFY REQUIREMENTS WITH
LOCAL CODE
MIXING BOX WITH ACTUATOR
AC
MC
INTERCONNECTIVE WIRING BY MC
AND 0-10 VOLT ADAPTER
VIBRATION ISOLATORS
AC
AC
EVAPORATOR FAN MOTOR,
ACI
AC
CHANGES REQUIRED FOR
SHEAVES AND BELTS
RAIANCE ARE PROVIDED BY MC
THERMAL EXPANSION VALVE
AC
MC
PRIMARY CONDENSATE PAN
AC
AC
OVERFLOW SWITCH
SECONDARY CONDENSATE PAN
AC
MC
OVERFLOW SWITCH
FAN PROVING SWITCH
AC
AC
AIR COOLED CONDENSING UNIT
AC
NC
CONDENSING UNIT DISCONNECT
ED
EC
SWITCH
CONDENSING UNIT GROUND
EC
EC
FAULT OUTLET
SAS CONTROLLER
AC
AC
SUPPLY AIR TEMPERATURE
AC
AC
SENSOR
SPACE TEMPERATURE SENSOR
•
CARBON DIOXIDE SENSOR
•
HUMIDITY SENSOR
•
OUTSIDE MR TEMPERATURE
AC
MIC
ONE PER
SENSOR
PROJECT
LOW AMBIENT KIT
AC
MC
REWIRES MOTOR CHANGE OUT
SINGLE ZONE VAV CONTROLS
AC
AC
UNITS WITH CAPACITY GREATER
THAN 110 MBH AT AHRI CONDITIONS
SPLIT SYSTEM COMMISSIONING
AC
AC
CALL
HVAC EQUIPMENT SUPPLIER
MONITORING SPACE
AD
MC
TEMPERATURE SENSOR
MONITORING CARBON DIOXIDE
AC
MC
SENSOR
ROOM TEMPERATURE/HUMIDITY
SENSOR
AC
MC
WNRNW DRY M M LLETB NIRI AXN00
CC
MC
INSTALL MONITORING
YAWS MD D NKAm1 O
CONTROLLER AT IFS
CONTROL TRANSFORMERS
MC
MC
AS REQUIRED FOR MONITORING
DEVICES
CONTROL SYSTEM WIRE FOR
CC
MC
FINAL CONN. BY MC
SYSTEM COMPONENTS
NOTE TO CONTRACTOR
ITEM(S) NOT SHOWN ON ANY OF THE RESPONSIBILITY SCHEDULES
ARE THE RESPONSIBILITY OF THE CONTRACTOR.
LOCAL
AREA REQUIREMENTS
YES
NO
YES
NO
❑
Z
1.
SMOKE EVACUATION
❑
N
5.
SPECIAL CURB HEIGHT REQUIREMENTS
❑
®
2.
CARBON DIOXIDE MONITORING
❑
N
6.
TEN MILE COASTAL PROXIMITY
❑
®
3.
HURRICANEZONE
❑
®
7.
OTHERS, I.E. METHANE, CARBON MONOXIDE, SOUND
❑
10
4.
SEISMIC ZONE
SENSITIVE, EFC. DESCRIPTION...
❑
N
S.
TYPE B+COMMISSIONING
®
❑
9.
TYPE B COMMISSIONING
❑
®
10.
TYPE C COMMISSIONING
ABBREVIATIONS,
RESPONSIBILITY SCHEDULES
AC
HVAC EQUIPMENT SUPPLIER
LC
LANDLORD CONTRACTOR
AHJ
AUTHOR" HAVING JURISDICTION
LD
LIGHTING PACKAGE DISTRIBUTOR
BAS
BUILDING AUTOMATION SYSTEM
U.
LANDLORD
EC
ELECTRICAL CONTRACTOR
LSD&C
LIMITED STORE DESIGN CONSTRUCTION
FAC
FIRE ALARM CONTRACT OR
MC
MECHANICAL CONTRACTOR
GC
GENERAL CONTRACTOR
CC
CONTROLS CONTRACTOR
HVAC RESPONSIBILITY SCHEDULE
FURNISHED BY
INSTALLED OR PERFORMED BY
RE -USE
ITEMEXISTING
N/A
REMARKS
-CONTR.
LSDAC
LANDLORD
CONTR.
LANDLORD
OTHER
SAS CONTROLLER
AC
MC
CONTROLLER ENCLOSURES
AC
MC
AIR CURTAIN
•
VIBRATION ISOLATION
AC
AC
FIELD ADJUSTED
ROOFING CUT A PATCH, INSULATED
MC
HIRE LANDLORD APPROVED
TOE KICK It CURB LEVELING.
ROOFING CONTRACTOR
DUCT SMOKE DETECTOR
FAC
MC
POWER WIRING PROVIDED BY FAC
SMOKE SYSTEM ACCESSORIES,
MC
MC
UNLESS FACTORY INSTALLED
ETC.
DIFFUSERS AND GRILLES
MC
MC
DIFFUSERS/GRILLES FIRE
MC
MC
DAMPERS
WALL FIRE DAMPERS
•
COMBINATION FIRE/SMOKE
•
-
DAMPERS
LOW PRESSURE DUCTWORK
MC
MC
RECTANGULAR TO ROUND DUCT
NC
MC
ADAPTER
HIGH/MEDIUM PRESSURE
•
DUCTWORK
DUCT SUPPORTS
MC
MC
SEISMIC BRACING
•
HURRICANE WIND BRACING
•
DUCT HEATER(S)
•
UNIT HEATER(S)
•
INUNE AND CEIUNG EXHAUST
FANS)
MC
MC
ROOF AND WALL MOUNTED
•
EXHAUST FAN(S) AND CURB
EXHAUST FAN ROOF CURB
•
TOILET EXHAUST DUCTWORK
•
WALL OR ROOF CAP
PIPING AND PIPING APPURTENANCES
(CIRCUIT SETTERS, ETC.)
NC
MC
BALANCE CONTRACTOR REPORT
GC
AABC OR NEBB CERTIFIED
AS -BUILT DRAWINGS
MC
LANDLORD REWIRED TEMPERATURE
•
HIRE LL REQUIRED CONTRACTOR
CONTROL SYSTEM COMPONENTS
WHEN REQUIRED BY U.
FOR a REQUIRED SYSTEM M
•
HIRE U. REQUIRED CONTRACTOR
WMMNM
WHEN REQUIRED BY U.
YOUNG REGULATOR W/ BOWDEN
MC
MC
CABLE
LOCKING QUADRANT VOLUME
MC
MC
DAMPER
PNEUMATIC TUBING
•
FIRE ALARM SHUTDDWN RELAY
FAC
FAC
WHERE APPUCABLE FOR FIRE
ALARM SYSTEMS
RELIEF MR DAMPER AND
•
ACTUATOR
RELIEF MR FAN OR RETURN AIR
•
FAN
SMOKE EVACUATION
•
OUTSIDE AIR INTAKE
HOOD/LOUVER WITH DAMPER
•
LANDLORD PROVIDED O.A.DUCT
OUTSIDE AIR INTAKE DAMPER
•
LANDLORD PROVIDED OakDUCT
ACTUATOR
real H
aUNTER-BMANCED MCKDMUT
MPER
•
DAMPERS FOR FIELD BUILT
•
ECONOMIZER
DAMPER ACTUATORS FOR FIELD
AC
BUILT. ECONOMIZER
OUTSIDE AIR DAMPER
MC
MC
OUTSIDE AIR DAMPER ACTUATOR
AC
MC
M-Engineering
750 Brookmage Blvd.
WasreMlle, Ohio 43061
phone: 614.839.4639
hex: 614.839.2222
wiew.menglamang.us.com
A
/\
Z
CNrn
V
O
M�
N
M
J\
M
n
U
Oa
CJ
V
r
a
O
X
Z
Z
E
LL
O
U
cio
Z
T
3^J
O
Y
N
V
Ln
D-
v
ILA
Or-
0)
J
O
N
r.
V)
H-
ED
H
d
EG'$uM_agRc
.ti e m ff»H g>TS�Ze`" "'
a
tE"�-gV �a3wg d
BN�E stalls tc�s
g pub >f>€sue 4Va5
€€„B o -Y %
$owaaga
"aa��
XW sea_ s-e ag
_o3Qa ljn3Ega
=
54c§� �e � xgetea
=N:6 `55ba3e W§esH3
_ z g
8 £WF=e €E'ivo
a Be e3 eAe
e i3sE zg
? is Rwm FO�YtJ�.,W3
all NMOo
O O
c0 i I
d�MO
N
all
all `0
O i de
qa CC U
V O O_ W
O W O
a li
Nd
UXW
Q W
a cDa
_1w
W M
p O N
Q O N W
s U O
O> \O
Ay� DO J W
•"" W DO
�ED
U LWJ m
6 Car0 1Q ce N
O KOr W O
cc LJ m rw,
2 It
01Iz ~ L) a 'O
V �U J � W
O iCW12.
Q Q OI W� W m O
'o� J�jQ ovto
t>_ m U�tn LJ v�ic!n
REVISIONS:
REQUIRED Is: DATE
DATE ISSUED: 05/31 /2019
DESIGNED BY: JD
DRAWN BY: JD
CHECKED BY: BM
MECHANICAL
RESPONSIBILITY
SCHEDULES
DRAWING NUMBER:
NTS.A_. _ a 4 n 1
NTs I J NETWORK WIRING AND SEQUENCE
NT8
HVAC RESPONSIBILITY SCHEDULES