HomeMy WebLinkAboutHVAC M0.2MOTORIZED DAMPER TO CLOSE
UPON DEACTIVATION OF AHU
RA OPENING UP 8" IN
VERTICAL FROM RETURN M
DUCT. SEE PLAN FOR SIZE
Oy9
D
REFRIGERANT
PIPING
I AH
L ALL)
DRAIN LINE
FROM UNIT WI FLEX
CONNECTIONS TO
RETURN AIR DUCT WITH FLEX CONNECTION TO
UNIT, DUCT TO BE PROVIDED WITH 1" ACOUSTIC
LINING, REFER TO PLANS FOR SIZES —
ANGLE SUPPORT FOR
AHU AND DRAIN PAN
RELEASED FOR CONSTRUCTION
Subject to compliance with all regulations
of State and meal Codes
City Bf Camel
�M;R��BtB,A�DA�1
DATE: 08/15/19
3" DEEP WATERTIGHT DRAIN PAN,
PAN SHALL BE 3' LARGER THAN
UNIT ON ALL SIDES
SEE STRUCTURAL DRAWINGS FOR
CONNECTION DETAILS AND FURTHER
INFORMATION
VIBRATION ISOLATOR (TYPICAL)
A
SUPPLY AIR DUCT WITH FLEX
CONNECTION TO UNIT, REFER
TO PLANS SIZES
SHUTDOWN UNIT WHEN CONDENSATE WATER
ENTERS DRAIN PAN. LOCATE SENSOR AT LOW
POINT IN PAN.
DETAIL NOTES
1. MC SHALL LOCATE AHU TO MAINTAIN A MINMUM 24" SERVICE CLEARANCE IN FRONT OF UNIT FOR MOTOR
ACCESS PANEL FROM ANY EXISTING BUILDING STRUCTURE OR PIPING EXTENDING DOWN TO CEILING
PER MANUFACTURERS RECOMMENDATIONS. MC SHALL COORDINATE WITH OTHER TRADES TO KEEP THIS
SERVICE AREA CLEAR OF ANY NE:V P PING OR CONDUIT.
1
SPLIT SYSTEM MIN OA AHU DETAIL
M0.2
SCALE: NONE
RECTANGULAR
DUCTWORK
VARIES
MINIMUM TAKE OFF
AREA 1.25 TIMES
BRANCH DUCT AREA
RECTANGULAR TO ROUND
"BUCKLEY FITTING"
RECTANGULAR
DUCTWORK
4'
BRANCH DUCT HEIGHT
DIMENSION 2' LESS THAN
MAIN DUCT HEIGHT DIMENSION
RECTANGULAR TO RECTANGULAR
ROUND
DUCTWORK
LOW -LOSS TEE FITTING OR SADDLE
2
DUCT BRANCH TAKE -OFF DETAIL
MU
SCALE: NONE
HANDTIGHT
PLUG
COPPER CONDENSATE DRAIN LINES
TO PREVENT AHU FROM RUST
DAMAGE, DO NOT USE PVC FOR
CONDENSATE BRAIN LINES, KEEP
VERTICAL CONDENSATE LINE A
MINIMUM OF T FROM AHU
4
AHU
CONDENSATE
DETAIL
110.2
SCALE:
NONE
nna.naLmnalay
FULL RADIUS ELBOW RECTANGULAR ELBOW
15, MAX T}
AIRFLOW /
TRANSITION LENGTH
TO BE 18" MIN
DIVERGING FLOW
LOW VELOCITY ELBOWS
15, MAX
AIR FLOW
TRANSITION LENGTH
TO BE 18' MIN
CONTRACTING FLOW
RECTANGULAR TO RECTANGULAR TRANSITIONS
III
FULL HALIUs WHercE
POSSIBLE (R- W)
W
ELBOWS
456 MAXIMUM
3
LOW
VELOCITY TRANSITIONS AND OFFSETS
Pill
SCALE:
NONE
MAX. 12" TO
BRANCH
CONNECTION
VOLUME DAMPER IF
INDICATED ON PLAN
1-112-THICK FIBERGLASS
INSULATION WI FOIL FACING
SUPPLY AIR DIFFUSER
GALVANIZEDSHEET
METAL DUCT
CED ELBOW
METAL OR VINYL ADJUSTABLE STRAP CLAMP
(TYR 2 PLACES)
INSULATED FLEXIBLE CONNECTION IN
VERTICAL ONLY (MAX. V)
r LAYINCEILING
DETAIL NOTES
1. CO NOT LOCATE DAMPERS ABOVE DRYWALUINACCESSIBLE CEILING LOCATIONS.
5
CEILING
DIFFUSER MOUNTING
DETAIL
M0.2
SCALE'. NONE
CURRAN
ARCHITECTURE
5719 LAWTON LOOP EAST DR STE 212
INDIANAPOLIS, IN 46216
O :: 317. 288.0681
F :: 317. 288. 0753
CONSULTANT
DRAWN BY: STK CHECKED BY: KDH
*T/E/S
ENGINEERING
25760 First Street
Cleveland, OH 44145
P 440 871 2410
F 440 8717954
tesengineering.com
CERTIFICATION
STATE OF
7/11/2019
THIS DRAWING AND THE IDEAS. DESIGNS
AND CONCEPTS CONTAINED HEREIN ARE
THE EXCLUSIVE I NTELLECTUAL PROPERTY
OF CURRAN ARCH ITECTJ RE, AND ARE NOT
TO BE USED OR REPRODUCED, WHOLE OR
IN PART, WITH OUT THE WRITTEN
CONSENT OF CURRAN ARCHITECTURE.
0 COPIRI 2019, CURMN ARCHITERUFE
INTERIOR BUILD -OUT FOR:
F45 CLAY TERRACE
CLAY TERRACE BLVD.
E14
CARMEL, IN
MECHANICAL DETAILS
ISSUE DATES
ISSUED
FOR REVIEW
413-19
ISSUED
FOR PERMIT
7-10-19
PROJECT NUMBER: 180364
M 0.2