HomeMy WebLinkAboutM001.0IECC 2009 Performance Compliance
Property Organization
7113 Antiquity Dr TSI Energy Solutions
CARMEL, IN 46033 317-846-4655
Model: SAUSALITO Michael Hill
Community: THE GROVE AT LEGA(
Builder
GL188A(AS DESIGNED) PYATT BUILDERS, LLC
THE GROVE AT LEGACY 188A
Design
Heating
Cooling
Water Heating
SubTotal - Used to determine compliance
Lights & Appliances
Onsite generation
Total
Inspection Status
Results are projected
Annual Energy Cost
IECC 2009 Performance
$888
$129
$263
$1,280
$635
$0
$1,915
Requirements
C",
Energy Solutions
As Designed
$817
$154
$263
$1,233
$628
$0
$1,861
Air sealing is 5.00 ACH at 50 Pa. It must not exceed 7.00 ACH at 50 Pa.
Design exceeds requirements for IECC 2009 Performance compliance by 3.6%.
As a 3rd party extension of the code jurisdiction utilizing these reports, I certify that this energy code compliance document has been created in accordance with the requirements of
Chapter 4 of the adopted International Energy Conservation Cade based on Climate Zone 5. If rating is Projected, I certify that the building design described herein is consistent with
the building plans, specifications, and other calculations submitted with the permit application. If rating is Confirmed, I certify that the address referenced above has been
inspectecnested and that the mandatory provisions of the IECC have been installed to meet or exceed the intent of the IECC or will be verified as such by another party.
Name: Michael Hill
Organization: TSI Energy Solutions
Signature:
Date: 6117119 at 9:22 PM
Ekotrope RATER - Version 3.1.0.2196
IECC 2009 Performance compliance results calculated using Ekotrope RATER's anergy and code compliance algorithm.
Ekotrope RATER is a RESNr7T Aocred ited HERS Rating Tool. All resuis are based on data entered by Ekotrope users.
Ekotrope disclaims all liability for the in for m atio n s how n on this report.
405.3
Performance-based compliance passes by 3.6%
R402.4.1.2
Air Leakage Testing
402.5
Area -weighted average fenestration 5HGC
402.5
Area -weighted average fenestration U -Factor
403.2.2
Duct Testing
Q
Mandatary Checklist
Mandatory code requirements that are not
checked by Ekotrope must be met.
Q
R405.2
Duct Insulation
C",
Energy Solutions
As Designed
$817
$154
$263
$1,233
$628
$0
$1,861
Air sealing is 5.00 ACH at 50 Pa. It must not exceed 7.00 ACH at 50 Pa.
Design exceeds requirements for IECC 2009 Performance compliance by 3.6%.
As a 3rd party extension of the code jurisdiction utilizing these reports, I certify that this energy code compliance document has been created in accordance with the requirements of
Chapter 4 of the adopted International Energy Conservation Cade based on Climate Zone 5. If rating is Projected, I certify that the building design described herein is consistent with
the building plans, specifications, and other calculations submitted with the permit application. If rating is Confirmed, I certify that the address referenced above has been
inspectecnested and that the mandatory provisions of the IECC have been installed to meet or exceed the intent of the IECC or will be verified as such by another party.
Name: Michael Hill
Organization: TSI Energy Solutions
Signature:
Date: 6117119 at 9:22 PM
Ekotrope RATER - Version 3.1.0.2196
IECC 2009 Performance compliance results calculated using Ekotrope RATER's anergy and code compliance algorithm.
Ekotrope RATER is a RESNr7T Aocred ited HERS Rating Tool. All resuis are based on data entered by Ekotrope users.
Ekotrope disclaims all liability for the in for m atio n s how n on this report.
7113 Antiquity Dr
CARMEL, IN 46033
Builder: PYATT BUILDERS, LLC
Ceiling Attic, R-38
Above Grade Walls R-15
Foundation Walls NIA
Framed Floor NIA
Slab R-10.0 Perimeter, R-10.0
Under
Infiltration 5 ACH50
Window U -Value: 0.31, SHGC: 0.32
Building Features
Duct Supply R-25.0, Return R-25.0
Duct Leakage to Outside 96.0 CFM @ 25Pa
Total Duct Leakage 128.0 CFM @ 25Pa
Heating Furnace • Natural Gas • 92.1 AFUE
Cooling Air Conditioner • Electric • 13 SEER
Water Heating Water Heater • Electric • 0.93 Energy Factor
As a 3rd party extension of the code jurisdiction utilizing these reports, I certify that this energy code compliance document has been created in accordance with the requirements of
Chapter Q of the adopted International Energy Conservation Code based on Climate Zane 5. If rating is Projected, I certify that the building design described herein is consistent with the
building plans, specifications, and other calculations submitted with the permit application. If rating is Confirmed, I certify that the address referenced above has been inspectedltested and
that the mandatory provisions of the IECC have been installed to meet or exceed the intent of the IECC or will be verified as such by another party.
Name:
Organization:
Michael Hill
TSI Energy Solutions
Signature:
Date:
6117119 at 9:22 PM
Ekotrope RATER - Version 3.1.0.2196
2009 IECC compliance results calculated using Ekotrope RATER's energy and code compliance algorithm.
Ekotrope RATER is a RESNETA—sdlted HERS Rating Tool. All results are based on data entered by Ekotrope users,
Ekotrope disclaims all liability forthe information shown on this report.
Energy Code Inspection Checklist
Property Organization
7113 Antiquity Dr TSI Energy Solutions
CARMEL, IN 46033 317-846-4655
Model: SAUSALITO Michael Hill
Community: THE GROVE AT LEGA(
GL188A(AS DESIGNED)
THE GROVE AT LEGACY 188A
General Building Information
Conditioned Area (sq ft)
Conditioned Volume (cubic ft)
Insulated Shell Area (sq ft)
Builder
PYATT BUILDERS, LLC
1,647
15,349
5,724
Inspection Status
Results are projected
C",
Energy Solutions
The building energy model in Ekotrope reflects the building assemblies and energy features listed below. Sometimes energy
features will change in the field from what has been modeled. The inspection process should identify any changes and ensure
that the home continues to meet the applicable energy code.
Slab
Name: SLAB (1,647 s.f.)
R-10 perimeter insulation, R-10 under slab insulation.
Framed Floor
None Present
Foundation Wall
None Present
Above Grade Wall
Name: COND/AMB (1,566 s.f.)
R-0 continuous insulation, R-15 cavity insulation
Insulation Grade: I
Name: COND/GAR (378 s.f.)
R-0 continuous insulation, R-15 cavity insulation
Insulation Grade: I
Name: COND/COND (387 s.f.)
R-0 continuous insulation, R-22 cavity insulation
Insulation Grade: I
Name: COND/ATTIC (99 s.f.)
R-3 continuous insulation, R-15 cavity insulation
Insulation Grade: I
Energy Code Inspection Checklist
Property
7113 Antiquity Dr
CARMEL, IN 46033
Model: SAUSALITO
Community: THE GROVE AT LEGA(
GL188A(AS DESIGNED)
THE GROVE AT LEGACY 188A
Rim Joist
None Present
Roof
Organization
TSI Energy Solutions
317-846-4655
Michael Hill
Builder
PYATT BUILDERS, LLC
Name: MAIN (1,647 s.f.)
R-27.55 continuous insulation, R-10.15 cavity insulation
Insulation Grade: I
Opaque Door
Name: FRONT (20 s.f.)
U: 0.182
Name: GARAGE (18 s.f.)
U: 0.182
Glazing
Inspection Status
Results are projected
E] Name: FRONT (80 s.f.), U: 0.310, SHGC: 0.32, Orientation: NORTH
El Name: BACK (59 s.f.), U:0.310, SHGC: 0.32, Orientation: SOUTH
El Name: SLIDER (128 s.f.), U:0.310, SHGC: 0.32, Orientation: SOUTH
El Name: LEFT SIDE (141 s.f.), U:0.310, SHGC: 0.32, Orientation: WEST
Name: RIGHT SIDE (83 s.f.), U:0.310, SHGC: 0.32, Orientation: EAST
Skylight
None Present
Mechanical Ventilation
C"IEnergySdutions
2
Energy Code Inspection Checklist
Property Organization Inspection Status
7113 Antiquity Dr TSI Energy Solutions Results are projected
CARMEL, IN 46033 317-846-4655
Model: SAUSALITO Michael Hill
Community: THE GROVE AT LEGA(
Builder
G1_188A(AS DESIGNED) PYATT BUILDERS, LLC
THE GROVE AT LEGACY 188A
Mechanical ventilation system rated for, and capable of, providing continuous ventilation.
System shall include automatic timing controls.
System type: Exhaust Only, 24 hrslday, 9 Watts.
Mechanical Equipment
L Fuel -fired air distribution • Natural Gas • 100% Heating Load @ 92.1 AFUE
0 Air conditioner • Electric • 100% Cooling Load @ 13 SEER
Water Heating • Electric • 100% Hot Water Load @ 0.93 Energy Factor
Air Leakage Control
Test Status: Blower -door tested
House is air -sealed as to achieve 1,279 CFM50 (5,00 ACH50) or less at final blower -door test,
Infiltration Requirements for IECC in Climate Zone 5
2009 IECC Infiltration limit for the design home is 7 ACH50.
2012 IECC Infiltration limit for the design home is 3 ACH50.
2015 IECC Infiltration limit for the design home is 3 ACH50.
Duct Leakage
Duct System 1
NOT entirely within conditioned space, testing required
Tested Post -Construction
Leakage to Outdoors is specified in Ekotrope at 96.0 CFM @ 25Pa
Total Duct Leakage is specified in Ekotrope at 128.0 CFM 9 25Pa
C",
Energy Solutions
Energy Code Inspection Checklist
Property Organization
7113 Antiquity Dr TSI Energy Solutions
CARMEL, IN 46033 317-846-4655
Model: SAUSALITO Michael Hill
Community: THE GROVE AT LEGA(
Builder
GL188A(AS DESIGNED) PYATT BUILDERS, LLC
THE GROVE AT LEGACY 188A
Duct Leakage Code Requirements for IECC
9009 IECC:
Inspection Status
Results are projected
Postconstruction Leakage Test: Duct Leakage to Outdoors <= 8 CFM95 / 100 sq ft CFA.
Rough in Test with AHU: Total Duct Leakage <= 6 CFM95 1100 sq ft CFA.
Rough in Test without AHU: Total Duct Leakage <= 4 CFM95 1100 sq ft CFA.
9019 IECC and 9015 IECC Prescriptive Path:
Postconstruction Leakage Test: Total Duct Leakage <= 4 CFM95 1 100 sq ft CFA.
Rough in Test with AHU: Total Duct Leakage <= 4 CFM95 1100 sq ft CFA.
Rough in Test without AHU: Total Duct Leakage <= 3 CFM95 1100 sq ft CFA.
9015 Performance Path (Cost Compliance):
C",
Energy Solutions
Leakage testing is required UNLESS all ducts and air handlers are located entirely within the thermal envelope.
There is no pass/fail threshold for duct leakage on the performance path.
Project Notes
4
Building Summary
Pro perty
7113 Antiquity Dr
CARMEL, IN 45033
Madel: SAUSALITO
Community: THE GROVE AT LEGACY 188A
GLI 88A (AS DESIGNED)
THE GROVE AT LEGACY 186A
General Building Information
Number Of Bedrooms
Number Of Floors
Conditioned Floor Area [sq. ft.]
Unconditioned, attached garage?
Conditioned Volume [cu. ft.]
Total Units in Building
Residence Type
Floor Number
Model
Community
Climate Zone
Foundation Wall
Organization
TSI E nerg y S olution s
317-846-4655
Michael Hill
Builder
PYATT BUILDERS, LLC
2
1
1,647
Yes
15,349
1
Duplex, single unit
SAUSALITO
THE GROVE AT LEGACY 188A
5A
None Present
Foundation Wall Library List
None Present
Inspection Status
Results are projected
CTMEnergy Solutions
Slab Ew— 9 0
Name Library Type Perimeter Floor Grade Carpet R Exposed Surface Area Location Enclosing
Masonry Area
SLAB R-10, 2'down,2' in 215 On Grade 1.23 0 1,647.0 sq. ft. Exposed Exterior Conditioned
Space
Slab Library L—is!A��� 9
Name Wall Construction Slab Completely Llndersiab Perimeter Perimeter Thermal Break Effective R -value
Type Insulated. Insulation Width [ft] Insulation Depth (ft] Insulation R Value
R-10, 2'down, 2' in Wood Frame f Other No 2 2 10 No 1D.00
Framed Floor rM
None Present
1
Building Summary
Property
Organization
7113 Antiquity Dr
TSI Energy Solutions
CARMEL, IN 46033
317-846-4655
Madel: SAUSALITO
Michael Hill
Community: THE GROVE AT LEGACY 188A
Surface Color
Surface Area
Builder
GLI 88A (AS DESIGNED)
PYATT BUILDERS, LLC
THE GROVE AT LEGACY 188A
Framed Floor Library List
E&M
G1 R-15 BATT, OSB
None Present
Rim Joist
1,566.D sq. It.
CONDIATTIC
None Present
Rim Joist Library List
None Present
CTMEnergy Solutions
Inspection Status
Results are projected
Wall
■
Name
Library Type
Surface Color
Surface Area
Location
CCNDIAMB
Exposed Exterior
G1 R-15 BATT, OSB
Medium
1,566.D sq. It.
CONDIATTIC
Attic
01 R-15 BATT, R,3.0
Medium
99.D sq. It.
CONDICOND
Conditioned Space (Adiabatic)
Gi R-22 Dbl Wall
Medium
387.0 sq. ft.
CONDIGAR
Unconditioned, attached garage
G1 R-15 Gar Walls
Medium
378.0 sq. ft.
Wall Library List
Name
Effective R -value
G1 R-15 BATT, OSB
13.423
G1 R-15 BATT, R-3.0
16.138
G7 R-15 Gar Walls
11.972
07 R-22 Dbl Wall
18.407
2
Building Summary
Property
Organization
Inspection Status
CTMEnergy Solutions
7113 Antiquity Dr
TSI Energy Solutions
Results are projected
CARMEL, IN 45033
317-846-4655
Madel: SAUSALITO
Michael Hill
Community: THE GROVE AT LEGACY 188A
Builder
GLI 88A (AS DESIGNED)
PYATT BUILDERS, LLC
THE GROVE AT LEGACY 188A
Glazing
Name Library Type Wall
Assignment Foundation Wall Overhang
Assignment
Depth Overhang Ft
Top
To Overhang Ft To
Bottom
Orientation Surface Area
BACK U-.31, SHGC-.32
South 59.0 sq. ft.
CONDIAMB
❑
0 ❑
FRONT U-.31, SHGC-.32
North 80.0 sq. ft.
CONDIAMB
❑
0 ❑
LEFT SIDE U-.31, SHGC-.32
West 1D1.0sq. ft.
CONDIAMB
❑
0 ❑
RIGHT SIDE U-.31, SHGC-.32
East 83.0 sq. ft.
CONDIAMB
0
0 ❑
SLIDER U-.31, SHGC-.32
South 128.0 sq. ft.
CONDIAMB
0
0 0
Glazing Library List
Name
Shgc
LI -factor
U-.31, SHGC-.32
0.32
0.31D
Skylight
—Mw
None Present
Skylight Library List
MEOW
None Present
Opaque Door
Name Library Type Wall Assignment Foundation Wall Emittance Solar Surface Color Surface Area Location
Assignment Abso rptan ce
FRONT Steel Door CONDIAMB 0.9 D.75 Medium 2D.0 sq. ft. Exposed Exterior
GARAGE Steal Door CONDIGAR 0.9 0.75 Medium 18.0 sq. ft. Exposed Exterior
3
Building Summary
Property
Organization
7113 Antiquity Dr
TSI Energy Solutions
CARMEL, IN 46033
317-846-4655
Madel: SAUSALITO
Michael Hill
Community: THE GROVE AT LEGACY 188A
Builder
GLI 88A (AS DESIGNED)
PYATT BUILDERS, LLC
THE GROVE AT LEGACY 188A
Opaque Door Library List
Name Effective 1.1 -factor
Steel Door 0.182
Roof Insulation
Name
MAIN R-38 Blown, GRI
Inspection Status
Results are projected
CTMEnergy Solutions
1,647 No Medium 1,647.0 sq. ft. Attic
Roof Insulation Library List
Name Has Radiant Barrier Effective R -value
R-38 Blown, GRI No 38.268
Whole House Infiltration
Infiltration Measure me nt Type She I to r C lass
5 ACH at 50 Pa Blower -door tasted 4
I
Mechanical Ventilation
Ventilation Type Ventilation Rate [Cubic Feet Operational hours per day Fan Watts Runs once every three Energy Recovery percent
/Mlnuta] hours
Exhaust Only 20 24 9 Yes 0
Lighting
% Interior Fluorescent
Lighting
0 ❑ ❑ ❑ ❑ 0
4
Building Summary
Pro perty
7113 Antiquity Dr
CARMEL, IN 46033
Model: SAUSALITO
Community: THE GROVE AT LEGACY 188A
GLI 88A (AS DESIGNED)
THE GROVE AT LEGACY 186A
Onsite Generation
Organization
TSI E nerg y S olution s
317-846-4655
Michael Hill
Builder
PYATT BUILDERS, LLC
None Present
Onsite Generation Library List
None Present
Solar Generation
None Present
Solar Generation Library List
None Present
Conditioning Equipment
Name
Air conditioner
Fuel -fired air
distribution
Water Heating
CA13NA048
912SA4806DS17
ENT 50 100
Equipment Type: 912SA4806OS17
Fuel Type Natural Gas
Distribution Type Forced Air
Motor Type PSG [Single Speed]
Heating Efficiency 92.1 AFUE
Heating Capacity [kBtufh] 56
Use default EAE No
EAE [kWh] 649
Inspection Status
Results are projected
0%
100%
0%
ng Percent wat
100%
0%
4%
CTMEnergy Solutions
0°%
VI6
100%
.7
Building Summary
Pro perty
7113 Antiquity Dr
CARMEL, IN 45033
Model: SAUSALITO
Community: THE GROVE AT LEGACY 188A
GLI 88A (AS DESIGNED)
THE GROVE AT LEGACY 186A
Equipment Type: CA13NA048
Fuel Type
Distribution Type
Motor Type
Cooling Efficiency
Cooling Capacity [kBtulh]
q
' Equipment Type: ENT 50100
Organization
TSI E nerg y S olution s
317-846-4655
Michael Hill
Builder
PYATT BUILDERS, LLC
Electric
Forced Air
PSC (Single Speed)
13 SEER
45.5
Inspection Status
Results are projected
Fuel Type
Electric
Distribution Type
Hydranic Delivery
Hot Water Efficiency
0.93 Energy Factor
Tank Capacity (gal.)
50
Hot Water Capacity [kBtu/h]
15.4
Recovery Efficiency
0.98
CTMEnergy Solutions
Building Summary
Property
Organization Inspection Status
7113 Antiquity Dr
TSI Energy Solutions Results are projected
CARMEL, IN 46033
317-846-4655
Model: SAUSALITO
Michael Hill
Community: THE GROVE AT LEGACY 188A
1
Supply Duct R Value
Builder
GLI 88A (AS DESIGNED)
PYATT BUILDERS, LLC
THE GROVE AT LEGACY 188A
444.69
Distribution System
Distribution Type
Forced Air
Heating Equipment
Fuel -fired air distribution
Cooling Equipment
Air conditioner
Sq. Feet Served
1647
# Return Grilles
1
Supply Duct R Value
25
Return Duct R Value
25
Supply Duct Area [sq. ft.]
444.69
Retum Duet Area [sq. ft.]
82.35
Duct Leakage to Outdoors (CFIM 25)
96
Total Leakage
128
Total Leakage Duct Test Conditions
Post -Construction
Use Default Flow Rate
Yes
Duct 1
Duct Location
Conditioned Space
Percent Supply Area
5
Percent Return Area
5
Duct 2
Duct Location
Attic (well vented, under insulation)
Percent Supply Area
95
Percent Return Area
95
Duct 3
Duct Location
Attic (well vented)
Percent Supply Area
6
Percent Return Area
t?
Duct 4
Duct Location
Conditioned Space
Percent Supply Area
0
Percent Return Area
0
Duct 5
Duct Location
Conditioned Space
Percent Supply Area
0
Percent Return Area
0
Duct 6
Duct Location
Conditioned Space
Percent Supply Area
0
Percent Return Area
0
Ceiling Fan
Has Ceiling Fan No
Cfm Per Watt 100
Water Distribution
Water Fixture Type
Use Default Hot Water Pipe Length
Hot Water Pipe Length [ft]
At Least R3 Pipe Insulation?
Hot Water Recirculation System?
Recirculation System Pipe Loop Length [ft]
Drain Water Heat Recovery?
Standard
No
25
No
No
10
No
CTMEnergy Solutions
VA
Building Summary
Pro perty
7113 Antiquity Dr
CARMEL, IN 46033
Model: SAUSALITO
Community: THE GROVE AT LEGACY 188A
GLI 88A (AS DESIGNED)
THE GROVE AT LEGACY 188A
Clothes Dryer
Fuel Type
Cef
Field Utilization
Clothes Washer
Label Energy Rating
Electric Rate
Annual Gas Cost
Gas Rate
Capacity
I met
Appliances and Controls
Programmable thermostat?
Dishwasher Size
Dishwasher Efficiency
Range/Oven Fuel
Convection Oven?
Induction Range?
Refrigerator Consumption
NMS
Organization
TSI E nerg y S olution s
317-846-4655
Michael Hill
Builder
PYATT BUILDERS, LLC
Electric
2.617
Timer Controls
704 kWhNear
$0.08/kWh
$23.00
$0.581Therm
2.874
0.33053
Yes
Standard
270 kWh
Natural Gas
No
No
709 kWh/Year
Inspection Status
Results are projected
CTMEnergy Solutions