HomeMy WebLinkAboutE-207 - ENLARGED FLOOR POWER PLAN-1KEY NOTES FOR ELECTRICAL ROOM ® Text 1 CONTRACTOR SHALL VERIFY ELECTRICAL EQUIPMENT, SUCH AS SWITCHBOARDS, PANEL BOARDS, AND METER SOCKET ENCLOSURES,THAT ARE IN OTHER THAN DWELLING UNITS SHALL BE MARKED TO WARN QUALIFIED PERSONS OF POTENTIAL ELECTRIC ARC FLASH HAZARDS AS REQUIRED BY SECTION 110.16 OF 170-2008 2 CONTRACTOR SHALL PROVIDE A PERSONNEL DOOR(S) INTENDED FOR ENTRANCE TOAND EGRESS FROM THE WORKING SPACE LESS THAN 7.6 M (25 FT) FROM THE NEAREST EDGE OF THE WORKING SPACE, THE DOOR(S) SHALL OPEN IN THE DIRECTION OF EGRESS AND BE EQUIPPED WITH PANIC BARS, PRESSURE PLATES, OR OTHER DEVICES THAT ARE NORMALLY LATCHED BUT OPEN UNDER SIMPLE PRESSURE AS PER SECTION 110.26(C)(3)OF THE NEC 3 PROVIDE HOUSE PHONE. 1n ELECTRICAL ROOM 1/4 11 /411 = 11.011 PUMP FOR WATER .ER SOFTNER II�i �II II npo ) PP: 9,11,13 WATER O 40/3P SOFTNER P :6 BOOSTER PUMP P :1 C3 CP-2 PNL'PP' PP: 8 O CP-1 PP:7 CP-2 P. 1 GWH-1 GWH-2 GWH-3 GWH4 GWH-5 1O� 1O� 1O Et�P:2 eii-DPP: 3SBi4 IS n AS n KEY NOTES FOR MECH ROOM ® Text CONTRACTOR SHALL CO-ORDINATE WITH PLUMBING VENDOR FOR EQUIPMENTS FINAL LOCATION AND PROVIDE POWER AND CONNECTION ACCORDINGLY. 1 CONTRACTOR SHALL MAINTAIN MIN CLEAR SPACE REQUIRED AS PER NEC ARTICLE 110.26. CONTRACTOR SHALL ALSO REFER CODE AND PROVIDE POWER FOR MOTOR ACCORDINGLY. 2 PROVIDE HOUSE PHONE. 3 AS PER NEC 210.8 PROVIDE GFCI RECEPTACLE AT READILY ACCESSIBLE LOCATION IF NOT CONTRACTOR SHALL PROVIDE GFCI PROTECTION IN BREAKER FOR CIRCUIT. RELEASED FOR CONSTRUCTION Subject to compliance with all regulations ;OOM of State and Local Codes City NCBmeI ((�� �vmlUtlenrJnw�L N DATE: 07/22/19 PLUMBING EQUIPMENT SCHEDULE EQU. TAG CITY I DESCRIPTION ELECTRICAL LOAD IN W ELECTRICAL SUPPLY MOUNTING HEIGHT(AFF) CIRCUIT 1 1 GWHA 450 120/6OHz/iPH VENDOR TO CONFIRM PP:2 2 1 GI 450 120/6OHz/1PH VENDOR TO CONFIRM PP:3 3 1 GWH-3 450 120/6011z/iPH VENDOR TO CONFIRM PP:4 4 1 GWH4 450 120/60Hz/1PH VENDOR TO CONFIRM PP:S 5 1 GI 450 120/60Hz/1PH VENDOR TO CONFIRM PP:14 6 1 Cl 625 120/60Hz/iPH VENDOR TO CONFIRM PP:7 7 1 Cl 285 120/6OHz/1PH VENDOR TO CONFIRM PP:B 8 1 BOOSTERPUMP 8970 208/60Hz/3PH VENDOR TO CONFIRM PP:9,11,13 9 1 WATERSOFTNER1 500 1 120/6011 iPH 1 VENDOR TO CONFIRM PP:6 KEY NOTES FOR FITNESS Text 1 PROVIDE HOUSE PHONE. 2 PROVIDE CABLE CONNECTION TO EACH LCD EQUIPPED EXERCISE MACHINE. 3 PROVIDE ELECTRICAL POINT FOR EACH FITNESS MACHINE. 4 CONTRACTOR SHALL PROVIDE CONDUIT FOR MACHINE RECEPTACLE CONNECTION. 5 CONTRACTOR NEED TOVERIFY TELEVISION HEIGHT WITH ARCHITECTURAL DRAWING. n FITNESS ROOM 1/4 If = 11.011 KEY NOTES FOR ELEVATOR Text 1 CAT. 6# CABLES TO CAT. 6# CABLES TO ELECTRICAL ROOM IN 3/4"C, ONE CABLE FOR EACH ELEVATOR. 2 JUNCTION BOX FOR TELEPHONE SERVICE TO ELEVATOR. 3 PROVIDE DISCONNECT SWITCH-20AMP-12OV-1PHASE-60HZ FOR ELEVATOR CAB LIGHTING. 4 WALL MOUNTED ELEVATOR PIT LIGHTING AND RECEPTACLE LOCATED AT EACH FLOOR. CONTRACTOR SHALL PROVIDE GFCI RECEPTACLE AT READILY ACCESSIBLE LOCATION. CONTRACTOR SHALL PROVIDE GFCI PROTECTION TO PIT RCPT ACCORDING TO NEC SECTION 620.85. 5 CONTRACTOR SHALL CO-ORDINATE WITH PLUMBING VENDOR FOR SUMP PUMP LOCATION AND CONTROLLER LOCATION AND PROVIDE DISCONNECT SWITCH ACCORDINGLY. 6 CONTROL CIRCUITS TO SHUT DOWN ELEVATOR POWER SHALL BE MONITORED FOR THE PRESENCE OF OPERATING VOLTAGE. LOSS OF VOLTAGE TO THE CONTROL CIRCUIT FOR THE DISCONNECTING MEANS SHALL CAUSE A SUPERVISORY SIGNAL TO BE INDICATED AT THE BUILDING FIRE CONTROL UNIT. 7 CONTRACTOR SHALL REFER SECTION 620.53 OF THE 2008 NEC AND CIRCUITS SHALL BE PROVIDED WITH AN ENCLOSED CIRCUIT BREAKER OR EXTERNALLY OPERABLE FUSED MOTOR CIRCUIT SWITCH AS A DISCONNECTING MEANS. 8 CONTRACTOR SHALL CO-ORDINATE WITH ELEVATOR VENDOR FOR EXACT LOCATION AND CONNECTION. ELEVATOR ROOM �1/4Il=11-0/4Il=11.011 1 FOR WATER COOLER STATION FITNESS ROOM 156 t23HP :38 IN DISCONNECTOR FOR SUMP PUMP 30/2P 8 P DISCONNECTOR FOR ELEVATOR-1 CAB LIGHT DISCONNECTOR FOR ELEVATOR-2 CAB LIGHT DISCONNECTOR FOR ELEVATOR-2 7 ELEV#1232 1 SHUNT TRIP 21 FOR ELEVATOR-1 PIT LIGHT FOR ELEVATOR-1 'IT LIGHT FOR ELEVATOR-2 ELEVATOR EQUIPMENT SCHEDULE EQU. TAG CITY DESCRIPTION ELECTRICAL LOAD IN W ELECTRICAL SUPPLY MOUNTING HEIGHTAFF)l CIRCUIT 1 1 ELEVATOR-1 15852 208/601 VENDOR TO CONFIRM EP:1,3,5 2 1 ELEVATOR-2 12609 208/601 VENDOR TO CONFIRM EP$4,6 3 1 SUMP PUMP 2782 208/60Hz(IPH VENDOR TO CONFIRM EP:8,10 BAS E4 BASE4 2901 CLINT MOORE ROAD, #114 BOCA RATON, FLORIDA 33496 888.901.8008 www.base-4.00m RICARDO J. MUNIZ-GUILLET, AIA 5453 NW 106TH DR CORAL SPRINGS, FL 33076 MEP ENGINEER GARRY VERMAAS PhD, PE 2183 S BERRYS CHAPEL ROAD FRANKLIN, TN 37069 Seal: H W VF QP��'\si EHh� e' %p m N 1 12 o ATE OF �gBrONAL ��` DATE: 2D1aos.04 GAREY YERMAAS. Phi HE Owner: W, THE WITNESS GROUP 600 ENTERPRISES DRIVE LEWIS CENTER,OH 513-623-9430 HOME©SUITES BY HILTON CARMEL, INDIANA PROTOTYPE VERSION-V2.2 2016 REVISION: MAY 2016 ISSUE NO. DELTA I ISSUED DATE DESCRIPTION 1 EO 2019.03.04 ISSUED FOR PERMIT CURRENT ISSUE ISSUED FOR PERMIT CURRENT ISSUE DATE 2019.03.04 DRAWN BY SKJ CHECKED BY GWV PROJECT NO 134-134-1705 SHEET NAME ENLARGED FLOOR POWER PLAN-1 DRAWINGS NO. E=207