HomeMy WebLinkAboutA-036 - FIRE RATED FLOOR DETAILSDesign No. L570
Finish Floorin `-Min 3l4 in. thickness of Floor Topping Mixture bearing the UL
9 Y PP 9 9
Marking Fir Resistance. FI r- n Roof -Topping Mi r
Classification a as to a See oo a dxtu es CCO%
( )
category for names of Classified Companies.
Floor Mat Materiels* -(Optional) uNom.4i in. thick loose laid over the subiloor. Floor
topping thickness shall bea minimum of 314 in.
551025 N
KEENE BUILDING PRODUCTS CO INC -Type Quiet at 551025 and . 318 i . thick
Alternate Floor Mat Materlals` g (Optional) -Floor mat material Mom. 3I8 in. thick loose laid
over the subfloor. Floor topping thickness shall be a minimum of 1 in.
KEENE BUILDING PRODUCTS CO INC -T a Ouiet Qurl 601040 and Quiet Qurl 60I040 M
YP
Alternate Floor Mat Materlals*- (Optional) -Floor mat material Mom. 3I4 in. thick loose laid
( P )
over the subiloor. Floor topping thickness shall be a minimum o/ 1 -1 12 in.
KEENE BUILDING PRODUCTS CO INC -Type Quiet Curl 651075, Quiet Curl 651075 N
Floor Mat Materials*- (Optional) -Floor mat material Mom. 118 in. thick loose laid
System No. 11
S
thick wood structuraleredtoriels installedperpendiculariahesive a dN. with
9P joists
- Noed. Plywood
end Dints staggered. PI ootl or nets secured to with construction adhesive and No. 6tl
Snd joints
I 99 Yw Pa I
each joist. Staples having equal or greater withdrawal
dngetl shank nails, spaced 12 is y be
and lateral resistance strength may be substituted for the 6tl nails.
9 Y
Vapor Barrier - (Optional) -Nom 0.030 in. thick commercial asphalt saturated felt.
Finish Flooring Floor Topping Mature' -Min 3r4 or 1 in. thickness of floortopping mixture for
2 - PP 9 DPP 9
19/32 or 1Refe in. thick wood structural panels respectively, having a min compressive strength of
psi. Refer to manufacturer's instructions accompanying the material for specific mix design.
DEPENDABLE LLC-GSL M3.4 GSL K2.6 GSL-CSD or GSL RH
DEPENDABLE
Floor Mal Materials` -(Optional) -Nam. 1/4 in. thick loose laid over the subfloor. Floortopping
thickness shall be a minimum of 3l4 in.
KEENE BUILDING PRODUCTS CO INC- Type Quiet Quit 551025 and Quiet Curl 55/025 N
4C. Alternate Steel Framing Members' - Not Shown -As an alternate to Items 4 4A 4B
turning channels and Steel Framing Members as described below.
9 9
a. Fuming Channels rt Formed of When i s MSG gale steel. A, or in. wide d, 7/e in. deep, spaced 24
in. OC perpendicular to'oists. When insulation Items 3 3A or 3B is used the fordo channel
P P I 9
spacing shall be reduced as described in Item 4. Channels secured to joists as described in Item b.
p g
Ends of adjoining channels overlapped 6 in. and tied bgefherwifh double strand of No. 18 SWG
galy steel wire near each end of overlap.
b. Steel Framing Members`- Used to attach furring channels (Item a) to the wood When joists (Item 2).
WhenwoodI � P P I sts
clips spaced max a ie Clips in. sec When woornating
16ior are spaced 19.2 in. spaced
are s aced i6 or 24 in. OC cuss aced a max ofro gh the Genie of secured to eels are
joists with No. t x 2p1/2 in. coarse drywall screw Through the center hale. Furring channels are
friction fitted into clips. Additional clips required to hold furring channel that supports the wallboard
buttjoints, as described in Item 5.
PLITEQ INC-Type Genie Clip
November 28, 20189
Unrestrained Assembly Rain -iHr.
Y 9
This design evaluated using aload design other than the Limit States Design
g g g g
Method (e.g., Working Stress Design Method). For jurisdictions employing the Limit States
Design Method, such as Canada, a load restriction factor shall be used - See Guide
BXUV or BXUV7
' Indicates such products shall bear the UL or cUL Certification Mark for
p I
employing the UL or cUL Codification (such as Canada), respectively.
LAlternate
ztover
T
the sulpAlternateiloor. Floor topping thickness shall be a minimum of 314 in.
KEENE BUILDING PRODUCTS CO INC -Type Quiet Curl 521013 and Quiet Curl 521013 N
Alternate Floor Mat Materials*- (Optional) th Floor mat material Mom. in. entangled net
core with acompressible fabric attached to the bottom loose laid over the he subfloor. Floor
Altethe subfloor. Floortopping thickness shall be a minimum of 1 in. ate Floor Mat Materials' -(Optional) - Floor mat material Nom. 3/8 in. thick loose laid over
KEENE BUILDING PRODUCTS CO INC - Type Quiet Quit60/040 and Quiet Carl 60/040 N
4D. Alternate Steel Framing Members' - (Not Shown) -As an alternate to items 44B, furring
channels and Steel Framing Members described below.
a. Fuming Channels - Formed of No. 256 MSG galy steel, 2-5I8 in. wide by 718 in deep, spaced 24
j
topping thickness shall be a minimum of 1 in.
KEENE BUILDING PRODUCTS CO INC -Quiet Curl 551025 MT and Quiet Curl 551025 N MT
System No. 6
Alternate Floor Mat Materials' -(Optional) - Floor mat material Mom. 3/4 in. thick loose laid over
the subfloor. Floortopping thickness shall be a minimum of 1-1/2 in.
KEENE BUILDING PRODUCTS CO INC- Type Quiet Quit 651075, Quiet Curl 65/075 N
in OC, perpendicular to joists. When insulation, Items 3, 3A, or 3B is used, the fuming channel
spacing shall ereeduced as described in Item 4. Channels secured to loners as dlesion in Item b.
b. Steel Framing Members'- Used to attach furring channels (Item a) to the wood joists (Item 2).
When wood joists are spaced 19.2 in. OC, clips spaced a max of 38.4 in. OC. When wood joists
Subflooring- Mom 19132 in. thick wood structural panels installed perpendicular to the
joists with and joints staggered. Plywood or panels secured to joists with construction
adhesive and No. 6tl dngetl shank nails, spaced 12 in. OC along each joist. Staples having
equal or greater withdrawal and lateral resistance strength may be substituted for the 6tl
nails.
Alternate Floor Mat Materials" -(Optional) - Floor mat material Mom. 1/8 in. thick loose laid over
the subfloor. Floortopping thickness shall be a minimum of 34 in.
KEENE BUILDING PRODUCTS CO INC- Type Quiet Quit 50013 and Quiet Curl 52/013 N
Alternate Floor Mat Materials` -(Optional) - Floor mat material Nam. 1/4 in. entangled net core
with compressible fabric attached to the bottom loose laid over the subfloor. Floortopping
are spaced 16 or 24 in. OC, clips spaced at 48' OC and secured to the bottom of the joists with
one 2 in. Coarse Drywall Screw with 1 in. diem washer through the center hale. Furring channels
are then friction fitted into clips. Ends of channels are overlapped 6" and tied together with double
strand of No. 18 AWG galvanized steel wire.Additional clips are required to hold the Gypsum Butt
joints as described in item 5.
STUDCO BUILDING SYSTEMS- RESILMOUNT Sound Isolation Clis-Type A237 or A237R
P
r"+ f'+. ��}
I
, ) + }
OOL
Finish Flooring mature
comprsToppingMixture'-Min 314in. floor f 6.8 gal
having a min compressive strength of 1100 psi. Mixture shall consist of 6.8 gal of water to 80
rshall consist
lips of floortopping mixture to 1.9 cu It of sand.
HACKER INDUSTRIES INC - Firm -Fill Gypsum Concrete, Firm -Fill 2010, Firm -Fill 3310, Firm.
Fill 4010, Finn -Fill High Strength and GypSpan Radiant
Metal Lath -(Optional) - For use with 318 in. (10 mm) floor mat materials, 318 in. expanded
steel diamond mesh, 3.416s1sq ytl placed over the floor mat material. Hacker Floor Primer to
be applied prior to the placement of the metal lath. When metal lath is used, floortopping
thickness a mom 1.114 in. over the floor mat.
Floor Mat Materials' - (Optional) Floor mat material mom 5164 in. (2 mm) thick adhered to
subfloorwith Hacker Floor Primer. Primer to be applied to the surface of the mat prior to the
placement of a min 1 in. of floor -topping mixture.
ECOR..J
INTERNATIONAL INC -Type cker S and-
HACKER
HACKER INDUSTRIES INC -T a Hacker Sound -Mat.
YP
Alternate Floor Mat Materials e(Optional)oPria Floor mat material nom 11h in. 6 ram thick
( )
adhered to subfloorwith Hacker Floor Primer. Primer to be applied to the surface of the mat
n be PRODum ofUCTS iin.
thickness shallBUILDING
KEENE BUILDING PRODUCTS CO INC - Quiet Quit 59025 MT and Quiet Carl 55/025 N MT
System No. 12
Subflooring- Nam 19/32 in. thick woad structural panels installed perpendicularto the joists with
end joints staggered. Plywood or panels secured to joists with construction adhesive and No. 6d
ringed shank nails, spaced 12 in. OC along each joist. Staples having equal orgreater withdrawal
and lateral resistance strength may be substituted for the 6d nails.
Finish Flooring' - Floor Topping Materials -Min 3/4 in. to 1-1/2 in. thickness of any Floor
Tapping Mixture bearing the UL Classification Marking as to Fire Resistance with a minimum
compressive strength of 1500 psi.
See Floor- and Roof -Topping Matures (CCOX) categoryfor names of Classified Companies.
Floor Mat Materials' -(Optional) - Floor mat material nom 1/8 in. to 3/4 in. thick. Loose laid over
the subfloor. When used, Acousti-flor CSM (crack suppression mat) is loose laid over the floor mat
material. Floortopping material thickness is dependent on thickness of floor mat used.
WALFLOR INDUSTRIES INCINC-T Type Acousti-flor CSM. Floor topping thickness
YP PP 9
depends on products used as follows:
Alternate Steel Framing Members' - As an alternate to items 440, fuming channels and
Steel Framing Members as described below.
a. Fuming Channels - Formed of No. 25 MSG galy steel, 2p1/2 in. wide by 7/8 in deep, spaced 24
in OC, perpendicular to joists. When insulation, Items 3, 3A, or 3B is used, the tuning channel
spacing shall be reduced as described in Item 4. Channels secured to joists as tlescribetl in Item b.
b. Steel Framing Members"- Used to attach furring channels (Item a) tothe woodjoists (Item 2).
When woad joists are spaced 19.2 in. OC, clips spaced a max of 38.4 in. OC. When woad joists
am spaced 16 or 24 in. OC, clips spaced at 48' OC and secured to the bottom of the joists with
one 2p1/2 in. Coarse Drywall Screw with 1 in. tliam washer through the center hole. Furring
channels are then friction fitted into clips. Ends of channels are overlapped 6" and tied together
with double strand of No. 18 AWG galvanized steel wim. Additional clips am required to hold the
Gypsum Buttjoints as described in Rem 5.
REGUPOLAMERICA-Type SonusClip
5. Gypsum Board" -Two layers of 1/2 in. or 5/8 in. thick by 4 ft wide gypsum panels, installed
r entlicularto resilient channels Item 4. The base layer of panels screw -attached to the
Pep ( ) Y pa
resilient channels with 1 in. long Type S screws spaced 8 in. OC at the butt joints and 16 in. OC in
h field f h panel. The f r r h h resilient nn wi h i in. T f e e tl o the a e a ace layer screw -attached etl to the channels s f 3/8 e 5
screws spaced a in. OC and 1-1/2 in. Type G screws spaced 8in. OC to the butt joints located
Yed
P YP P I
mid -span between resilient channels. When Steel Framing Members (item 4A) are used, gypsum
7' A C
`T e7
4 {
'
prior to the placement of a min 1.114 in. (32 mm) of floor -topping mixture.
ECORE INTERNATIONAL INC -Type OTrbm 3006.3
HACKER INDUSTRIES INC -Type Hacker Sound -Mat II.
Alternate Floor Mat Materials -(Optional) - Floor mat material nom 1181n. (3 mm) thick
loose laid over the subfloor. Floor topping thickness shall be a min of 314 in. (19 mm)
HACKER INDUSTRIES INC - FIRM -FILL SCM 125
Alternate Floor Mat Materials -(Optional) - Floor mat material nom 1141n. (6 mm) thick
loose laid over the subfloor. Floor topping thickness shall be a min of 1 1n. (25 mm)
HACKER INDUSTRIES INC -Type FIRM -FILL SCM 250, ON let Curl 551025
Alternate Floor Mat Materials -(Optional) - Floor mat material nom 318 in. (10 mm) thick
loose laid overthe subfloor. Floor topping thickness shall be a min of 1.114 in. (32 mm)
HACKER INDUSTRIES INC- FIRM -FILL SCM 400 Curet Cur1601040
Alternate Floor Mat Materials - (Optional) -Floor mat material mom 314 In. 19 ram thick
( p ) ( )
loose laid Nover DUS a subfloor. Floor topping thickness shall of a min of i-112 in. (38 ram)
HACKER INDUSTRIES INC -Type FIRM -FILL SCM ]50, Do let Curl 651075
System No. 7
Subfloornng- Mom 19/32 in. thick wood structural panels installed perpendicular to the joists with
end joints staggered. Plywood or panels secured to joists with construction adhesive and No. 6tl
ringed shank nails, spaced 12 in. OC along each joist. Staples having equal or greater wthdrawal
and lateral resistance strength may be substituted for the 6tl nails.
Finish Floor- M ineml and Fiber Boats' - Min 1/2 in. thick, so pplied in sizes ranging from 3 ft by
4 ft to 8 ft by 12 ft. All joints to be staggered a min of 12 in. with adjacent sub -floor joints.
HOMASOTE CO -Type 440-32 Mineral and Fiber Board
System No. 8
Subflooring - Nam 19/32 in. thick wood structural panels installed perpendicular to the joists with
end joints staggered. Plywood or panels secured to joists with construction aches Ne and No. III
ringed shank nails, spaced 12 in. OC along each joist. Staples having equal or greater withdrawal
and lateral resistance strength may be substituted forthe 6tl nails.
Vapor Barrier - (Optional) - Mom 0.030 in thick commercial asphalt saturated felt.
Finish Flooring- Floor Topping Mature` -Min 34 in. thickness of floor topping mature having a
min compressive strength of 1500 psi. Refer to manufacturer's instructions accompanying the
material for specific mix design.
MAXXON CORP -Type D-C, GC, GC2000, L-R, T-F, CT, SS
RAPID FLOOR SYSTEMS -Type RF, RFP, RFU, Ortecrete
Floor Mat Materials`- Floor mat material loose laid over the subflooc Refer to manufacturers
instructions regarding the minimum thickness of floor tapping over each floor mat material.
MAXXON CORP -Type Acousti-Mat 1/8, Acousti-Mat 1/4, Acousti-Mat 1/4 Premium, Acousti-Mat
3/8, Acousti-Mat 318 Premium, Acousti-Mat 314, Acousti-Mat 314 Premium, Acousi
Floor Mat Reinforcement - (Optional) Refer to manufacturer's instructions regarding minimum
thickness of floortopping for use with floor mat reinforcement.
Metal Lath -(Optional)318 in. expantletl galvanized steel diamond mesh, 3.4 lbs/sq ytl loose laid
over the floor mat material.
Acousti-flor (1/8 in. thick) - Floortopping thickness shall be a minimum of 3r4 in.
Acousfi-flor (1/4 in. thick) - Floortopping thickness shall be a minimum of 1 in.
Acousti-flor (318 in. thick) - Floortopping thickness shall be a minimum of 1 in.
Acousti-flor (3/4 in. thick) - Floortopping thickness shall be a minimum of 1-1/2 in.
Metal Lath - (Optional) - Expanded steel diamond mesh, 2.5 Ib/ sq ytl loose laid over floor mat
material.
Fiberglass Mesh Reinforcement- (Optional) -Coated non -woven glass fiber mesh grid loose
laid over floor mat material.
System No. 13
Structural Cement -Fiber Units' -For use with UNITED STATES GYPSUM CO gypsum boards
only. Nam 3/4 in. thick with Ian edges tongue and moved. Lan dimension N over to be
Y 9 9 9 9 9 ce
to wood trusses with end staggered a min of 2 ft and centered over the
perpendicular I 99
trusses. Panels secured to wood fielder with crew o long, No. 8, self- countersinking wood screw
spaced a max of to in. OC in the floc with a screw located s ie, and a in. from each edge, and 8in.
OC on the perimeter with a screw Iocatetl 2 in. fmm each edge, Iocatetl ill in. fmm the end edges
of the panel.
UNITED STATES GYPSUM CO- Types STRUCTO-CRETE, USGSP
2. Structural Wood Members' - Min 9-1/tin. deep "I" shaped wood joists spaced of a max of 19.2
in. OC. Joists shall conform to ICC-ES ESR-1153 Report. Joist top and bottom chords minimum
i 3I8 in. deep by 2.3 in. wide and constructed of either Microllam laminated veneer lumber (LVL) or
Timber5trond laminated strand lu mber(LSL). Webs constructed of in in im um 3r8 in. thick
Performance Plus OSB, PS2, Exposure 1. Installation shall be in accordance with manufacturers
published litemtu re. Spacing may be increased to 24 in. OC when Batts and Blan kete` (Item 3B) is
used.
3.Insulation - Batts and B lankets'-(Optional)- G lass fiber insu cation, secured to the
subflooring with staples, or to the mod joists with 0.090 in. tliam galy steel wires, or draped over
the resilient channel/gypsum panel (or Steel Framing Members/gypsum panel) ceiling membrane.
Any thickness of glass fiber insulation bearing the UL Classification Marking as to Surface Burning
Characteristics anNor Fire Resistance.
3A.Insulation- Loose Fill Mai -(Optional)- As an alternate to Item 3-Any thickness of
loose fill material bearing the UL Classification Marking for Surface Burning Characteristics, applied
within the concealed space, over the resilient or fuming channel/gypsum panel or Steel Framing
Members/gypsum panel ceiling membrane.
3B. Insulation - Batts and Blankets' - (Optional) - Min. 1 in. thick glass fiber insulation bearing
the UL Classification Marking as to Surface Burning Characteristics and/or Fire Resistance draped
over the resilient channetgypsum panel (or Steel Framing Members/gypsum panel) ceiling
membrane.
4. Resilient Channels - Formed fmm 25 MSG galy steel installed perpendicular to the joists.
When no insulation is installed in the concealed space the resilient channels are spaced 24 in. OC.
When insulation (Item 3) is installed to the underside of the subfloor the resilient channels are
spaced .16 in. OC When insulation (items 3, 3A or 3B) is applied over the resilient
channel/gypsum panel ceiling membrane, the resilient channels am spaced 12 in. OC.. Two
board installed with long dimension perpendicular to cross tees. The base layer of panels fastened
to cross tees with s in. long Type S screws spaced 8 in. OC at the butt joints and 16 in. OC in the
field of the panel. The face layer screw -attached to the emss tees with 1-518 in. Type S screws
spaced 8 in. OC and 1-112 in. Type G screws spaced 8 in. OC at the butt joints located mid -span
between cross tees. Screws along sides and ends of panels spaced 3/8 to 1/2 in. from panel edge.
End joints of panels shall be staggered with spacing between joints on adjacent panels not less
than 4 ft OC. When Steel Framing Members (Item 4B) am used, panels installed with long
dimension parallel with joists. Base layer attached to the tuning channels using 1 in. long Type S
bugle -head steel screws spaced 8 in. OC along butted end joints and 12 in. OC in the field of the
panels. Butted end joints shall W staggered min. 2 ft. within the assembly, and occur midway
between the continuous furring channels. Each end of the gypsum panels shall be supported by a
single length of funding channel equal to the width of the panel plus 6 in. an each end. The furring
9 9 9 9 P P 9
channels shall be spaced a roximafe 3-1/2 in. OC and be attached to untlersitle ct the joist with
P PP N
one RSIC-1 clip at each end of the channel. Butted base layer end Dints to be offset a minimum of
P Y I
24 le in adjacent nurses. Outer layer affected buffed the furring channels using 1-5/8 in. long Type S
ts. B and 12 in. OC in the field. Butted end
bugle -head steel screws spaced 8in. la er end joints.
joints to be offset min 12 in, from base layer end loinfs. Buffed side joints of outer layer to be offset
min 12 in. from butted side joints of base layer. When Steel Framing Members (Item 4C) are used,
panels installed with long dimension parallel with joists. Base layer attached to the furring channels
using l in. long Type S bugle- head steel screws s paced 8 in. OC along buffed end joints and 12 in.
OC in the field of the panels. Butted end joints shall be staggered min. 2 ft. within the assembly,
and occur midway between the continuous furring channels. Each end of the gypsum panels shall
W s upported by a single length of furring channel equal to the width of the panel plus 6 in. on each
end. The furring channels shall be spaced approximately 3-1/2 in. OC, and be attached to
underside of the joist with one Genie clip at each end of the channel. Butted base layer end joints
to be offset a minimum of 24 in. in adjacent courses. Outer layer attached to the furring channels
using 1-5/8 in. long Type S bugle -head steel screws spaced 8 in. OC at butted joints and 12 in. OC
in the field. Butted end joints to be offset min 12 in. from base layer end joints. Buffed side joints of
outer layer fo be offset in in 12 in. from butted s itle joints of base layer. When Steel Framing
Members (Item 4D) are used, base layer gypsum board is installed with long dimensions
Parpendicularto fuming channels. Gypsum board secured to furring channels with nom 1 in. long
Type S bugle -head steel screws spaced 8 in. OC in the field of the board. Gypsum board butted
end joints shall be staggered minimum 48 in. and centered over main fuming channels. At the
gypsum board buff joints, each end of each gypsum board shall be suppoded by a single length of
fuming channel equal to the width of the gypsum board plus 3 in. on each end. The two support
fuming channels shall be spaced approximately 3 in. in from joint. Screw spacing along the gypsum
board butt joint and along bath additional channels shall W 8 in. OC. Butt joint furring channels
shall be attached with one RESILMOUNT Sound Isolation Clip at each end of the channel. Face
layer secured as described above.
When Steel Fmming Members (Item 4E) are used, base layer gypsum board is installed with long
dimensions perpendicular to furring channels. Gypsum board secured to fuming channels with nom
1 in. long Type S bugle -head steel screws spaced 8 in. OC in the field of the board. Gypsum board
butted end joints shall be staggered minimum 48 in. and centered over main furring channels.At
the gypsum board butt joints, an additional single length of fuming channel shall be Installed and be
spaced approximately 3 in. from the buff joint (Sin. from the continuous furring channels)to
support the floating end of the gypsum board. Each of these shorter sections of fuming channel
shall extend one joist beyond the width of the gypsu in panel and be attached to the adjacent joists
with one SonusClip of every joist involved with the butt joint.
P q
I (
1. Flooding System -The flooding system shall consist of one of the following:
System No. 1
Subfloodng -Nom 19/32 in. thick wood structural panels installed perpendicular to thejoists
with end joints staggered. Plywood or panels secured to joists with construction adhesive and
No. 6d Ringed shank nails, spaced 12 in. OC along each joist. Staples having equal or greater
withdrawal and lateral resistance strength may W substituted for the III nails.
Vapor Bamier - (Optional) -Nom 0.030 in. thick commercial asphalt saturated felt.
Finish Floor- Min 1 by 4 in. T & G lumber installed perpendicular to the joists, or min 15132 in.
thick wood structural panels, min grotle'Undedayment' or 'Single -Floor. Face grain of plywood
or strength axis of panel to W perpendicular to joists with joints staggered.
System No. 2
Subflooring- Mom 19/32 in. thick wood structural panels installed perpendicular to the joists
with end joints staggered. Plywood or panels secured to joists with construction adhesive and
No. 6tl dngetl shank nails, spaced 12 in. OC along each joist. Staples having equal or greater
wthdmwal and lateral resistance strength may be substituted for the 6tl nails.
Vapor Bamier - (Optional) -Nom 0.010 in. thick commercial asphalt saturated felt.
Finish Flooding- Floor Topping Mixture'- Min 3/4 inthickness of floor topping mixture having
a minimum compressive strength of 1800 psi. Refer to manufacturer's instructions
accompanying the material for specific mix design.
UNITED STATES GYPSUM CO -Types LRK, HSLRK, CSD
LATICRETE SUPERCAP L L C - Types LRK, HSLRK
USG MEXICO S A DE C V -Types LRK, HSLRK, CSD
Floor Mat Materials' - (Optional) - Floor mat material loose laid overthe subfloor. Referto
manufacturer's instructions regarding the minimum thickness of floortopping over each floor mat
material.
UNITED STATES GYPSUM CO -Types SAM, LEVELROCKV Brand Sou nit Reduction Board,
LEVE LROCK® Brand Floor Underlaymenf SRM-25
Alternate Floor Mat Materlals'-(Optional)-Mom 318 in. thick floor mat material loosely laid
over the subfloor.
GRASSWORX L L C-Type SC50
System No. 3
Subflooring- Mom 19/32 in. thick wood structural panels installed perpendicular to the joists
with end joints staggered. Plywood or panels secured to joists with construction adhesive and
Fiber Glass Reinforcement - (Optional) 0.015 in. thick PVC coated non -woven fiberglass mesh,
0.3681bs./sq. yd loose laid over the floor mat material.
System No. 9
Subflooring- Nam 19132 in. thick wood structural panels installed perpendicular to thejoists with
end joints staggered. Plywood or panels secured to joists with construction adhesive and No. III
ringed shank nails, spaced 12 in. OC along each joist. Staples having equal or greater withdrawal
and lateral ms istance strength may be substituted for the 6d nails.
Vapor Barrier -(Optional) Mom 0.030 in. thick commercial as that saturated felt.
Finish Flooring- Floor Topping Mixture' - Min 314 in. thickness of floor topping mixture having a
minimum compressive strength of 1500 psi. Refer to manufacturers instructions accompanying the
material for specific mix design.
FORMULATED MATERIALS LLC - Types FR-25, FR-3Q and SifeMix
Alternate Floor Mat Material' - (Optional) Floor mat material nominal 2 - 9.5 mm thick loose laid
over the subfloor. Floortopping thickness shall be a minimum of 34 in.
FORMULATED MATERIALS LLC - Types M1, M2, M3, R1, and R2
courses of resilient channel positioned 6 in. OC at gypsum panel butt -joints (3 in. from each end of
wallboard). Channels oriented opposite at gypsum panel butt joints. Channel splices overlapped 4
in. beneath wood trusses. Channels secured to each truss with 1AA in. long Type S screws.
4A. Alternate Steel Framing Members -(Nat Shawn) -As an alternate to Item 4, main runners,
cross tees, cross channels and wall angle as listed below.
a. Main Runners- Mom 10 or 12 ft long,15/16 in. orl-1/2 in. wide face, spaced 4 ff. OC. Main
runners suspended by min 12 SWG galy steel hanger wires spaced 48 in. OC. Hanger wires to be
located adjacent to main mnnerlemss tee intersections. Hanger wires wrapped and twist -tied on
16tl nails driven in to side of joists of least 5 in. above the bottom face.
b. Cross Tees - Mom 4 ft long, 1-V2 in. wide face, installed perpendicular to the main runners,
spaced 16 in. OC. Additional cross tees or cross channels used of 8 in. from each side of buffed
gypsum panel end joints. The cross tees or cross channels may be riveted or screw attached to the
wall angle or channel to facilitate the ceiling installation.
c. Cross Channels - Nam 4 or 12 ft long, installed perpendicular to main runners, spaced 16 in.
CDC INC -112 in. Type C, IP-X2, IPC-AR; 518 in. Type C, IP-X2. When them is no insulation in
the cavity, or when insulation (Item 3) is secured to the underside of the subfloor 5/8 in. Type SCX
or IPi maybe used
UNITED STATES GYPSUM CO- 1/2 in. Type C, IP-X2, IPC-AR; 5/8 in. Type C, IP-X2, ULIX.
When there is no insulation in the cavity, or when insulation (item 3) is secured to the underside of
the subfloor 518 in. Type SCX, or IP-Xi may be used
USG BORAL DRYWALL SFZ LLC-1/2 in. Type C; 5/8 in. Type C. When there is no insulation in
the cavity, or when insulation (item 3) is secured to the underside of the outdoor 518 in. Type SCX
may be used
6. Finishing System - Fiber tape embedded in compound over joints and exposed nail heads,
covered with compound with edges of compound feathered out. As an alternate, nom 3132 in. thick
gypsum veneer plaster may be applied to the entire surface of classified veneer baseboard. Joints
reinforced.
No. 6tl dngetl shank nails, spaced 12 in. OC along each joist. Staples having equal or greater
wthdmwal and lateral resistance strength may be substituted for the 6tl nails.
Vapor Banner - (Optional) - Nam 0.030 in. thick commercial asphalt saturated felt.
Finish Flooding- Floor Tapping Mixture'- Min 314 or 1 in. thickness of floortopping mixture for
19/32 or 15/32 in. thick wood sfructu al panels respectively, havin a min compressive strength
t9 t 9
System No. 10
Subflooring - Min 19132 in. thick wood structural panels, min grade "C-0"or"Sheathing".Face
min of plywood or strength axis of panels to be perpendicular to the joists with joints staggered.
g PYw 9 P P P I I 99
OC. When Batts and Blankets (Item 5) am used, cross channels spaced 16 in. OC.
d. Wall Angle or Channel- Painted orgacv steel angle with s in. legs orchannel with l in. legs,
1-9116 in. deep attached to walls at perimeter of ceiling with fasteners 16 in. OC. To support steel
framing member ends and forscrew-attachment of the sum panels.
9 gypsum
"Indicates such products shall bear the UL or cUL Certification Mark forlunsdictions employing the
UL or cUL Certification (such as Canada), respectively.
of 5000 pen. Referto manufacturer's instructions accompanying the maternal for specific mix
Vapor Banner- (Optional) - Commercial asphalt saturated felt, 0.030 in. thick.
CGC INC - Type DGL or RX
design.
ACG MATERIALS-AccuCrefe types NexGen, Green, Prime, B, M, and PrePour, AccuRadianf,
Accul-evel types G40, G50 and SD30.
Alternate Floor Mat MatedaP -(Optional) - Floor mat material nominal - 9.5 mm thick loose
laid over the subfloor. Floortopping shall be a min of 34 in. or 1 in. thick for 19132 or 15/32 in.
thick wood structural panels respecitnvely.
Vapor Barrier - (Optional) - Nam 0.010 in. thick commercial rosin sized building paper.
Finish Flooring"- Min 3r4 in. thickness of any Floor Topping Mature bearing the UL Classification
Marking as to Fire Resistance. See Floor- and Roof -Topping Matures (CCOX) category for names
of Classified Companies.
Floor Mat Mafedals' - (Optional) - Mom 3132 in. thick loose laid over the subfloor. Floortopping
thickness shall be a minimum of 34 in.
USG INTERIORS LLC -Type DGL or RX
4B. Alternate Steel Framing Members'- (Not Shown) -As an alternate to Items 4 and 4A,
fuming channels and Steel Framing Members as described below.
a. Furring Channels - Formed of No. 25 MSG galy steel. 2-9/16 in. or 2-23132 in. wide by 7/8 in.
ACG MATERIALS-AccuQuiet types P80, C40, D13, D-18, D25, DX38, EM.125, EM.125S,
PLITEQ INC - Type GenieMat RST02
deep, spaced 24 in. OC, perpendicular to joists. When insulation, Items 3, 3A, or 3B is used, the
EM.250, EM.250S, EM.375, EM.375S, EM.750, and EM.750S.
Floor Mat Materlals' - (Optional) - Mom 3/16 in. thick loose laid over the subfloor. Floortopping
thickness shall be a minimum of 34 in.
fuming channel spacing shall be reduced as tlescribetl in Item 4. Channels secured to joists as
described in Item D. Ends of adjoining channels overlapped 6 in. and tied together with double
System No. 4
strand of No. 18 SWG gacv steel wire near each end of overlap.
Structural Cenni iber U nits* -Nom 3141n.thick, with l ong edges tongue and grooved.
PLITEQ INC- Type Gen ieMat FF03NP
Long dimension of panels to be perpendicular to joists with and joints staggered a min of
2 R and ce irered over the joists. Panels secured to joists with 1-518 in. long No. 8 self-
Floor Mat Materials* -(Optional)-Mom 1/4 in. thick loose laid over the so bfloor.Floor topping
thickness shall be a minimum of 314 in.
b. Steel Framing Members"- Used to attach to wing channels (item a) to the wood joists (item 2).
When wood joists are spaced 19.2 in. OC, clips spaced a max of 38.4 in. OC. When wood joists
drilling, set/ -countersinking steel screws spaced a max o/ 12 in. OC in the field with a
screw located in. and in. from each edge, and in. OC on the perimeter with a screw
PLITEQ INC - Type GenieMat FF06
Floor Mat Materials* -(Optional)-Mom 3/8 in. thick loose laid over the subflooc Floor topping
am spaced 16 or 24 in. OC, clips spaced a max of 48 in. OC. RSIC-1 and RSIC-1 (2.75) clips
secured to alternating joists with No. 8 x 2-1/2 in. coarse drywall screw through the center
located 2 in. from each edge, located 1Q in. from the side edges of the panel.
thickness shall be a minimum of 1 in.
PLITEQ INC - Type GenieMat F710
grommet. RSIC-V and RSIC-V (2.75) clips secured to alternating joists with No. 8 x 1-1/2 in. coarse
drywall screw through the center hole. Fuming channels am friction fitted into clips. RSIC-1 and
'Sqy
UNITED STATES GYPSUM CO- Types STRUCTO-CRETE, USGSP
Q••-•-- kl- &
RELEASED FOR CONSTRUCTION Is, min grade "C-D" or "Sheathing'.
perpendicular to the joists with
91q Su6jecHocompliance ratd Local all regulations
of State and Local Codes
Floor Mat Materials" -(Optional)- Mom 3/4 in. thick loose laid over the subflooc Floortopping
thickness shall be a minimum of 1-1/2 in.
PLITEQ INC - Type GenieMat F717
FloorMatMafedals'-(Optional)- Mom lin. thick loose laid over the subfloor.Floor topping
thickness shall be GemeM of F25 in.
PLITEQ INC - Type GenieMat FF25
RSIC-V clips for use with 2-9/16 in. wide furring channels. RSIC-1 (2.75) and RSIC-V (2.75) clips
for use with 2-23132 in. wide fuming channels. Adjoining channels are overlapped as described in
Item a. As an alternate, ends of adjoining channels may be overlapped 6 in. and secured together
with two self -tapping No.6 framing screws min. 7/16 in. Ion of the midpoint of the overlap, with
PP 9 9 9 P that
one screw on each flange of the channel. Additional clips required to hold fuming channel that
inttC-V,
supports the wallboard butt joints, Types
PAC INTERNATIONAL L L C - Types RSIC-1, RSIC-V, RSIC-1 (2.75), RSIC-V (2.75)
City of Camel nercial rosin -sized building paper.
AMYksitUpgg `//`��ff �
'" uto
a DATE: 07/22/19
10
4e*
BASE 4
BASE4
2901 CLINT MOORE ROAD, #114
BOCA RATON, FLORIDA 33496
888.901.8008 WWW.base4.conn
RICARDO J. MUNIZ-GULLIET, All
5453 NW 106TH DR
CORAL SPRINGS, FL 33076
Seal:
jttMUMI2 of
`.p
;.. GISTE/kO:. ie
Z Q7
_�
U;
a a,: iTooisif0;
OF z
•
1 •
DIASN46"-:IN
' P•
'aria �HITEG%N%%,
11In ItRi
Owner
isI1
1/ I
�'
1 I
So
�� a
THE WITNESS GROUP
600 ENTERPRISES DRIVE
LEWIS CENTER,OH
513.623.9430
HOME
SUITES BY HILTON
11
CARMEL,INDIANA
PROTOTYPE VERSION-V2.2 2016
REVISION: MAY 2016
DECOR PACKAGE: TRIBECA
ISSUE
NO.
DELTA
ISSUE DATE
I DESCRIPTION
1
AO
2019.03.04
ISSUED FOR PERMIT
CURRENT ISSUE
ISSUED FOR PERMIT
CURRENT ISSUE DATE
2019.03.04
DRAWN BY
NP
CHECNED BY
NIL
PROJECTNO,
B4-134-1705
SHEET NAME
FIRE RATED FLOOR
DETAILS
DRAWINGS NO.
A=036