June 19, 2019 - ecurryE-501ELECTRICAL SCHEDULES &ONE-LINE DIAGRAMMAR LT
A. CONTRACTOR IS RESPONSIBLE FOR LOADING ON ALL PANELS AND FEEDERS PER THE N.E.C.
CONTRACTOR SHALL KEEP CIRCUIT CONTINUITY TO DEVICES TO REMAIN. E.C. SHALL VERIFY
THAT ALL LOADS PLACED ON EXISTING PANELS DO NOT EXCEED THE MAXIMUM LOADING
REQUIREMENT PER THE LATEST EDITION OF THE NEC. NOTIFY A/E IF OVERLOAD IS POSSIBLE.
PRIOR TO START OF WORK.
LOADING NOTES
1. CONTRACTOR IS RESPONSIBLE FOR LOADING ON ALL PANELS AND FEEDERS PER THE N.E.C.
CONTRACTOR SHALL KEEP CIRCUIT CONTINUITY TO DEVICES TO REMAIN. E.C. SHALL VERIFY THAT
ALL LOADS PLACED ON EXISTING PANELS AND FEEDERS DO NOT EXCEED THE MAXIMUM LOADING
REQUIREMENT PER THE LATEST EDITION OF THE NEC. NOTIFY A/E IF OVERLOAD IS POSSIBLE.
2. E.C. SHALL VERIFY THAT THE NEW LOADS DO NOT OVERLOAD EXISTING UTILITY SERVICE, THE
CONTRACTOR IS ALSO RESPONSIBLE TO CALCULATE AND VERIFY THAT ALL UPSTREAM PANELS AND
FEEDERS ARE NOT OVERLOADED DUE TO THE NEW LOADS. CONTRACTOR SHALL NOTIFY ENGINEER
OF LOAD CALCULATIONS PRIOR TO COMMENCING WORK.
3. ELECTRICAL CONTRACTOR SHALL VERIFY EXISTING SERVICE, PANELS, AND FEEDERS IN FIELD
BEFORE START OF WORK, AND INFORM ENGINEER OF FINDINGS.
PANEL SCHEDULE GENERAL NOTES:
LIGHTING FIXTURE SCHEDULE NOTES
1. LIGHT FIXTURES ARE PNC FURNISHED THRU VILLA LIGHTING.
REFER TO THE MATRIX OF RESPONSIBILITY ON TS-001. VILLA
LIGHTING CONTACTS: MATT KAESTNER, 314-633-0456,
matt.kaestner@villalighting.com OR, DAN PUELLMANN,
314-633-0472, dan.puellmann@villalighting.com. THE E.C. IS
RESPONSIBLE FOR CONTACTING VILLA LIGHTING TO OBTAIN
PRICING TO INCLUDE IN HIS BID. PNC WILL ORDER LIGHT
FIXTURES.
2. E.C. SHALL PROVIDE VILLA LIGHTING WITH SHIPPING
ADDRESS TO CONTRACTOR'S WAREHOUSE. LIGHT FIXTURES
SHALL NOT BE SHIPPED DIRECTLY TO SITE.
EXISTING
METER
EXISTING
CT CABINET
M
TO EXISTING POWER Co.
TRANSFORMER
1. THIS IS A FULLY RATED SYSTEM. MAIN BREAKER AND FEEDER BREAKERS IN SWITCHGEAR ARE BE
RATED FOR 65,000 AMPS (MIN.) INTERRUPTING CURRENT (SYMMETRICAL). PROVIDE IDENTIFICATION
LABELING FOR ALL FULLY RATED EQUIPMENT AS REQUIRED IN NEC 110.22 & 240.86.
2. THE E.C. SHALL COORDINATE WITH THE POWER Co. AND PROVIDE ARC-FLASH AND FAULT CURRENT
CALCULATIONS AND LABELS ON ELECTRICAL EQUIPMENT PER NEC 110.16, NEC 110.24 AND LOCAL
JURISDICTION REQUIREMENTS.
3. EXISTING SERVICE ENTRANCE GROUNDING TO REMAIN. E.C. SHALL VERIFY BONDING AND GROUND
SYSTEM IS COMPLIANT WITH THE NEC. AND LOCAL JURISDICTIONS. INFORM CONSTRUCTION
MANAGER WITH ANY ISSUES.
4. EXISTING FEEDERS TO REMAIN AS IS. UNLESS NOTED OTHERWISE.
5. E.C. SHALL INSPECT EXISTING CIRCUIT BREAKER SHOWN ON DRAWING TO BE REUSED AS
SUFFICIENT FOR SERVICE. IF ANY IMPERFECTIONS ARE FOUND IN THE ENCLOSURE, REPAIR OR
REPLACE AS REQUIRED. CIRCUIT BREAKER MUST RETAIN THEIR UL LISTING IN ACCORDANCE WITH
NEC COMPLIANCE.
6. EXISTING GROUNDING TO REMAIN.
EXISTING TO REMAIN
LEGEND
ONE-LINE DIAGRAM NOTES
1 PARTIAL EXISTING ONE-LINE DIAGRAM
N.T.S.
ONLY PANELS WITH ADDITIONAL NEW LOADS ARE SHOWN. BESIDES VERIFYING THAT
THE NEW LOADS DO NOT OVERLOAD EXISTING PANELS, THE CONTRACTOR IS ALSO
RESPONSIBLE TO CALCULATE AND VERIFY THAT ALL UPSTREAM PANELS AND FEEDERS
ARE NOT OVERLOADED DUE TO THE NEW LOADS.
EXIST.
PANEL
"E"
400A. MLO
277Y/480V,
3Ø, 4W
2
EXIST
PANEL
"F"
400A. MLO
277Y/480V,
3Ø, 4W
2
EXIST. 75 KVA
TRANSFORMER
208Y/120V-3ɸ-4W
SECONDARY
480V-3ɸ-3W
PRIMARY
6
EXIST.
PANEL
"D"
225A. MCB
120Y/208V,
3Ø, 4W
2
EXIST.
PANEL
"C"
100A. MLO
120Y/208V,
3Ø, 4W
2
EXISTING
400A-3P
TO REMAIN.
1 2
5
EXISTING LANDLORD'S SWTICHGEAR MAIN DISTRIBUTION,
FULLY RATED 65KAIC, 480Y/277V-3ɸ-4W, 1200AMP MCB,
LANDLORD MAIN ELECTRICAL ROOM
NEUT. BUS
GND. BUS
3
TRANSFORMER FED
FROM EXSIT.
100A/3P CIRCUIT
BREAKER IN EXIST.
PANEL 'E'
208V-3ɸ-4W
SECONDARY
4
T-1
4
4
4
CONTRACTOR IS RESPONSIBLE FOR LOADING ON ALL PANELS AND FEEDERS PER THE
N.E.C. CONTRACTOR SHALL KEEP CIRCUIT CONTINUITY TO DEVICES TO REMAIN. E.C.
SHALL VERIFY THAT ALL LOADS PLACED ON EXISTING PANELS AND FEEDERS DO NOT
EXCEED THE MAXIMUM LOADING REQUIREMENT PER THE LATEST EDITION OF THE NEC.
NOTIFY A/E IF OVERLOAD IS POSSIBLE.
ONE LINE DIAGRAM SHOWN FOR REFERENCE ONLY TO SHOW GENERAL
ARRANGEMENT OF PANELS. E.C. SHALL FIELD VERIFY ALL FEEDERS AND
ARRANGEMENT OF PANELS IN FIELD PRIOR TO BID. NOTIFY A/E OF ANY
DISCREPANCIES THAT WOULD PROHIBIT COMPLETION OF WORK.
EXISTING MAIN SWITCHGEAR POSITION GIVEN FOR GENERAL ARRANGEMENT OF
CIRCUITS AND FEEDERS. EXISTING MAIN CIRCUIT BREAKER AND OR FUSES TO BE
REUSED TO SERVE NEW/EXISTING PNC PANELBOARDS. E.C. SHALL VERIFY AVAILABLE
CIRCUITS AFTER DEMOLITION AND REUSE FOR NEW/EXISTING PNC PANELBOARDS.
PROVIDE TYPED UPDATED PANEL DIRECTORIES AFTER NEW WORK IS COMPLETE.
CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO SUBMITTING
FINAL BIDS. CONTRACTOR SHALL CAREFULLY COORDINATE NEW WORK AND
DEMOLITION WITH ALL OTHER DISCIPLINES AND EXISTING CONDITIONS.