10
1/2" jl5mmj ROUND ROD PIN
INSULATION
Ducr
INSULATION
STAND-OFF
DAMPER BLADE
VDLE WITH LOCKING
QUADRANT
INSIDE END BEARING -
OUTSIDE END BEARING
1/8" 161Pm1 CLEARANCE All /
AROUND SECTION
NOTE:
1. DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER
INSTALLATION SHALL BE SIMILAR FOR MULTI -BLADE
DAMPERS & ROUND DAMPERS.
STANDARD RADIUS ELBOW
NOTE:
I. THE INTERIOR SURFACE
OF ALL ELBOWS SHALL
BE MADE SQUARE.
2. ALL SQUARE ELBOWS SHALL
HAVE VANES. VANES SHALL BE
CONSTRUCTED, SUPPORTED AND
FASTENED AS RECOMMENDED
BY SMACNA.
R SHALL EQUAL
3R BE GREATER
THAN 1/3W.
2 SHALL EQUAL OR
3E GREATER THAN 1/6W.
NOTE:
1. THE INTERIOR SURFACE OF ALL
RADIUS ELBOWS SHALL BE MADE
ROUND.
2. ALL STANDARD RADIUS ELBOWS
SHOWN ON FLOOR PLANS MAY BE
MADE SHORT RADIUS ELBOWS.
ALL SHORT RADIUS ELBOWS
SHALL HAVE VANES. VANES SHALL
BE CONSTRUCTED, SUPPORTED
SHORT RADIUS ELBOW WITH TWO VANES AND FASTENED AS RECOMMENDED
BY SMACNA.
DUCTWORK SQUARE & RADIUS ELBOWS
I V .. .LUG. ...... -
2X2X1/8" GALVANIZED
0'-0" ANGLE H. D.
�� V.
(TYP.) (2)EA#14X1-i14 - THREADED CAP.
T-5 METAL SCREWS
W/CAULK SILICONE. O/A DUCT O.D.
T(TYP,)(2)EA#
METALSCREWS
WICAULK CONE
1-1/2"e GALVANIZED
SCHEDULE40 PIPE.-
@
2X2X1/8"GALVANIZED
0
ANGLE H.D.
PLYWOOD
SILICONE
P
SHEATHING
(BY OTHERS)
NAILED
SS PIPE CLAMP
ROOF FLASHING
(BY OTHERS TYP.
(BV OTHER)Zy
6X6x3/8"BASE 11/2"
3"
1 /
3
1
PLATE FIX TO
PLANK W/ (4) 0.145
P.A.F. WI 1 3A"
EMBED
PRE-ENGINEERED WOOD L FLOOR
NOTE: FLOOR TRUSSES
' ALL DUCT JOINTS TO BE SEALED WITH SILICON CAULK ON ROOF.
' TOP OF DUCT TO BE PITCHED TO SHED WATER.
' DUCT SHALL BE SUPPORTED WITH APPROVED HANGERS AT INTERVALS NOT EXCEEDING 10 FEET (3048 MM) IN
ACCORDANCE WITH THE REQUIREMENTS OF IMC SECTIONS 61 BYOTHER APPROVED DUCT SUPPORT
SYSTEMS DESIGNED IN ACCORDANCE WITH THE IMC.
NOTE:
' DUCT SHALL BE ANCHORED TO WITHSTAND TOTAL WIND SPEED OF 115 MPH
`PRESSURE TREATED 4X4 BLOCKING UNDER DUCTS, LAID ON ROOF, WITH
GALVANIZED METAL STRAPS OVER DUCTS IS AN ACCEPTABLE ALTERNATE
DUCT ROOF SUPPORT DETAIL
I,
RGLLRJGY FYR 4YI1 J I RUL, I W 11
Subject to compliance with all regulations
of State and Local Codes
City of Camel ((��
`�vmlUllDnrJnDIJ�L
DATE: 07/22/19
SECURE SIDE GRILLE
TO DUCT COLLAR AT
AS PER MANUFACTURER
RECOMMENDATIONS -
SUPPLY SIDE GRILLE -�
11
iC!
SUPPLY DUCT
CEILING
DRYER ENCLOSURE
(SEE ARCHITECTURE
AND MECHANICAL OPL-300 LINT COLLECTOR
PLAN)
DUCT EACH DRYER WALL CAP WITH NO
COLLAR BIRDSCREEN
SEPARATELY TO AVOID A FIRE
1 HAZARD DUE TO LINT 5
COLLECTING IN THE MANIFOLD _N ARCHITECTURAL LOUVER
PROVIDE MOD
INTERLOCKED
DRYER WITH DRYER
OPERATION
FINISHED FLOOR
VENT
ING DETAIL
MVD
PAINTED TO
\DJACENT WALL
FLEXIBLE DUCT
MAIN EXHAUST OR RETURN
AIR FLOW
1/4W OR 4" 1102mm1 MIN.
BRANCH DUCT yl=L PROVIDE VOLUME
DAMPER
PLAN VIEW
EXHAUST OR RETURN BRANCH DUCTW
12
NOTESEVERAL DRYERS D UCT ED SEPARATE LV TO ONE LINT FILT ER
1. REFER TO MANUFACTURER'S RECOMMENDATION & INDIANA FUEL GAS CODE SECTION 304.6.2 FOR COMBUSTION AIR
OPENING SIZES.
2. WHERE THE SOURCE OF CONTAMINANT IS LOCATED WITHIN 10' HORIZONTALLY OF COMBUSTION INTAKE OPENING,
SUCH OPENING SHALL BE LOCATED A MINIMUM OF T BELOW THE CONTAMINANT SOURCE AS PER IMC 401.4.1.
3. THE INSTALLATION OF DRYER EXHAUST DUCTS SHALL COMPLY W ITH THE MANUFACTURER'S INSTALLATION
INSTRUCTIONS AND IMC 504.7.
4. GC SHALL INSTALL DRYER INA SEPARATE ENCLOSURE. GC SHALL COORDINATE WITH MANUFACTURER FOR
ENCLOSURE AND CLEARANCE REQUIREMENT FOR DRYER.
APPLY DUCT MASTIC, 3M 900,
OR EQUAL TO JOINTS,
ALL AROUND, BOTH SIDES. -
VERTICAL GUILLOTINE
DAMPER W/U.L. RATING
18 GA. STEEL SLEEVE t
FASTEN TO F.D. FRAME
W/l/2"WELDS6"O.C.
DUCTWORK SEE
FOR SIZES PLANS
ACCESS PANEL SCHEDULE
DUCT WIDTH
PANEL SIZE
UPTO 12"
6"x12"
13"TO 24"
12"x12'
25"80VER
1B'X18"
ELEVATION \
HORIZONTAL FIRE DAMPER AT WALL
INSTALL FIRE DAMPER IN ACCORDANCE
WITH N.F.P.A. PAMPHLET NO. 90 A.
15 rlrcLJMIVI
NOT TO SCALE
SYSTEM NUMBER-W-L-7161
FEBRUARY 07, 2007
F RATING -1 AND 2 HE
T RATING -0 HR
"A" FRAME FIRE DAMPER RATED FOR
1-112 HRS. UNLESS NOTED OTHERWISE.
FIRE DAMPER ACCESS DOOR.
LABEL "FIRE DAMPER ACCESS".
SEE SCHEDULE FOR SIZE.
PACK 112" TO III
W/FIBROUS MATERIAL AND
SEAL W/NON HARDENING SEALER.
RETAINING ANGLES TO BE 2" X 2" X 1/8".
SECURE TO 18 GA. SLEEVE ini
WELDS AT 6" O.C. DO NOT SECURE
ANGLES TO WALL. PROVIDE ANGLES ON
ALL FOUR SIDES OF SLEEVE, AT BOTH
SIDES OF WALL.
FIRE RATED WALL
Bill
SECTION A -A
1. WALL ASSEMBLY - THE 1 OR 2 HR FIRE -RATED GYPSUM BOARD/STUD SHAFT WALL ASSEMBLY SHALL BE CONSTRUCTED
OF THE MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL U400 OR V400 SERIES WALL AND PARTITION
DESIGNS IN THE UL FIRE RESISTANCE DIRECTORYAND SHALL INCORPORATE THE FOLLOWING CONSTRUCTION FEATURES:
A. STEEL STUDS -"C-H"OR "C-T" SHAPED STUDS, MIN 2-1/2 IN. (64 MM) WIDE BY 1-1/2 IN. (38 MM) DEEP, FABRICATED FROM
MIN NO. 25 GAUGE (0.6 MM THICK) GALV STEEL, SPACED MAX 241N. IS 10 MM) OC.
B. GYPSUM BOARD' -1 IN. (25 MM) THICK, 24 IN. (610 MM) WIDE GYPSUM LINER PANELS INSTALLED VERTICALLY. MAX DIAM OF
CIRCULAR CUTOUT IN GYPSUM LINER PANEL IS 6IN. (152 MM).
C. GYPSUM BOARD' -1/2IN. OR 518 IN. (13 OR 16 MM) THICK, 48 IN. (1.2 M) WIDE GYPSUM BOARDS. THE GYPSUM BOARD TYPE,
THICKNESS,NUMBER OF LAVERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL
WALL AND PARTITION DESIGN. MAX DIAM OF CIRCULAR CUTOUT IN GYPSUM BOARD IS 6 IN. (152 MM). THE HOURLY F RATING OF
THE FIRESTOP SYSTEM IS EQUAL TO THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED.
2. STEEL DUCT- NOM 5 IN. (127 MM) DIAM (OR SMALLER) NO. 30 GAUGE (OR HEAVIER) GALV STEEL DUCT INSTALLED
CONCENTRICALLY OR ECCENTRICALLY WITHIN OPENING. ANNULAR SPACE BETWEEN DUCT AND PERIPHERY OF OPENING TO BE
MIN 0 IN. (0 MM, POINT CONTACT) TO MAX 1 IN. (25 MM). DUCT TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY.
3. FILL, VOID OR CAVITY MATERIALS' -CAULK OR SEALANT- MIN 1 IN. (25 MM) THICKNESS OF FILL MATERIAL APPLIED
WITHIN THE GYPSUM BOARD LINER PANEL FLUSH WITH THE FACES OF THE LINER PANEL. MIN 581N. (16 MM) THICKNESS
OF FILL MATERIAL APPLIED WITHIN THE GYPSUM BOARD ANNULUS, FLUSH WITH THE FINISHED SIDE OF THE WALL. MIN 112
IN. (13 MM) DIAM BEAD OF CAULKAPPLIED TO THE PENETRANT/GYPSUM BOARD INTERFACE AT THE POINT CONTACT
LOCATION ON THE FINISHED SIDE OF THE WALL.
3M COMPANY - CP25WB+ Caulk or FB-3000 WT Sealant
INDICATES SUCH PRODUCTS SHALL BEAR THE UL OR CUL CERTIFICATION MARK FOR
JURISDICTIONS EMPLOYING THE UL OR CUL CERTIFICATION RESPECTIVELY.
fd4" OA / EX DUCT THROUGH RATED WALL DETAIL
9 NOT TO SCALE
SYSTEM NUMBER-C-AJ-7076
OCTOBER 14, 2009
F RATING -2 HR
T RATING -0 HR
v SECTION A -A
1. FLOOR OR WALL ASSEMBLY -MIN 4-1/2 IN. (114 MM) THICK REINFORCED LIGHTWEIGHT OR
NORMAL WEIGHT (100-150 PCF OR 1600 2400 KG/M3) CONCRETE. FLOOR ASSEMBLY MAY ALSO BE
CONSTRUCTED OF ANY MIN 6 IN. THICK UL CLASSIFIED HOLLOW -CORE PRECAST CONCRETE UNITS'.
WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS'. MAX AREA OF
OPENING 640 SO IN. (4129 CM2) WITH A MAX DIMENSION OF 321N. (812 MM). MAX AREA OF IN FLOORS
CONSTRUCTED OF HOLLOW -CORE CONCRETE IS 49 SQ IN. (316 CM2 WITH A MAX DIMENSION OF 71N.
(178 MM).SEE CONCRETE BLOCKS (CAZT) AND PRECAST CONCRETE UNITS (CFTV) CATEGORIES IN
FIRE RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS.
2. STEEL DUCT - NOM 30 BY 18 IN. (762 BY 457 MM) (OR SMALLER) STEEL DUCT TO BE INSTALLED
CONCENTRICALLY OR ECCENTRICALLY WITHIN OPENING. THE DUCT SHALL BE CONSTRUCTED AND
REINFORCED IN ACCORDANCE WITH SMACNA CONSTRUCTION STANDARDS. ANNULAR SPACE
BETWEEN DUCT AND PERIPHERY OF OPENING SHALL BE SHALL BE MIN O IN.(POINT CONTACT) TO
MAX 21N. (51 MM). DUCT TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL
ASSEMBLY.
3. FIRESTOP SYSTEM - THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING:
A. PACKING MATERIAL - MIN 3 IN. (76 MM) THICKNESS OF MIN 4 PCF OR 64111 MINERAL WOOL
BATT INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM. PACKING MATERIAL TO
BE RECESSED FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL AS REQUIRED
TO ACCOMMODATE THE REQUIRED THICKNESS OF FILL MATERIAL. IN FLOORS CONSTRUCTED OF
HOLLOW -CORE CONCRETE, PACKING MATERIAL TO BE RECESSED FROM TOP AND BOTTOM
SURFACES OF FLOOR AS REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF FILL
MATERIAL.
Al. FORMING MATERIAL' -AS AN ALTERNATE TO THE PACKING MATERIAL IN ITEM M, NOM 41N. (102
MM) WIDE STRIPS OF MIN 1/21N (13 MM) THICK COMPRESSIBLE MAT TO BE STACKED TO A
THICKNESS GREATER THAN THE WIDTH OF THE ANNULAR SPACE AND COMPRESSION -FITTED,
EDGE -FIRST, TO FILL THE ANNULAR SPACE TO A MIN 4 IN. (102 MM) DEPTH. TOP OF FORMING
MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL
AS NECESSARY TO ACCOMMODATE THE REQUIRED THICKNESS OF CAULK FILL MATERIAL. IN
FLOORS CONSTRUCTED OF HOLLOW -CORE CONCRETE, FORMING MATERIAL TO BE RECESSED
FROM TOP AND BOTTOM SURFACES OF FLOOR AS REQUIRED TO ACCOMMODATE THE REQUIRED
THICKNESS OF FILL MATERIAL. 3M COMPANY - FIRE BARRIER PACKING MATERIAL.
B. FILL, VOID OR CAVITY MATERIALS' -CAULK OR SEALANT - MIN 1/21N. (13 MM) THICKNESS OF
CAULKAPPLIED WITHIN THE ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR WITH BOTH
SURFACES OF WALL. IN FLOORS CONSTRUCTED OF HOLLOW -CORE CONCRETE, MIN 1/21N. (13 MM)
THICKNESS OF CAULK APPLIED WITHIN THE ANNULUS, FLUSH WITH TOP AND BOTTOM SURFACES OF
FLOOR. MIN 1141N. (6 MM) DIAM BEAD OF CAULK APPLIED TO THE DUCT/CONCRETE INTERFACE AT
THE POINT CONTACT LOCATION ON THE TOP SURFACE OF FLOOR OR BOTH SURFACES OF WALL OR
HOLLOW -CORE CONCRETE. 3M COMPANY - IC 151 CP 25WB+CAULK, OR FB-3000 WT SEALAN.
C. RETAINING ANGLES - MIN 16 GA GALV STEEL ANGLES SIZED TO LAP DUCT A MIN OF 2 IN. (51 MM)
AND LAP PERIPHERY OF OPENING A MIN OF 1 IN. (25 MM). ANGLES ATTACHED TO ALL FOUR SIDES
OF STEEL DUCT ON TOP SURFACE OF FLOOR OR BOTH SURFACES OF WALL WITH NO. 10 (OR
LARGER) STEEL SHEET METAL SCREWS SPACED A MAX 1 IN. (25 MM) FROM EACH END AND MAX 6 IN.
(152 MM) OC.
' INDICATES SUCH PRODUCTS SHALL BEAR THE UL OR CUL CERTIFICATION MARK FOR
JURISDICTIONS EMPLOYING THE UL OR CUL CERTIFICATION RESPECTIVELY.
RATED FLOOR/WALL PENETRATION DETAIL
IV „ter r�cnuv
CLEARANCE REQUIREMENT
FOR CONDENSING UNITS
(DIMENSION A)
WIDTH OF EQUIP.
(INCHES)
CLEARANCE
(INCHES)
UPT024
14
25 TO 36
18
37 TO 48
24
49 TO 60
30
61&WIDER
48
BASE RAIL SYSTEM
(TYPICAL)
PROVIDE SPRING & NEOPRENE
ISOLATOR RAILS UNDER UNIT (TYP.)
HURRICANE STRAP
000
voJS
ROOF EQUIPMENT SUPPORT
ALL ROOF MOUNTED EQUIPMENT MUST ADHERE TO CURRENT
HURRICANE CODES REGARDING ROOF TIE-IN AND WIND RESISTANCE.
CONDENSING UNIT MOUNTING DETAIL
LV NOT NUSE
BAS E4
BASE4
2901 CLINT MOORE ROAD, #114
BOCA RATON, FLORIDA 33496
888.901.8008 wWw.base-4.corn
RICARDO J. MUNIZ-GUILLET, AIA
5453 NW 106TH DR
CORAL SPRINGS, FL 33076
MEP ENGINEER
GARRY VERMAAS PhD, PE
2183 S BERRYS CHAPEL ROAD
FRANKLIN, TN 37069
Seal:
H W VF
isi EHh
o.m
Oc.x
N
12
o AE
90 .
01I PNP.I
�g4RONAL E�`
DATE: 2019.03.04
GARRY VERMMS. PhD. PE
Owner:
THE WITNESS GROUP
600 ENTERPRISES
DRIVE
LEWIS CENTER,OH
513-623-9430
HOMEN,
SUITES BY HILTON
CARMEL, INDIANA
PROTOTYPE VERSION-V2.2 2016
REVISION: MAY 2016
ISSUE NO.
DELTA
I ISSUED DATE
I DESCRIPTION
1
MO
2019.03.04
ISSUED FOR
PERMIT
CURRENT ISSUE
ISSUED FOR PERMIT
CURRENT ISSUE DATE
2019.03.04
DRAWN BY
DIRT
CHECKED BY
GWV
PROJECT NO.
B4-134-1705
SHEET NAME
DETAILS-2
DRAWINGS NO.
M -102