HomeMy WebLinkAboutLEGACY RIDGE 88 - LR088 (AS DESIGNED)IECC 2009 Performance Compliance
Property
6790 PULASKI CT
CARMEL, IN 46033
Model: SOUTHILL (A)
Community: LEGACY RIDGE 88
LR088 (AS DESIGNED)
LEGACY RIDGE 88
Organization
TSI Energy Solutions
Matthew Timmons
Builder
LENNAR HOMES
Design
Heating
Cooling
Water Heating
SubTotal - Used to determine compliance
Lights & Appliances
Onsite generation
Total
Inspection Status
Results are projected
Annual Energy Cost
IECC 2009 Performance
S1,658
$255
$410
$2,324
$922
$0
$3,246
Requirements
C-M,
Energy Solutions
As Designed
$1,591
$242
$410
$2,243
$922
$0
$3,165
C4405.3 Performance -based compliance passes by 3.5%
R402.4.12 Air Leakage Testing Air sealing is 6.DD ACH at 5D Pa. It must not exceed 7.DD ACH at 50 Pa.
C4402.5 Area -weighted average fenestration SHGC
402.5 Area -weighted average fenestration U-Factor
40322 Duct Testing
Mandatory Checklist Mandatory code requirements that are not
checked by Ekotrope must be met.
R4052 Duct Insulation
Design exceeds requirements for IECC 2009 Performance compliance by 3.5%.
As a 3rd party extension of the code jurisdiction utilizing these reports, I certify that this energy code compliance document has been created in accordance with the requirements of
Chapter 4 of the adopted International Energy Conservation Code based on Climate Zone 5. If rating is Projected, I certify that the building design described herein is consistent with
the building plans, specifications, and other calculations submitted with the permit application. If rating is Confirmed, I certify that the address referenced above has been
inspected/tested and that the mandatory provisions of the IECC have been installed to meet or exceed the intent of the IECC orwill be verified as such by another party.
Name: Matthew Timmons
Organization: TSI Energy Solutions
Signature:
Date:
6118119 at 3:17 PM
Ekotrope RATER - Version 3.1.0.2197
IECC 2009 Performance compliance results calculated using Ekotrope RATER's energy and code compliance algorithm.
Ekotrope RATER is a RESIN ET Accredited HERS Rating Tool. All results are based on data entered by Ekotrope users.
Ekotrope disclaims all liability for the information shown on this report.
6790 PULASKI CT
CARMEL, IN 46033
Builder: LENNAR HOMES
4Fri MI
Ceiling Attic, R-38
Above Grade Walls R-16
Foundation Walls R-11
Framed Floor N/A
Slab R-0.0 Perimeter, R-0.0 Under
Infiltration 6 ACH50
Window U-Value: 0.32, SHGC: 0.31
Building Features
Duct Supply R-30.0, Return R-30.0
Duct Leakage to Outside 308.0 CFM @ 25Pa
Total Duct Leakage 411.0 CFM @ 25Pa
Heating Furnace • Natural Gas • 95.5 AFUE
Cooling Air Conditioner • Electric • 13 SEER
Water Heating Water Heater • Electric • 0.93 Energy Factor
As a 3rd party extension of the code jurisdiction utilizing these reports, I certify that this energy code compliance document has been created in accordance with the requirements of
Chapter 4 of the adopted International Energy Conservation Code based on Climate Zone 5. It rating is Projected, I certify that the building design described herein is consistent with the
building plans, specifications. and other calculations submitted with the permit application. If rating is Confirmed, I certify that the address referenced above has been inspected/tested and
that the mandatory provisions of the I ECC have been installed to meet or exceed the intent of the IECC or will be verified as such by another party.
Name: Matthew Timmons
Organization: TSI Energy Solutions
Signature:
Date: 6/18119 at 3:17 PM
Ekotrope RATER - Version 3.1.0.2197
20091ECC compliance results calculated using Ekotrope RATER's energy and code compliance algorithm.
Ekotrope RATER is a RESIN ETAccredited HERS Rating Tool. All results are based on data entered by Ekotrope users.
Ekotrope disclaims all liability for the information sh own on this report.
Energy Code Inspection Checklist
Property Organization
6790 PULASKI CT TSI Energy Solutions
CARMEL, IN 46033 Matthew Timmons
Model: SOUTHILL (A)
Community: LEGACY RIDGE 88 Builder
LENNAR HOMES
LR088 (AS DES IG NED)
LEGACY RIDGE 88
General Building Information
Conditioned Area (sq ft) 5,144
Conditioned Volume (cubic ft) 45,306
Insulated Shell Area (sq ft) 8,815
inspection Status
Results are projected
C",
Energy Solutions
The building energy model in Ekotrope reflects the building assemblies and energy features listed below. Sometimes energy
features will change in the field from what has been modeled. The inspection process should identify any changes and ensure
that the home continues to meet the applicable energy code.
Slab
[ Name: BSMT (1,812 s.f.)
R-0 perimeter insulation, R-0 under slab insulation.
Framed Floor
None Present
Foundation Wall
[ Name: CONDIAMB (Exterior Perimeter [ft]: 161, Height Above Grade [ft]: 1, Depth Below Grade [ft]: 7)
R: 11.00
Feet from top of wall to top of insulation: 0, Feet from top of wall to bottom of insulation: 4
E[ Name: CONDIGAR (Exterior Perimeter [ft]: 32, Height Above Grade [ft]: 1, Depth Below Grade [ft]: 7)
R: 11.00
Feet from top of wall to top of insulation: 0, Feet from top of wall to bottom of insulation: 4
Above Grade Wall
El Name: CONDIAMB (2,274 s.f.)
R-3 continuous insulation, R-13 cavity insulation
Insulation Grade: I
[ Name: CONDIAMB 2X6 (468 s.f.)
R-3 continuous insulation, R-19 cavity insulation
Insulation Grade: I
Energy Code Inspection Checklist
Property Organization
6790 PULASKI CT TSI Energy Solutions
CARMEL, IN 46033 Matthew Timmons
Model: SOUTHILL (A)
Community: LEGACY RIDGE 88 Builder
LENNAR HOMES
LR088 (AS DESIGNED)
LEGACY RIDGE 88
Name: CONDIGAR (288 s.f.)
R-0 continuous insulation, R-13 cavity insulation
Insulation Grade: I
Name: CONDIATTIC (256 s.f.)
R-3 continuous insulation, R-13 cavity insulation
Insulation Grade: I
Rim Joist
Name: CONDIAMB (296 s.f.)
R: 13.575
Name: CONDIGAR (32 s.f.)
R: 10.876
Name: CONDIATTIC (32 s.f.)
R: 13.575
Roof
El Name: MAIN (1,813 s.f.)
R-27.55 continuous insulation, R-10.15 cavity insulation
Insulation Grade: I
Opaque Door
Name: FRONT (20 s.f.)
U: 0.182
Name: GARAGE (18 s.f.)
U: 0.182
Glazing
Inspection Status
Results are projected
El Name: FRONT (123 s.f.), U: 0.320, SHGC: 0.28, Orientation: EAST
El Name: BACK (210 s.f.), U: 0.320, SHGC: 0.31, Orientation: WEST
C-M,
Energy Solutions
2
Energy Code Inspection Checklist
C-M
Energy Solutions
Property Organization Inspection Status
6790 PULASKI CT TSI Energy Solutions Results are projected
CARMEL, IN 46033 Matthew Timmons
Model: SOUTHILL (A)
Community: LEGACY RIDGE 88 Builder
LENNAR HOMES
LRO88 (AS DESIGNED)
LEGACY RIDGE 88
E] Name: BACK BSMT (11 s.f.), U: 0.320, SHGC: 0.31, Orientation: WEST
E] Name: SLIDER (40 s.f.), U: 0.280, SHGC: 0.32, Orientation: WEST
El !Name: RIGHT SIDE (50 s.f.), U: 0.320, SHGC: 0.31, Orientation: NORTH
El Name: LEFT SIDE (94 s.f.), U: 0.320, SHGC: 0.31, Orientation: SOUTH
Skylight
None Present
Mechanical Ventilation
None Present
Mechanical Equipment
0 Fuel -fired air distribution (1) • Natural Gas • 100% Heating Load @ 95.5 AFUE
Air conditioner (2) • Electric • 100% Cooling Load @ 13 SEER
E] Water Heating (3) • Electric • 100% Hot Water Load @ 0.93 Energy Factor
Air Leakage Control
ElTest Status: Blower -door tested
House is air -sealed as to achieve 4,531 CFM50 (6.00 ACH50) or less at final blower -door test.
Infiltration Requirements for IECC in Climate Zone 5
2009 IECC Infiltration limit for the design home is 7 ACH50.
2012 IECC Infiltration limit for the design home is 3 ACH50.
2015 IECC Infiltration limit for the design home is 3 ACH50.
3
Energy Code Inspection Checklist
Property
6790 PULASKI CT
CARMEL, IN 46033
Model: SOUTHILL (A)
Community: LEGACY RIDGE 88
LR088 (AS DES IG NED)
LEGACY RIDGE 88
Duct Leakage
Duct System 1
Organization
TSI Energy Solutions
Matthew Timmons
Builder
LENNAR HOMES
Inspection Status
Results are projected
NOT entirely within conditioned space, testing required
Tested Post -Construction
Leakage to Outdoors is specified in Ekotrope at 308.0 CFM @ 25Pa
Total Duct Leakage is specified in Ekotrope at 411.0 CFM @ 25Pa
Duct Leakage Code Requirements for IECC
2009 IECC:
Postconstruction Leakage Test: Duct Leakage to Outdoors <= 8 CFM25 / 100 sq ft CFA.
Rough in Test with AHU: Total Duct Leakage <= 6 CFM25 / 100 sq ft CFA.
Rough in Test without AHU: Total Duct Leakage <= 4 CFM25 / 100 sq ft CFA.
2012 IECC and 2015 IECC Prescriptive Path:
Postconstruction Leakage Test: Total Duct Leakage <= 4 CFM25 / 100 sq ft CFA.
Rough in Test with AHU: Total Duct Leakage <= 4 CFM25 / 100 sq ft CFA.
Rough in Test without AHU: Total Duct Leakage <= 3 CFM25 / 100 sq ft CFA.
2015 Performance Path (Cost Compliance):
C",
Energy Solutions
Leakage testing is required UNLESS all ducts and air handlers are located entirely within the thermal envelope.
There is no pass/fail threshold for duct leakage on the performance path.
Project Notes
4
Building Summary
Property
Organization Inspection Status
6790 PULASKI CT
TSI Energy Solutions Results are projected
CARMEL, IN 46033
Matthew Timmons
Model: SOUTHILL (A)
Community: LEGACY RIDGE •C-•
Builder
LENNAR HOMES
LR088 (AS DESIGNED)
LEGACY RIDGE 88
Genera?Building Information
Number Of Bedrooms
4
Number Of Floors
2
Conditioned Floor Area [sq_ ft.]
5;144
Unconditioned, attached garage?
Yes
Conditioned Volume [Cu. ft.]
45;306
Total Units in Building
1
Residence Type
Single family detached
Floor Number
Model
SOUTHILL (A)
Community
LEGACY RIDGE 88
Climate Zone
5A
C-M,
Energy Solutions
Foundation Wall
Name Library Type Height Above Grade Depth Below Grade Perimeter Location Enclosing
CONDIAMB R-11 Draped, 4ft 1 7 161 Exposed Exterior Conditioned Space
CONDIGAR R-11 Draped, 4ft 1 7 32 Exposed Exterior Conditioned Space
Foundation Wall Library List
Name Feet From Wall Top To Feet From Wall Top To Is Fully Insulated Continuous R-value Cavity R-value Effective Insulation R-
Continuous Insulation Continuous Insulation value
Top Bottom
R-11 Draped_ Oft 0 4 No N?A NIA 11.00
Slak
BSMT Uninsulated 1 Below Grade 0 0 1.812.0 sq. ft. Exposed Exterior Conditioned
Space
Slab Library Lis
Name Wall Construction Slab Completel Underslab Perimeter Perimeter Thermal Break Effective R-value
Type Insulated. Insulation Width [ft] Insulation Depth [ft] Insulation R Value
Uninsulated Wood Frame / Other No 0 0 0 No D.00
1
Building Summary
Property
6790 PULASKI CT
CARMEL, IN 46033
Model: SOUTHILL (A)
Community: LEGACY RIDGE 68
LR088 (AS DESIGNED)
LEGACY RIDGE 88
Wramed Floor
Framed Floor Library List
Rim Joist
Organization
TSI Energy Solutions
Matthew Timmons
Builder
LENNAR HOMES
Inspection Status
Results are projected
C-M,
Energy Solutions
Name
Library Type
Surface Area
Location
CONDIAMB
G1 R-13, R-3.0
296.0 sq.ft.
Exposed Exterior
CONDIATTIC
G1 R-13, R-3.0
32.0 sq. ft.
Attic
CONDIGAR
G1 R-13, OSB
32.0 sq. ft.
Unconditioned, attached garage
Rim Joist Library Lis
Name
Effective Insulation R-value
G1 R-13, OSB
10.876
G1 R-13, R-3.0
13.575
Name
Library Type
Surrace COIOr
Surtace Area
LOCatIOn
CONDIAMB
G1 R-13 BATT, R-3.0
Medium
2,274.0 sq. fl.
Exposed Exterior
CONDIAMB 2X6
G1 R-19, R-3.0 2X6
Medium
468.0 sq. fl.
Exposed Exterior
CONDIATTIC
G1 R-13 BATT, R-3.0
Medium
256.0 sq. fl.
Attic
CONDIGAR
G1 R-13 Gar Walls
Medium
288.0 sq. ft.
Unconditioned, attached garage
2
Building Summary
Property
6790 PULASKI CT
CARMEL, IN 46033
Model: SOUTHILL (A)
Community: LEGACY RIDGE 88
LR088 (AS DESIGNED)
LEGACY RIDGE SS
FWaliTibrary List
Organization
TSI Energy Solutions
Matthew Timmons
Builder
LENNAR HOMES
G1 R-13 BATT, R-3.0
15.12
G1 R-13 Gar Walls
11.141
G1 R-19, R-3.0 2X6
20217
Glazing
Inspection Status
Results are projected
C-M,
Energy Solutions
Name
Library Type Wall Assignment
Foundation Wall Overhang Depth
Assignment
Overhang Ft To
Top
Overhang Ft To
Bottom
Orientation
Surface Area
BACK
111-.32, SHGG.31
CONDIAMB
0
0
0
West
210.0 sq. ft.
BACK BSMT
11-.32, SHGG.31
CONDIAMB 0
0
0
West
11.0 sq. ft.
FRONT
11-.32, SHGG28
CONDIAMB
0
0
0
East
123.0 sq. ft.
LEFT SIDE
11-.32, SHGG.31
CONDIAMB
0
0
0
South
94.0 sq. fL
RIGHT SIDE
11-.32, SHGG.31
CONDIAMB
0
0
❑
North
50.0 sq. fL
SLIDER
11-28, SHGG.32
CONDIAMB
0
0
0
West
40.0 sq. ft.
Glazing Library List
Name
U-28, SHGC-.32
U-.32, SHGC-28
11-.32, SHGC-.31
Skylight
Shgc
U #actor
0.32 0.280
028 0.320
0.31 0.320
9
Building Summary
Property
6790 PULASKI CT
CARMEL, IN 46033
Model: SOUTHILL (A)
Community: LEGACY RIDGE 88
LR088 (AS DESIGNED)
LEGACY RIDGE 88
kylight Library List I
Organization
TSI Energy Solutions
Matthew Timmons
Builder
LENNAR HOMES
Opaque Door
Name Library Type Wall Assignmen,
FRONT Steel Door CONDIAMB
GARAGE Steel Door CONDIGAR
Assign ment
Opaque Door Library List
JL
Name Effective U-factor
Steel Door 0.182
C-M
Energy Solutions
Inspection Status
Results are projected
r Surface Area Location
Ab sorpta n ce
0.9 0.75 Medium 20.0 sq- fL Exposed Exterior
0.9 0.75 Medium 18.0 sq- fL Exposed Exterior
Roof Insulation
M=
Name
Library Type
Attic Exterior Area
Clay or Concrete Roof Surface Color Surface Area Location
P.f.]
Tiles
MAIN
R-38 Blown. GR1
7.813
No Medium 1.813-0 sa. fL Attic
Roof Insulation Library List
Name Has Radiant Barrier Effective R-value
'•0 :a l No 38268
Whole House Infiltrati
I nfiItration
6 ACH at 50 Pa
Blower -door tested 4
M
Building Summary
Property
6790 PULASKI CT
CARMEL, IN 46033
Model: SOUTHILL (A)
Community: LEGACY RIDG: C-•C-•
LR088 (AS DESIGNED)
LEGACY RIDGE 88
Mechanical Ventilation
Lighting
o Interior Fluorescent
Lighting
Organization
TSI Energy Solutions
Matthew Timmons
Builder
LENNAR HOMES
Inspection Status
Results are projected
% Interior LED Lighting % Exterior Fluorescent % Exterior LED Lighting
Lighting
100 10 tDO
Gnsite Generation
Onsite Generation Library List
None Present
Solar Generation
None Present
Solar Generation Library List
None Present
C-M,
Energy Solutions
Lighting
0
100
Building Summary
Property
Organization
Inspection Status
6790 PULASKI CT
TSI Energy Solutions
Results are projected
CARMEL, IN 46033
Matthew Timmons
Model: SOUTHILL (A)
Community: LEGACY RIDG: C-•C-•
Builder
LENNAR HOMES
LR088 (AS DESIGNED)
LEGACY RIDGE 88
onditioning Equipment
Name
Library Type
Heating Percent Load Co(
Air conditioner (2)
CA13NA042
0%
C-M,
Energy Solutions
g Percent Load Hot Water
100%
0%
Fuel4red air 915SA4808OS17 100% ❑ % 0%
distribution (1)
Water Heating (3) RE350" 0% 0% 100%
1
Equipment Type: 915SA4808OS17
Fuel Type
Natural Gas
Distribution Type
Forced Air
Motor Type
PSG (Single Speed)
Heating Efficiency
95.5 AFUE
Heating Capacity [kBtulh]
78
Use default EAE
No
EAE [kWh]
946
Equipment Type: CA13NA042
Fuel Type
Electric
Distribution Type
Forced Air
Motor Type
PSG (Single Speed)
Cooling Efficiency
13 SEER
Cooling Capacity [kBtulh]
40
Equipment Type: RE350*
Fuel Type
Electric
Distribution Type
Hydronic Delivery
Hot Water Efficiency
0.93 Energy Factor
Tank Capacity (gal.)
50
Hot Water Capacity [kBtulh]
15.4
Recovery Efficiency
0.98
Building Summary
Property
6790 PULASKI CT
CARMEL, IN 46033
Model: SOUTHILL (A)
Community: LEGACY RIDG: C-•C-•
LR088 (AS DESIGNED)
LEGACY RIDGE 88
1bution System
Lion Type
Equipment
Equipment
t Served
i Grilles
Xct R Value
]uct R Value
Xct Area [sq. ft.]
]uct Area [sq. ft_]
akage to Outdoors (CFM25)
akage
akage Duct Test Conditions
fault Flow Rate
cation
Supply Area
Return Area
cation
Supply Area
Return Area
cation
Supply Area
Return Area
cation
Supply Area
Return Area
cation
Supply Area
Return Area
cation
Supply Area
Return Area
rCeiling Fan
Has Ceiling Fan
Ctm Per Watt
Organization Inspection Status
TSI Energy Solutions Results are projected
Matthew Timmons
Builder
LENNAR HOMES
Forced Air
Fuel -fired air distribution (1)
Air conditioner (2)
5144
6
3❑
3❑
1041.7
964.5
308
411
Post -Construction
Yes
Conditioned Space
7❑
70
Attic (well vented; under insulation)
3❑
3❑
Conditioned Space
0
0
Conditioned Space
Conditioned Space
Conditioned Space
No
C-M,
Energy Solutions
7
Building Summary
Property
6790 PULASKI CT
CARMEL, IN 46033
Model: SOUTHILL (A)
Community: LEGACY RIDGE 88
LR088 (AS DESIGNED)
LEGACY RIDGE 88
ater DistributionMM
I
ter Fixture Type
e Default Hot Water Pipe Length
t Water Pipe Length [ft]
Least R3 Pipe Insulation?
t Water Recirculation System?
circulation System Pipe Loop Length [ft]
in Water Heat Recovery?
Clothes Dryer
Fuel Type
Cef
Field utilization
Clothes Washer
Label Energy Rating
Electric Rate
Annual Gas Cost
Gas Rate
Capacity
I met
Appliances and Controls
Programmable thermostat?
Dishwasher Size
Dishwasher Efficiency
Range/Oven Fuel
Convection Oven?
Induction Range?
Refrigerator Consumption
Organization Inspection Status
TSI Energy Solutions Results are projected
Matthew Timmons
Builder
LENNAR HOMES
Standard
No
121
No
No
20
No
Electric
Timer Controls
glow
704 kWh/Year
$0.081kWh
$23.00
$0.581Therm
2.847
❑.331
Yes
Standard
270 kWh
Electric
No
No
709 kWh/Year
"M �
C-M,
Energy Solutions
,�