PNC BANK - PENNWOOD OFFICE11405 NORTH PENNSYVANIA STREETCARMEL, IN 4603206/19/19
06/19/19
-
-REV. DATE DESCRIPTIONDESIGNERPROJECT MANAGER Drawing Name: O:\2019\2019190\32 Carmel (Penn) Office IN\dwg\ConstructionDocuments\Architectural\050_201919032_E-601.dwg
June 19, 2019 - ecurryE-601LIGHTING CONTROL DETAILSMAR LT
QSGR-TC-3S-WH-CPN5825
QS TIMECLOCK
4 GANG BACKBOX
LOCATE IN I.T./ELEC. RM. 102
ADJACENT TO ESN-A & ESN-B
QSE-CI-AP-D
ENERGI SAVR NODE
PROGRAMMING INTERFACE
LOCATE IN I.T./ELEC. RM. 102
APPLE IPOD TOUCH
OR IPHONE MOBILE
DIGITAL DEVICE
®
®
C-ESN-SETUP KIT
WIRELESS ROUTER
E
Q-LINK 1
277/120V: P1-2
QSN-4T16-S ENERGI SAVR NODE QS
(ESN)WITH (4) 0-10V CHANNELS AND(1) QS
COMMUNICATIONS LINK
ZONE 1: 0-10V DIMMING TO SINGLE OFFICES, OPEN AREA
OFFICES, TEAM ROOM AND CONFERENCE ROOM, TYPES
'L01' & 'L15'.
LUTRON
QSM2-4W-C
QUANTUM SENSOR MODULE (QSM)
WITH WIRED & WIRELESS INPUTS
LOCATE IN I.T. / ELEC RM 102
SYMBOL ON PLAN -
120V: C-1
QSN-4S16-S ENERGI SAVR NODE QS (ESN)WITH (4)
SWITCHED OUTPUTS, AND(1) QS
COMMUNICATIONS LINK
ZONE 5: XXXX
120V: D-22
Q-LINK 1 Q-LINK 1 Q-LINK 1
ESN-B
LOCATE IN LOCATE IN
I.T. / ELEC RM 102
WIRING NOTES:
QS LINK WIRING AS REQUIRED BY CONTROL LINK LENGTH
(SEE CHART BELOW):
CONTROL LINK LENGTH WIRE GAUGE AVAILABLE FROM LUTRON IN
ONE CABLE:
LESS THAN 500FT (153M)
POWER (TERMINALS 1&2):
1 PAIR 18 AWG (1.0MM²)
GRX-CBL-346S
or
GRX-PCBL-346S
DATA (TERMINALS 3&4):
1 PAIR 22 AWG (0.5MM²),
TWISTED AND SHIELDED*
500ft (153m) to 2000ft (610m)**
POWER (TERMINALS 1&2):
1 PAIR 12 AWG (1.0MM²)
GRX-CBL-46LDATA (TERMINALS 3&4):
1 PAIR 22 AWG (0.5MM²),
TWISTED AND SHIELDED*
E
2#12AWG,1#12(G)
CAT5E OR BETTER CABLE FOR DEDICATED LUTRON
NETWORK TERMINATED WITH RJ45 CONNECTORS (TO
BE PROVIDED BY OTHERS). 328 FEET (100M) MAXIMUM
RUN.
0-10V SIGNAL OR LV CONTROL: 2#18AWG
WIRING LEGEND
QS
1. ALL LUTRON LIGHTING CONTROL SYSTEM COMPONENTS ARE PNC FURNISHED THRU VILLA LIGHTING, EXCEPT FOR THE LOW VOLTAGE
CABLES, WHICH SHALL BE BY THE E.C. REFER TO THE MATRIX OF RESPONSIBILITY ON TS-001 FOR VENDOR INFORMATION. VILLA
LIGHTING CONTACTS: MATT KAESTNER, 314-633-0456, matt.kaestner@villalighting.com OR, DAN PUELLMANN, 314-633-0472,
dan.puellmann@villalighting.com. E.C. IS RESPONSIBLE FOR CONTACTING VILLA LIGHTING TO PLACE ORDER.
2. THE QS CONTROL LINK HAS A FREE WIRING TOPOLOGY (DAISY CHAIN, T-TAP, ETC). THE SYSTEM WIRING ILLUSTRATED BY THIS
DIAGRAM HAS BEEN LAID OUT TO ENSURE APPROPRIATE POWER TO EACH DEVICE. IF, FOR ANY REASON, THE SYSTEM IS TO BE WIRED
DIFFERENTLY THAN WHAT IS SHOWN, CONFIRM ALL DEVICE POWER REQUIREMENTS ARE MET.
3. INSTALLATION OF LIGHTING CONTROL COMPONENTS SHALL COMPLY WITH MANUFACTURERS INSTRUCTIONS AND REQUIREMENTS.
GENERAL LIGHTING CONTROL SYSTEM NOTES
PJ2-2BRL-GWG-L01 434 MHZ PICO WIRELESS 2
BUTTON CONTROL WITH RAISE/LOWER WITH
CW-1-WH CLARO WALLPLATE.
SYMBOL ON PLAN -
LRF2-OCR2B-P-WH 434MHZ WIRELESS
OCCUPANCY/VACANCY SENSOR. DEVICE IS
SURFACE-MOUNTED AND BATTERY POWERED. DOES NOT
REQUIRE POWER FEED.
SYMBOL ON PLAN -
RF
RF
LRF2-DCRB-P-WH 434MHZ WIRELESS DAYLIGHT SENSOR.
DEVICE IS SURFACE-MOUNTED AND BATTERY POWERED.
DOES NOT REQUIRE POWER FEED.
SYMBOL ON PLAN -
RF
SWITCHED
POWER
(5A MAX)
0-10V DIM
(60 mA MAX)
'POWPAK' DIMMING MODULE
WITH 0-10 V CONTROL
RMJ-8T-DV-B
RF
VS
DS
LPPSYMBOL ON PLAN -
PWS(OCCURS IN FLEX 104/105/106 ONLY)
NOTES:
1. REFER TO DETAIL 1/E-602 FOR WIRING LEGEND AND LIGHTING CONTROL
SYSTEM GENERAL NOTES.
2. TYPICAL FOR THE FOLLOWING ROOMS: COLLABORATIVE 104, FLEX RMS
105,106,107, BREAK RM 109, CASH ROOM 110 AND OFF STAGE 114.
PX-2B-GWH-I01 PICO WIRED 2 BUTTON CONTROL WITH CW-1-WH CLARO
WALLPLATE, LOCATE IN OPEN AREA. SWITCH SHALL OVERRIDE ALL
NETWORKED INTERIOR LIGHTS IN OPEN AREA (ESN-A ZONE 1).
SYMBOL ON PLAN -
PWCS
H N
LOAD
TS
1:00
D
A
L
O
VSS
6 TIMER SWITCH WIRING DIAGRAM
N.T.S.4 AND NIGHT LIGHT WIRING DIAGRAM
CONTROLLED COMBINATION EMERGENCY
N.T.S. 3 SENSOR WIRING DIAGRAM
WALL MOUNTED VACANCY
N.T.S.
2 LIGHTING CONTROL DIAGRAM
LUTRON INDIVIDUAL ROOM
N.T.S.
1 LUTRON LIGHTING CONTROL SYSTEM WIRING DIAGRAM
N.T.S.
NOTE:
EXHAUST FAN (ZONE 5) SHALL BE PROGRAMMED
FOR TIME OF DAY CONTROL. COORDINATE
SCHEDULE WITH PNC.
5 LIGHT WIRING DIAGRAM
CONTROLLED EMERGENCY
N.T.S.
ZONE 6: XXXXZONE 1: SWITCHED POWER TO SINGLE OFFICES, OPEN
AREA OFFICES, TEAM ROOM AND CONFERENCE ROOM,
TYPES 'L01' & 'L15'.
ZONES 2, 3 AND 4 ARE
SPARE ZONES ZONE 7 & 8 IS A
SPARE ZONE
120V: CIRCUIT #
VARIES SEE E-110
120V: C-3
ESN-A
LOCATE IN
I.T./ELEC. RM. 102
120V: D-24
RF 434 MHZ PICO WIRELESS 2 BUTTON CONTROL WITH
CW-1-WH CLARO WALLPLATE. LOCATE SWITCH IN
IT/DATA/ELECTRICAL 101. SWITCH SHALL OVERRIDE
EXTERIOR SIGN (ESN-B, ZONE 6).
SYMBOL ON PLAN -
PJ2-2B-GWG-L01
QSS
120V: D-24