HomeMy WebLinkAboutM-301 - SCHEDULESAIR CONDITIONING SPLIT
SYSTEM EQUIPMENT SCHEDULE
CONDENSING UNIT
NOMINAL
TOTAL
SENSIBLE
WEIGHT
LxWxH
CU TAG
MANUFACTURER BMODEL
COOLING
COOLING
VOLTAGE/PH
MCA
MOCP
FAN HP/FLA
EER
NOTES
TONNAGE
BTUH
BTUH
(LBS)
(IN)
CU-1
TRANE If4TTL6024
2B
21,940
19,514
208/1/60
13B
20B
0.083/0.54
13B
165
40x14x36
1TO6
CU-2
TRANE If 4TTR6060
5.0
52,713
40,292
20811160
32.0
50.0
0.20/1.05
12.0
327
38x34x46
1TO6
CU-3
TRANE/4TTI6048
4.0
44.522
34.750
208/1/60
24.0
40.0
0.20/1AIS
12.5
243
47xl8x36
1TO6
CU4
TRANS If 4TTR6030
2.5
27,215
23,622
208/1/60
17.0
25.0
0.126/0.64
14.0
184
32x3Ox36
1TO6
CU-5
TRANS/4TTL6048
4.0
44,522
34,750
208/1/60
24.0
40.0
0.20/1.18
12.5
243
47xi8x36
1TO6
AIR HANDLING UNIT
NOMINAL
TOTAL
MIN
MINCIA
ELECTRIC HEAT
WEIGHT
LxWxH
II
AHU TAG
MANUFACTURER B MODEL
EAT DBIWB
VOLTAGE/PWZ
MCA
MOCP
FAN HPIFLA
EER
NOTES
TONNAGE
CFM
INPUT(kW)
CIRCUIT
(LBS)
(IN)
AHU-1
TRANE/GAM5BOA24M
2.0
840
85
75.0/60.90
208I1I60
4.80
1
29.0
30.0
0.33/2.8
13.0
126
22x18x52
7, 8, 9, 11, 12,13
AHU-2
TRANE/GAM5BOC60M
5.0
1795
610
75.0/62.40
208/1/60
19.20
2
110.0
110.0
1.0/7.6
12.0
180
62x24x22
7, 8, 10, 11, 12,13
AHU-3
TRANE1GAM5BOC48M
4.0
1605
395
75.0/6Z80
20811160
9.60
1
58.0
60.0
0.75/6.0
12.5
176
24x22xfi2
7, 8, 9, 11, 12,13
AHU4
TRANE/GAM51301330M
2.5
1000
115
75.0/61.20
208W60
4.80
1
29.0
30.0
0.33/2.8
14.0
140
22x1
7, 8, 9, 11, 12,13
AHU-5
TRANE/GAM5B0C48M
4.0
1605
395
75.0/62.80
208/1/60
4.80
1
33.0
35.0
0.75/6.0
12.5
176
62x24x22
7, 8, 10, 11, 12,13
NOTES:
1. PROVIDE WITH THERMAL EXPANSION VALVES, LIQUID LINE FILTER DRYER AND MULTI -USE SERVICE VALVES. 9. VERTICAL INSTALLATION OF AHU.
2. PROVIDE COMPRESSOR WITH CRANKCASE HEATER AND MIN. 5-YEAR WARRANTY.
10. HORIZONTAL INSTALLATION OF AHU.
3. PROVIDE HIGH AND LOW PRESSURE CONTROL AND OVER TEMPERATURE PROTECTION.
11. PROVIDE 1"THROWAWAY, MIN. 30% EFF. FILTER AND VIBRATION ISOLATION FOR AHU.
4. PROVIDE WEATHERPROOF ELECTRIC CONTROLS AND SINGLE SIDE SERVICE ACCESS.
12. UNITS SHALL INCLUDE MICROPROCESSOR CONTROLS THAT MINIMIZE SUPPLEMENTAL
5. COORDINATE WITH MANUFACTURER FOR THE ALLOWED MAXIMUM LENGTH OF
HEAT USAGE DURING START-UP, SET-UP, AND
DEFROST CONDITIONS.
REFRIGERANT SUCTION AND LIQUID LINES PRIOR TO PURCHASE.
13, APPROVED EQUALS ARE ACCEPTABLE.
6. "CONTACT THE TRANE LODGING TEAM AT LODGING®TRANE.COM OR CALL I-800-2294178."
7. PROVIDE DISCONNECT/STARTER FOR A.H.U./CU. POWER TO FEED FROM CU DOWN TO AHU.
COORDINATE WITH ELECTRICAL CONTRACTOR PRIOR TO PURCHASING.
8. PROVIDE FACTORY PROGRAMMABLE THERMOSTAT TO MATCH CAPACITY STAGES.
PACKAGED TERMINAL AIR CONDITIONER SCHEDULE
SUPPLY - FAN DATA
COOLING
ELEC. AUXILIARYHEAT
ELEC. DATA
UNIT
AREA
EER
MANUFACTURER
REVERSE CYCLE
WEIGHT
Lx WH
NO,
LOCATION
SERVED
pry
TOTAL FAN
TOTAL
BMODEL NO.
HEAT (BTUH)
INPUT
OUTPUT
VOLT/PH
VOLT/PH
MOCP
(LBS)
(IN))
NOTES
CFM RPM
MBH
KW
MBH
PI
WALL
GUEST ROOM
72
4]0
BV
77
122
PREMAIRE&
61100
3.0
10.2
208V/10
208V/10
20
145
42xl4xl6
1T07
MFG
PTW0723H3G
PTAC-2
WALL
GUEST ROOM
24
470
BY
90
114
PREMAIRE&
8,100
3.0
10.2
20W110
20BV110
20
145
42xl4xl6
1TO7
MFG
PTW0923H3G
NOTES:
1. WALL CASE 8 ARCHITECTURAL LOUVER COORD. COLOR WITH ARCHITECT 5. CONDENSATE'SLINGER'
( )
2. ELECTRICAL CONNECTION KIT (208 VOLT) 6.SAUERMANN MINI INLINE CONDENSATE PUMP TO BE INSTALLED ON UNITS WHERE 1/8"MIN. SLOPE
3. CONDENSATE DRAIN, ROUTED IN MAIN DOWN WALL 8 EXTERIOR. CANNOT BE MAINTAINED TO DISPOSAL POINT. INSTALL PUMP CONCEALED IN UNIT.
4. WALL THERMOSTATS LOCATED PER ELECTRICAL S PROVIDE VERDANT/INCOMM BRAND WIRED 7. PROVIDE SLEEVE DRAIN KIT
TSYS
TSTAT.STANO-ALONE PTAC ENERGY MANAGEMENT SYSTEM.
AIR CONDITIONING MINI SPLIT EQUIPMENT SCHEDULE
OUTDOOR (CONDENSING) UNIT
NOMINAL
TOTAL
TOTAL
WEIGHT
WxDxH
TAG
MANUFACTURER& MODEL
OTY
COOLING
HEATING
FLA
VOLTAGE/PH
MCA
MOCP
SEER
NOTES
TONNAGE
(BTUH)
BTUH
(LBS)
(IN)
CCU-1
MITSUBISHI/PUY-Al2NKA7
1
1.0
12,000
-
0.5
208/10
11.0
30.0
20.6
92
32x12x24
ATOP
CCU-2
MITSUBISHI/PUZ-Al2NKA]
1
16
12,000
9,200
0.5
208/10
11.0
306
20A
93
32x12x24
ATOP
CCU3
MITSUBISHI I PUZ-Al2NKA7
1
2.0
24,000
15,700
0.4
208110
19.0
26.0
21.4
153
38x14x38
ATOP
INDOOR (AIR HANDLING) UNIT
TAG
MANUFACTURER& MODEL
QTY
NOMINAL
TOTAL
VOLTAGE/PH/Z
HEATING BTUH
( )
MCA
FAN FLA
SEER
WEIGHT
WxDxH
NOTES
TONNAGE
CFM
(LBS)
(IN)
DS-1
MITSUBISHI /PKA-Al2HA7
1
1.0
320-370425
208/1/60
-
1.0
0.33
20.8
29
3fix10x12
GTOJ
DS-2
MITSUBISHI/PKA-Al2HA7
1
1.0
320-370425
208/1/60
9,200
1.0
0.33
20.8
29
3fix10x12
GTOJ
DS-3
MITSUBISHI/PKA-A24KA7
1
2.0
635-705-775
208/1/60
15,700
1.0
0.36
21.4
4fi
46xl2xl6
GTOJ
CONDENSING UNIT ACCESSORIES: FAN COIL UNIT ACCESSORIES:
A. MOUNTING CURB E. CORROSION RESISTANT COIL (IN COSTAL AREAS) I. INDOOR UNIT MUST BE CONNECTED TO OUTDOOR UNIT. SEE OUTDOOR UNIT FOR DATA.
B. LOW AMBIENT COOLING TOO DEG F F. EXTENDED REFRIGERANT LINE KIT J. APPROVED EQUALS ARE ACCEPTABLE.
C COIL GUARDS G. INTEGRAL CONDENSATE PUMP K. FOR MITSUBISHI NATIONAL ACCOUNT PRICING CALL DAN PABST AT-608-6304371.
D. SERVICE VALVES H. WALL MOUNT TDAY PROGRAMABLE T-STAT (NO REMOTE)
POOL DEHUMIDIFICATION UNIT SCHEDULE
COOLONG
RETURN AIR
MOISTURE
AUXILLARY
ELECTRICAL
DATA
ESTIMATED
MARK
MANUFACTURER&
TOTALAIR
MINIMUM
SUPPLYAIR
CAPACITY
TEMPERATUR
REMOVAL
HEAT
RELATIVE
REFRIGERAN
MOTOR
SIZE
WEIGHT
MODEL NO.
FLOW(CFM)
O.A.(CFM)
E.S.P(IN H2O)
HE
MBH
E F
CAPACITY LBSIHR
CAPACITY (EDH)
HUMIDITY(%)
TYPE
HE
VOLTIPHIZ MCA MOCP
(LxWxH)
LBS
SERESCO
DHU-1
NE-004-PV-1-A3NT
2000
440
1B
2.2
53.3
82
23.7
17.5 kW
60
R410A
2.2
208/3/60
88
90
40x42x86
860
1202E5C2AE0
OUTDOOR (CONDENSING) UNIT FOR DHU
HEAT REJECTION
WEIGHT(LBS)
REMARKS
MARK
TYPE
FLA
MCA
MOCP
MOTOR HE
VOLTAGE/PWHZ
LxWxH
MBTUH
ACCU-1
SERESCO NC-B-1V-CUC-V
66.6
2.6
4.0
15.0
0.60
208/3(60
32x34x30
90
1
NOTE:
1.FURNISH W/MICROPROCESSOR CONTROLS AND SPACE TEMPERATURE AND HUMIDITY SENSORS. 4. COORDINATE INSTALLATION W/POOL EQUIPMENT CONTRACTOR.
2.UNIT TO BE FLOOR MOUNTED. 5.CONTACT SERESCO NATIONAL ACCOUNT SERVICES((613) 741-3603) FOR PRICING INSTALLATION INFORMATION.
3.PROVIDE OUTSIDE AIR CONNECTION.
ERV UNIT SCHEDULE
FAN COIL UNIT SCHEDULE
OUTDOOR UNIT
NOMINAL
TOTAL
TOTAL
TOTAL
WEIGHT
LXWXH
UNIT TAG
MANUFACTURERS MODEL
QTY
COOLING
HEATING
INPUT
VOLTAGE/PH
MCA
MOCP
SEER
NOTES
TONNAGE
(BTUH)
BTUH
(KW)
(LBS)
(IN)
ODU-1/2
MITSUBISHI/PUZ-Al2NKA7
2
1.0
12,000
8,700
1.03
208/10
11.0
30.0
21,1
93
32xl2x24
ATOP
INDOOR UNIT
NOMINAL
TOTAL
HEATPUMP
WEIGHT
WxDxH
UNIT TAG
MANUFACTURERS MODEL
QTY
TONNAGE
CFM
VOLTAGF/PH/Z
MCA
FAN MOTOR/FLA
SEER
(LBS)
(IN)
NOTES
HEATING (BTUH)
FCU-1/2
MITSUBISHI/PEAD-Al2AA7
2
1 1.0
342/415
208/1/60
1 8,700
1.45
85W/1.18
1 21.1
1 58
1 36x29x10
GTOI
CONDENSING UNIT ACCESSORIES:
FAN COIL UNIT ACCESSORIES:
A. MOUNTING CURB D.
SERVICE VALVES
G. INTEGRAL CONDENSATE PUMP
B. LOW AMBIENT COOLING TO 0 DEG F E.
CORROSION RESISTANT COIL (IN COSTAL AREAS)
H. WALL MOUNT 7-DAY PROGRAMABLE T-STAT (NO REMOTE)
C. COIL GUARDS F.
EXTENDED REFRIGERANT LINE KIT
I. INDOOR UNIT MUST BE CONNECTED TO OUTDOOR UNIT. SEE OUTDOOR UNIT FOR DATA.
J. FOR MITSUBISHI NATIONAL ACCOUNT PRICING CALL DAN PABST AT- 608-630-4371.
SUPPLY/EXHAUST FAN SCHEDULE
FAN
SERVICE
INSTALL
MANUF.&
CFM
MOTOR
I S.P.
HVI
VOLTS-
WEIGHT
NOTES
NO.
LOCATION
MODEL
SONES
PH
(LBS)
EF-1
INDOOR POOL
CEILING
COOK /GC-720
550
301W
0.125"
6.6
120-10
36
1,2,3&4
EF-2
ELEVATOR
ROOF
COOK/70CPV
1 450
1 0.158BHP
0.250"
-
120-10
164
1.2.3.5.6&7
NOTES:
1. BACKDRAFT DAMPER.
4. LOUVER MOUNT AT LEAST 10' ABOVE GRADE. PAINT TO MATCH EXTERIOR.
2. PREW IRED FAN SPEED CONTROLLER.
5. UNIT SHALL BEAR AN ENGRAVED ALUMINIUM NAMEPLATE.
3. FAN TO RUN CONTINUOUSLY. UNLESS OTHERWISE
NOTED. 6. MOTOR MOUNT SHALL BE MINIMUM 14 GAUGE STEEL.
7. THE FAN HOUSING SHALL HAVE AIR TIGHT LOCK SEAMS AND SHALL BE FIELD
ROTATBLE TO ANY ONE OF EIGHT DISCHARGE POSITIONS.
BOOSTER FAN SCHEDULE
MARK
QTY.
MANUFACTURER
MODEL NO.
CFM
AMP
W
VOLTS -PH
WEIGHT
ES.
BE
1
FANTECH
DBL4XL
190
0.54
64.8
120-10
10
UNIT HEATER SCHEDULE (ELECTRIC)
MARK
ANUFACTURER
MODELNO.
TYPE
CFM
CAP
RPM
EAT
AMP
KW
OLTS-PH
LX
REMARKS
(MBH)
NxH
LBS
CUH
REDD-I
AFA848D
cUMIPAUt
MOUNTED
175
16.56
600
65
23
4.8
208-10
14x4x20
26
1TO4
UH
REDD-I
FEP4620-3RA
SURFACE
MOUNTED
2954
-
65
21.1
7.6
208J0
58x9x18
85
1T04
NOTES:
1. BUILT-IN DISCONNECT
SWITCH. 3. BUILT-IN FAN DELAY SWITCH.
2. BUILT-IN THERMOSTAT.
4. APPROVED EQUALS PER SPECS.
POP VENT EXHAUST
SCHEDULE
MARK
QTY.
MANUFACTURER
MODEL NO.
APPLICATION PER
WEIGHT
SQ. FOOT
LBS.
ACTIVE VENTILATION
AV
4
PRODUCT INC
pV-12-CO2
225
4
GRILLE &DIFFUSER SCHEDULE
TAG
MANUFACTURER
MODEL
FRAME OR
BORDERTYPE
MODULE SIZE
DAMPER
MODELNO
FINISH
A
TITUS
TDC
LAY IN SURFACE
24x24
N/A
WHITE
B
TITUS
PAR
LAY IN SURFACE
24x24
NIA
WHITE
BRIE
TITUS
CT480
SEE PLANS
NIA
WHITE
TO
TITUS
CT-700
--
SEE PLANS
N/A
WHITE
CSICR
TITUS
272FL&3FL
SEE PLANS
N/A
WHITE
MS/MR
TITUS
ML-38/MLR-38
SEE PLANS
N/A
WHITE
D
AMERICAN ALDES
CSRB-WB-II
SEE PLANS
N/A
WHITE
Ei
I AMERICANALDES
CERB-CS-II
SEE PLANS
NIA
WHITE
E2
TITUS
MLR-38
SEE PLANS
N/A
WHITE
NOTES:
1. ALL CEILING DIFFUSERS ARE AWAY THROW UNLESS INDICATED OTHERWISE ON PLAN.
2. PROVIDE WITH MANUFACTURERS PLENUM.
GENERAL NOTES:
1. PROVIDE SWITCHES AT OPERABLE WINDOWS TO SHUT DOWN UNIT WHEN WINDOW IS OPEN.
2. PROVIDE MERV-8 PREFILTERS AND MERV-12 FINAL FILTERS ATALL AIR HANDLING UNITS.
3. PROVIDE INDOOR AIR HANDLING UNITS, FAN COILS, OR STANDARD PACKAGED ROOFTOP UNITS WITH CLOSED -CELL ELASTOMERIC INSULATION.
4. PROVIDE UV PROTECTIVE COATING ON ALL ELASTOMERIC PIPEMUCT INSULATION WHERE EXPOSED TO SUNLIGHT.
5. SMOKE DETECTORS SHALL BE INSTALLED IN DOWNSTREAM OF SUPPLYAIR SYSTEMS (IN THE SUPPLYAIR DUCT) WITH A DESIGN CAPACITY GREATER THAN
2,000 CFM (0.9111
6. MECHANICAL CONTRACTOR TO PROVIDE FINAL FILTER FOR MAKE-UP AIR UNITS AND AS PER HOTEL STANDARD REQUIREMENTS FOUND IN THE BRAND
STANDARD DESIGN MANUAL.
]. PROVIDE APPROVED BARRIERS FOR ALL EQUIPMENTS WHICH SUBJECTS TO MECHANICAL DAMAGE AS PER IMC 303.4.
SUPPLYAIR
ENERGYRECOVERYWHEEL
COOLING
GAS HEATING
ELECTRICAL
MARK
EXH.
MFG.B
BLOWER
MCA
MOCP
WEIGHT
LxW xH
NOTES
E'S'P'
SOPPY
EXHAUST
TOTAL
SENS.
IN
OUT
CFM
CFM
SUMMER EAT
WINTER EAT
EAT
LAT
EADB
LADB
VOLTSI PH
MODEL
(Hp)
(LBS)
(IN)
(IN.WG.)
CFM
CFM
(MBH)
(MBH)
(MBH)
(MBH)
ERV-1
3900
1 1.50
1 2900
3900
2900
83.0/74.5
-2.7
206.8
115.5
786/68.7
51.8/51.6
38.5
86.0
250.0
200.0
208/3/60
RVE40-41-30H-15S-1
5
92.5
110
3666
202x86x66
1TO13
ERV-2
4500
1 1.50
1 3800
4500
3800
83.0174.5
-2.7
228.9
131.3
77.8167.8
51.3r51.1
46.0
95.4
300.0
240.0
1 208/3160
IRVE-85-52-15H-17.5S-JI
5
1 98.3
1 125
1 5109
1224x98x76
1 TO 13
NOTES: (UNIT WILL SIZED BY GREENHECK REPRESENTATIVE
RELEASED FOR CONSTRUCTION INS.
Subject to compliance WA all regulations
of State and meal Codes
City of Camel ((��
�vm�' ilmnr)nD1J4L
x
DATE: 07/22/19
5. PHASE PROTECTION.
6. CONVENIENCE OUTLET.
7. UNIT TORUN CONTINUOUSLY.
8. INTEGRAL DISCONNECT.
9. COILGUARDS.
10. PROVIDE MANUAL SHUTDOWN SWITCH
FOR ERV'S NEAR FIRE ALARM PANEL.
11. CORROSION RESISTANT COATING ON COILS
(IN COASTAL AREAS).
12. PROVIDE FACTORY INSTALLED DUCT DETECTORS.
13. ENERGY WHEEL CASSETTE TO SLIDE OUT FOR SERVICIBILITY.
REFRIGERANT PIPE INSULATION THICKNESS
A. 1/2 INCH (13 MM) INSULATION FOR ONE INCH (25 MM) PIPE OUTSIDE DIAMETER AND SMALLER PIPE.
B. 3/41NCH (19 MM) INSULATION FOR 1-1/8 THROUGH 21NCH (28 THROUGH 50 MM) PIPE OUTSIDE DIAMETER PIPE.
C. ONE INCH (25 MM) INSULATION FOR 2-1/8 INCHES (53 MM) PIPE OUTSIDE DIAMETER AND LARGER PIPE (TWO LAYERS OF 12 INCH 13 MM).
D. ONE INCH (25 MM) INSULATION SHEET FOR FITTINGS AS RECOMMENDED BY MANUFACTURER.
BAS E4
BASE4
2901 CLINT MOORE ROAD, #114
BOCA RATON, FLORIDA 33496
888.901.8008 www.base-4.00m
RICARDO J. MUNIZ-GUILLET, AIA
5453 NW 106TH DR
CORAL SPRINGS, FL 33076
MEP ENGINEER
GARRY VERMAAS PhD, PE
2183 S BERRYS CHAPEL ROAD
FRANKLIN, TN 37069
Seal:
H W VF
QP��'\si EHh�
o'
m
N
1 12
o ATE
b
9O ...'1O
I j N.. ..
CBS TONAL El`
DATE: W180304
GI Wn0d S. PhD. PE
Owner:
�; yr
THE WITNESS GROUP
600 ENTERPRISES
DRIVE
LEWIS CENTER,OH
513-623-9430
E
suirss BY xiHOMLrox
CARMEL, INDIANA
PROTOTYPE VERSION-V2.22016
REVISION: MAY 2016
ISSUE NO.1
DELTA
I ISSUED DATE
I DESCRIPTION
1
MO
2019.03.04
ISSUED FOR
PERMIT
CURRENT ISSUE
ISSUED FOR PERMIT
CURRENT ISSUE DATE
2019.03.04
DRAWN BY
DIRT
CHECKED BY
GWV
PROJECT NO,
134-134-1705
SHEET NAME
SCHEDULES
DRAWINGS NO.