HomeMy WebLinkAboutHVAC M1.0GENERAL SHEET NOTES 1. EXISTING MECHANICAL INFORMATION IS BASED ON LIMITED EXISTING BUILDING DRAWINGS AND FIELD WORK. THE CONTRACTOR SHALL FIELD VERIFY THE EXISTING CONDITIONS FOR ACCURACY. CONTRACTOR SHALL NOTIFY OWNER, ARCHITECT AND ENGINEER OF ANY SITUATIONS THAT MODIFY OR INCREASE THE SCOPE OF WORK FROM THAT IS DESCRIBED IN THE DOCUMENTS. 2, ANYTHING NOT NOTED AS EXISTING IS TO BE FURNISHED AND INSTALLED AS PART OF THIS PROJECT. 3, REFER TO DRAWINGS AND PROJECT SPECIFICATIONS OF OTHER DISCIPLINES FOR ADDITIONAL PROJECT INFORMATION AND REQUIREMENTS. NOTIFY ENGINEER OF ANY CONFLICTS BETWEEN THE INFORMATION PRESENTED AND FIELD CONDITIONS. 4. PRIOR TO ANY ISOLATION OF SYSTEMS, SHUTDOWNS OR DEMOLITION THE CONTRACTOR SHALL PROVIDE NECESSARY INVESTIGATION AND NOTIFY THE FACILITIES ENGINEERINGIMAINTENANCE PERSONNEL OF WORK TO BE PERFORMED SO AS TO AVOID ANY DETRIMENTAL SHUTDOWN OF SYSTEMS TO ADJACENT SPACES. 5, PROTECT EQUIPMENT, FIXTURES, PIPING, DUCTWORK,ETC. INDICATED TO REMAIN AGAINST DAMAGE AND SOILING DURING SELECTIVE DEMOLITION. WHEN PERMITTED BY THE ARCHITECT, ITEMS MAY BE REMOVED TO A SUITABLE, PROTECTED STORAGE LOCATION DURING SELECTIVE DEMOLITION AND THEN CLEANED AND REINSTALLED IN THEIR ORIGINAL LOCATIONS. 6, WHERE PIPE ,DUCTWORK, INSULATION, FIXTURES OR EQUIPMENT TO REMAIN IS DAMAGED OR DISTURBED, REMOVE THE DAMAGED PORTIONS AND INSTALL NEW PRODUCTS OF EQUAL CAPACITY AND QUALITY. WHERE IDENTICAL MATERIALS ARE UNAVAILABLE OR CANNOT BE USED, USE MATERIALS WHOSE INSTALLED PERFORMANCE EQUALS OR SURPASSES THAT OF THE EXISTING MATERIALS. 7, MAINTAIN AND RESTORE, IF INTERRUPTED BY DEMOLITION OR IN THE PATH OF NEW CONSTRUCTION, ALL UTILITIES PASSING THROUGH AND SERVING OUTSIDE OF DEMOLITION AREA. 8, MECHANICAL SYSTEMS INSTALLATIONS MUST MAINTAIN INTEGRITY OF WALLS, PARTITIONS AND FLOORS DESIGNATED AS EITHER FIRE RATED OR"SMOKE TIGHT". PROVIDE CODE REQUIRED THROUGH - PENETRATION RESISTOR SYSTEM AT RATED OR SMOKE TIGHT ASSEMBLIES WHERE FIRE DAMPERS ARE NOT REQUIRED. COORDINATE W/ARCHITECTURAL PLANS AND GENERAL CONTRACTOR. 9. SPACE ABOVE CEILING IS INDICATED TO BE A RETURN AIR PLENUM. CONSTRUCTION MATERIALS ABOVE CEILING SHALL BE NONCOMBUSTIBLE, OR HAVE A MAXIMUM 25 FLAME SPREAD AND 50 SMOKE DEVELOPMENT FINISH RATING. WIRING SHALL BE LABELED PLENUM RATED PER NFPA 70. 12. NOTHING IS PERMITTED TO BE ATTACHED TO, SUSPENDED FROM, OR PENETRATE THE ROOF DECK. CONTRACTOR MAY ATTACH TO OR SUSPEND FROM THE TOP CHORD OF THE JOIST OR THE STRUCTURAL STEEL WHICH EXISTS ABOVE THE SPACE. 13. COORDINATE FINAL CONDENSING UNIT LOCATIONS WITH LANDLORDS STRUCTURAL ENGINEER. UNITS TO BE LOCATED WITHIN STRUCTURAL BAY. PROVIDE 10' CLEARANCE FROM OUTSIDE AIR INTAKE TO ANY EXHAUSTNENTS ON ROOF, 14, GENERAL CONTRACTOR TO LABEL ALL EQUIPMENT WITH TENANT NAME, SPACE NUMBER AND EQUIPMENT IDENTIFICATION (RTU-1, ETD), PER MALL SPECIFICATIONS AND STANDARDS. 15. REFER TO MALL CRITERIA MANUAL FOR ADDITIONAL STANDARDS AND REQUIREMENTS. 16. COORDINATE ALL THERMOSTAT AND SENSOR LOCATIONS WITH FURNITURE LAYOUT AND ARCHITECTURAL PLANS. DEVICES ARE TO BE INSTALLED AND WIRED BY THE HVAC CONTRACTOR, MOUNT PER ADA REQUIREMENTS. 17. ALL EXPOSED DUCTWORK TO BE PAINTED. REFER TO ARCHITECTURAL PLANS. 18. CHANGES IN DUCT SIZES SHALL BE MADE BY UNIFORM TAPER SECTION WITH A MAXIMUM INCLUDE ANGLE OF DIVERGENCE OF 15 DEGREE. 19. DUCT SIZES INDICATED REPRESENT EXTERNAL SHEET METAL DIMENSIONS AND INCLUDE ALLOWANCE FOR INTERNAL INSUATION. 20. SUPPLY AIR DUCTWORK NOT LOCATED IN A RETURN AIR PLENUM OR EXPOSED SHALL BE EXTERNALLY INSULATED. ALL OUTSIDE AIR DUCTWORK NOT EXPOSED SHALL BE EXTERNALLY INSULATED. 21. BRANCH DUCTS SERVING DIFFUSERS SHALL BE SIZED TO MATCH DIFFUSER NECK SIZE INDICATED UNLESS NOTED OTHERWISE. 22. PROVIDE ACCESS HATCHES (24"x24') FOR ALL MECHANICAL EQUIPMENT LOCATED ABOVE A HARD CEILING. COORDINATE WIARCHITECTURAL CEILING PLANS. 23. PITCH POCKETS ARE NOT PERMITTED ON THE ROOF FOR CONDENSATE DRAINS, POWER OR CONTROL WIRING. ALL CONNECTIONS ARE TO BE MADE INSIDE THE EQUIPMENT CURB OR THROUGH PRE -MANUFACTURED PIPING CURB. 11 LIMITED ABOVE CEILING CLEARANCES EXIST. COORDINATE LOCATION AND ELEVATION OF MECHANICAL 24. CONTRACTOR MUST REPLACE ALL AIR FILTERS IN AIR HANDLING UNITS WITH NEW CLEAN FILTERS WORK WITH ALL DUCTWORK, SPRINKLERS LIGHT FIXTURES, AND OTHER CEILING BUILT-IN FIXTURES. BEFORE AIR BALANCING AND PRIOR TO FINAL TURNOVER TO TENANT. CONTACT ENGINEER OR ARCHITECT IMMEDIATELY SHOULD ANY CONFLICT ARISE. ^^^ ^^^^'^ RELEASED FOR CONSTRUCTION Subject to compliance with all regulations of State and Local Codes City d Camel �VT�12'�B*VAWMC_ DATE: \ 08/15/19 O SHEET KEYNOTES 1 EXISTING TO REMAIN AIR HANDLING UNIT SUSPENDED FROM STRUCTURE. REFER TO SHEET M028 M03 FOR MORE INFORMATION 2 CONNECT SUPPLY,RETURN, AND OUTSIDE AIR DUCTS TO FULL SIZE OF AIR HANDLING UNIT FRONT SUPPLY, TOP RETURN, AND REAR OUTSIDE AIR CONNECTIONS WITH FLEX CONNECTION AT UNIT. TRANSITION AS REQUIRED PER SPECIFICATIONS. 3 SMOKE DETECTOR MOUNTED IN RETURN DUCT OF AIR HANDLING UNIT. DETECTOR SHALL BE PROVIDED AND WIRED BY ELECTRICAL CONTRACTOR, MOUNTED BY MECHANICAL CONTRACTOR. 4 PROVIDE WIRE MESH CAP ON TOP OF 26'x24' RETURN OPENING. 5 TEMPERATURE AVERAGING SENSOR MOUNTED ON WALL AT 60" ARE. COORDINATE EXACT LOCATION WITH FURNITURE LAYOUT AND ARCHITECTURAL PLANS. SENSOR SHALL BE WIRED TO CONTROL INTERFACE ON ASSOCIATED AIR HANDLING UNIT. 6 THERMOSTAT MOUNTED ON WALL AT 48'AFF. COORDINATE EXACT LOCATION WITH FURNITURE LAYOUT AND ARCHITECTURAL PLANS. THERMOSTAT SHALL BE WIRED TO CONTROL INTERFACE ON ASSOCIATED AIR HANDLING UNIT. 7 CONNECT I2.0 EXHAUST DUCT TO EXISTING LANDLORD EXHAUST DUCTWORK. 8 COORDINATE WITH GC TO PROVIDE 1' UNDERCUT ON DOOR, 9 STOCK RESTROOM IS EXISTING TO REMAIN. CLEAN AND REFURBISH ALL GRILLES AND MECHANICAL ITEMS IN THIS AREA TO LIKE NEW CONDITION. 10 EXTEND AND CONNECT NOTED SIZE OUTSIDE AIR CONNECTION TO OUTSIDE AIR MAIN. PROVIDE MOTORIZED DAMPER TO SUPPLY OUTSIDE AIR DURING OCCUPIED MODE. N KEY PLAN CURRAN ARCHITECTURE 5719 LAWTON LOOP EAST DR STE 212 INDIANAPOLIS, IN 46216 O :: 317.288.0681 F :: 317.288.0753 CONSULTANT DRAWN BY: ELK CHECKED BY: RICH *T/E/S ENGINEERING 25760 First Street Cleveland, OH 44145 P 440 871 2410 F 440 8717954 tesengineering.com CERTIFICATION STATE OF 7/11/2019 THIS DRAWING AND THE IDEAS. DESIGNS AND CONCEPTS CONTAINED HEREN ARE THE EXCLUSIVE I NTELLECTUAL PROPERTY OF CURRAN ARCHITECT JRE, AND ARE NOT TO BE USED OR REPRODUCED. WHOLE OR IN PART, WITH OUT THE WRITTEN CONSENT OF CURRAN ARCHITECTURE. 0 COP USHT 2019, CURR9N AROH1TECrJRE INTERIOR BUILD -OUT FOR: FE F45 CLAY TERRACE CLAY TERRACE BLVD. E14 CARMEL, IN MECHANICAL PLAN ISSUE DATES ISSUED FOR REVIEW 413-19 ISSUED FOR PERMIT 7-10-19 PROJECT NUMBER: 180364 M 1.0