HomeMy WebLinkAboutA-021 - FLOOR TYPES1 /8"TYPE X GYP.BD.
1/2" RESILIENT CHANNEL
1ST FLOOR/CORRIDOR F 2 TYPICAL FLOOR GUESTROOM
3HR UL J924 iHR UL P545
STC = 66 ' STC = 55
ROOFING
5/8" RIGID INSULATION
BLOWN IN INSULATION
OPEN WEB TRUSS
RESILIENT CHANNEL
TYPE X GYP.BD.
F-3 TYPICAL CORRIDOR FLOOR UPPER FLOOR
iHR UL L 516
STC = 66 ROOF
R-1
1 HR UL P 545
BATT INSULATION
'.STC =55
TPO ROOFING
MEMBRANE
PARTICLEBOARD
RIGID INSULATION
--2X10 JOIST
L 3/4" D
®FLOOR
III
II
II
II
-
1
1
I
1
\
5(1 TYPE X GYP.BD
RELEASED FOR CONSTRUCTION
Subject to compliance with all regulations
of State and Local Codes
City NCamel
x
DATE: 07/22/19
GENERAL NOTES WALL TYPES
ALL GYPSUM BOARD IS TO BE 5/8" THICK UNLESS NOTED
OTHERWISE
INSTALL ACOUSTICAL SEALANT AT ALL GYP BD TERMINATIONS
HOLD ALL SUBSTRATE 1/2" ABOVE CONCRETE TO AVOID
WICKING ACTION
ALL EDGES OF GYP. BD. SHALL BE LOCATED ATAND SECURED
TO FRAMING SUPPORT
USE PAPERLESS MOISTURE RESISTANT GYP BD (FIRE RATED
IN FIRE RATED AREAS) IN ALL WET AREAS. ON WALLS WITH
MULTIPLE LAYERS ONY THE OUTERMOST LAYER NEEDS TO
MEET THIS CRITERIA. THIS INCLUDES BUT IS NOT LIMITED TO:
GUEST BATHROOMS
PUBLIC& STAFF RESTROOMS.
JANITOR CLOSETS
LAUNDRY AREA
-POOL AREAS
.USE CEMENT BOARD BEHIND ALL SHOWERS, TUB
SURROUNDS B TILED AREAS
USE CEMENT BOARD BEHIND ALL EXTERIOR ADHEARED
FINISHES
ON A NON FIRE RATED WALL GYP. BD SHALL TERMINATE 6"
ABOVE THE FINISH CEILING MATERIALS OR CONTINUE TO THE
UNDERSIDE OF THE STRUCTURE ABOVE IF FIRE RATED OR
CEILING IS EXPOSED TO STRUCTURE
ALL CMU WALL SHALL CONTINUE TO THE UNDERSIDE OF
STRUCTURE UNO. FINISHES APPLIED TO THESE WALLS SHALL
TERMINATE AT THE FINISH CEILING MATERIAL OR CONTINUE
TO THE STRUCTURE ABOVE IF THE CEILING IS EXPOSED TO
STRUCTURE
.ALL FIRE RATED EXTERIOR WALLS WITH A DISTANCE
GREATEER THAN 10' FROM ANOTHER STRUCTURE SHAL BE
.RATED FROM THE INSIDE ONLY
SEE STRUCTURAL PLANS FOR SPACING OF STUDS UNLESS
SPECIFICALLY NOTED
PROVIDE FIRE BLOCKING AT FLOOR AND ROOF LEVELS,
CONCEALED SPACES BETWEEN STAIRWAY STRINGERS,
PENETRATIONS IN FLOORICEILING ASSEMBLIES AND OTHER
LOCATIONS AS REQUIRED PER CODE
FIRE RATED EGRESS CORRIDORS ARE TO BE SEALED WITH
INTUMESCENT SEALING SYSTEMS. RATED WALLS ARE TO BE
SEALED TO DECK. VERTICAL JOINTS AT CMU/GYPSUM BOARD
WALLS ARE TO BE SEALED BOTH SIDES. WALL PENETRATIONS
SUCH AS BAR JOISTS, PIPING, CONDUIT, DUCTWORK, ETC. ARE
TO BE SEALED PER FIRE STOP MANUFACTURER'S
RECOMMENDATIONS.
PROVIDE BLOCKING AT ALL WALL HUNG EQUIPMENT AS
REQUIRED AND DETAILED IN DRAWINGS. COORDINATE EXACT
LOCATION WITH ARCHITECT/OWNER/TENANT.
.MAXIMUM HEIGHT OF NON LOAD BEARING WALL ABOVE
HEADER TO BE 20'-0"
REFERENCE CAPTURE TRACK DETAILS FOR DEFLECTION
REQUIREMENTS.
METAL STUD WALLS RECEIVING PLYWOOD SHALL BE 22
GAUGE OR HEAVIER.
PROVIDE HORIZONTAL BRACING FOR METAL STUDS AT 1/3 &
213 OF WALL HEIGHT
GENERAL NOTES STC NOTES
SOUND ATTENUATION REQUIREMENTS EMPLOY THE BEST
PRACTICES OUTLINED BY THE AMERICAN SOCIETY OF TESTS
AND MEASURES (ASTM), SECTION E497 TO ENSURE GOOD
SOUND CONTROL; CONFER WITH GYPSUM WALLBOARD
MANUFACTURERS FOR SPECIFIC RECOMMENDATIONS ON HOW
BEST IMPLEMENT THEIR SYSTEMS TO OPTIMIZE SOUND
CONTROL
THE ENTIRE PERIMETER OF SOUND -INSULATING ASSEMBLIES
SHALL BE AIRTIGHT, SO AS TO ELIMINATE FLANKING PATHS
THROUGH WHICH SOUND CAN TRAVEL; SOUND -INSULATING
ASSEMBLIES THEMSELVES SHALL BE AIRTIGHT— NO HOLES OR
HAIRLINE CRACKS ARE ALLOWED, AS THEY WOULD CREATE
FLANKING PATHS FOR SOUND
APPLY ACOUSTICAL SEALANT BETWEEN SOUND INSULATING
ASSEMBLIES AND OTHER DISSIMILAR ASSEMBLIES, OR
BETWEEN SOUND INSULATING ASSEMBLIES AND SIMILAR
SURFACES, WHERE PERIMETER RELIEF IS REQUIRED. TAPING
AND CAULKING OF GYPSUM WALLBOARD AND WALL / CEILING
INTERSECTIONS WILL PROVIDE AN ADEQUATE SEAL AT THESE
LOCATIONS
RECESSED WALL FIXTURES, SUCH AS CABINETS, OUTLETS AND
OTHER ITEMS THAT PENETRATE THE GYPSUM WALLBOARD
SURFACE SHALL NOT BE LOCATED BACK-TO-BACK IN THE SAME
STUD CAVITY. ANY OPENINGS FOR SUCH FIXTURES SHALL BE
CAREFULLY CUT TO SIZE AND CAULKED
WALL TYPE ABBREVIATIONS
EX= EXTERIOR
ER= EXTERIOR RATED
CR= CORRIDOR
GD= GUESTROOM DEMISING
ST= STAIRS
CM-- CMU WALL
CN= CONCRETE WALL
FS= FIRE SEPERATION
IP= INTERIOR PARTION
IR= INTERIOR PARTITION RATED
FR= FURRING
PR-- PARAPET WALL
SH= SHAFT WALL
STRUCTURAL SHEATHING
COORDINATE WITH STRUCTURAL DRAWINGS ON
LOCATIONS OF STRUCTURAL SHEATHING. WALLS IN THE
SAME PLANE REQUIRING STRUCTURAL SHEATHING, GC
IS TO FURR OUT SO ALL FINAL FINISHES PLANE OUT
OPTION 1:
R-3.8d + R-20 BATT INSULATION
NOTE:
FLOORIMPACT
1.SUrrE TO SUITE -SSIIC
2.SUrrE SLEEPING AREA TO MECHANICAL ROOM -SSIIC
FLOOR ASSEMBLY HAS AN PROPER TIC RATING
BAS F.
BASE4
2901 CLINT MOORE ROAD, #114
BOCA RATON, FLORIDA 33496
888.901.8008 w .base-4.00m
RICARDO J. MUNIZ-GULLIET, All
5453 NW 106TH DR
CORAL SPRINGS, FL 33076
Seal: -........
11
uN1U
7
``OpNu�
.
U�OOPEGISTE/kO
1700161
OF
DIANP. -. •��``
' 'u/CHITI�G41`�.
Owner
/V�•�iI
THE WITNESS GROUP
600 ENTERPRISES DRIVE
LEWIS CENTER,OH
513.623.9430
HOME
SUITES BY HILTON
CARMEL,INDIANA
PROTOTYPE VERSION-V2.2 2016
REVISION: MAY 2016
DECOR PACKAGE: TRIBECA
ISSUE
NO.
DELTA
I ISSUE DATE
DESCRIPTION
1
AO
12DI9.M.04
ISSUED FOR PERM IT
CURRENTISSUE
ISSUED FOR PERMIT
CURRENT ISSUE DATE
2019.03.04
DRAWN BY
NP
CHECKED BY
NL
PROJECTNO. -
B4-134-1705
SHEET NAME
FLOOR TYPES
DRAWINGS NO.
A=021