Loading...
HomeMy WebLinkAboutE002 - ELECTRICAL SPECIFICATIONS5 RELEASED FOR CONSTRUCTION Subject to compliance with all regulations of State and Local Codes City of Camel DATE: 08/23/19 DIVISION 260000 -ELECTRICAL 1. GENERAL A. REQUIREMENTS 1. PRODUCTS AND EXECUTION SHALL BE PROVIDED FOR A COMPLETE AND FULLY OPERATIONAL ELECTRICAL SYSTEM THROUGHOUT THE EXTENT OF THE PROJECT, IN CONFORMANCE WITH APPLICABLE CODES, LAWS, ORDINANCES AND AGENCY STANDARDS OF GOVERNING BODIES HAVING JURISDICTION, AND IN STRICT ACCORDANCE WITH THE CONTRACT DOCUMENTS, AND BUILDING STANDARDS. 2. PRODUCTS, INCLUDING EQUIPMENT, DEVICES, FIXTURES, AND MATERIALS SHALL BE NEW UNLESS NOTED OTHERWISE, UL LISTED, AND BEAR APPROPRIATE LABEL. 3. EXECUTION, INCLUDING PREPARATION, INSTALLATION, STARTING, AND TESTING SHALL BE PERFORMED BY SKILLED TRADES PERSONNEL, IN COMPLIANCE WITH THE ASSOCIATED MANUFACTURERS RECOMMENDATIONS, AND COORDINATED WITH THE OTHER CONSTRUCTION TRADES. B. APPLICABLE CODES 1. 2009 INDIANA ELECTRICAL CODE NEC 2. 2014 INDIANA BUILDING CODE IBC 3. CITY OF CARMEL, INDIANA ORDINANCES AND AMENDMENTS C. APPLICABLE LAWS AND AGENCY STANDARDS 1. AMERICAN NATIONAL STANDARDS INSTITUTE ANSI 2. AMERICAN SOCIETY FOR TESTING AND MATERIALS ASTM 3. AMERICANS WITH DISABILITIES ACT ADA 4. ASSOCIATION OF EDISON ILLUMINATING COMPANIES AEIC 5. CERTIFIED BALLAST MANUFACTURERS GEM 6. ELECTRICAL TESTING LABORATORIES ETL 7. ELECTRONIC/TELECOMMUNICATIONS INDUSTRIES ASSOCIATION EIA/TIA 8. 2010 INDIANA ENERGY CONSERVATION CODE IECC 9. UNDERWRITERS'LABORATORIES UL 10. ILLUMINATING ENGINEERING SOCIETY OF NORTH AMERICA IESNA 11. INSTITUTE OF ELECTRICALAND ELECTRONICS ENGINEERS IEEE 12. INSULATED CABLE ENGINEERS ASSOCIATION ICEA 13. NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION NEM4 14. NATIONAL FIRE PROTECTION ASSOCIATION NFPA D. APPROVALS 1. EMERGENCY AND EXIT LIGHTING DOCUMENTS SHALL BE PREPARED AND SUBMITTED TO THE LOCAL FIRE DEPARTMENT FOR THEIR APPROVAL OF SYSTEM LAYOUT, CIRCUITING, AND FIXTURE TYPE. APPROVED DRAWINGS SHALL BE SUBMITTED FOR REVIEW PRIOR TO CONSTRUCTION. 2. FIRE ALARM AND LIFE SAFETY DOCUMENTS SHALL BE PREPARED AND SUBMITTED TO THE LOCAL FIRE DEPARTMENT FOR THEIR APPROVAL OF SYSTEM EXPANSION, LAYOUT, CIRCUITING, EQUIPMENT AND DEVICE TYPE. THE BASE BUILDING FIRE ALARM AND LIFE SAFETY SYSTEM MANUFACTURER/INSTALLER SHALL BE RETAINED TO PRODUCE OR UPDATE THE BUILDING FIRE ALARM AND LIFE SAFETY DOCUMENTS, AND TO MAKE FINAL CONNECTIONS AND ALTERATIONS TO THE EXISTING SYSTEM. APPROVED DRAWINGS SHALL BE SUBMITTED FOR REVIEW PRIOR TO CONSTRUCTION. E. SUBMITTALS 1. SHOP DRAWINGS SHALL BE PREPARED AND SUBMITTED FOR REVIEW PRIOR TO CONSTRUCTION FOR THE FOLLOWING PRODUCTS: METERING EQUIPMENT, DISTRIBUTION PANELBOARDS, BRANCH PANELBOARDS, AND FIRE ALARM EQUIPMENT. 2. UTILITY SERVICE REQUEST SHALL BE PREPARED AND SUBMITTED PRIOR TO CONSTRUCTION. UTILITY PREPARED DRAWINGS SHALL BE SUBMITTED FOR REVIEW PRIOR TO CONSTRUCTION. 3. PROJECT RECORD DOCUMENTS SHALL BE PREPARED USING AUTOCAD OR EQUIVALENT CAD PACKAGE. PROJECT RECORD DOCUMENTS SHALL BE SUBMITTED ON REPRODUCIBLE MEDIA AND ON DISKETTE PRIOR TO PROJECT COMPLETION FOR ELECTRICAL SYSTEMS. RECORD ACTUAL LOCATION OF EQUIPMENT, DEVICES, FIXTURES, ETC. RECORD ACTUAL ROUTING OF OVERHEAD FEEDERS. RECORD ACTUAL ROUTING OF FEEDERS BELOW SLAB AND BRANCH CIRCUITS WITHIN OR BELOW SLAB. F. COORDINATION 1. ELECTRICAL ENGINEER: NOTIFY THE ENGINEER OF ANY CONFLICTING DESIGN INFORMATION OR ANY DESIGN INTENTIONS WHICH ARE NOT READILY INTERPRETED FROM THE CONTRACT DOCUMENTS PRIOR TO ANY PRODUCT SELECTION OR EXECUTION OF WORK. NOTIFY THE ENGINEER OF ANY PRODUCTS WHICH ARE DAMAGED, UNSUITABLE, INCOMPATIBLE, OR NON -COMPLIANT WITH ANY APPLICABLE CODES OR ORDINANCES OF ANY GOVERNING BODIES HAVING LAWFUL JURISDICTION. 2. ARCHITECT: COORDINATE CONSTRUCTION OF THE ELECTRICAL SYSTEM WITH THE ARCHITECT. FINAL LOCATIONS AND MOUNTING HEIGHTS OF ELECTRICAL EQUIPMENT, FIRE ALARM EQUIPMENT, RECEPTACLES, SWITCHES, COMMUNICATIONS DEVICES, FIRE ALARM DEVICES, LIGHTING FIXTURES, ETC. SHALL BE AS DIRECTED BY THE ARCHITECT. 3. CONSTRUCTION TRADES: COORDINATE WORK WITH OTHER CONSTRUCTION TRADES. 4. BUILDING MANAGEMENT: MEET ON SITE WITH THE BUILDING MANAGEMENT TO BECOME FAMILIAR WITH BUILDING STANDARDS. NORMAL BUILDING WORKING HOURS SHALL BE RECOGNIZED. AFTER-HOURS WORK OR TEMPORARY SERVICES SHALL BE WITH PRIOR WRITTEN APPROVAL FROM BUILDING MANAGEMENT. ENCLOSE CONSTRUCTION AREA FROM OTHER AREAS TO PREVENT TRANSMISSION OF DUST, DIRT AND NOISE INTO OTHER EXISTING TENANT AREAS. PRODUCT AND WASTE TRANSFER SHALL BE COORDINATED WITH BUILDING MANAGEMENT FOR SCHEDULING OF THE ELEVATORS, DELIVERIES, AND WASTE REMOVAL. 5. EXISTING BUILDING SYSTEMS: REVIEW BUILDING STANDARDS WITH THE BUILDING ENGINEER. PERFORM A SITE VISIT TO VERIFY THE EXISTING SITE CONDITIONS. COSTS ASSOCIATED WITH UNFORSEEN CONDITIONS AS RESULT OF NOT PERFORMING A SITE VISIT SHALL NOT BE AN ENTITLEMENT FOR AN INCREASE TO THE CONTRACT. CONSTRUCTION SHALL BE PERFORMED WITHOUT INTERRUPTION TO THE BUILDING POWER, COMMUNICATIONS, SECURITY, FIRE ALARM AND LIFE SAFETY SYSTEMS, OR INTERFERENCE TO COMMON AREAS, CORRIDORS, EXITS OR EXISTING TENANTS. WHERE ANY CONSTRUCTION WOULD INTERFERE WITH THE DAILY OPERATIONS OF THE BUILDING OR OTHER TENANTS, AFTER-HOURS WORK OR TEMPORARY SERVICES SHALL BE PROVIDED AT NO INCREASE TO THE CONTRACT. 2. PRODUCTS A. CABINETS, ENCLOSURES AND ACCESS PANELS SHALL BE CODE GAGE STEEL WITH BAKED ENAMEL FINISH AND FLANGELESS HINGES AND FASTENERS. EQUIPMENT BASES SHALL BE INCH HIGH CONCRETE, STEEL BRACED AND REINFORCED WITH 114 INCH CHAMFER, AND SHALL EXTEND A MINIMUM OF 2 INCHES AROUND BASE OF EQUIPMENT. VIBRATION ISOLATION SHALL BE SPRING ELEMENTS IN SUSPENDED RODS AND ISOLATION PADS BELOW EQUIPMENT, ELECTRICAL CONNECTIONS SHALL BE FLEXIBLE CONDUIT. B. CONDUITS SHALL BE HOT -DIPPED GALVANIZED OR ELECTRO-GALVANIZED STEEL, MINIMUM SIZE SHALL BE 3l4 INCH, EXCEPT SWITCH LEGS MAY BE ill INCH AND FLEXIBLE CONNECTIONS TO RECESSED LIGHTING FIXTURES WHICH MAY BE 318 INCH. FLEXIBLE STEEL CONDUIT SHALL BE GALVANIZED STEEL, WITH UL LISTED LIQUID TIGHT JACKET AS REQUIRED, FOR FINAL CONNECTIONS TO MOTORS, RECESSED LIGHTING FIXTURES, AND LIFE SAFETY DEVICES. SUPPORTS, INCLUDING CHANNELS, ANGLES, RODS, AND FASTENERS SHALL BE HOT -DIPPED GALVANIZED STEEL. MANUFACTURER SHALL BE ALLIED,LTV/REPUBLIC, STEELDUCT, OR WHEATLAND. C. CONDUIT FITTINGS SHALL BE STEEL, DIE CAST FITTINGS OF POT METAL ARE NOT ACCEPTABLE. ELECTRICAL METALLIC TUBING (EMT) FITTINGS SHALL BE COMPRESSION TYPE WITH INSULATED THROATS; SETSCREW FITTINGS ARE NOT ACCEPTABLE. INTERMEDIATE METAL CONDUIT (IMC) AND RIGID METAL CONDUIT (RMC) FITTINGS SHALL BE OF THREADED JOINTS; SETSCREW AND COMPRESSION FITTINGS ARE NOT ACCEPTABLE. MANUFACTURER SHALL BE APPLETON, CROUSE HINDSIMIDWEST, OZ/GGEDNEY, RACO, STEEL CITY, OR T&B. D. OUTLET BOXES FOR ALL TOGGLE SWITCHES, RECEPTACLES, COMMUNICATIONS DEVICES, FIRE ALARM DEVICES, AND LIFE SAFETY DEVICES SHALL INCLUDE PLASTER RINGS, DEVICE PLATES, AND COVER PLATES WHERE REQUIRED. PROVIDE BOXES SUITABLE FOR PLENUM, WET, OR HAZARDOUS LOCATIONS AS REQUIRED. DEVICE COVER PLATES SHALL BE STAINLESS STEEL PAINTED TO MATCH FINISH. MULTI -GANG OUTLET BOXES SHALL INCLUDE SUITABLE ONE-PIECE DEVICE COVER PLATE. OUTLETS LOCATED ON OPPOSITE SIDES OF A PARTITION SHALL BE STAGGERED BY 12 INCHES,MINIMUM. MANUFACTURER SHALL BE APPLETON, RACO, OR STEEL CITY. E. FLOOR BOXES SHALL BE ADJUSTABLE CONCRETE TIGHT PRESSED STEEL WITH BRASS FLANGE AND COVERS. FLUSH FLOOR BOXES SHALL INCLUDE BRASS TRIM AND HINGED OUTLET OPENING COVERS. MANUFACTURER SHALL BE HUBBELL, WALKER, OR STEEL CITY. F. WIRE SHALL BE 600 VOLT INSULATED COPPER, MINIMUM SIZE SHALL BE NO.12 AWG, WIRE SIZES NO.8 AWG AND LARGER SHALL BE STRANDED. MANUFACTURER SHALL BE AMERICAN INSULATED WIRE CORP., CERRO, COLLYER, CAPITOL WIRE AND CABLE, OKONITE, SENETOR, SOUTH WIRE, OR TRIANGLE. G. CABLE SUPPORTS SHALL BE APPROPRIATE FOR THE SIZE OF CONDUIT AND TYPE OF WIRE AND CABLES. CABLE LUBRICANT SHALL BE LESS THAN SIX PERCENT SOLID RESIDUE AFTER DRYING AND SHALL NOT CONTAIN ANY WAXES, GREASES, SILICONES, OR GLYCOL OILS. H. LOCAL DISCONNECT SWITCHES FOR ELECTRICALLY OPERATED EQUIPMENT SHALL BE HEAVY DUTY WITHIN ENCLOSURE SUITABLE FOR THE LOCATION. MANUFACTURER SHALL BE CUTLER- -HAMMER, SIEMENS, OR SQUARE D. I. GROUNDING SYSTEM, INCLUDING SERVICE AND EQUIPMENT GROUNDING AND BONDING, SHALL BE IN ACCORDANCE WITH CODE AND SHALL CONNECT ALL ELECTRICALLY OPERATED EQUIPMENT. PROVIDE A SEPARATE GREEN GROUND WIRE FOR EACH BRANCH CIRCUIT AND FEEDER. J. RECEPTACLES SHALL BE DUPLEX NEMA 5-20R, BACKAND SIDE WIRED, SPECIFICATION GRADE, UNLESS NOTED OTHERWISE. SPECIAL RECEPTACLE CONFIGURATIONS, DUPLEX GROUND FAULT INTERRUPTER RECEPTACLES SHALL BE AS REQUIRED OR AS INDICATED ON THE CONTRACT DOCUMENTS. GENERAL RECEPTACLE WHITE, UNLESS NOTED OTHERWISE, OTHERWISE, VERIFY COLOR WITH ARCHITECT. MANUFACTURER SHALL BE BRYANT, HUBBELL, LEVITON, OR PASS & SEYMOUR. K. TOGGLE SWITCHES SHALL BE SINGLE POLE 20 AMP, 120-277 VOLT, BACK AND SIDE WIRED, SPECIFICATION GRADE, UNLESS NOTED OTHERWISE. SPECIAL SWITCHES, INCLUDING 3-WAY, PILOT LIGHT AND MOMENTARY CONTACT, SHALL BE AS REQUIRED OR AS INDICATED ON THE CONTRACT DOCUMENTS. COLOR SHALL BE WHITE UNLESS SPECIFIED OTHERWISE, VERIFY COLOR WITH ARCHITECT. MANUFACTURER SHALL BE BRYANT, HUBBELL, LEVITON, OR PASS& SEYMOUR. L. LIGHTING CONTACTORS SHALL BE ENCLOSED AND MECHANICALLY HELD, AND SHALL INCLUDE ALL REQUIRED CONTROL MODULES, TIMECLOCKS, AND REMOTE PHOTOCELLS. MULTI -POLE CONTACTORS FOR BRANCH CIRCUITS SHALL BE RATED AT 20 AMPS, OR MORE, AS REQUIRED FOR THE SPECIFIC M. NEW FIRE ALARM DEVICES PROVIDED WITHIN EXISTING SYSTEMS SHALL MATCH EXISTING DEVICE MANUFACTURER AND TYPE. STROBES SHALL MEETADA GUIDELINES FOR THE APPLICATION AND SHALL RATED 75DC, EXCEPT IN SLEEPING AREAS WHICH SHALL BERATED 110DC. STROBES RATED 15175DG WITH 75DC ON AXIS ARE NOT ACCEPTABLE EXCEPT IN SMALL CONFERENCE ROOMS. EXISTING FIRE ALARM DEVICES SHALL BE EXTENDED AS REQUIRED. EXISTING FIRE ALARM EQUIPMENT SHALL BE EXPANDED AS REQUIRED WITH ANY ADDITIONAL COMPONENTS FOR PROPER OPERATION OF NEW DEVICES ON EXISTING EQUIPMENT. N. BRANCH PANELBOARDS SHALL BE FULLY RATED WITH COPPER PHASE, NEUTRAL, AND GROUND BUS, BRACED AT 10,000 AIC FOR 208Y/120 VOLT SYSTEMS, OR MORE TO BE GREATER THAN THE AVAILABLE SHORT CIRCUIT CURRENT. MANUFACTURERS SHALL BE CUTLER -HAMMER, SIEMENS, OR SQUARE D. O. TRANSFORMERS SHALL BE COPPER WOUND, DRY TYPE VENTILATED, 115-C RISE WITH NEMA STANDARD VOLTAGE TAPS AND SOUND RATINGS. SP-NGA spin a strength • yoga 3. EXECUTION A. PENETRATIONS AND CHANNELS IN FLOORS AND WALLS SHALL BE VIA CUTTING AND CORING AS REQUIRED FOR THE SIZE OF PRODUCT, ONLY IN ACCORDANCE WITH THE ARCHITECT AND ENGINEER RECOMMENDATIONS, AND AS SCHEDULED WITH THE BUILDING MANAGEMENT. PATCH AND FILL SLEEVES, INSERTS, PENETRATIONS, AND CHANNELS WITH APPROPRIATE CODE APPROVED FIRE SAFING OR FILLING TO MATCH OR RESTORE THE ORIGINAL FIRE RATING OF THE CONSTRUCTION. B. MAKE FINAL CONNECTIONS TO VIBRATING EQUIPMENT, FIXTURES, AND DEVICES WITH FLEXIBLE FOXFIELD COMTRUCION LTD. METAL CONDUIT OR LIQUID TIGHT FLEXIBLE METAL CONDUITAS REQUIRED. EXTENDGROUND ur�xeaoc�rxrooas WIRE THROUGH FLEXIBLE CONNECTIONS. C. INSTALL CONDUIT, FITTINGS, SUPPORTS, ETC. IN ACCORDANCE WITH CODES, STANDARDS, AND CGGWiiIILLLiii MANUFACTURERS RECOMMENDATIONS. THE VOLTAGES IDENTIFIED IN THE FOLLOWING SCHEDULES ARE LINE -TO -LINE OR LINE -TO -NEUTRAL. INTERIOR CONCEALED LOCATIONS ARE THOSE LOCATIONS WHICH ARE ABOVE CEILINGS, WITHIN WALLS, WITHIN FLOOR SLABS, AND WITHIN DEDICATED ELECTRICAL ROOMS. CONDUIT INSTALLATION SHALL BE AS FOLLOWS UNLESS NOTED OTHERWISE: VOLTAGE GV ABOVE50TH THRU26GV VIRTUAL LOCATION TMRU 50V V INTERIOR EMT EMT CONCEAL EDINTTERIORERIOREMT <2"EMT ENERGY EXPOSED i 2 1Y2"IMC EXTERIOR IMC RING SOLUTIONS LOCATIONS D. INSTALLATIONS WITHIN AIR HANDLING SPACES, INCLUDING PLENUM CEILINGS AND BUILT UP AIR 6252 W 59th STREET, CHICAGO, IL 60638 HANDLING SYSTEMS SHALL BE APPROVED FOR PLENUM INSTALLATION AND SHALL BE IN STRICT 312.583.7023 ACCORDANCE WITH ALL APPLICABLE CODES. W W W.VESCHICAGO.COM #AA26003751 E. INSTALL PULL BOXES, JUNCTION BOXES, AND OUTLET BOXES IN ACCORDANCE WITH CODES, STANDARDS, AND MANUFACTURERS RECOMMENDATIONS. BOXES SHALL INCLUDE ACCESSIBLE COVERS, SHALL BE FABRICATED OF HEAVY GAGE GALVANIZED STEEL, AND SHALL BE SIZED WITH CODE TO ADEQUATELY FACILITATE PULLING AND CONNECTING THE QUANTITY OF WIRES, CABLES, AND FEEDERS CONTAINED. CONDUIT TERMINATIONS SHALL BE MADE WITH BUSHINGS ANDLOCKNUTS. SUPPORTS FOR CONDUITS AND BOXES SHALL BE SUSPENDED DIRECTLY TO THE BUILDING STRUCTURAL COMPONENTS AND IN NO CASE SHALL THEY BE ATTACHED TO SUSPENDED CEILING GRID, DUCTWORK, OR PIPING COMPONENTS. F. INSTALL FEEDERS AND BRANCH CIRCUIT WIRING IN ACCORDANCE WITH CODES, STANDARDS, AND MANUFACTURERS RECOMMENDATIONS. INSTALL POWER WITHIN A CONTINUOUS METAL RACEWAY. INSTALL CONCEALED FIRE ALARM AND COMMUNICATION WIRING WITHIN > N CONTINUOUS METAL RACEWAYS. SEPARATE EACH SYSTEM INTO INDEPENDENT RACEWAYS. 170 WM PROVIDE CABLE SUPPORTS AS REQUIRED. TERMINATE CABLES PER CODE AND O MANUFACTURERS RECOMMENDATIONS. PROVIDE (2) HOLE LUGS FOR CABLES 250 KCMIL AND LARGER. POWER WIRING INSULATION SHALL BE AS FOLLOWS UNLESS NOTED OTHERWISE: WIRE 300 KCMIL 350 KCMIL ENVIRONMENTAL U c9 V LOCATION ANDSMALLER ANDLARGER CONDITIONS INTERIOR THHN/THWN XHHW DRY L m LOCATIONS EXTERIOR THHWTHWN XHHW DAMP LOCATIONS THHN/THWN XHHW-2 WET C G. INSTALL ELECTRICAL DISTRIBUTION EQUIPMENT AND DEVICES, INCLUDING METERING, Q^ DISTRIBUTION PANELBOARDS, BRANCH PANELBOARDS, MOTOR STARTERS, LOCAL DISCONNECT C)C J T) SWITCHES, OVERCURRENT PROTECTION,TRANSFORMERS, MAIN CONTACTORS, RECEPTACLES, ETC. IN ACCORDANCE WITH CODES, STANDARDS, AND MANUFACTURERS RECOMMENDATIONS. H. INSTALL GROUNDING SYSTEMS IN ACCORDANCE WITH CODES, STANDARDS, AND r MANUFACTURERS RECOMMENDATIONS. COMMUNICATIONS TO THE ELECTRICAL ICAL SERVICE INCLUDE GROUND LUG AND AW G NO. 6 WHICH SHALL CONNECT TO THE ELECTRICAL SERVICE EQUIPMENT v GROUND BUS. r J. INSTALL LIGHTING AND ASSOCIATED CONTROLS, INCLUDING FIXTURES, BALLASTS, LAMPS, TOGGLE SWITCHES, SLIDE DIMMERS, DIMMING EQUIPMENT, LIGHTING CONTACTORS, ETC IN ACCORDANCE WITH CODES,STANDARDS, AND MANUFACTURERS RECOMMENDATIONS. K. INSTALL SINGLE AND MULTIPLE DEVICE COVER PLATES AS REQUIRED. EXTEND EXISTING DEVICES TO FINISHED SURFACE AS REQUIRED. L. INSTALL FIRE ALARM AND OTHER LIFE SAFETY SYSTEMS IN ACCORDANCE WITH CODES, STANDARDS, AND MANUFACTURERS RECOMMENDATIONS. M. INSTALL INSCRIPTION PLATES AND IDENTIFICATION MARKINGS FOR PRODUCTS AND WIRING INCLUDING THE SAME INSCRIPTIONS WHERE INDICATED ON THE CONTRACT DOCUMENTS. INSTALL PLASTIC LAMINATE NAMEPLATES ON ENCLOSURES FOR EACH DEVICE WITHIN METERING EQUIPMENT, DISTRIBUTION PANELBOARDS, BRANCH PANELBOARDS, MOTOR STARTERS, DISCONNECT SWITCHES, TRANSFORMERS, AND CONTACTORS. NAMEPLATES SHALL BE WHITE I WITH BLACK CORE, 1-1/4 INCHES BY3 INCHES MINIMUM, TH 3/16 INCH J ,I EE SECURED QUIPMENTWTHTWO MACHI ESCREWS. PREPARE AND INSTALL TYPE -WRITTEN PANEL DIRECTORY WITHIN EACH BRANCH PANEL. DEVICE PLATES SHALL BE ENGRAVED FOR .�`��`GCPEgs'��,, TOGGLE SWITCHES AND OTHER DEVICES WHOSE FUNCTION IS NOT READILY APPARENT. �• GI$TER •'••'T' �. MARKERS SHALL BE SELF -STICKING FOR EACH WIRE AND CABLE AT TERMINATIONS AND AT EACH ACCESSIBLE POINT IN EQUIPMENT AND RACEWAY. = PEI]600637 N. CLEAN ELECTRICAL APPARATUS PRIOR TO COMPLETION OF CONSTRUCTION. KEEP WORK AREAS w CLEAN AT ALL TIMES. STATE OF j,?C VIES project number: 190301 sheet title: ELECTRICAL SPECIFICATIONS sheet number: E002 ® 2018 Virtual Energy Solutions, Inc.