HomeMy WebLinkAboutL100TRAVEL DISTANCE = 122'-1"
AREA NOT IN CONTRACT
RELEASED FOR CONSTRUCTION
Subject to compliance with all mgulatims
of State and Local Codes
City d Camel
DATE: 08/02/19
ENLARGED LIFE SAFETY PLAN
0 4' 8' 16'
CODE SUMMARY
SCOPE OF WORK
OFFICE REMODEL OF PREVIOUSLY BUILT OUT OFFICE SPACE
PREVIOUS USE OF SPACE
BIUSINESSI
OCCUPANCY CLASSIFICATION
BIUSINESSI
CHANGE OF OCCUPANCY CLASS9
NO
TOTAL BUILDING AREA
32,209 SF/FLOOR
X
1 4 STORIES
=
128,836 SF
TOTAL PROJECT AREA
Emw
OCCUPANCY CALCULATIONS
NUMBER OF EXITS
2561 SF
SPACE TYPE
AREA
I SF PER OCCUPANT
OCCUPLOAD
GEN. OFFICE
2,561 SF
1 100
26
TOTAL OCCUPANTS IN PROJECT AREA 26
REQUIRED:I PROVIDED
SPRINKLER SYSTEM(YES/NO)
YES- EXISTING TO REMAIN
TOTAL AREA OF ACCESSORY USES
0 SF
TOTAL AREA ON THE FLOOR
32,209 SF
ACCESSORY AREA EXCEEDS 10%
NO
FIRE WALLS, AND/OR OCCUPANCY
SEPARATIONS (IF REQUIRED)
N/A
ASHRAE 90.1 SUMMARY
REQUIREMENTS WILL BE MET (SEE REFLECTED CEILING PLAN)
BUILT BEFORE 19788
NO
BUILDING CONSTRUCTION TYPE
II-B
Ep EXISTING ELECTRICAL PANEL LOCATION
EX EXISTING EXIT- BUILDING STAIR LOCATION
TIFF FIRE EXTINGUISHER
® EXITSIGN
11(1�® EMERGENCYLIGHT
— — — TRAVEL DISTANCE
OVERALL BUILDING
NOT TO SCALE
GENERAL NOTES
LI. REFER TO ARCHITECTURAL PLAN FOR WALL TYPE AND CONSTRUCTION
DETAILS.
E2. EXISTING COMMON CORRIDOR TO REMAIN. EXISTING EXIT SIGNS, FIRE
PULLS, FIRE EXTINGUISHERS, ALARM NOTIFICATION APPLIANCES TO
REMAIN. RELOCATE EXISTING EXIT SIGNS, FIRE PULLS, FIRE
EXTINGUISHERS AND ALARM NOTIFICATIONS AS REQUIRED TO MEET
ALL LOCAL AND STATE CODES.
LIFE SAFETY NOTES
I. PROVIDE EMERGENCY LIGHTING IN TENANT SPACE AS REQUIRED PER
NEMA AND IBC. EMERGENCY BATTERY PACKS OR LIGHTS
CONNECTED TO AN EMERGENCY POWER SOURCE ARE REQUIRED IF
THE SPACE CONTAINS 50 PERSONS OR MORE. FIXTURES SHOWN ON
PLAN ARE FOR REFERENCE ONLY.
2. PROVIDE ALARM NOTIFICATION APPLIANCES(HORNS/STROBES),
EMERGENCY SPEAKERS, SMOKE DETECTORS, FIRE PULLS, AND ANY
OTHER REQUIRED ALARM & DETECTION SYSTEMS AS NECESSARY TO
MEET ALL APPLICABLE CODES (INTERNATIONAL BUILDING CODE,
INTERNATIONAL FIRE CODE, NFPA). IN RECEPTION AREAS,
CONFERENCE ROOMS AND OTHER HIGH PROFILE AREAS WITHIN SUITE,
ALL LOCATIONS OF SUCH DEVICES MUST BE APPROVED BY SDI OR
TENANT P FOR TO INSTALLATION. FAILURE TO DO SO MAY RESULT IN
CONTRACTOR RELOCATING THESE ITEMS AT THEIR EXPENSE.
3. FIRE EXTINGUISHERS: CONTRACTOR TO ENSURE ALL NEW AND
EXISTING FIRE EXTINGUISHERS ARE INSTALLED ACCORDING TO NFPA
10. COORDINATE WITH OWNER/LANDLORD ON EXTINGUISHER TYPE
AND HOUSING. MAXIMUM TRAVEL DISTANCE OF 75 FEET FROM ANY
POINT TO A VISIBLE EXTINGUISHER.
4. FIRE PROTECTION WORK IS TO BE PROVIDED BY DESIGN/BUILD
SERVICES UNDER THE GENERAL CONTRACT. PROVIDE A COMPLETE,
WORKING SYSTEM. SCHOTT DESIGN, INC., IS NOT RESPONSIBLE FOR
THE DESIGN, INSTALLATION, OR RENOVATION OF THE FIRE SPRINKLER
SYSTEM.
5. THE FIRE PROTECTION CONTRACTOR SHALL GENERATE ALL REQUIRED
DRAWINGS, AND SHALL FILE THOSE DRAWINGS, AND RELATED
DOCUMENTS, WITH THE STATE AN D LOCAL AUTHORITIES HAVING
JURISDICTION OVER THE PROJECT.
NC
THIS DRAWING. AND THE IDEAS,
DESIGNS AND CONCEPTS CONTAINED
HEREIN. ARE THE EXCLUSIVE
INTELLECTUAL PROPERTY OF SCH07
DESIGN, INC., AND ARE NOT TO BE
USED OR REPRODUCED IN WHOLE, OR
IN PART, WITHOUT THE WRITTEN
CONSENT OF SCH OII DESIGN.
r
ISSUE
DATE
DESCRIPTION
06.17.19
REVIEW SET
06.19.19
PERMIT SET
PROJECT NUMBER
2018.479
2ND FLOOR
LIFE SAFETY
L 100