1 POWER AND SYSTEMS PLAN
1/4"=1'-0"
1 2 3 4 5
B
A
JOB NO.
D
C
ISSUED FOR:
PERMIT
RECORD
CONSTRUCTION
BID
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax 330.572.2102
2019190.32
PNC BANK - PENNWOOD OFFICE11405 NORTH PENNSYVANIA STREETCARMEL, IN 4603206/19/19
06/19/19
-
-
PLAN KEYNOTES GENERAL NOTES #
A. MOUNT RECEPTACLES WITH THE LONG DIMENSION OF THE DEVICE VERTICAL AND THE U-SHAPED
GROUND POSITION AT BOTTOM EXCEPT WHERE SPECIFICALLY NOTED ON THE PLANS TO BE MOUNTED
WITH THE LONG DIMENSION OF THE DEVICE HORIZONTAL (WITH THE U-SHAPED GROUND POSITION ON
THE RIGHT). MOUNT ADJACENT SYSTEMS DEVICES TO MATCH RECEPTACLE MOUNTING CONFIGURATION.
B. REFER TO E-501 FOR ONE-LINE DIAGRAM.REV. DATE DESCRIPTIONDESIGNERPROJECT MANAGER Drawing Name: O:\2019\2019190\32 Carmel (Penn) Office IN\dwg\ConstructionDocuments\Architectural\050_201919032_E-101.dwg
June 19, 2019 - ecurryE-101POWER AND SYSTEMS PLANMAR AJR
LEGEND
UNOCCUPIED FUTURE TENANT, NOT IN
SCOPE.
N MATCH LINE - SEE 1/E-101.1
CONFERENCE
104
LOBBY
101
VESTIBULE
ENTRY
100
LOBBY 2
103
VESTIBULE 2
ENTRY
102
ROOM
NEW MOTHER'S
105
CENTER
SERVICE
106
OFFICE
107
OFFICE
108
OFFICE
109
OFFICE
110
OFFICE
111
OFFICE
112
OPEN AREA
116
TEAM ROOM
117
HALL
118
1. PROVIDE RECEPTACLE FOR REFRIGERATOR AT HEIGHT INDICATED.
2. FLUSH FLOOR BOX. REFER TO FLOOR BOX SCHEDULEON E-501 FOR ADDITIONAL INFORMATION.
3. RECEPTACLE FOR PRINTER/COPIER (MFD) - 120V-1ɸ, NEMA 5-20R.
4. NEW MOTHERS ROOM DOOR CARD/BIOMETRIC READER ACCESS CONTROL PANEL FURNISHED BY
PNC AND INSTALLED AND WIRED BY E.C. PER MANUFACTURER'S REQUIREMENTS. THE COMPLETE
OPERATING CARD/BIOMETRIC ACCESS SYSTEM SHALL INCLUDE INSTALLATION AND WIRING OF
ALL REQUIRED SYSTEM COMPONENTS, SOME OF WHICH MAY BE SUPPLIED BY OTHER TRADES.
COORDINATE WITH THE G.C. TO VERIFY WHAT OTHER SYSTEM COMPONENTS WILL BE SUPPLIED
BY OTHERS. COORDINATE WITH PNC FOR FINAL LOCATION OF ALL SYSTEM COMPONENTS PRIOR
TO ROUGH-IN OF ANY WORK FOR THIS SYSTEM. REFER TO DWG. E-602 DETAIL #7 FOR MORE
INFORMATION.
5. 1"PVC. FROM POWER SECTION OF FLOOR BOX . STUB CONDUIT UP IN WALL, TRANSITION TO EMT,
AND RUN CONDUIT OVERHEAD TO PANEL INDICATED.
6. THE DIMENSIONED LOCATION OF THE FLOOR BOX IS PROVIDED FOR BIDDING PURPOSES ONLY.
THE E.C. SHALL VERIFY THE EXACT LOCATION OF THE FLOOR BOX WITH PNC AND FURNITURE
VENDOR PRIOR TO ROUGH-IN.
7. PROVIDE TELEVISION BOX FOR POWER,AND DATA ARLINGTON INDUSTRIES CATALOG #TVBS505,
2-GANG STEEL. PROVIDE (1) 20A. SURGE PROTECTED DUPLEX RECEPTACLE FOR POWER,
LEVITON #7380-W IN ONE GANG AND DATA IN THE OTHER GANG. PROVIDE BARRIER BETWEEN
SECTIONS. BOX SHALL BE FLUSH MOUNTED. COORDINATE MOUNTING HEIGHTS WITH
ELEVATIONS ON SHEETS I-201 THRU I-203. VERIFY WITH PNC PRIOR TO ROUGH-IN.
8. CENTERLINE SHOWN IS THE CENTERLINE OF THE TV MOUNTING BRACKET. DIMENSIONS SHOWN
ARE CRITICAL FOR THE PROPER CLEARANCES FOR THE TV POWER AND DATA CABLES.
9. PROVIDE (1) 1"C. BETWEEN POWER SECTION OF FLOOR BOX AND TELEVISION BOX REFERENCED
IN KEY NOTE 11. STUB CONDUIT UP IN WALL UP TO TELEVISION BOX AND FROM TELEVISION BOX
RUN CONDUIT OVERHEAD TO PANEL INDICATED.
10. PROVIDE (1) 1-1/4" PVC CONDUIT BETWEEN SYSTEMS SECTION OF FLOOR BOX AND TELEVISION
BOX REFERENCED IN KEY NOTE 11. STUB CONDUIT UP IN WALL, TRANSITION TO EMT AND ROUTE
TO TELEVISION BOX, AND THEN FROM TELEVISION BOX. STUB UP ABOVE CEILING WITH
INSULATING BUSHING ON END OF CONDUIT.
11. 1-1/4" PVC. FROM SYSTEMS SECTION OF FLOOR BOX. STUB UP IN WALL, TRANSITION TO EMT AND
ROUTE CONDUIT UP IN WALL TO ABOVE LAY-IN CEILING. TERMINATE CONDUIT ABOVE CEILING
WITH AN INSULATING BUSHING.
12. FIELD VERIFY LOCATION OF EACH EXISTING PANEL AND TRANSFORMER IN THIS AREA.
13. OPEN OFFICE RECEPTACLES AND DATA FLOOR BOX SHALL BE LOCATED IN TRENCH. DEVICES
ARE FED THROUGH CONDUITS RUNNING IN TRENCH. COORDINATE EXACT LOCATIONS WITH
FURNITURE VENDOR PRIOR TO ROUGH-IN. REFER TO ARCH. DRAWINGS FOR EXACT LOCATION OF
TRENCH.
14. RECEPTACLES AND DATA PORTS SHALL BE COORDINATED WITH FURNITURE VENDOR. DEVICES
SHALL BE EASILY ACCESSIBLE . COORDINATE EXACT LOCATION WITH VENDOR PRIOR TO
ROUGH-IN.
15. LUTRON "EcoSystem" "Energi Savr Node" (ESN), A & B. MOUNT DEVICES ONE ABOVE THE OTHER ON
WALL ABOVE "EcoSystem" TIMECLOCK REFERENCED IN NOTE 16. REFER TO DETAIL 1/E-601 FOR
WIRING REQUIREMENTS.
16. LUTRON "EcoSystem" TIMECLOCK. SURFACE MOUNT IN A STANDARD 4-GANG BOX BELOW ESN-A &
B AT 48" A.F.F. REFER TO DETAIL 1/E-601 FOR WIRING REQUIREMENTS.