HomeMy WebLinkAboutElectrical E2.0MECHANICAUPLUMBING EQUIPMENT CONNECTION SCHEDULE
NAME
VOLTAGE
PHASE
MCA
MOCP
CONDUIT/WIRE
PANEL
GRCUIT#
NOTES
EXAHUA
480
3
ETR
ETR
ETR
ETR
ETR
3
EXAHU-2
480
3
ETR
ETR
ETR
ETR
ETR
3
EXCU-1
480
3
ETR
ETR
ETR
ETR
ETR
3
EX4CLL2
208
3
ETR
ETR
ETR
ETR
ETR
3
ECH-1
208
1
19.2
25
2910,1#10GND-3/41,C
LPB
40,42
1
EX-EF-1
120
1
ETR
ETR
ETR
ETR
ETR
3
EF-2
120
1
0.1
20
2912,1#12GND-3/4"C
EPA
5
1
EF-3
120
1
0.1
20
2#12,1#12GND-3/4"C
EPA
5
1
EF-4
120
1
0.1
20
2#12,1#12GND-3/4"C
LPA
5
1
WHA
480
3
9.6
15
3#12,1#12GND-3/4"C
H
2O,22,24
2
NOTES'
1. EQUIPMENT PROVIDED WITH INTEGRAL DISCONNECT SWITCH.
2. PROVIDE CODE -SIZED DISCONNECT SWITCH AT EQUIPMENT.
3. EXISTING EQUIPMENTTO REMAIN, MAINTAIN ALL ASSOGATED CONDUIT AND WIRING.
RELEASED FOR CONSTRUCTION
Subject to compliance with all regulations
of State and Local Codes
City of Camel
�VT�12'�B*VAWML
DATE: \ 08/15/19
GENERAL SHEET NOTES
1. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING INCREASED WIRE SIZES
DUE TO FIELD CONDITIONS RESULTING IN EXTENDING CONDUIT PATHS. GROUND WIRE SITES ARE
REQUIRED TO BE ADJUSTED PER ARTICLE 2500F THE NEC WHEN WIRES ARE INCREASED FOR VOLTA(
DROP.
2. ALL BRANCH CIRCUIT WIRING SHALL BE#12AWG UNLESS OTHERWISE NOTED AND IN CONDIAMINT.
EACH BRANCH CIRCUIT SHALL HAVE A SEPARATE NEUTRAL CONDUCTOR
O SHEET KEYNOTES
1 PROVIDE JUNCTION BOX,SWITCH, AND WHIP FOR STORE SIGN. ADDITIONAL JUNCTION BOXES, CONDUIT,
AND WIRING MAY BE REQUIRED FORA COMPLETE INSTALLATION OF SIGN. COORDINATE ALL
REQUIREMENTS WITH SIGN VENDOR.
2 PROVIDE SHOW WINDOW RECEPTACLE PER NEC REQUIREMENTS. RECEPTACLE SHALL BE INSTALLED
WITHIN 18' OF THE TOP OF THE SHOW WINDOW FOR EACH 12' OF SHOW WINDOW. VERIFY EXACT
LOCATION WITH ARCHITECT.
3 LOCATION OF TIME CLOCKSICONTACTORS. REFER TO DETAIL 21E2.0 AND WE2.0 FOR ADDITIONAL
INFORMATION.
4 LOCATION OF EXISTING TELCO DEMARK, MAINTAIN EXISTING PUNCH DOWN BLOCK AND PLYWOOD
BACKWARD FOR TELEPHONENATA SERVICES. COORDINATE ALL REQUIREMENTS WITH OWNER.
5 EXISTING ELECTRICAL EQUIPMENT TO REMAIN.
6 PROVIDE RECESSED RECEPTACLE AND DATA JACK FOR MONITOR. COORDINATE EXACT LOCATION AND
MOUNTING HEIGHT WITH ARCHITECT.
7 CONNECT FIRE ALARM DEVICE TO EXISTING SYSTEM. REFER TO DETAIL 11E0.1 FOR ADDITIONAL
INFORMATIGN. DEVICE SHALL MATCH EXISTING SYSTEM MANUFACTURER
8 REFER TO MECHANICAUPLUMBING EQUIPMENT SCHEDULE ON THIS SHEET FOR CIRCUITING
INFORMATION. COORDINATE EXACT LOCATION WITH MECHANICAL CONTRACTOR.
0
0
N
KEY PLAN
CURRAN
ARCHITECTURE
5719 LAWTON LOOP EAST DR STE 212
INDIANAPOLIS, IN 46216
O 317.288. 0681
IF :: 317.288.0753
CONSULTANT
DRAWN BY: JDJ CHECKED BY: JSD
OT/E/S
ENGINEERING
25760 First Street
Cleveland, OH 44145
P 440 871 2410
F 440 871 7954
tesengineering.com
CERTIFICATION
STATE OF
7/11/2019
THIS DRAWING AND THE IDEAS. DESIGNS
AND CONCEPTSCONTAINEDHERFIN ARE
THE EXCLUSIVE INTELLECTUAL PROPERTY
OF CURRAN ARCHITEC RE, AND ARE NOT
TO BE USED OR REPRODUCED, WHOLE OR
IN PART, WITHOUT THE WRITTEN
CONSENT OF CURRAN ARCHITECTURE
8 COPYFSM 2019, OWN ARMRECUFE
INTERIOR BUILD -OUT FOR:
F45 CLAY TERRACE
CLAY TERRACE BLVD.
E14
CARMEL, IN
POWER PLAN
ISSUE DATES
ISSUED
FOR REVIEW
4-13-19
ISSUED
FOR PERMIT
7-10-19
PROJECT NUMBER: 180364
E2.0