HomeMy WebLinkAboutHVAC M0.3EXISTING TO REMAIN AIR HANDLING UNIT SCHEDULE
SUPPLY FAN DATA
DX COOLING COOLING COIL DATA
ELECTRIC HEATING DATA
UNIT CHARACTERISTICS
TAG
SERVICE
MFR
MODEL No.
NOMINAL
MIN CA
(CFM)
NOTESIACCESSORIES
AIRFLOW
ESP
MOTOR
FAN
EAT°DBINB
LAT °DBI°WB
SENSIBLE
TOTAL
COOLING
EAT/FAT
INPUT
OUTPUT
HEATING
VOLTAGE
OPERATINGTONS
(CFM)
(IN WC)
(HP)
(RPM)
(°F)
(°F)
(MBH)
(MSH)
STAGES
(°F)
(KW)
(MSH)
STAGES
(V-0-H2)
UNIT MCA
UNIT MOCP
WEIGHT
(LBS)
AHU-1
BOH AND REAR WORKOUT
CARRIER
CAELHEAT008
75
400
2500
O]5
2.4
111
80I61
SSI54
21
89.S
2
58409.0
15
51.2
2
460-3d0
25.8
30.0
385
1
All
RETAIL AND WORKOUT
CARRIER
DAELHEATD66
]5
630
2400
0.75
2.4
]12
80167
55154
68.9
845
2
584I/0.0
75
51.2
2
HERO-3d0
25.8
30.0
385
1
NOTESIACCESSORIES
1. UNIT IS EXISTING TO REMAIN. CLEAN AND REFURBISH EXISTING AHU TO LIKE NEW CONDITION.
EXISTING TO REMAIN CONDENSING UNIT SCHEDULE
CONDENSING
FAN DATA
ELECTRICAL DATA
OPERATING
TAG
SERVICE
LOCATION
MFR
MODEL No.
EERIIEER
NOMINAL
WEIGHT
NOTESIACCESSORIES
(SEER)
TONS
LEE)
QUANTITY
(OLTAG
MCA
MOCP
Cu1
AHU-1
ROOF
CARRIER
38ARZ008
-
]5
1
4ER0-3d0
20.3
25
392
1
CU-2
All
ROOF
CARRIER
WANZ008
-
75
1
HERO-3d0
203
25
392
1
NOTESIACCESSORIES
1. UNIT IS EXISTING TO REMAIN. CLEAN AND REFURBISH EXISTING CO TO LIKE NEW CONDITION.
OUTSIDE AIR SCHEDULE
ZONE DATA
SYSTEM DATA
ZONENAME
FLOOR
AREA
(SF)
REQUIRED
OUTSIDE AIR
(CFWSF)
OCCUPANCY
REQUIRED
OUTSIDE AIR
(CFWPERSON)
BREATHINGZONE
OUTSIDEAIR
(CFM)
ZONEAIR
DISTRIBUTION
EFFECTIVENESS
REQUIRED
OUTSIDEAIR
(CFM)
SUPPLY
AIR
(CFM)
OUTDOOR AIR
FRACTION
SYSTEM NAME
SYSTEM
VENTILATION
EFFICIENCY
REQUIRED
OUTSIDEAIR
(CFM)
DELIVERED
OUTSIDEA IR
(CFM)
CORRIDOR
139
0.06
0
0
B
0.8
10
200
0.050
AHU-1
0.900
393
IN
MENS SHOWER
68
0
0
0
D
0.8
0
W
0000
REAR CORRIDOR
200
006
0
0
12
0.8
15
200
0075
REARSTOCKA
615
0.12
1
0
74
0.8
93
600
0.155
REAR STOCK
365
0.12
1
0
44
0.8
55
3W
0.183
STOCK RR
m
0
0
0
D
0.8
0
0
0000
STORAGE
118
1 0.12
1 1
1 0
1 14
1 0.8
1 18
100
0,180
WOMENS SHOWER
68
0
0
0
D
D.B
0
SO
amo
WORKOUT REAR
670
0.3
18
0
201
0.8
252
1000
0.252
RETAIL LOBBY
391
0.12
6
7.5
92
0.8
115
1000
0,115
AH0.2
0]90
620
830
WORKOUT FRONT
1341
0.3
34
0
402
0.8
503
1400
0359
NOTES
SPACE OUTSIDE AIR REQUIREMENTS BASED ON 20121MC
AIR DISTRIBUTION SCHEDULE
TAG
SERVICE
MOUNTING
MFR
MODEL No.
MODULE/
DIFFUSER SIZE
FRAMUBOROER
DAMPER
NOTES/
ACCESSORIES
S1
SUPPLY
CEILING
TITUS
OMNI
24'x24"
LAYIN-
12
S2
SUPPLY
CEILING
TITUS
OMNI
12'02'
#1 SURFACE
-
1-3
S3
SUPPLY
DUCT
TITUS
30ORL
NECK SIZE+Z
#1 SURFACE
AS151
S4
SUPPLY
WALL
TITUS
30ORL
8'x6'
#1 SURFACE
-
1
Rl
RETURN
CEILING
TITUS
SOT
24'x2ar
LAYIN-
1,3
R2
RETURN
CEILING
TITUS
SOF
12"x12'
LAY -IN
-
1,3
R3
RETURN
WALL
TITUS
35ORL
NECKSIZE+Z'
#1 SURFACE
-
1
NOTESIACCESSORIES
1. FINISH - MATCH TO CEILING COLOR
2 SECTORIZING BAFFLE (SB) AS REQUIRED BY DIRECTIONAL SHADING ON PLAN, OTHERWISE FOUR (4) WAY BLOW
3. ALUMINUM RAPID MOUNT FRAME (TRIM)
RELEASED FOR CONSTRUCTION
Subject to compliance with all regulations
of State and Local Codes
City of Camel
�VT�12'�B*VAWML
DATE: \ 08/15/19
ELECTRIC HEATER SCHEDULE
ELECTRIC HEATING DATA
FAN DATA
UNIT CHARACTERISTICS
TAG
SERVICE
MFR
MODELNI
MOUNTING
NOTESIACCESSORIES
INPUT
OUTPUT
HEATING
AIRFLOW
ESP
FAN
VOLTAGE
UNIT
OPERATING
(KW)
(MBH)
STAGES
(CFM)
(IN WC)
(RPM)
N O Al
FLAMCA
WEIGHT
(LBS)
ECH 1
ENTRY
MARKEL
F3386D-RP
CEILING
4.0
136
1
175
0.2
700
208-1-60
192
22
115
NOTESIACCESSORIES
1. ELECTRIC DISCONNECT
2. INTEGRAL THERMOSTAT WITH CONTROL TRANSFORMER
3, LOW VOLTAGE CONTROL FOR ELECTRIC HEATERS
4. LOUVERED DISCHARED
5, HIGH LIMIT SWITCH
EXHAUST FAN SCHEDULE
AIRFLOW
ESP
MOTOR
FAN
VOLTAGE
OPERATING
TAG
SERVICE
MFR
MODEL No.
(CFM)
(IN WC)
ON)
DRIVE
(RPM)
SONGS
(V-O-Hz)
WEIGHT
NOTESIACCESSORIES
(LBS)
EFI ETR
STOCK RESTROOM
GREENHECK
ETR
100
0.25
120-1d0
9
EF-2
SHOWERROOM
GREENHECK
SP-AW 130-VG
100
0.25
12
DIRECT
960
04
120-1d0
12
1d
EF-3
SHOWERROOM
GREENHECK
SP-AW 130-VG
100
0.25
12
DIRECT
960
04
120-1d0
12
1d
EF4
SHOWERROOM
GREENHECK
SP-AW 130FVG
100
0.25
12
DIRECT
960
04
120-1d0
12
1d
NOTESIACCESSORIES
1, AMCA SEAL & U.L. LISTED
2. DISCONNECT SWITCH - NEMA 1- FACTORY MOUNTED & WIRED
3. BACKDRAFT DAMPER -GRAVITY
4. FAN SPEED CONTROLLER- FACTORY MOUNTED & WIRED
5. GRILLE- WHITE PLASTIC
6, FAN CONTROLLED BY OCCUPANCY SENSOR
7. HANGING VIBRATION ISOLATORS
8. APPROVED ALTERNATES: COOK, HARTZEL, STROBIC AIR, AND COOL AIR
9. EXHAUST FAN IS EXISTING TO REMAIN. CLEAN AND REFURBISH TO LIKE NEW CONDITION.
CURRAN
ARCHITECTURE
5719 LAWTON LOOP EAST DR STE 212
INDIANAPOLIS, IN 46216
O :: 317.288.06,81
F :: 317.288.0753
CONSULTANT
DRAWN BY: STK CHECKED BY: KDH
OT/E/S
ENGINEERING
25760 First Street
Cleveland, OH 44145
P 440 871 2410
F 440 8717954
tesengineering.com
CERTIFICATION
STATE OF
7/11/2019
THIS DRAWING AND THE IDEAS. DESIGNS
AND CONCEPTS CONTAINED HEREIN ARE
THE EXCLUSIVE I NTELLECTUAL PROPERTY
OF CURRAN ARCHITECTURE, AND ARE NOT
TO BE USED OR REPRODUCED, WHOLE OR
IN PART, WITH WT THE WRITTEN
CONSENT OF CURRAN ARCH ITECTME.
0 COPIR'LH72019, CURMN ARCHITECTURE
INTERIOR BUILD -OUT FOR:
FE
F45 CLAY TERRACE
CLAY TERRACE BLVD.
E14
CARMEL, IN
MECHANICAL
SCHEDULES
ISSUE DATES
ISSUED
FOR REVIEW
413-19
ISSUED
FOR PERMIT
7-10-19
PROJECT NUMBER: 180364
M 0.3