HomeMy WebLinkAboutE-0011 2 3 4 5
B
A
JOB NO.
D
C
ISSUED FOR:
PERMIT
RECORD
CONSTRUCTION
BID
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax 330.572.2102
2019190.32
PNC BANK - PENNWOOD OFFICE11405 NORTH PENNSYVANIA STREETCARMEL, IN 4603206/19/19
06/19/19
-
-REV. DATE DESCRIPTIONDESIGNERPROJECT MANAGER Drawing Name: O:\2019\2019190\32 Carmel (Penn) Office IN\dwg\ConstructionDocuments\Architectural\050_201919032_E-001.dwg
June 19, 2019 - ecurryE-001ELECTRICAL DETAILSMAR LT
1. ALL WORK SHALL COMPLY WITH THE NATIONAL ELECTRICAL CODE (N.E.C.) AND APPLICABLE CODES, ORDINANCES, RULES,
REGULATIONS, AND LAWS OF ALL LOCAL, MUNICIPAL, OR STATE AUTHORITIES HAVING JURISDICTION.
2. COORDINATE WORK WITH THAT OF ALL OTHER TRADES AFFECTING OR EFFECTED BY WORK OF THIS SECTION. COOPERATE
WITH SUCH TRADES TO ASSURE PROGRESS OF ALL WORK UNDER THIS CONTRACT.
3. ALL OUTLETS AND SWITCHES SHALL BE AS SPECIFIED IN SPECIFICATION SECTION 262726.
4. MOUNT RECEPTACLES WITH THE LONG AXIS VERTICAL EXCEPT WHERE SPECIFICALLY NOTED ON THE PLANS TO BE
MOUNTED WITH THE LONG AXIS HORIZONTAL.
5. ALL RECEPTACLES SHALL BE WIRED USING 2#12 & 1#12(G). MINIMUM CONDUIT SIZE (WHERE UTILIZED) SHALL BE 3/4". REFER
TO SPECIFCATION SECTION 16110 FOR ALLOWABLE USES FOR MC CABLE. NUMERAL INDICATES CIRCUIT NUMBER.
6. SEE ARCHITECTURAL PLANS AND ELEVATIONS FOR EXACT LOCATIONS OF ALL DATA/POWER RECEPTACLES AND LIGHTING.
7. ALL PENETRATIONS OF WALLS, PARTITIONS, CHASES, SHAFTS, FLOORS, AND ROOF SHALL BE COMPLETELY SEALED.
PENETRATIONS THROUGH FIRE RATED WALLS AND FLOORS SHALL BE SEALED TO PROVIDE A FIRE RATING EQUAL TO OR
GREATER THAN THAT OF THE WALL OR FLOOR PENETRATED.
8. E.C. SHALL PROVIDE TYPEWRITTEN DIRECTORIES FOR ALL PANELS. PANEL DIRECTORIES SHALL INCLUDE MONTH AND YEAR IN
LOWER RIGHT CORNER.
9. E.C. SHALL PROVIDE OWNER WITH COMPLETE AND ACCURATE 'RECORD' DOCUMENTS FOR THE WORK PROVIDED/INSTALLED.
10. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ALL ELECTRICAL WORK AS SHOWN ON THE DRAWINGS AND
THESE SPECIFICATIONS HEREIN. WORK INCLUDES THE FOLLOWING UNDERSTANDINGS.
a.CONTRACT DRAWINGS ARE DIAGRAMMATIC AND INTENDED TO OUTLINE BASIC ENGINEERING AND SYSTEMS DESIGN,
THEREFORE DO NOT SHOW DETAILS AND ACCESSORIES. IT IS THE CONTRACTOR'S RESPONSIBILITY FOR FURNISHING
AND INSTALLING ALL SUCH ITEMS NECESSARY TO PROVIDE COMPLETE, OPERATIVE AND PROPERLY INSTALLED
SYSTEMS TO THE OWNER. THE CONTRACTOR SHALL BE REQUIRED TO OBTAIN A WRITTEN RESPONSE FROM THE
ENGINEER PRIOR TO BID FOR ANY DOCUMENT CLARIFICATION.
b.THE DRAWINGS SHOW THE INTENDED LOCATION OF THE EQUIPMENT, HOWEVER, THE CONTRACTOR SHALL BE
RESPONSIBLE FOR ANY MINOR ADJUSTMENTS OR RELOCATIONS NECESSARY DUE TO CHOICE OF EQUIPMENT AND
COORDINATION CONFLICTS. ALL EQUIPMENT RELOCATIONS MUST BE SUBMITTED TO THE ARCHITECT/ENGINEER FOR
APPROVAL.
c.THE PROJECT CONTRACT DRAWINGS, SPECIFICATION, AND OTHER RELATED DOCUMENTS ARE COMPLIMENTARY. ITEMS
REQUIRED BY ONE SHALL DESIGNATE REQUIREMENT BY THE OTHER, WHETHER EXPLICITLY STATED OR NOT. WHERE
DOCUMENTS CONFLICT, THE WORK OF THE MORE STRINGENT NATURE SHALL BE REQUIRED.
d.THE CONTRACTOR SHALL PROVIDE ALL NECESSARY ASSOCIATED ELECTRICAL EQUIPMENT, DISCONNECTS, STARTERS,
WIRE, CONDUIT ETC. FOR ALL MECHANICAL/PLUMBING SYSTEMS. REFER TO MECHANICAL/ PLUMBING PLANS FOR
SCOPE OF WORK.
e.THE CONTRACTOR SHALL FURNISH AND INSTALL ALL NECESSARY ASSOCIATED EQUIPMENT FOR A COMPLETE AND
OPERATIONAL SECURITY/ CCTV SYSTEM.
11. CONTRACTOR SHALL VISIT THE SITE AND INSPECT THE PREMISES IN ORDER TO BE FAMILIAR WITH THE EXISTING CONDITIONS
WHICH MAY IN ANY WAY AFFECT THE INSTALLATION OF THE WORK SPECIFIED HEREIN. NO ADDITIONAL COMPENSATION WILL
BE ALLOWED FOR THE CONTRACTORS FAILURE TO COMPLY HEREIN.
12. PROCURE AND PAY ALL PERMITS AND LICENSES REQUIRED FOR WORK UNDER THIS SECTION.
13. ALL EQUIPMENT AND MATERIALS INSTALLED ON THIS PROJECT AS WELL AS THE COMPLETE ELECTRICAL INSTALLATION SHALL
COMPLY WITH ALL THE REQUIREMENTS OF THE OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA) WHEREVER
THEY APPLY.
14. ELECTRICAL CONTRACTOR SHALL ASSUME FULL RESPONSIBILITY FOR LAYING OUT HIS WORK AND FOR ANY DAMAGE CAUSED
TO THE OWNER OR OTHER CONTRACTORS BY IMPROPER LOCATION OR CARRYING OUT HIS WORK.
15. ELECTRICAL CONTRACTOR SHALL COORDINATE HIS WORK WITH OTHER TRADES AND IN SUCH MANNER AS TO NOT
INTERFERE WITH OTHER WORK. THE CONTRACTOR SHALL COORDINATE WITH OTHER TRADES IN ORDER TO HAVE ALL PIPES,
CONDUITS, ETC., INSTALLED ON THE DRAWINGS AND SPECIFICATIONS.
16. THE WORK INCLUDES THE FURNISHING OF MATERIALS, TOOLS, EQUIPMENT, TRANSPORTATION SERVICES, SCAFFOLDING,
SUPERVISION, LABOR, AND OTHER ITEMS WHICH MAY NOT BE MENTIONED, BUT ARE NECESSARY FOR THE FABRICATION,
INSTALLATION, OR APPLICATION AND COMPLETION OF THE ELECTRICAL WORK AS SHOWN ON THE DRAWINGS AND
SPECIFICATIONS.
17. CONDUCTORS #4 AWG AND SMALLER SHALL BE TYPE THWN/THHN. CONDUCTORS LARGER THAN #4 AWG SHALL BE TYPE
XHHW, ALL RATED 600 VOLTS, COPPER CONDUCTORS. ALL CONDUCTORS SHALL BE STRANDED COPPER, WHERE AVAILABLE.
ALL CONDUIT SHALL BE EMT 3/4" MINIMUM UNLESS OTHERWISE NOTED.
18. MINIMUM CONDUCTOR SIZE SHALL BE #12 AWG FOR POWER AND #14 AWG STRANDED FOR CONTROL.
19. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CLEARANCES IN THE FIELD.
20. CONTRACTOR SHALL FOLLOW OWNER'S SAFETY RULES AND SHALL BROOM CLEAN DAILY. ALL DEBRIS SHALL BE REMOVED
FROM THE BUILDING AND GROUNDS.
21. NO COMBUSTIBLE MATERIALS WILL BE PERMITTED IN CEILING PLENUMS.
22. ALL RECEPTACLES TO BE INSTALLED BY ELECTRICAL CONTRACTOR SHALL BE INSTALLED AT +18" A.F.F. UNLESS OTHERWISE
SPECIFIED ON PLANS.
23. ALL EXPOSED CABLES INSTALLED IN AIR PLENUM CEILINGS SHALL HAVE PLENUM RATED INSULATION. IT SHALL BE THE
RESPONSIBILITY OF THIS CONTRACTOR TO COORDINATE WITH OTHER TRADES TO VERIFY THAT ANY CABLES INSTALLED IN
AIR PLENUM CEILINGS BY THOSE TRADES IS RATED FOR USE IN PLENUM CEILINGS.
24. ALL LIGHTING FIXTURES SHALL BE WIRED USING 2#12 & 1#12(G). MINIMUM CONDUIT SIZE (WHERE UTILIZED) SHALL BE 3/4".
REFER TO SPECIFICATION SECTION 260210.00 FOP ALLOWABLE USES FOR MC CABLE.
25. GROUNDING OF THE NON-CURRENT CARRYING METALLIC PARTS OF ALL ELECTRICAL EQUIPMENT AND ENCLOSURES
INCLUDING CONDUITS, SUPPORTS, CABINETS, TRANSFORMERS, MOTOR FRAMES. SWITCHGEAR ENCLOSURES, CONTROL
PANELS, ETC. WHICH ARE INSTALLED OR CONNECTED UNDER THIS CONTRACT, SHALL BE PROPERLY CONNECTED TO THE
GROUNDING SYSTEM PER N.E.C. ARTICLE 250, REGARDLESS OF WHETHER OR NOT THESE CONNECTIONS ARE SHOWN ON THE
DRAWINGS.
26. ELECTRICAL CONTRACTOR SHALL ASSUME FULL RESPONSIBILITY TO ACQUIRE THE LATEST AND CURRENT SET OF
CONSTRUCTION DOCUMENTS. THESE DOCUMENTS TO INCLUDE ALL GENERAL BULLETINS AND BULLETINS ADDRESSING
SPECIFIC CHANGES TO THE PROJECT.
27. VERIFY EXISTING GROUND IS COMPLIANT WITH NEC & LOCAL JURISDICTION. INFORM CONSTRUCTION MANAGER AND
ENGINEER OF ANY ISSUES.
28. CONTRACTOR SHALL COORDINATE WITH POWER COMPANY, DETERMINE ARC FAULT, AND PROVIDE LABELS PER N.E.C.
PROJECT GENERAL NOTES
SYMBOLS AND ABBREVIATIONS LIST
NOTES:
T
X/Y/Z
S
M
WP
DUPLEX RECEPTACLE GROUND FAULT
DUPLEX RECEPTACLE GROUND FAULT
INTERRUPTER TYPE. INSTALL IN
TELECOMMUNICATIONS
INTERRUPTER TYPE
WEATHERPROOF HOUSING
G
G
LINE VOLTAGE VACANCY SENSOR SWITCH
DUPLEX RECEPTACLE
RECEPTACLES
VSS
NEW PANELBOARD - SURFACE
DISCONNECT SWITCH. 'X' INDICATES
SWITCH SIZE. 'Y' INDICATES NUMBER
OF POLES. 'Z' INDICATES FUSE SIZE
(NF = NON-FUSED)
MOTOR STARTING SWITCH
MOTOR
M
TRANSFORMER
JUNCTION BOX
IG
DENOTATIONS & ABBREVIATIONS
C
AFF
A
E
D
CU
G
FF
UT
UE
NTS
V
WP
W
AUDIO/VISUAL
TV
S2
VC
POWER
PHOTOCELLPC
SINGLE POLE SWITCHS
LIGHTING
TELEVISION OUTLET WITH 3/4"
RACEWAY AND WIRE BACK TO
SPEAKER - WALL MOUNTED
SPEAKER - CEILING MOUNTED
VOLUME CONTROL
TERMINATION AREA
GROUND FAULT INTERRUPTER
UNDERGROUND TELEPHONE
WEATHERPROOF
WALL MOUNTED
VOLTS
ISOLATED GROUND
NOT TO SCALE
UNDERGROUND ELECTRIC
DOUBLE DEVICE
EMERGENCY
FLUSH FLOOR MOUNTED
CONDUIT
COPPER
ABOVE FINISHED FLOOR
AMPERE
S1
ALL BULLETINS) PRIOR TO STARTING CONSTRUCTION.
SET OF CONSTRUCTION DOCUMENTS (INCLUDING
ELECTRICAL CONTRACTOR TO CONTACT GENERAL
CONTRACTOR FOR VERIFICATION OF THE LATEST
SOME OF THESE SYMBOLS MAY NOT BE USED UNDER
THIS PROJECT. SEE THE CONTRACTOR NOTES FOR
ADDITIONAL REQUIREMENTS.
MISCELLANEOUS
#12 AWG BRANCH CIRCUIT WIRING WITH 3/4"
BRANCH CIRCUIT WIRING - #10 AWG IN 3/4" CONDUIT
BRANCH CIRCUIT WIRING IN 1" CONDUIT - UNDER FLOOR
CONDUIT CONCEALED IN WALLS OR ABOVE CEILING
HOME RUN BACK TO PANEL
CONDUIT TURNED DOWN
CONDUIT TURNED UP
EWC ELECTRIC WATER COOLER
DOWNLIGHT WITH EMERGENCY BATTERY BALLAST
EDGE LIT EXIT SIGN - DIRECTIONAL
WALL MOUNTED LIGHT FIXTURE
ARROWS AS INDICATED ON DRAWINGS
LIGHTING FIXTURE - SEE FIXTURE
SCHEDULE FOR MORE INFORMATION
SEE FIXTURE SCHEDULE FOR MORE
EMERGENCY LIGHTING FIXTURE WITH
EMERGENCY BATTERY BALLAST -
INFORMATION
DOWNLIGHT
('D' - DENOTES DOUBLE FACED)
DOUBLE DUPLEX RECEPTACLE
DOOR CHIMEB
INFORMATION OUTLET. OUTLET SHALL HAVE 4 PAIR, CATEGORY 6A PLENUM CABLE(S),
QUANTITY AS SHOWN, TERMINATED ON THE DATA PATCH PANELS IN THE DATA RACK BY
VENDOR. REFER TO SPECIFICATION SECTION 270500 FOR INSULATION COLORS.
J
FIRE RATED POKE-THRU
ATM
STACK
EXT
CCTV CAMERA IN ENVIRONMENTAL ENCLOSURE TO VIEW DRIVE UP STACKING FURNISH AND INSTALL TYPE "N" AND "G"
CABLES TO THE DVR CONTROL IN THE MDF.
ATM CAMERA ON ATM VENDOR SUPPLIED MOUNT FURNISH AND INSTALL TYPE "N" AND "G" CABLES TO THE DVR CONTROL IN THE
MDF.
CCTV CAMERA IN A DOME HOUSING FURNISH AND INSTALL TYPE "N" AND "G" CABLES TO THE DVR CONTROL IN THE MDF.
CCTV CAMERA IN ENVIRONMENTAL ENCLOSURE WITH LENS. FURNISH AND INSTALL TYPE "N" AND "G" CABLES TO THE DVR
CONTROL IN THE MDF.
INTERIOR CCTV CAMERA WITH 2.8-12 mm LENS ON A STICK MOUNT. FURNISH AND INSTALL TYPE "N" AND "G" CABLES TO THE
DVR CONTROL IN THE MDF.
SAFE
ALARM
IR
DC
BACK-UP
ALARM
ATM
ALARM
ATM ALARM. FURNISH AND INSTALL 18 GAUGE, 8 CONDUCTOR, STRANDED CABLE. CABLE SHALL
BE RUN IN A 3/4" CONDUIT FROM THE ATM TO THE ALARM CONTROL PANEL (TYPE "H" CABLE).
DMP ALARM CONTROL. 120 VAC CIRCUIT SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR. PRESIDER SHALL BE
MOUNTED IN THE TELECOMMUNICATIONS RACK. FIELD VERIFY EXACT LOCATION WITH THE OWNER.
BACK-UP ALARM. CELLULAR BACK-UP SYSTEM DEPENDING ON SITE AVAILABILITY. 120 VAC CIRCUIT SHALL BE
PROVIDED BY THE ELECTRICAL CONTRACTOR. FIELD VERIFY EXACT LOCATION WITH THE OWNER.
DIGITAL VIDEO RECORDER. DVR SHALL BE MOUNTED IN PNC SUPPLIED TELECOMMUNICATIONS
RACK UNLESS OTHERWISE NOTED.
HEIGHT CCTV CAMERA HEIGHT STRIP MOUNTED IN MULLION FURNISH AND INSTALL TYPE "N" AND "G" CABLES TO THE DVR
CONTROL IN THE MDF.
CAMERA POWER SUPPLYPS
VIDEO MONITOR REQUIRES A RG 59U COAXIAL CABLE TO THE DVR CONTROL AND A 120 VAC CIRCUIT PROVIDED BY ELECTRICAL
CONTRACTOR (SEE E-101).
HOLD UP BUTTON. FURNISH AND INSTALL 22 GAUGE, 4 CONDUCTOR, STRANDED CABLE (TYPE "C" CABLE).
MONEY CLIP. FURNISH AND INSTALL 22 GAUGE, 4 CONDUCTOR, STRANDED CABLE (TYPE "C" CABLE).
HOLD UP INDICATOR. FURNISH AND INSTALL 22 GAUGE, 8 CONDUCTOR, STRANDED CABLE (TYPE "D" CABLE).
MOTION SENSOR, CORNER OR CEILING MOUNT, FURNISH AND INSTALL 22 GAUGE, 4 CONDUCTOR, STRANDED CABLE (TYPE "C" CABLE).
SAFE ALARM. FURNISH AND INSTALL 18 GAUGE, 8 CONDUCTOR, STRANDED CABLE. CABLE SHALL BE RUN IN A 3/4" CONDUIT
FROM THE SAFE TO THE ALARM CONTROL PANEL (TYPE "H" CABLE).
ALARM KEYPAD. FURNISH AND INSTALL (2) 22 GAUGE, 8 CONDUCTOR, STRANDED CABLES (TYPE "D" CABLE).
DOR CONTACT. FURNISH AND INSTALL 22 GAUGE, 4 CONDUCTOR, STRANDED CABLE (TYPE "C" CABLE). CABLING SHALL
BE RUN IN WINDOW MULLIONS AND FRAMING DURING CONSTRUCTION TO ENSURE ACCESS.
VIDEO MONITOR. REQUIRES (2) RG 59U COAXIAL CABLES TO THE DVR CONTROL AND A 120 VAC CIRCUIT PROVIDED
BY PNC BANK ELECTRICAL CONTRACTOR.
STK
ELECTRIC DOOR CONTROL MAGNETIC LOCK. FURNISHED WITH DOOR HARDWARE, INSTALLED AND WIRED BY E.C. TO ATM
VESTIBULE DOOR ACCESS CONTROL PANEL. WIRING PER CONTROL PANEL MANUFACTURER'S REQUIREMENTS.
ATM VESTIBULE CARD READER. FURNISHED WITH DOOR ACCESS CONTROL PANEL AND INSTALLED & WIRED BY E.C.
WIRING PER CONTROL PANEL MANUFACTURER'S REQUIREMENTS.CR
EXT IP
Axis
IPHEIGHT
Anixter
IP CAMERAS. FURNISH AND INSTALL "CAT6A" CABLES TO THE DVR
CONTROL IN THE MDF.
IR
(NOTE: ALL SYMBOLS MAY NOT BE USED)
SECURITY
CABLE TYPE DESCRIPTION CABLE PART #
C
D
H
G
N
BELDEN 6502UE
BELDEN 6506UE
BELDEN 6306UE
BELDEN 6300UE
4 CONDUCTOR #22 GAUGE, STRANDED CABLE IN 3/4"
CONDUIT
8 CONDUCTOR #22 GAUGE, STRANDED CABLE IN
3/4" CONDUIT
8 CONDUCTOR #18 GAUGE, STRANDED CABLE IN 3/4"
CONDUIT
2 CONDUCTOR #18 GAUGE, STRANDED, TWISTED PAIR
CABLE* IN 3/4" CONDUIT
RG-59 COAXIAL CABLE*
IN 3/4"C.
*NOTE: COMBINATION COAX AND POWER
CABLE MAY BE USED TO REPLACE "N" AND "G"
TYPE CABLES
NOTE:
CABLES SHOWN HERE ARE FOR BIDDING PURPOSES
ONLY. E.C. SHALL VERIFY EXACT CABLING
REQUIREMENTS WITH SECURITY VENDOR PRIOR TO
ROUGH-IN.
SECURITY CABLING SCHEDULE
LUTRON LIGHTING CONTROLS
LPP
PW SQS SLINE VOLTAGE TIME SWITCHTS
ESN
VS
DS
LUTRON "PowPak" DIMMING MODULE. REFER TO DETAIL 2/E-603 FOR
WIRING. MOUNT ABOVE ACCESSIBLE CEILING WHERE SHOWN ON
E-111.
LUTRON "Energi Savr Node" MODULE. REFER TO DETAIL 1/E-603 FOR
WIRING. MOUNT WHERE SHOWN ON E-111.
LUTRON "PICO" WIRELESS WALL SWITCH. REFER TO DETAIL 1/E-603
FOR ADDITIONAL INFORMATION.
LUTRON MULTI-BUTTON QSN SYSTEM WALL SWITCH. REFER TO DETAIL 1/E-603
FOR ADDITIONAL INFORMATION.
LUTRON WIRELESS VACANCY SENSOR. REFER TO DETAIL 1/E-603 FOR
ADDITIONAL INFORMATION.
LUTRON WIRELESS DAYLIGHT SENSOR. REFER TO DETAIL 1/E-603 FOR
ADDITIONAL INFORMATION.
QS LUTRON 'QS' SENSOR MODULE. REFER TO DETAIL 1/E-603 FOR
ADDITIONAL INFORMATION.
1. SYMBOLS ARE NOT SHOWN TO SCALE
2. ALL SYSMBOLS MAY NOT BE USED
PWC SLUTRON "PICO" WIRED WALL SWITCH. REFER TO DETAIL 1/E-603 FOR
ADDITIONAL INFORMATION.
IP DOME
WIRELESS PENDANTSWP
DS LUTRON WIRED DAYLIGHT SENSOR. REFER TO DETAIL 1/E-603 FOR
ADDITIONAL INFORMATION.
W
TRIPLEX RECEPTACLE
06/20/2019
07/23/19
William Hohlt