HomeMy WebLinkAboutE-6021 2 3 4 5
B
A
JOB NO.
D
C
ISSUED FOR:
PERMIT
RECORD
CONSTRUCTION
BID
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax 330.572.2102
2019190.32
PNC BANK - PENNWOOD OFFICE11405 NORTH PENNSYVANIA STREETCARMEL, IN 4603206/19/19
06/19/19
-
-REV. DATE DESCRIPTIONDESIGNERPROJECT MANAGER Drawing Name: O:\2019\2019190\32 Carmel (Penn) Office IN\dwg\ConstructionDocuments\Architectural\050_201919032_E-602.dwg
June 19, 2019 - ecurryE-602ELECTRICAL DETAILSMAR LT
IDENTIFY EACH CABLE SEGMENT AT
SUBMIT LISTING OF NAMEPLATES FOR APPROVAL.
CABLE MARKERS-PANDUIT SELF LAMINATING TYPE PSWM.
LAMINATED NAMEPLATE-SIMILIAR TO ABOVE-SEE DETAIL.
3.
2.
1.
NOTES:
EACH END.
BOX #-OUTLET
"001-D2"
"001-V1"
"015-TV"
"001-D1"
INDICATE THUS.
EXAMPLE:
VC
70V
ALL SPEAKER AND VOLUME
CONTROL WIRE IS TO BE
WPW #25224WT OR EQUIV.
18G/2C TWISTED PLENUM
LOCATION TO BE
DETERMINED BY PNC
1. ALL CABLING RUNS SHALL BE ESTIMATED AT 200' FOR BIDDING
PURPOSES. CONSTRUCTION DRAWINGS SHALL BE ISSUED WITH FINAL
LOCATIONS AT A LATER DATE.
2. CONTRACTOR SHALL FURNISH AND INSTALL AV CABLING ONLY.
EQUIPMENT AND TERMINATIONS PROVIDED BY OTHERS UNDER A
SEPARATE CONTRACT.
3. ALL ROUGH-INS FOR VOLUME CONTROLS SHALL BE ADJACENT TO LIGHT
SWITCHES.
4. TAP SPEAKERS IN LOBBY 101, CHECK DESK 108 AND CONCIERGE 111 AT
4W. EACH AND SPEAKERS IN FLEX OFFICES AT 1W. EACH.
(6) ATLAS SD72W SPKRS IN LOBBY 101,
CHECK DESK 108 AND CONCIERGE 111
VC
ATLAS
AT10
FUTURE MUSIC
SOURCE
(1) ATLAS SD72W SPKR IN FLEX 106.
VC
VC
PASO MUDMA230
AMPLIFIER
9 10 11 12
DVR
2 13 11
11
11
11
11
11
11
13 16
9
1
3
3
414
5
12
12
15
6
7
8
6
10
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
RACK FRONT VIEW
TELECOMMUNICATIONS DATA RACK
GENERAL NOTES
1. ADD (1) ADDITIONAL HORIZONTAL WIRE MANAGER FOR EACH NETWORK SWITCH.
2. AT BRANCHES WITH MORE THAN 44 DATA DROP LOCATIONS, (2) ADDITIONAL PATCH PANELS
WILL BE ADDED AFTER EACH 48 PORT PATCH PANEL.
TELECOMMUNICATIONS DATA RACK
NUMBERED NOTES
BRANCH 24 PORT ANALOG EXTENSION PANEL,
HUBBELL 25 PORT PATCH PANEL #P5E22BUE.
BRANCH A PATCH PANELS, HUBBELL 48 PORT PATCH
PANEL #HP648.
BRANCH CISCO 2960 POE SWITCH.
2900 SERIES ROUTER.
BRANCH OUT OF BAND ROUTER & BACKUP ROUTER.
HUBBELL 10 OUTLET POWER STRIP #HPWPWR.
BRANCH DIGITAL MERCHANDISING PC(S) &
TIC DUAL WRITE PC(S).
BRANCH DVR.
HUBBELL 84" FLOOR MOUNT DATA RACK
#HPW84RR19.
HUBBELL VERTICAL WIRE MANAGER #VS76.
INSTALL ON WALL SIDE OF RACK.
HUBBELL 2 U HORIZONTAL WIRE MANAGERS
#HC219CE3N.
HUBBELL CANTILEVERED SHELF #MCCCS19.
HUBBELL REAR CABLE ORGANIZER BAR #ECMBR3
(1 PER HORIZONTAL CABLING PATCH PANEL,
REAR OF RACK)
25 PAIR VOICE CABLE WITH AMPHENAL MALE
CONNECTOR.
66 BLOCK IS AT THE DEMARC AND CONNECTS TO #1
ON THE RACK VIA A 25 PAIR CAT5E CABLE.
BRANCH B PATCH PANELS, HUBBELL 48 PORT
PATCH PANEL #HP648.
9 10 11 12
1
134 2
3 3
5
(1) CAT5E
6
7
8
6
1
2
3
4
5
6
7
8
9
10
11
12
13
INCOMING TELEPHONE CABLE.
66 BLOCKS PROVIDED FOR INCOMING TELEPHONE COMPANY CABLE. NUMBER OF
PAIRS AS SPECIFIED BY THE TELEPHONE SERVICE PROVIDER.
PROVIDE CROSS CONNECT CABLES SO THAT EVERY PAIR IS CONNECTED TO EACH TERMINATION BLOCK.
66 BLOCK ON PROTECTED SIDE OF CABLE PROTECTORS. SEE EQUIPMENT ELEVATIONS ON DETAIL 9/E-5
FOR MORE INFORMATION.
PNC SHALL EXTEND ALL ANALOG LINES FROM PATCH PANEL TO 66 BLOCKS.
PROVIDE 48 PORT CAT 5E PATCH PANEL MOUNTED IN RACK. TERMINATE THE CAT 5E CABLES.
DATA EQUIPMENT RACK WITH OWNER PROVIDED ELECTRONICS.
OWNER PROVIDED VOIP SWITCH.
PROVIDE (1) CAT 5E CABLE FROM EVERY JACK TO PATCH PANEL IN EQUIPMENT RACK. TERMINATE
EVERY CABLE AT BOTH ENDS.
PROVIDE CAT 5E PATCH CABLES AT EACH END OF NEW CABLE RUNS. AT OUTLET PROVIDE 10' CABLE
AND AT PATCH PANEL PROVIDE 5' CABLES.
ALL PATCH CABLES SHALL BE INSTALLED INTO THE PATCH PANEL. CABLE GUIDES ARE TO BE USED TO
KEEP THE CABLES ORDERLY. THE EQUIPMENT END OF THE PATCH CABLE IS TO BE LEFT HANGING IN
FRONT OF THE RACK. THESE WILL BE PATCHED INTO THE OWNER PROVIDED ELECTRONICS BY THE PNC
BANK IT DEPARTMENT.
IF THE CONTRACTOR PROVIDES ANY OPENINGS THROUGH WALLS, FLOOR, ETC. THEN THE CONTRACTOR
SHALL BE RESPONSIBLE FOR FIRESTOP SEALING, PATCHING, AND PAINTING ALL AREAS DISTURBED BY
THIS CONTRACT.
CABLE PROTECTORS. EVER INCOMING COPPER CABLE MUST BE PROTECTED. PROTECTORS ARE
SPECIFIED IN THE SPECIFICATIONS.
TELECOMMUNICATIONS WIRING DIAGRAM NUMBERED NOTES
VC
ATLAS
AT10
ATLAS
AT10
ATLAS
AT10
ATLAS
AT10
(1) ATLAS SD72W SPKR IN FLEX 105.
(1) ATLAS SD72W SPKR IN COLLABORATIVE
104.
(1) ATLAS SD72W SPKR IN FLEX 107.
TOP VIEW
WALL ANCHOR
WALL METAL BRACKET
STAND OFF INSULATOR
COPPER BUS
.281" DIA
HOLE
4"
1"
16"
1/4" X 4"
COPPER BUS
6 AUDIO BACKBONE SINGLE LINE DIAGRAM
N.T.S.
4 TELECOMMUNICATIONS WIRING DIAGRAM
N.T.S.
3 TELECOMMUNICATIONS DATA RACK ELEVATION
N.T.S.
2 CABLE MARKER DETAIL
N.T.S.
1 COPPER GROUND BAR DETAIL
N.T.S.7 CARD READER/SECURITY INTERFACE
N.T.S.
J2-6J2-4
PARABIT CARD READER CONTROLLER
LOCATED IN TELE/DATA 102
(1) 8 CONDUCTOR #18AWG STRANDED
CABLE, BELDEN #6360UE
(1) 4 CONDUCTOR #22AWG STRANDED
CABLE, BELDEN #6502UE
CARD READER FURNISHED WITH
PARABIT CONTROLLER AT EXTERIOR
SWINGING LOBBY DOOR.
DOOR LOCKING DEVICE FURNISHED WITH
DOOR HARDWARE PACKAGE AND
INSTALLED BY G.C.
DOOR LOCKING DEVICE POWER
SUPPLY FURNISHED WITH DOOR
HARDWARE PACKAGE, AND
INSTALLED AND WIRED BY E.C.(1) 4 CONDUCTOR #18AWG STRANDED
CABLE, BELDEN #6302UE
DIEBOLD "DMP" PANEL
LOCATED IN TELE/DATA 102
(1) 8 CONDUCTOR #22AWG
STRANDED CABLE, BELDEN #6560UE
NUMBERED NOTES
DIEBOLD FURNISHES AND INSTALLS DEVICE AND MAKES WIRE
TERMINATIONS.
E.C. FURNISHES AND INSTALLS 120VAC POWER. REFER TO E-101.
LVC FURNISHES AND INSTALLS LOW VOLTAGE CABLE.
06/20/2019
07/23/19
William Hohlt