HomeMy WebLinkAbout19070127 EnergyIECC 2009 Performance Compliance
Property
1761 BEAUFAIN ST
CARMEL, IN 46032
Model: CUSTOM
Community: VILLAGE OF WEST CL
VWC212 (AS DESIGNED)
VILLAGE OF WEST CLAY 212
Organization
TSI Energy Solutions
Matthew Timmons
Builder
GRADISON DESIGN
BUILD
Design
Heating
Cooling
Water Heating
SubTotal - Used to determine compliance
Lights &Appliances
Onsite generation
Total
Inspection Status
Results are projected
Annual Energy Cost
IECC 2009 Performance
$2,824
$460
$204
$3,488
$1,819
$0
$5,306
Requirements
C-M,
Energy Solutions
As Designed
$2.860
$381
$204
$3,445
$1,819
$0
$5,264
Air sealing is 5.00 ACH at 50 Pa. It must not exceed 7.00 ACH at 50 Pa.
Design exceeds requirements for IECC 2009 Performance compliance by 1.2%.
As a 3rd party extension of the code jurisdiction utilizing these reports, I certify that this energy code compliance document has been created in accordance with the requirements of
Chapter 4 of the adopted International Energy Conservation Code based on Climate Zone 5. If rating is Projected, I certify thatthe building design described herein is consistent with
the building plans, specifications, and other calculations submitted with the permit application. If rating is Confirmed, I certify that the address referenced above has been
inspected/tested and thatthe mandatary provisions of the IECC have been installed to meet or exceed the intentof the IECC or will be verified as such by another party.
Name: Matthew Timmons
Organization: TSI Energy Solutions
Signature:
Date:
7/15/19 at 11:21 AM
Ekotrope RATER -Version 3.1.1.2213
IECC 2009 Performance compliance results calculated using Ekotrope RATER's energy and code complianceaIgo rithm.
Ekotrope RATER is a RESNET Accredited H ERS Rating Tool. All results are based on data entered by Ekotrope users.
Ekotropedisclaims all liabilityforthe information shown on this report.
405.3
Performanoe-based compliance passes by 1.2%
R40241.2
Air Leakage Testing
402.5
Area -weighted average fenestration SHGC
402.5
Area -weighted average fenestration U -Factor
403.2.2
Duct Testing
Mandatory Checklist
Mandatory code requirements that are not
checked by Ekotrope must be met -
et.R4052
R40 52
Duct Insulation
C-M,
Energy Solutions
As Designed
$2.860
$381
$204
$3,445
$1,819
$0
$5,264
Air sealing is 5.00 ACH at 50 Pa. It must not exceed 7.00 ACH at 50 Pa.
Design exceeds requirements for IECC 2009 Performance compliance by 1.2%.
As a 3rd party extension of the code jurisdiction utilizing these reports, I certify that this energy code compliance document has been created in accordance with the requirements of
Chapter 4 of the adopted International Energy Conservation Code based on Climate Zone 5. If rating is Projected, I certify thatthe building design described herein is consistent with
the building plans, specifications, and other calculations submitted with the permit application. If rating is Confirmed, I certify that the address referenced above has been
inspected/tested and thatthe mandatary provisions of the IECC have been installed to meet or exceed the intentof the IECC or will be verified as such by another party.
Name: Matthew Timmons
Organization: TSI Energy Solutions
Signature:
Date:
7/15/19 at 11:21 AM
Ekotrope RATER -Version 3.1.1.2213
IECC 2009 Performance compliance results calculated using Ekotrope RATER's energy and code complianceaIgo rithm.
Ekotrope RATER is a RESNET Accredited H ERS Rating Tool. All results are based on data entered by Ekotrope users.
Ekotropedisclaims all liabilityforthe information shown on this report.
1761 BEAUFAIN ST
I tTj M- l'1I
CARMEL, IN 46032
Builder: GRADISON DESIGN BUILD
Ceiling Attic, R-38
Above Grade Walls R-13
Foundation Walls R-11
Framed Floor NIA
Slab R-0.0 Perimeter, R-0.0 Under
Infiltration 5 ACH50
Window U -Value: 0.29, SHGC: 0.25
Building Features
Duct Supply R-10.4, Return R-10.0
Duct Leakage to Outside 425 CFM a[7 25Pa (4.94 / 1 DD s.f.)
Total Duct Leakage 680.0 CFM @ 25Pa
Heating Furnace • Natural Gas • 92.1 AFUE
Cooling Air Conditioner • Electric • 13 SEER
Water Heating Water Heater • Natural Gas • 0.97 Energy Factor
As a 3rd party extension of the code jurisdiction utilizing these reports, I certify that this energy code compliance document has been created in accordance with the requirements of
Chapter 4 of the adopted International Energy Conservation Code based on Climate Zone 5. If rating is Projected. I certify that the building design described herein is consistent with the
building plans, specifications, and other calculations submitted with the permit application. If rating is Confirmed, I certify that the address referenced above has been inspectedltested and
that the mandatory provisions of the IECC have been installed to meet or exceed the intentof the IECC or will be verified as such by another party.
Name: Matthew Timmons
Organization: TSI Energy Solutions
Signature:
Date:
7/15/19 at 11:21 AM
Ekotrope RATER - Version 3.1.1.2213
2009 IECC compliance resuits calculated using Ekotrope RATER's energy and code compliance algorithm-
Ekotrope RATER is a RESNET Accredited HERS Rating Tool. All results are based on data erd.ered by Ekotrope users.
Ekotrope disclaims all liability for the information shown on this report.
Energy Code Inspection Checklist
Property Organization
1761 BEAUFAIN ST TSI Energy Solutions
CARMEL, IN 46032 Matthew Timmons
Model: CUSTOM
Community: VILLAGE OF WEST CL Builder
GRADISON DESIGN
VWC212 (AS DESIGNED) BUILD
VILLAGE OF WEST CLAY 212
General Building Information
Conditioned Area (sq ft) 8,598
Conditioned Volume (cubic ft) 80,256
Insulated Shell Area (sq ft) 13,395
Inspection Status
Results are projected
C-M,
Energy Solutions
The building energy model in Ekotrope reflects the building assemblies and energy features listed below. Sometimes energy
features will change in the field from what has been modeled. The inspection process should identify any changes and ensure
that the home continues to meet the applicable energy code.
Slab
Name: BSMT(2,850 s.f., 259 ft. exterior perimeter)
R-0 perimeter insulation, R-0 under slab insulation.
Framed Floor
None Present
Foundation Wall
]l Name: FIN (Exterior Perimeter [ft]: 137, Height Above Grade [ft]: 1, Depth Below Grade [ft]: 8)
R: 10.595
Fully insulated (top to bottom)
Name: UNFIN (Exterior Perimeter [ft]: 81, Height Above Grade [ft]: 1, Depth Below Grade [ft]: 8)
R: 0.00
Fully insulated (top to bottom)
Name: CONDIGAR UNFIN (Exterior Perimeter [ft]: 41, Height Above Grade [ft]: 1, Depth Below Grade [ft]: 8)
R: 0.00
Fully insulated (top to bottom)
Above Grade Wall
] Name: CONDIAMB (4,169 s.f.)
R-0 continuous insulation, R-13 cavity insulation
Insulation Grade: I
Energy Code Inspection Checklist
Property Organization
1761 BEAUFAIN ST TSI Energy Solutions
CARMEL, IN 46032 Matthew Timmons
Model: CUSTOM
Community: VILLAGE OF WEST CL Builder
GRADISON DESIGN
VWC212 (AS DESIGNED) BUILD
VILLAGE OF WEST CLAY 212
El Name: CONDIGARAGE (410 s.f.)
R-0 continuous insulation, R-13 cavity insulation
Insulation Grade: I
El Name: CONDIATTIC (252 s.f.)
R-0 continuous insulation, R-13 cavity insulation
Insulation Grade: I
Rim Joist
Name: RIM CONDIAMB (218 s.f.)
R: 11.691
El Name: BAND CCND/AMB (165 s.f.)
R: 11.691
Name: CONDIGAR (41 s.f.)
R: 11.691
El Name: CONDIATTIC (84 s.f.)
R: 11.691
Roof
Name: SECOND (2,875 s.f.)
R-27.55 continuous insulation, R-10.15 cavity insulation
Insulation Grade: I
Opaque Door
Name: FRONT (24 s.f.)
U: 0.182
Name: GARAGE (24 s.f.)
U: 0.182
El Name: GARAGE (20 s.f.)
U: 0.182
Inspection Status
Results are projected
C-M,
Energy Solutions
2
Energy Code Inspection Checklist
Property
1761 BEAUFAIN ST
CARMEL, IN 46032
Model: CUSTOM
Community: VILLAGE OF WEST CL
VWC212 (AS DESIGNED)
VILLAGE OF WEST CLAY 212
Glazing
Organization
TSI Energy Solutions
Matthew Timmons
Builder
GRADISON DESIGN
BUILD
Inspection Status
Results are projected
Name: FRONT (131 s.f.), U: 0.290, SHGC: 0.25, Orientation: NORTH
C-M,
Energy Solutions
El Name: FRONT RIGHT (24.65278 s.f.), U: 0.290, SHGC: 0.2 5, Orientation: NORTH—WEST
E] Name: FRONT LEFT (24.65278 s.f.), U: 0.290, SHGC: 0.25, Orientation: NORTH—EAST
E] Name: BACK (316 s.f.), U: 0.290, SHGC: 0.25, Orientation: SOUTH
El Name: BACK GD (54 s.f.), U:0.290: SHGC: 0.25, Orientation: SOUTH
El Name: BACK BSMT (18 s.f.), U:0.290, SHGC: 0.25, Orientation: SOUTH
El Name: SLIDER (60 s.f.), U:0.290, SHGC: 0.25, Orientation: EAST
Name: RIGHT SIDE (197 s.f.), U:0.290, SHGC: 0.25, Orientation: WEST
Name: LEFT GD (24 s.f.), U:0.290, SHGC: 0.25, Orientation: WEST
E] Name: LEFT (201 s.f.), U: 0.290, SHGC: 0.25, Orientation: WEST
Name: RIGHT BSMT (42 s.f.), U:0.290, SHGC: 0.25, Orientation: WEST
Skylight
None Present
Mechanical Ventilation
None Present
Mechanical Equipment
El FURNACE • Natural Gas • 100% Heating Load @ 92.1 AFUE 3
Energy Code Inspection Checklist
Property Organization
1761 BEAUFAIN ST TSI Energy Solutions
CARMEL, IN 46032 Matthew Timmons
Model: CUSTOM
Community: VILLAGE OF WEST CL Builder
GRADISON DESIGN
VWC212 (AS DESIGNED) BUILD
VILLAGE OF WEST CLAY 212
El AC • Electric • 100% Cooling Load @ 13 SEER
Inspection Status
Results are projected
El Water Heating • Natural Gas • 100% Hot Water Load @ 0.97 Energy Factor
Air Leakage Control
Test Status: Blower -door tested
House is air -sealed as to achieve 6,688 CFM50 (5.00 ACH50) or less at final blower -door test.
Infiltration Requirements for IECC in Climate Zone 5
2009 IECC Infiltration limit for the design home is 7 ACH50.
2012 IECC Infiltration limit for the design home is 3 ACH50.
2015 IECC Infiltration limit for the design home is 3 ACH50.
Duct Leakage
Duct System 1
NOT entirely within conditioned space, testing required
Leakage to Outside specified as: 425 CFM @ 25Pa (4.941 100 s.f.)
Total Duct Leakage specified as 680.0 CFM @ 25Pa (Post -Construction)
Duct Leakage Code Requirements for IECC
2009 IECC:
Postconstruction Leakage Test: Duct Leakage to Outdoors <= 8 CFM25 / 100 sq ft CFA.
Rough in Test with AHU: Total Duct Leakage <= 6 CFM25 / 100 sq ft CFA.
Rough in Test without AHU: Total Duct Leakage <= 4 CFM251100 sq ft CFA.
2012 IECC and 2015 IECC Prescriptive Path:
Postconstruction Leakage Test: Total Duct Leakage <= 4 CFM25 / 100 sq ft CFA.
Rough in Test with AHU: Total Duct Leakage <= 4 CFM25 / 100 sq ft CFA.
Rough in Test without AHU: Total Duct Leakage <= 3 CFM25 1100 sq ft CFA.
2015 Performance Path (Cost Compliance):
CTSI
Energy Solutions
Leakage testing is required UNLESS all ducts and air handlers are located entirely within the thermal envelope.
There is no pass/fail threshold for duct leakage on the performance path. 4
Energy Code Inspection Checklist
Property
1751 BEAUFAIN ST
CARMEL. IN 45032
Model: CUSTOM
Community: VILLAGE OF WEST CL
VWC212 (AS DESIGNED)
VILLAGE OF WEST CLAY 212
Project Notes
Organization
TSI Energy Solutions
Matthew Timmons
Builder
GRADI SON DESIGN
BUILD
Inspection Status
Results are projected
C",
Energy Solutions
Building Summary
Properly
1761 BEAU FAINST
CARMEL. IN 46032
Model: CUSTOM
Cornmunity: VILLAGE OF WEST CLAY 212
VWC212 [AS DESIGNED]
VILLAGE OF WEST CLAY 212
General Building Information
Organization
TSI Energy Solutions
Matthew Timmons
Builder
GRADISON DESIGN BUILD
Inspection Status
Results are projected
Number Of Bedrooms
4
Number Of Floors
2
Conditioned Floor Area [sq. ft.]
8,598
Unconditioned, attached garage?
Yes
Conditioned Volume [cu. ft.]
80,256
Total Units in Building
1
Residence Type
Single family detached
Floor Number
Model
CUSTOM
Community
VILLAGE OF WEST CLAY 212
Climate Zone
5A
Foundation Wall
Name
C-M,
Energy Solutions
CONDIGAR UNFIN Uninsulated 1 8 41 Exposed Exterior Conditioned Space
FIN R-13 Finished. G1 1 8 137 Exposed Exterior Conditioned Space
UNFIN Uninsulated 1 8 81 Exposed Exterior Conditioned Space
Foundation Wall Library List
Name Feet From Wall Top To Feet From Wall Top To Is Fully Insulated Continuous R -value Cavity R -value Effective Insulation R•
Continuous Insulation Continuous Insulation value
Top Bottom
R-13 Finished, G1 N'A N/A Yes NIA NIR 14.595
Uninsulated N.'A NJA Yes NIA NIA 0.00
Slab
7NameLibraryType
BSMT Uninsulated
I
Perimeter
25S Belove Grade 0 0 2,850.0 f[' Exposed Exterior Conditioned
Space
1
Building Summary
C-M
Energy Solutions
Properly Organization Inspection Status
1761 BEAUFAIN ST TSI Energy Solutions Results are projected
CARMEL. IN 46032 Matthew Timmons
Model: CUSTOM
Community: VILLAGE OF WEST CLAY 212 Builder
GRADISON DESIGN BUILD
VWC212 [AS DESIGNED]
VILLAGE OF WEST CLAY 212
ibrary List
Name Wall Construction slab Completer Underslab Perimeter Perimeter Thermal Break Effective R -value
Type Insulated . Insulation Width [frj Insulation Depth [ftJ Insulation R Value
Uninsulated Wood Frame? Other No ❑ 0 ❑ No ❑.D❑
Framed Floor I
Framed Floor Library List
None Present
None Present
id
Rim Joist
Name
Library Type
Surface Area
Location
BAND CONDIAMB
G1 R-15, OSB
165.0 f[s
Exposed Exterior
CONDIATTIC
G1 R-15, OSB
84.0 f[s
Attic
CONDIGAR
G1 R-15, OSB
41.0 fts
Unconditioned. attached garage
RIM CONDIAMB
G1 14-15, OSB
218.0 fls
Exposed Exterior
Rim Joist Library List
Name Effective Insulation R-Yalm
G" F.-1�- 11.691
0
Building Summary
U-29, SHGC-25
CONDIAMB
❑
Properly Organization
Inspection Status
South
C-MEnergy Solutions
1761 BEAUFAIN ST TSI Energy Solutions
Results are projected
FIN
❑
CARMEL. IN 46032 Mathew Timmons
0
South
18.0 ftz
Model: CUSTOM
U-29, SHGC-25
CONDIAMB
❑
Community: VILLAGE OF WEST CLAY 212 Builder
0
South
54.0 fr'
GRADISON DESIGN BUILD
U-29, SHGC-25
CONLVAMB
❑
VWC212 [AS DESIGNED]
0
North
131.0 12
VILLAGE OF WEST CLAY 212
U-29, SHGC-25
COND+AMB
❑
Name Library type
Surface Color
Surface Area
Location
CONDIAMB G1 R-13 BATT. OSB
Medium
4,169.0 12
Exposed Exterior
CONDIATTIC G1R-13 BATT. OSB
Medium
252.0 f[2
Attic
CONDIGARAGE G1 R-13 Gar Walls
Medium
410.0 f['
Unconditioned, attached garage
Wall Library List
Name
G1 R 13 BATT, OSB
G1 R-13 Gar Walls
Effective R -va I u e
12.516
BACK
U-29, SHGC-25
CONDIAMB
❑
❑
0
South
316.0 ftp
BACK BSMT
U-29, SHGG25
FIN
❑
0
0
South
18.0 ftz
BACK GD
U-29, SHGC-25
CONDIAMB
❑
0
0
South
54.0 fr'
FRONT
U-29, SHGC-25
CONLVAMB
❑
0
0
North
131.0 12
FRONT LEFT
U-29, SHGC-25
COND+AMB
❑
0
0
Northeast
24.7 12
FRONT RIGHT
U-29, SHGC-25
COND+AMB
❑
0
0
Northwest
24.7 ft'
LEFT
U-29, SHGC-25
COND+AMB
❑
0
0
West
2010.ft'
LEFT GD
U-29, SHGC-25
COND+AMB
❑
0
0
West
24.0 ft'
RIGHT BSMT
U-29, SHGC-25
FIN
❑
0
0
West
42.0 ft'
RIGHT SIDE
U-29, SHGG25
COND+AMB
❑
0
0
West
197.0 frl
SLIDER
U-29, SHGC-25
FIN
❑
0
0
East
60.0 fts
3
Building Summary
Properly Organization Inspection Status
1761 BEAU FAIN ST TSI Energy Solutions Results are projected
CARMEL. IN 46032 Mathew Timmons
Model: CUSTOM
Community: VILLAGE OF WEST CLAY 212 Builder
GRADISON DESIGN BUILD
VWC212 [AS DESIGNED]
VILLAGE OF WEST CLAY 212
rMg Library List
Name Shgc Ufiactor
U-29, SHGC-25 0.25 0290
Skylight
None Present
Skylight Library List
None Present
Opaque Door
Name
Library Type Wall Assignment
Foundation Wall
Assignment
FRONT
Steel Door COND+AMB
GARAGE
Steel Door CONDlGARAGE
GARAGE
Steel Door
CONDlGAR
Opaque Door Library List
Name Effective Ufiactoi
tee -•HCl 0.182
C-M,
Energy Solutions
T
Emittance Solar Surface Color Surface Area
Absorptance
Q9 0.75 Medium 24.0 ft' Exposed Exterior
Location
0.9 0.75 Medium 24.0 ft' Exposed Exterior
0.9 0.75 Medium 20.0 ft' Exposed Exterior
Roof Insulation JIL
Name Library Type Attic ExtenorArea Clay or Concrete Roof Surface Color Surface Area Location
6.f.] Tiles
SECOND R-38 BIGwn, GR1 2,875 No Medium 2,875.0 fts Attic
4
Building Summary
Properly
1761 BEAU FAINST
CARMEL, IN 46032
Model: CUSTOM
Cornmunity: VILLAGE OF WEST CLAY 212
VWC212 [AS DESIGNED]
VILLAGE OF WEST CLAY 212
Jp400f Insulation Library List
L Name Has
IR-38 Blown, GR1
Organization
TSI Energy Solutions
Mathew Timmons
Builder
GRADISON DESIGN BUILD
Inspection St3tus
Results are projected
No 38268
Whole House Infiltration
I nfi Itration Measurement Type
5ACH at 50 Pa Blower -door tested
Mechanical Ventilation
I
Lightii
1 Interior
Shelter Class
4
C-M,
Energy Solutions
20 0 20 0 20
Onsite Generation
None
Onsite Generation Library List
None Present
Solar Generation
None Present
0
r�
Building Summary
Properly
1761 BEAU FAINST
CARMEL, IN 46032
Model: CUSTOM
Community: VILLAGE OF WEST CLAY 212
VWC212 [AS DESIGNED]
VILLAGE OF WEST CLAY 212
Organization
TSI Energy Solutions
Mathew Timmons
Builder
GRADISON DESIGN BUILD
olar Generation Library List
None Present
Conditioning Equipment MIA 1111
Name Library Type Heating
AC CA13NA060
0%
Inspection Status
Results are projected
C-M,
Energy Solutions
n
0% Conditioned Space
FURNACE 912SA6012OS24 100% 0% 0% Conditioned Space
Water Heating NPE-2405 0% 0% 100% Conditioned Space
Equipment Type: 912SA6012OS24 MM
Fuel Type
Natural Gas
Distribution Type
Forced Air
Motor Type
PSG {Single Speed}
Heating Efficiency
92.1 AFUE
Heating Capacity [kBtulh]
112
Use default EAE
No
EAE [kWh]
1,247
Equipment Type: CA13NA060
Fuel Type
Distribution Type
Motor Type
Cooling Efficiency
Cooling Capacity [kBtulh]
Equipment Type: NPE-2405
Fuel Type
Distribution Type
Hot Water Efficiency
Tankless?
Hot Water Capacity [kBtulh]
Recovery Efficiency
Electric
Forced Air
PSG (Single Speed)
13 SEER
582
Natural Gas
Hydronic Delivery
0.97 Energy Factor
Yes
1999.
0.99
Building Summary
Properly
1761 BEAU FAINST
CARMEL. IN 46032
Model: CUSTOM
Cornmunity: VILLAGE OF WEST CLAY 212
VWC212 [AS DESIGNED]
VILLAGE OF WEST CLAY 212
stributivn System
Distribution Type
Heating Equipment
Cooling Equipment
Sq. Feet Served
# Return Grilles
Supply Duct R Value
Return Duct R Value
Supply Duct Area [ftJ
Return Duct Area [ft2]
Lea kageto Outdoors
Total Leakage
Total Leakage Duct Test Conditions
Use Default Flow Rate
Duct 1
Duct Location
Percent Supply Area
Percent Return Area
Duct 2
Duct Location
Percent Supply Area
Percent Return Area
Duct 3
Duct Location
Percent Supply Area
Percent Return Area
Duct 4
Duct Location
Percent Supply Area
Percent Return Area
Duct 5
Duct Location
Percent Supply Area
Percent Return Area
Duct 6
Duct Location
Percent Supply Area
Percent Return Area
Ceiling Fan
Has Ceiling Fan
Cfm Per Watt
Organization Inspection Status
TSI Energy Solutions Results are projected
Mathew Timmons
Builder
GRADISON DESIGN BUILD
Forced Air
FURNACE
AC
8598
6
10
10
2321.46
2149.5
425 CFM @ 25Pa (4.941100 s fl
680
Post -Construction
Yes
Conditioned Space
75
75
Attic (well vented, under insulation)
25
25
Conditioned Space
0
Conditioned Space
Conditioned Space
0
Conditioned Space
0
No
100
C-M,
Energy Solutions
7
Building Summary
Properly
1761 BEAU FAINST
CARMEL, IN 46032
Model: CUSTOM
Cornmunity: VILLAGE OF WEST CLAY 212
VWC212 [AS DESIGNED]
VILLAGE OF WEST CLAY 212
Water Fixture Type
Use Default Hot Water Pipe Length
Hot Water Pipe Length [ft]
At Least R3 Pipe Insulation?
Hot Water Recirculation System?
Recirculation System Pipe Loop Length [ft]
Drain Water Heat Recovery?
Clothes Dryer
Fuel Type
Cef
Field Utilization
Clothes Washer
Label Energy Rating
Electric Rate
Annual Gas Cost
Gas Rate
Capacity
I met
Appliances and Controls
Programmable thermostat?
Dishwasher Size
Dishwasher Efficiency
Range/Oven Fuel
Convection Oven?
Induction Range?
Refrigerator Consumption
Organization
TSI Energy Solutions
Matthew Timmons
Builder
GRADISON DESIGN BUILD
Standard
No
60
No
No
24
No
Electric
2.617
Timer Controls
704 kWh/Year
$0.081kWh
$23.00
$0.581Therm
2.874
0.331
Yes
Standard
270 kWh
Electric
No
No
709 kWh/Year
Inspection Status
Results are projected
C-M,
Energy Solutions