HomeMy WebLinkAboutPlumbing P1.0RELEASED FOR CONSTRUCTION
Subject to compliance with all regulations
of State and Local Codes
City Bf Camel
�VT�12'�B*VAWMC_
DATE: \ 08/15/19
Q SHEET KEYNOTES
GENERAL SHEET NOTES
1 112' DOMESTIC COLDWATER DOWN IN WALL TO WG1.
A.
FIELD VERIFY EXACT CONDITIONS AND ROUTING OF WORK. CONTACT ENGINEER OR ARCHITECT
IMMEDIATELY SHOULD ANY CONFLICT ARISE.
2 112' DOMESTIC COLDWATER AND HOT WATER DOWN IN WALL TO LAV4. PROVIDE THERMOSTATIC MIXING
VALVE.
B.
EXISTING PLUMBING INFORMATION IS BASED ON EXISTING BUILDING DRAWINGS AND LIMITED FIELD
WORK. THE CONTRACTOR SHALL FIELD VERIFY THE EXISTING CONDITIONS FOR ACCURACY. NO
3 712'DOMESTIC COLD WATER AND HOT WATER DOWN IN WALL TO MS-1.
ADDITIONAL COMPENSATION SHALL BE ALLOWED FOR REVISIONS TO THE DESIGN TO CORRECT FOR
4 1314' DOMESTIC COLD WATER AND HOT WATER DOWN IN WALL T0(2) SH-1,
EXISTING CONDITIONS NOT AS INDICATED ON THE PLANS.
5 314' DOMESTIC COLD WATER AND HOT WATER DOWN IN WALL TO WH-1.
C.
CONTRACTOR TO VERIFY EXISTING CONDITIONS AND COORDINATE CONFLICTS PRIOR TO BIDDING.
6 112' DOMESTIC COLD WATER DOWN IN WALL TO EWC 1.
D.
ANYTHING NOT NOTED AS EXISTING IS TO BE FURNISHED AND INSTALLED AS PART OF THIS PROJECT.
7 112' DOMESTIC COLD WATER DOWN IN WALL TO TRAP PRIMER.
E.
REFER TO DRAWINGS, GENERAL NOTES OF OTHER DISCIPLINES, AND PROJECT SPECIFICATIONS FOR
ADDITIONAL PROJECT INFORMATION AND REQUIREMENTS. NOTIFY ENGINEER OF ANY CONFLICTS
8 1'CW PIPING CONNECT TO EXISTING CW MAIN. CONTRACTOR TO FIELD VERIFY EXACT SIZE AND
BETWEEN THE INFORMATION PRESENTED AND FIELD CONDITIONS.
LOCATION OF EXISTING CW MAIN PRIOR TO COMMENCING WORK.
F.
PROVIDE STOP VALVES AT EVERY FIXTURE ON COLD WATER SUPPLY LINES. VALVES, ESCUTCHEONS,
FITTINGS, ETC. MUST BE CHROME PLATED. WHERE EXPOSED, CHROME PLATED PIPE IS TO BE USED.
G.
ALL OVERHEAD PIPING IS TO BE ROUTED TIGHT TO BUILDING STRUCTURE.
H.
PIPING IS NOT PERMITTED IN DEMISING WALLS.
I.
DO NOT ROUTE ANY WATER CONVEYING PIPING OVER ELECTRICAL EQUIPMENT.
J.
ALL EXPOSED OR ACCESSIBLE P-TRAPS MUST BE PROVIDED WITH BOTTOM CLEANOUT PLUGS.
K.
INSULATE EXPOSED P-TRAPS, HOT AND COLD VALVES AND PIPING SERVING HANDICAPPED LAVATORIES.
L.
PRIOR TO ANY ISOLATION OF SYSTEMS, SHUTDOWNS OR DEMOLITION THE CONTRACTOR SHALL
PROVIDE NECESSARY INVESTIGATION AND NOTIFY THE FACILITIES ENGINEERINGIMAINTENANCE
PERSONNEL OF WORK TO BE PERFORMED 50 AS TO AVOID ANY DETRIMENTAL SHUTDOWN OF SYSTEMS
TO ADJACENT SPACES.
M.
CONSTRUCTION MATERIALS ABOVE CEILING SHALL BE NONCOMBUSTIBLE. OR HAVE A MAXIMUM 25
FLAME SPREAD AND 50 SMOKE DEVELOPMENT FINISH RATING. WIRING SHALL BE LABELED PLENUM
RATED TYPE PER NFPA 70.
N.
NO PLUMBING OR FIRE PROTECTION PIPING OR EQUIPMENT MAY BE SUPPORTED FROM THE
SUSPENDED CEILING SYSTEM, BUT MUST BE INDEPENDENTLY SUPPORTED FROM THE BUILDING
STRUCTURE.
0.
PROVIDE HEAT TRACING FOR ALL PLUMBING LINES EXPOSED TO OUTSIDE ELEMENTS.
N
KEY PLAN
CURRAN
ARCHITECTURE
5719 LAWTON LOOP EAST DR STE 212
INDIANAPOLIS, IN 46216
O :: 317.288.06,81
F :: 317.288.0753
CONSULTANT
DRAWN BY: JJC CHECKED BY: KDH
*T/E/S
ENGINEERING
25760 First Street
Cleveland, OH 44145
P 440 871 2410
F 440 8717954
tesengineering.00m
CERTIFICATION
STATE OF
7/11/2019
THIS DRAWING AND THE IDEAS. DESIGNS
AND CONCEPTS CONTAINED HEREN ARE
THE EXCLUSIVE I NTELLECTUAL PROPERTY
OF CURRAN ARCHITECTURE, AND ARE NOT
TO BE USED OR REPRODUCED, WHOLE OR
IN PART, WITH WT THE WRITTEN
CONSENT OF CURRAN ARCHITECTURE.
0 COPIWLHT 2019, CURMN ARCHITECTURE
INTERIOR BUILD -OUT FOR:
FE
F45 CLAY TERRACE
CLAY TERRACE BLVD.
E14
CARMEL, IN
PLUMBING DOMESTIC
WATER PLAN
ISSUE DATES
ISSUED
FOR REVIEW
4 13-19
ISSUED
FOR PERMIT
7-10-19
PROJECT NUMBER: 180364
P1.0