HomeMy WebLinkAboutE 001.0 - ELECTRICAL NOTESELECTRICAL GENERAL NOTES I. All electrical work, installation, equipment shall comply with the current N.E.G. (NFPA 10), State and Local Code Requirements, to assure a complete, safe and workable system. 2. All disconnects shall be labeled for identification. Disconnects shall be Installed as per the motor and/or equipment manufoctvrer's recommendations. Verify mounting location, at Job Site, 3. Provide a NEMA 3 outdoor rated disconnect switch and weather -protected, ground-foult protected convenience outlet at each Packaged Roof -Top Unit, Heat Pump or Air Conditioning Compressor location. 4. The electrical system shall be grounded throughout and shall be bonded to the metal pipe cold -water entrance line, building steel and (5) 10 foot copper rod grounding field, at the service entrance. 5. The emergency lighting system shall be a battery pack type, solid state, permanently wired Into a circuit with a lock -on breaker. 6. The Final location of convenience outlets and power requirements shall be verified with the Owner, other trades and mechanical units prior to rough -in. Mount 15" A.F.F., typical unless otherwise noted. Location and mounting heights shall comply with currant AN51 Standard for Accessibility for People with Disabilities. 1. The Electrical Contractor shall coordinate his work with all other trades to assure a complete and workable system. 8. All dimenslons must be verified In the field. 9. The Electrical Contractor shall provide empty P.V.G. conduit with pull -wires for the sound system where shown on the plans. 10. P.V.G. condvit under slab may be used if permitted by the State and Local Codes. 11. Dining and bar area light Fixtures to be verified with Owner. The Electrical Contractor shall submit fixture types for approval, prior to ordering. The E.G. to furnish and install. 12. Mount all switches at 48" A.F.F., typical unless otherwise noted. Location and mounting heights shall comply with current AN51 Standard for Accessibility for People with Disabilities. 15. Final location of floor outlets for television jacks and power shall be coordinated with the Owner and/or AudioNisvol Gonsultant, prior to Installation. 14. The Electrical Contractor shall verify the voltage available For the project, either single or three phase. The E.G. shall be responsible for equipment compatibility with voltage available for the project. The E.G. shall coordinate with all other Trades and Contractors. 15. All wiring shall be In metallic conduit or MG cable type, as per NEC, State and Local requirements. 16. All wire shall be minimum #12 AW6; copper. All 120 V; 20 Amp circuits over 101 In length, shall be #10 AW6, copper. Aluminum or Coder -Glad Aluminum Are Will Not Be Accepted . I1. The Electrical Contractor to wire all water heaters, provided by Plumber. 18. The Electrical Contractor to wire all exhaust fans, provided by others. Provide Z Pile switches, where E.F. is controlled by light switch. 11. The Timeclock to be coordinated and confirmed with the Owner and/or General Contractor. Timeclock shall be 208/240 V; I Phase; 20 Amp.; l-Day; 24-Hour; Day Exclusion copablllty; Reserve Power. Timeclock shall be NEMA I enclosure, control by Photocell. 20, Telephone locations to be coordinated and confirmed with the Owner. The Local Telephone Company to install. LIGHT FIXTURE SCHEDULE MARK SYMBOL MANUFACTURER AND NUMBER MOUNT LAMP REMARKS LED -I 5 LAMP CHANDELIER SUSPENDED (5) 60W PENDANT, (8) 60W EDISON, BRONZE SHADE LED-2 5 LAMP PENDANT SUSPENDED (5) 40W PENDANT, 5RU5HED NICKEL FIN15H LED-3 3 LAMP PENDANT SUSPENDED (3) 60A PENDANT, BRONZE NICKEL FIN15H LED-4 4 LAMP PENDANT SUSPENDED (4) 60W PENDANT, BRONZE NICKEL FIN15H LED-5 3 LAMP PENDANT SUSPENDED (5) 60W PENDANT, BRONZE NICKEL FIN15H LED-6 I LAMP RECESSED SUSPENDED (1) 30W PENDANT, BRUSHED NICKEL FIN15H SELECTIONS TO BE CONFIRMED NITH OPINES LED-1 I LAMP WALL SCONCE SCONCE (U 40W WALL SCONCE, 5RA55 LED-8 LED RIBBON SURFACE (U IOW LED RIBBON K-1 O HAT60 #DL-084-R-115 SUSPENDED (1) 150W PENDANT, BRONZE NICKEL FINISH F-I LITHONIA Fli 2 15W T8 -- Al2 MVOLT OEBIOI5 SUSPENDED (1) 15W T8 8- 2 TUBE CHANNEL, SUSPENDED FROM STRUCTURE, ELEGTRONIG BALLAST F-2 LITHONIA #WA48 3 28W T8 -- Al2 MVOLT GEBIOI5 SUSPENDED (2) T8 28W SUSPENDED 2X4 FIXTURE, ELECTRONIC, BALLAST X-1 Lw DUAL LITE # LZ25N-12V WALL o +90" A.F.F. HAL MP -lb 120/211 VAG, 12 V., 2 HEAD WALL -PACK, NICKEL -CADMIUM X-2 EXI DUAL LITE # LT U R W 3-0 UNIVERSAL LED 120/211 VAG, UNIVERSAL, HEADLESS, REMOTE CAPABLE, NICKEL -CADMIUM BATT. X-3 = DUAL LITE # LXTOS WALL o +90" A.F.F. HAL MR16 120/211 VAG, 12 V., SINGLE REMOTE HEAD, NET LOCATION ELECTRICAL SYMSOL LEISENC) 5YM50L DESCRIPTION SYMBOL DE5CRIPTION SYMBOL I7E5CRIPTION SINGLE RECEPTACLE OUTLET R MICROPHONE JACK BELL DEVICE qp DUPLEX REGEPTACLE OUTLET ® FLOOR MOUNTED MICROPHONE JACK BUZZER DEVICE DUPLEX RECEPTACLE OUTLET MOUNTED HORIZONTALLY CEILING MOUNTED MICROPHONE JACK MOTOR UNIT OUADRUPLEX RECEPTACLE OUTLET TELEPHONE OUTLET ❑J JUNCTION BOX DUAL VOLTAGE RECEPTACLE OUTLET FLOOR MOUNTED TELEPHONE OUTLET [y DISCONNECT SWITCH SPECIAL PURPOSE DEDICATED OUTLET AUDIO / VIDEO OUTLET ❑T TIME CLOCK UNIT ® FLOOR MOUNTED DUPLEX OUTLET RECEPTACLE (i)wl GEILIN6 MOUNTED AUDIO / VIDEO OUTLET i — CONDUIT SYSTEM CONGEALED IN WALL OR GEILIN6 Q® GEILIN6 MOUNTED OUTLET RECEPTACLE = DATUM OUTLET CONDUIT SYSTEM CONGEALED IN FLOOR CONDUIT 51 2" ABOVE FINISH FLOOR No FLOOR MOUNTED DATUM OUTLET HOME RUN TO PANEL BOARD 67FI GROUND FAULT INTERRUPTION DEVICE $ LIGHT 5WITGH O-Ly THERMOSTAT ( VERIFY w/ MECHANICAL PLANS ) UUP WEATHER PROTECTED DEVIGE $3 Y4 3-WAY LIGHT 5WITGH ® FAN IT GEILIN6 EXHAUST FAN +42" DISTANCE DEVICE ABOVE FINISH FLOOR / GRADE 4-WAY LIGHT SNITCH ®L F EXHAUST FAN / LIGEXH HT COMBO UNIT ❑® REMOTE MULTI -SCENE CONTROL PANEL �U DIMMER 5WITGH �5 / CORNER MOUNTED MOTION DETECTOR ' "" - - - "' " -" rMi'llA. RFLFASFO FOR CONSTRUCTION �P LIGHT 5WITGH H/ PILOT LIGHT / MS Y GEILIN6 MOUNTED MOTION DETECTOR Subject to compliance with all regulations of State and Local Codes City of Camel PH: DATE: Li 16/ 1 `J LIGHTS LT502-ILZ O 0 o LL L4 SWITCH LOCATE AS NOTED ry POWER ELEC, R CAL NOfi 5 AND SCHEDULES EI.O O i-r �p ry ryI, U ZM J U Z 4 O e �Q- M N E-t NCali