E-303 - PANEL SCHEDULE-III
SERVICE:3 PHASE,4-WIRE PANEL'2GA' MAIN BUS (A) 400 VOLTAGE:120/208 NEUTRAL(%) 100% MOUNTING:WALL MOUNTED MAINS (A) 400 TYPE:LOAD CENTRE AIC (A) 22,000 LOAD DESCRIPTION PHASE R Y B TRIP POLE WIRE CONDUIT (INCH) CKT NO. CKT NO. CONDUIT (INCH) WIRE TRIP POLE PHASE LOAD DESCRIPTION R Y B SECTION-11GA' ROOM 201 PNL'A' 8200 8200 70/2P 4 11/4 2 1 6 60/2P 6430 6430 ROOM 202 PNL'B' 3 ROOM 203 Pi 64306430 70/2P 4 11/4 1 6 60/2P 6340 ROOM 204 PNL'G' 7 8 6340 ROOM 205 PNL'H' 6430 60/2P 6 1 9 10 1 6 60/2P 6340 ROOM 206 PI6430 111 11 12 6340 ROOM 207 PNL'H' 6430 60/2P 6 1 13 14 11/4 4 70/2P 6430 ROOM 208 PN L'D' 6430 15 16 6430 ROOM 209 PNL'H' 6430 6430 60/2P 6 1 17 18 11/4 4 70/2p 6430 ROOM 210 PNL'D' 19 20 6430 ROOM 211 PHLIP 6430 60/2P 6 1 21 22 11/4 4 70/2P 6430 1 A 6430 ROOM 212 Pi6430 23 24 2nd FLOOR COORIDOR RCPT 720 20/lP 12 3/4 1 25 26 1 3/4 12 1 20/lP 540 2nd FLOOR COORIDOR RCPT 2nd FLOOR ELECTRICAL ROOM POET 2nd FLOOR STORAGE RCPT 360 540 20/lP 20/1P 12 12 3/4 3/4 27 29 28 30 3/4 3/4 12 12 20/lP 20/lP(GFCI) 540 1000 2nd FLOOR HOUSEKEEPING RCPT 2nd FLOOR ICE DISPENSER RCPT SPACE 31 32 SPACE SPACE SPACE 33 35 34 36 SPACE SPACE SPACE 37 38 SPACE SPACE SPACE 39 41 40 42 SPACE SPACE SUBTOTALVA 28210 127850 26260 26170 26170 26540 SUBTOTALVA 28210 27850 26260 54380 54020 1528001 TOTALVA: 161200 LOAD CONNECTED LOAD DEMAND FACTOR DEMAND LOAD NOTE: 1)ASPER NEC 230.8 GFCI RECEPTACLE SHALL BE ON READILY ACCESIIBLE LOCATION IF NOT CONTRACTOR SHALL PROVIDE GFCI BREAKER IN PANEL. PROVIDE GFCI TYPE RECEPTACLE AT KITCHEN COUNTER AND SHALL BE READILY ACESSIBLE LOCATION. IF ANY GFCI RECEPTACLE COMING BEHIND EQUIPMENT PROVEDE GFCI PROTECTION IN BREAKER ASPER CODE. GUEST ROOMS: LIGHTING 1.25 RCPT 2700 NECARTICLE 220.44 2700 TOTAL GUEST ROOM LOAD IN VA 157500 NECARTICLENO 220.84 67725 ARTIFICIAL COOKTOP LOAD 96000 NEC ARTICLE NO 220.94 41280 MISC LOAD 1000 1 1000 TOTAL LOAD IN VA 257200 112705 TOTAL LOAD IN AMPERE 714 313 TAKING 20%SPARE CAPACITY IN AMP 375 SERVICE:3 PHASE,4-WIRE PANEL'3GA' MAIN BUS (A) 400 VOLTAGE:120/208 NEUTRAL(%) 100% MOUNTING:WALL MOUNTED MAINS (A) 400 TYPE:LOAD CENTRE AIC (A) 22,000 LOAD DESCRIPTION PHASE R Y B TRIPPOLE WIRE CONDUIT (INCH) CRT NO. CKT NO. CONDUIT (INCH) WIRE TRIP POLE PHASE LOAD DESCRIPTION R Y B SECTION-1'3GA' ROOM 301 Pi8110 8110 80/2P 4 1 V4 1 6 60/2P 6430 ROOM 302 PNL'B' 3 4 6430 ROOM 303 Pi6430 6430 70/2P 4 11/4 6 1 6 60/2P 6340 ROOM 304 Pi 5 6340 ROOM 305 PNL'H' 6430 60/2P 6 1 9 10 1 6 60/2P 6340 ROOM 306 PNL'G' 6430 11 12 6340 ROOM 307 PNL'H' 6430 60/2P 6 1 13 14 11/4 4 70/2P 6430 6430 ROOM 308 Pi6430 15 16 ROOM 309 PNL'H' 6430 60/2P 6 1 17 18 11/4 1 4 70/2P 6430 ROOM 310 Pi6430 19 1 20 6430 ROOM 311 PHLIP 6430 6430 60/2P 6 1 21 22 11/4 4 70/2P 6430 6430 ROOM 312 PNL'D' 23 24 3rd FLOOR COORIDOR RCPT 720 20/lP 12 3/4 25 26 3/4 12 20/lP 540 3rd FLOOR COORIDOR RCPT 3rd FLOOR ELECTRICAL ROOM RCPT 3rd FLOOR STORAGE RCPT 360 20/1P 20/1P 12 12 3/4 3/4 27 29 28 30 3/4 3/4 12 12 20/lP 20/lP(GFCI) 540 1000 3rd FLOOR HOUSEKEEPING RCPT 3rd FLOOR ICE DISPENSER RCPT 540 SPACE 31 33 32 34 SPACE SPACE SPACE SPACE 35 36 SPACE SPACE 37 38 SPACE SPACE 39 40 SPACE SPACE 41 42 SPACE SUBTOTALVA 28120 27760 26260 126170 126170 126540 1 SUBTOTALVA L54290 28120 27760 2626 0 53930 5280LVA: 161020 LOAD CONNECTED LOAD DEMAND FACTOR DEMAND LOAD NOTE: 1) ASPER NEC 310.8 GFCI RECEPTACLE SHALL BE ON READILY ACCESIIBLE LOCATION IF NOT CONTRACTOR SHALL PANEL. PROVIDE GFCI TYPE RECEPTACLE AT KITCHEN COUNTER AND SHALL BE READILY ACESSIBLE LOCATION. COMING BEHIND EQUIPMENT PROVIDE GFCI PROTECTION IN BREAKER ASPER CODE. PROVIDE GFCI BREAKER IN IF ANY GFCI RECEPTACLE GUEST ROOMS: LIGHTING 1.25 RCPT 2700 NECARTICLE 220.44 2700 TOTAL GUEST ROOM LOAD IN VA 157320 NEC ARTICLE NO 220.84 67648 ARTIFICIAL COOKTOP LOAD 96000 NEC ARTICLE NO 220.84 41280 MISC LOAD 1000 1 1000 TOTAL LOAD IN VA 257020 112628 TOTAL LOAD IN AMPERE 713 313 TAKING 20%SPARE CAPACITY IN AMP 375 RELEASED FOR CONSTRUCTION Subject to compliance with all regulations of State and Local Codes City of Camel ((�� `�vmlUtlDnrJnD�L x DATE: 07/22/19 SERVICES PHASE,4-WIRE PANEL'2GB' MAIN BUS (A) 400 VOLTAGE:120/208 NEUTRAL(%) 100% MOUNTING:WALL MOUNTED MAINS (A) 350 TYPE:LOAD CENTRE All (A) 22,000 LOAD DESCRIPTION PHASE R Y B TRIP POLE WIRE CONDUIT (INCH) CKTNO. CKTNO. CONDUIT (INCH) WIRE TRIPPOLE PHASE LOAD DESCRIPTION R Y B SECTION-1'2GB' ROOM 213 PNL'E' 6610 6610 60/2P 6 1 2 11/4 4 70/2P 6430 6430 ROOM 216 PNL'D' 3 ROOM 215 Pi 64306430 70/2P 4 11/4 11/4 4 70/2P 6430 6430 ROOM 218 PNL'D' 7 8 ROOM 217 PNL'D' 6430 70/2P 4 11/4 9 10 11/4 4 70/2P 6430 ROOM 220 PNL'D' 6430 11 12 6430 ROOM 219 Pi6430 70/2P 4 11/4 13 14 11/4 4 70/2P 6430 ROOM 222 Pi6430 15 16 6430 ROOM 221 PNL'C' 8110 80/2P 4 11/4 17 18 11/4 4 70/2P 6430 6430 ROOM 224 PNL'D' 8110 19 20 2ND FLOOR CORRIDOR LTG 2ND FLOOR ELEV. LOBBY LTG 340 15/1P 1 70 15/1P 12 12 3/4 3/4 21 1 23 22 24 3/4 1 3/4 12 12 15/1P 15/1P 340 60 2ND FLOOR CORRIDOR LTG 2ND FLOOR ELEV. LOBBY LTG 2ND FLOOR HSKG/IDF/ELECT. LTG 100 15/1P 12 3/4 25 26 3/4 12 15/1P 50 2ND FLOOR STORAGE LTG 2ND FLOOR EXTERIOR LTG SPACE 50 15/lP 12 3/4 27 29 28 30 3/4 12 15/IP 50 2ND FLOOR EXTERIOR LTG SPACE SPACE 31 32 SPACE SPACE SPACE 33 35 34 36 SPACE SPACE SPACE 37 38 SPACE SPACE 39 41 40 42 SPACE SPACE SPACE SUBTOTALVA 27680 19860 121040 25770 19680 19350 SUBTOTALVA 27680 53450 19860 21040 39540 40390 TOTAL VA: 233380 LOAD CONNECTED LOAD DEMAND FACTOR DEMAND LOAD NOTE: 1) ASPER NEC 210.8 GFCI RECEPTACLE SHALL BE ON READILY ACCESIIBLE LOCATION IF NOT CONTRACTOR SHALL PROVIDE GFCI BREAKER IN PANEL. PROVIDE GFCI TYPE RECEPTACLE AT KITCHEN COUNTER AND SHALL BE READILY ACESSIBLE LOCATION. IF ANY GFCI RECEPTACLE COMING BEHIND EQUIPMENT PROVIDE GFCI PROTECTION IN BREAKER ASPER CODE. GUEST ROOMS: LIGHTING 1060 1.25 1325 RCPT NECARTICLE 220.44 TOTAL GUEST ROOM LOAD IN VA 132320 NECARTICLENO 220.84 56898 ARTIFICIAL COOKTOP LOAD 80000 NECARTICLENO 220.84 34400 MISC LOAD 1 TOTAL LOAD IN VA 213380 92623 TOTAL LOAD IN AMPERE 592 257 TAKING 20%SPARE CAPACITY IN AMP 309 SERVICE:3 PHASE,4-WIRE PANEL'3GB' MAIN BUS (A) 400 VOLTAGE:120/208 NEUTRAL(%) 100% MOUNTING:WALL MOUNTED MAII(A) 350 TYPE:LOAD CENTRE AIC (A) 18,000 LOAD DESCRIPTION PHASE R Y B TRIP POLE WIRE CONDUIT (INCN) CKT NO. CKT NO. CONDUIT (INCH) WIRE TRIPPOLE PHASE LOADDESCRIPTION R Y B SECTION-1'3GB' ROOM 313 PNL'E' 6610 60/2P 6 1 2 1 V4 4 70/2P 6430 6430 ROOM 316 Pi 6610 3 ROOM 315 PNL'D' 6430 6430 70/2P 4 11/4 11/4 4 70/2P 6430 ROOM 318 PNL'D' 7 8 6430 ROOM 317 PNL'D' 6430 70/2P 1 4 11/4 9 10 11/4 4 70/2P 6430 6430 ROOM 320 Pi 6430 11 12 ROOM 319 PNL'D' 6430 70/2P 4 11/4 13 14 11/4 4 70/2P 6430 ROOM 322 Pi6430 15 16 6430 ROOM 321 PNL'C' 8110 8110 80/2P 4 11/4 17 18 11/4 4 70/2p 6430 ROOM 324 PNL'D' 19 20 6430 3RD FLOOR CORRIDOR LTG 340 15/lP 12 3/4 21 22 3/4 12 15/1P 340 3RD FLOOR CORRIDOR LTG 3RD FLOOR ELEV. LOBBY LTG F 70 15/1P 1 12 3/4 23 24 3/4 1 12 15/IP 60 3RD FLOOR ELEV. LOBBY LTG 3RD FLOOR HSKG/IDF/ELECT. LTG 100 15/1P 12 3/4 25 26 3/4 12 15/1P 5o 3RD FLOOR STORAGE LTG SPACE SPACE 27 28 SPACE SPACE IF 29 31 30 32 SPACE SPACE SPACE 33 34 7 SPACE SPACE _ 35 36 SPACE SPACE SPACE 37 38 SPACE 39 41 40 1 42 SPACE SPACE SPACE SUBTOTAL VA 127680 119810 21040 1 25770 1 19630 119350 SUBTOTALVA 27680 19810 21040 53450 39440 40390 TOTAL VA: 133280 LOAD CONNECTED LOAD DEMAND FACTOR DEMAND LOAD NOTE: 1)ASPER NEC 310.8 GFCI RECEPTACLE SHALL BE ON READILY ACCESIIBLE LOCATION IF NOT CONTRACTOR SHALL PROVIDE GFCI BREAKER IN PANEL. PROVIDE GFCI TYPE RECEPTACLE AT KITCHEN COUNTER AND SHALL BE READILY ACESSIBLE LOCATION. IF ANY GFCI RECEPTACLE COMING BEHIND EQUIPMENT PROVIDE GFCI PROTECTION IN BREAKER AS PER CODE. GUEST ROOMS: LIGHTING 960 1.25 1200 RCPT NECARTICLE 220.44 TOTAL GUEST ROOM LOAD IN VA 132320 NEC ARTICLE NO 220.94 56898 ARTIFICIAL COOKTOP LOAD 80000 NEC ARTICLE NO 220.94 34400 MISC LOAD 1 TOTAL LOAD IN VA 213280 92498 TOTAL LOAD IN AMPERE 592 1 257 TAKING 20%SPARE CAPACITY IN AMP 1 308 PANEL'2GA' PANEL'2GB' PANEL'3GA' PANEL'3GB' BAS E'' BASE4 2901 CLINT MOORE ROAD, #114 BOCA RATON, FLORIDA 33496 888.901.8008 www.base-4.00m RICARDO J. MUNIZ-GUILLET, AIA 5453 NW 106TH DR CORAL SPRINGS, FL 33076 MEP ENGINEER GARRY VERMAAS PhD, PE 2183 S BERRYS CHAPEL ROAD FRANKLINI TN 37069 Seal: 1 W VF QP��'\'sYpHA� 1 12 o ATE �gBrONAI E�` DATE: M1e 0a 04 GARRY VERMMS. PhD. PE Owner: e 4 THE WITNESS GROUP 600 ENTERPRISES DRIVE LEWIS CENTER,OH 513-623-9430 HOME©SUITES BY HILTON CARMEL, INDIANA PROTOTYPE VERSION-V2.2 2016 REVISION: MAY 2016 ISSUE NO.1 DELTA I ISSUED DATE I DESCRIPTION 1 EO 2019.03.04 ISSUED FOR PERMIT CURRENT ISSUE ISSUED FOR PERMIT CURRENT ISSUE DATE 2019.03.04 DRAWN BY SKJ CHECKED BY GWV PROJECT NO, 134-134-1705 SHEET NAME PANEL SCHEDULE -III DRAWINGS NO. E=303