HomeMy WebLinkAboutM001.0IECC 2009 Performance Compliance Property Organization 7104 CHERRY CREEK BLVD TSI Energy Solutions CARMEL, IN 46033 317-846-4655 Model: SAUSALITO Michael Hill Community: THE GROVE AT LEGA[ Builder GL200A (AS DESIGNED) PYATT BUILDERS, LLC THE GROVE AT LEGACY 200A Design Heating Cooling Water Heating SubTotal - Used to determine compliance Lights & Appliances Onsite generation Total Inspection Status Results are projected Annual Energy Cost IECC 2009 Performance $888 $129 $263 $1,280 $635 $0 $1,915 Requirements C-M, Energy Solutions As Designed S817 $154 $263 $1,233 5628 s0 $1,861 C4405.3 Performance-based compliance passes by 3.19% R402.4.12 Air Leakage Testing Air sealing is 5 -DD ACH at 5D Pa. It must not exceed 7.DD ACH at 50 Pa. C4402.5 Area -weighted average fenestration SHGC 402.5 Area -weighted average fenestration 11 -11 -Factor 40322 Duct Testing Mandatory Checklist Mandatory code requirements that are not checked by Ekotrope must be met. R4052 Duct Insulation Design exceeds requirements for IECC 2009 Performance compliance by 3.6%. As a 3rd party extension of the code jurisdiction utilizing these reports, I certify that this energy code compliance document has been created in accordance with the requirements of Chapter 4 of the adopted International Energy Conservation Code based on Climate Zone 5. If rating is Projected, I certify that the building design described herein is consistent with the building plans, specifications, and other calculations submitted with the permit application. If rating is Confirmed, I certify that the address referenced above has been inspected/tested and that the mandatory provisions of the IECC have been installed to meet or exceed the intent of the IECC orwill be verified as such by another party. Name: Michael Hill Organization: TSI Energy Solutions Signature: Date: 6113119 at 8:22 AM Ekotrope RATER - Version 3.1.0.2194 IECC 2009 Performance compliance results calculated using Ekotrope RATER's energy and code compliance algorithm. Ekotrope RATER is a RESIN ET Accredited HERS Rating Tool. All results are based on data entered by Ekotrope users. Ekotrope disclaims all liability for the information shown on this report. 7104 CHERRY CREEK BLVD CARMEL, IN 46033 Builder: PYATT BUILDERS, LLC Ceiling Attic, R-38 Above Grade Walls R-15 Foundation Walls NIA Framed Floor NIA Slab R-10.0 Perimeter, R-10.0 Under Infiltration 5 ACH50 Window U -Value: 0.31, Sll 0.32 Building Features Duct Supply R-25.0, Return R-25.0 Duct Leakage to Outside 96.0 CFM @ 25Pa Total Duct Leakage 128.0 CFM @ 25Pa Heating Furnace • Natural Gas • 92.1 AFUE Cooling Air Conditioner • Electric • 13 SEER Water Heating Water Heater • Electric • 0.93 Energy Factor As a 3rd party extension of the code jurisdiction utilizing these reports. I certify that this energy code compliance document has been created in accordance with the requirements of Chapter 4 of the adopted International Energy Conservation Code based on Climate Zone 5. If rating is Projected. I certify that the building design described herein is consistent with the building plans, specifications. and other calculations submitted with the permit application. If rating is Confirmed. I certify that the address referenced above has been inspectetlrtested and that the mandatory provisions of the I ECC have been installed to meet or exceed the intent of the I ECC cr will be venfied as such by another party. Name Organization Michael Hill TSI Energy Solutions Signature: Date: 6113119 at 8:22 AM Ekotrope RATER -Version 3.1.0.2194 2009 l compliance results calculated using Ekotrope RATER's energy and code cnmptance algorithm_ Ekotrope RATER is a RESIN ET Accredited HERS Rating Tool. All results are based on data entered by Ekotrope users. Ekotrope disclaims all liability for the information sh— on this report. Energy Code Inspection Checklist Property Organization 7164 CHERRY CREEK BLVD TSI Energy Solutions CARMEL, IN 46633 317-846-4655 Model: SAUSALITO Michael Hill Community: THE GROVE AT LEGA( GL266A (AS DESIGNED) THE GROVE AT LEGACY 266A General Building Information Conditioned Area (sq ft) Conditioned Volume (cubic ft) Insulated Shell Area (sq ft) Builder PYATT BUILDERS, LLC 1,647 16,349 5,724 Inspection Status Results are projected C", Energy Solutions The building energy model in Ekotrope reflects the building assemblies and energy features listed below. Sometimes energy features will change in the field from what has been modeled. The inspection process should identify any changes and ensure that the home continues to meet the applicable energy code. Slab Name: SLAB (1,647 s.f.) R-16 perimeter insulation, R-16 under slab insulation. Framed Floor None Present Foundation Wall None Present Above Grade Wall El Name: CONDIAMB (1,566 s.f.) R-6 continuous insulation, R-15 cavity insulation Insulation Grade: I El Name: CONDIGAR (378 s.f.) R-6 continuous insulation, R-15 cavity insulation Insulation Grade: I Name: CONDICOND (387 s.f.) R-6 continuous insulation, R-22 cavity insulation Insulation Grade: I Name: CONDIATTIC (99 s.f.) R-3 continuous insulation, R-15 cavity insulation Insulation Grade: I Energy Code Inspection Checklist Property 7104 CHERRY CREEK BLVD CARMEL, IN 46033 Model: SAUSALITO Community: THE GROVE AT LEGA[ GL200A (AS DESIGNED) THE GROVE AT LEGACY 200A Rim Joist None Present Roof Organization TSI Energy Solutions 317-846-4655 Michael Hill Builder PYATT BUILDERS, LLC Name: MAIN (1,647 s.f.) R-27.55 continuous insulation, R-10.15 cavity insulation Insulation Grade: I Opaque Door Name: FRONT (20 s.f.) U: 0.182 Name: GARAGE (18 s.f.) U: 0.182 Glazing Inspection Status Results are projected E] Name: FRONT (80 s.f.), U:0.310, SHGC: 0.32, Orientation: NORTH El Name: BACK (59 s.f.), U:0.310, SHGC: 0.32, Orientation: SOUTH El Name: SLIDER (128 s.f.), U:0.310, SHGC: 0.32, Orientation: SOUTH El Name: LEFT SIDE (101 s.f.), U:0.310, SHGC: 0.32, Orientation: WEST 11 Name: RIGHT SIDE (83 s.f.), U:0.310, SHGC: 0.32, Orientation: EAST Skylight None Present Mechanical Ventilation C-M, Energy Solutions 2 Energy Code Inspection Checklist Property Organization Inspection Status 7104 CHERRY CREEK BLVD TSI Energy Solutions Results are projected CARMEL, IN 46033 317-846-4655 Model: SAUSALITO Michael Hill Community: THE GROVE AT LEGA( Builder GL200A (AS DESIGNED) PYATT BUILDERS, LLC THE GROVE AT LEGACY 200A ElMechanical ventilation system rated for, and capable of, providing continuous ventilation. System shall include automatic timing controls. System type: Exhaust Only, 24 hrslday, 9 Watts. Mechanical Equipment El Fuel -fired air distribution • Natural Gas • 100% Heating Load @ 92.1 AF UE 0 Air conditioner • Electric • 100% Cooling Load @ 13 SEER Water Heating • Electric • 100% Hot Water Load @ 0.93 Energy Factor Air Leakage Control ElTest Status: Blower -door tested House is air -sealed as to achieve 1,279 CFM50 (5.00 ACH50) or less at final blower -door test. Infiltration Requirements for IECC in Climate Zone 5 2009 IECC Infiltration limit for the design home is 7 ACH50. 2012 IECC Infiltration limit for the design home is 3 ACH50. 2015 IECC Infiltration limit for the design home is 3 ACH50. Duct Leakage Duct System 1 NOT entirely within conditioned space, testing required Tested Post -Construction Leakage to Outdoors is specified in Ekotrope at 96.0 CFM @ 25Pa Total Duct Leakage is specified in Ekotrope at 128.0 CFM @ 25Pa C", Energy Solutions Energy Code Inspection Checklist Property Organization 7104 CHERRY CREEK BLVD TSI Energy Solutions CARMEL, IN 46033 317-846-4655 Model: SAUSALITO Michael Hill Community: THE GROVE AT LEGA( Builder GL200A (AS DESIGNED) PYATT BUILDERS, LLC THE GROVE AT LEGACY 200A Duct Leakage Code Requirements for IECC 2009 IECC: Inspection Status Results are projected Postconstruction Leakage Test: Duct Leakage to Outdoors t= 8 CFM25 / 100 sq ft CFA. Rough in Test with AHU: Total Duct Leakage <= 6 CFM25 / 100 sq ft CFA. Rough in Test without AHU: Total Duct Leakage <= 4 CFM25 / 100 sq ft CFA. 2012 IECC and 2015 IECC Prescriptive Path: Postconstruction Leakage Test: Total Duct Leakage <= 4 CFM25 / 100 sq ft CFA. Rough in Test with AHU: Total Duct Leakage <= 4 CFM25 / 100 sq ft CFA. Rough in Test without AHU: Total Duct Leakage <= 3 CFM25 / 100 sq ft CFA. 2015 Performance Path (Cost Compliance): C", Energy Solutions Leakage testing is required UNLESS all ducts and air handlers are located entirely within the thermal envelope. There is no pass/fail threshold for duct leakage on the performance path. Project Notes 4 Building Summary Property 7104 CHERRY CREEK BLVD CARMEL, IN 46033 Model: SAUSALITO Community: THE GROVE AT LEGACY 200A GL200A [AS DESIGNED] THE GROVE AT LEGACY 200A Genera?Building Information Number Of Bedrooms Number Of Floors Conditioned Floor Area [sq_ ft.] Unconditioned, attached garage? Conditioned Volume [cu. ft.] Total Units in Building Residence Type Floor Number Model Community Climate Zone Foundation Wall Foundation Wall Library List Slab Organization Inspection Status TSI Energy Solutions Results are projected 317-846-4655 Michael Hill Builder PYATT BUILDERS, LLC 2 1 1;647 Yes 15;349 1 Duplex; single unit SAUSALITO THE GROVE AT LEGACY 200A 5A None Present None Present Masonry Area C-M, Energy Solutions n SLAB R-10, 2'down, 2' in 216 On Grade 1.23 0 1,647.0 sq. R. Exposed Exterior Conditioned Space Slab Library List Name Wall Construction Slab Completel Underslab Perimeter Perimeter Thermal Break Effective R -value Type Insulated. Insulation Width [ft] Insulation Depth [ft] Insulation R Value R-10, 2'down, 2' in Wood Frame /Other No 2 2 10 No 10.00 Framed Floor None Present 1 Building Summary Property Organization 7104 CHERRY CREEK BLVD TSI Energy Solutions CARMEL, IN 46033 317-846-4655 Model: SAUSALITO Michael Hill Community: THE GROVE AT LEGACY 200A Builder GL200A [AS DESIGNED] PYATT BUILDERS, LLC THE GROVE AT LEGACY 200A 1,566.0 sq. ft. Framed Floor Library List None Present Rim Joist Rim Joist Library List _ None Present Wall Inspection Status Results are projected C-M, Energy Solutions Name Library Type Surface Calor Surface Area Location CONDIAMB Exposed Exterior G1 R-15 BATT, OSB Medium 1,566.0 sq. ft. CONDIATTIC Attic G1 R-15 BATT, R-3.0 Medium 99.0 sq. ft. CONDICOND Conditioned Space [Adiabatic] G1 R-22 Dbl Wall Medium 387.0 sq. ft. CONDIGAR Unconditioned, attached garage G1 R-15 Gar Walls Medium 378.0 sq. ft. Wall Library List Name Effective R value G1 R-15 BATT, OSB 13.423 G1 R-15 BATT, R-3.0 16.138 G1 R-15 Gar Walls 11.972 G1 R-22 Dhl Wall 18.407 2 Building Summary Name Library Type Wall Assignment Foundation Wall Emittance Solar Surface Color Property Organization Inspection Status C-MEnergy Solutions 7104 CHERRY CREEK BLVD TSI Energy Solutions Results are projected 0.9 0.75 Medium 20.0 sq_ ft GARAGE Steel Door CONDIGAR CARMEL, IN 46033 317-846-4655 Exposed Exterior 0.9 0.75 Medium 18.0 sq_ ft Model: SAUSALITO Michael Hill Community: THE GROVE AT LEGACY 200A Builder GL200A [AS DESIGNED] PYATT BUILDERS, LLC THE GROVE AT LEGACY 2DOA FGlazing Name Library Type WaIT Assignment Foundation Wall Overhang Depth Overhang Ft To Overhang Ft To Orientation Surface Area Assignment Top Bottom BACK U-.31, SHGC-.32 CONDIAMB ❑ ❑ ❑ South 59.0 sq. ft FRONT U-.31, SHGG.32 CONDIAMB ❑ ❑ ❑ North 80.0 sq. ft LEFT SIDE U-.31, SHGG.32 CONDIAMB 0 ❑ ❑ West 101.0 sq. R. RIGHT SIDE U-.31, SHGG.32 CONDIAMB ❑ ❑ ❑ East 83.0 sq. ft SLIDER U-.31, SHGG.32 CONDIAMB 0 0 0 South 128.0 sq. R. Glazing Library List Name Shgc U -factor U-.31, SHGC-.32 0.32 0.31 ❑ Skylight None Present Skylight Library List None Present Opaque Door Name Library Type Wall Assignment Foundation Wall Emittance Solar Surface Color Surface Area Location Assignment Ab sorpta n ce FRONT Steel Door CONDIAMB Exposed Exterior 0.9 0.75 Medium 20.0 sq_ ft GARAGE Steel Door CONDIGAR Exposed Exterior 0.9 0.75 Medium 18.0 sq_ ft Building Summary Property 7104 CHERRY CREEK BLVD CARMEL, IN 46033 Model: SAUSALITO Community: THE GROVE AT LEGACY 200A GL200A [AS DESIGNED] THE GROVE AT LEGACY 200A F4paque Door Library List Name Steel Door Roof Insulation Has Radiant Barrier Name Library Typ ktAIN R-38 Blown. GRI Roof Insulation Library List Organization TSI Energy Solutions 317-846-4655 Michael Hill Builder PYATT BUILDERS, LLC 0.182 Inspection Status Results are projected r Area Clay or Concrete Roof Vt.] Tiles 1,647 No Name Has Radiant Barrier R-38 Blown, GR1 No Whale House Infiltration Infiltration Measurement Type 5 ACH at 50 Pa Blower -door tested Mechanical Ventilation Ventilation Type Ventilation Rate [Cubic Feet Operational hours per day !Minute] Exhaust Only 20 24 Lighting Interior Fluorescent Lighting 0 38268 Shelter Class 4 C-M, Energy Solutions :e Color Surface Area Location Medium 1,647.0 sq. ft Attic Fan Watts Runs once every three Energy Recovery Percent hours 9 Yes 0 ■ ■ 4 Building Summary Property Organization 7104 CHERRY CREEK BLVD TSI Energy Solutions CARMEL, IN 46033 317-846-4655 Model: SAUSALITO Michael Hill Community: THE GROVE AT LEGACY 200A Builder GL200A [AS DESIGNED] PYATT BUILDERS, LLC THE GROVE AT LEGACY 200A nsite Generation None Present Onsite Generation Library List M None Present Solar Generation None Present Solar Generation Library List None Present Conditioning Equipmenl Name Air conditioner Fuel4red air distribution Water Heating C-M Energy Solutions Inspection Status Results are projected g Percent Load Hot water CA13NA048 0% 10D% 9125A48060917 100% 0% 0% 0% ENT 50 100 0% 0% 100% Equipment Type: 912SA48060S17 Fuel Type Natural Gas Distribution Type Forced Air Motor Type PSG (Single Speed) Heating Efficiency 92.1 AFUE Heating Capacity [kBtulh] 56 Use default EAE No EAE [kWh] 649 :j Building Summary Property 7104 CHERRY CREEK BLVD CARMEL, IN 46033 Model: SAUSALITO Community: THE GROVE AT LEGACY 200A GL200A [AS DESIGNED] THE GROVE AT LEGACY 200A ■ quipment Type: Fuel Type Distribution Type Motor Type Cooling Efficiency Cooling Capacity [kBtulh] Organization TSI Energy Solutions 317-846-4655 Michael Hill Builder PYATT BUILDERS, LLC GA13NA048 ." Equipment Type: ENT 50 100 Fuel Type Distribution Type Hot Water Efficiency Tank Capacity (gal.) Hot Water Capacity [kBtulh] Recovery Efficiency Electric Forced Air PSC (Single Speed) 13 SEER 45.5 Electric Hydronic Delivery 0.93 Energy Factor 50 15.4 0.98 Inspection Status Results are projected C-M, Energy Solutions Building Summary Property 7104 CHERRY CREEK BLVD CARMEL, IN 46033 Model: SAUSALITO Community: THE GROVE AT LEGACY 200A GL200A [AS DESIGNED] THE GROVE AT LEGACY 200A 1butivn System tion Type Equipment Equipment t Served i Grilles Xct R Value ]uct R Value Xct Area [sq. ft.] ]uct Area [sq. ft_] akage to Outdoors (CFM25) akage akage Duct Test Conditions fault Flow Rate cation Supply Area Return Area cation Supply Area Return Area cation Supply Area Return Area cation Supply Area Return Area cation Supply Area Return Area cation Supply Area Return Area rCeiling Fan Has Ceiling Fan Ctm Per Watt Organization TSI Energy Solutions 317-846-4655 Michael Hill Builder PYATT BUILDERS, LLC Forced Air Fuel -fired air distribution Air conditioner 1647 1 25 25 444.69 82.35 96 128 Post -Construction Yes Conditioned Space 5 5 Attic (well vented; under insulation) 95 95 Attic (well vented) 0 0 Conditioned Space Conditioned Space Conditioned Space No Inspection Status Results are projected C-M, Energy Solutions 7 Building Summary Property 7104 CHERRY CREEK BLVD CARMEL, IN 46033 Model: SAUSALITO Community: THE GROVE AT LEGACY 200A GL200A [AS DESIGNED] THE GROVE AT LEGACY 200A ater Distribution Water Fixture Type Use Default Hot Water Pipe Length Hot Water Pipe Length [ft] At Least R3 Pipe Insulation? Hot Water Recirculation System? Recirculation System Pipe Loop Length [ft] Drain Water Heat Recovery? r es Dryer e zation Clothes Washer Label Energy Rating Electric Rate Annual Gas Cost Gas Rate Capacity I met Appliances and Controls Programmabie thermostat? Dishwasher Size Dishwasher Efficiency Range/Oven Fuel Convection Oven? Induction Range? Refrigerator Consumption FV I Organization Inspection Status TSI Energy Solutions Results are projected 317-846-4655 Michael Hill Builder PYATT BUILDERS, LLC Standard No 25 No No 10 No Electric Timer Controls 704 kWh/Year $0.081kWh $23.00 $0.581Therm 2.874 ❑.33053 Yes Standard 270 kWh Natural Gas No No 709 kWh/Year C-M, Energy Solutions ,�