Loading...
HomeMy WebLinkAboutE601 - ELECTRICAL SCHEDULES AND RISER DIAGRAMS5 PANEL SCHEDULE - NEW "TP-1316-HV" SERVICE: 480r277V-3E-4W NEUTRALBUS: STANDARD,COPPER MAIN CIRCUIT BREAKER: 200A,3P GROUNDBUS: STANDARD,COPPER BUSSIZE: 225A MOUNTING: SURFACE INTERRUPTRATING: 10KAIC ENCLOSURE: NEMA1 DESCRIPTION CCT. NO. CIRCUIT BREAKER CIRCUIT CONNECTED LOAD NA) CIRCUIT CIRCUIT BREAKER CCT. NO. DESCRIPTION LOAD LOAD A B C ACM RTUA 1 45A-3P 4299 10928 6629 70A-3P 2 AGH RTU-3 3 4299 10928 6629 4 5 4299 10928 6629 6 ACTH RTU-2 7 70A-3P 6629 6629 - 8 S SPACE 9 6629 6629 - 10 S SPACE 11 6629 6629 - 12 S SPACE S SPACE 13 - - - 14 S SPACE S SPACE 15 - - - 16 S SPACE S SPACE 17 -- - - 18 S SPACE S SPACE 19 -- - - 20 S SPACE S SPACE 21 -- - - 22 S SPACE S SPACE 23 - - - 24 S SPACE S SPACE 25 - - - 26 S SPACE S SPACE 27 - - - 28 S SPACE S SPACE 29 - -- - 30 S SPACE S SPACE 31 -- - - 32 S SPACE S SPACE 33 S SPACE 35 -- - - 36 S SPACE S SPACE 37 -- 8853 8853 80A.3P 1 38 1 45 KVA TRANSFORMER S SPACE 39 -- 6138 6138 40 S SPACE 41 -- 9167 9167 42 26410 25693 26727 TOTAL VA PER PHASE CONNECTED LOAD DEMAND FACTOR DEMAND LOAD L LIGHTING & SIGN 3.44 kVA 1.25 4.3 kVA R RECEPTACLES 7.38 <VA 1.0(FISRT 10KVA)+0.5(REST) 7.38 KVA M MOTOR I EQUIPMENT 15.336 kVA 1.0 15.336 kkVA AC AIR CONDITIONING - kVA 1.0 VA H ELECTRIC HEAT 52.671 kVA 1.25 65.839 kVA TOTAL CONNECTED LOAD: 78.83 kVA TOTAL DEMAND LOAD: 92.86 kVA TOTAL DEMAND CURRENT: 111.7 AMPS(48OV,30) RELEASED FOR CONSTRUCTION Subject to compliance with all regulations of State and Local Codes City of Camel DATE: 08/23 19 INTERCEPT THE EXISTING 200A SERVICE FEEDING THE SUITE AND EXTEND TO THE NEW PANEL NEW 100A,3P NEMA1 DISCONNECT SWITCH NEW 3#3 & 1#8 GRD, IN A 1-1/4" CONDUIT NEW 45KVA TRANSFORMER 480V, 3-PHASE, 3-WIRE PRIMARY 120/208V, 3-PHASE, 4-WIRE SECONDARY (PROVIDE A 4" CONCRETE PAD) 200A NICE 150A NICE T GROUND FLOOR 1#6 GRD, 3r4'CONDUIT�-NEW4#1/0&1#13GRD, TO BUILDING STEEL - IN 1-1/2"CONDUIT (MAXIMUM 10' IN LENGTH TO MAIN) 1 RISER DIAGRAM PANEL SCHEDULE - NEW "TP-1316-LV" LOCATION: STORAGE SERVICE: 208N20V-3E4W NEUTRALBUS: STANDARD,COPPER MAIN CIRCUIT BREAKER: 150A,3P GROUNDBUS: STANDARD,COPPER BUSSIZE: 225A MOUNTING: SURFACE INTERRUPTRATING: 22KAIC ENCLOSURE: NEMA1 DESCRIPTION CCT. NO. CIRCUIT BREAKER CIRCUIT CONNECTED LOAD (VA) CIRCUIT CIRCUIT BREAKER CCT. NO. DESCRIPTION LOAD LOAD A B C S SPARE 1 20A-lP 0 360 360 20A-lP 2 R R-WOMENS BATHROOMS S SPARE 3 20A-1P 0 180 180 20A-1P 4 R R-MENS BATHROOMS S SPARE 5 20A-1P 0 960 960 20A-1P 6 M MIENS HAND DRYER S SPARE 7 20A-1P 0 960 960 20AIP 8 M WOMENS HAND DRYER S SPARE 9 20AAP 0 696 696 20AAP 10 M TEF-1 R R-CORRIDOR 11 20A-1 P 540 1260 720 201 12 R R-ROOF/UTILITY R R-STRENGTH 13 20A-1P 720 1420 700 20A-1P 14 M R-AUDIONISUAL M STRENGTH (3) TVS 15 201 900 1600 700 201 16 M R-AUDIONISUAL M STRENGTH (3) TV'S 17 20A-IP 900 1600 700 20A-1P 16 M R-TELEMATA R R-YOGNROOF 19 20A-1P 540 1240 700 20A-1P 20 M R-TELEIDATA R R-FRAGRANCE MACHINE RTU'S 21 20A-1P 360 560 200 20A-1P 22 M RECIRC PUMP R R-SPIN 23 20A-1P 640 1260 72U 20A-1P 24 R R-LOBBY M SPIN (3)TV'S 25 20A-1P 900 1800 900 20A-1P 26 R R-LOBBY DESK R R-SPIN FLOOR BOX 27 20A-lP 360 780 420 20A-1P 28 M EWC L L-FRONT ROOMS/CORFBDOR 29 201 1147 1747 600 20A-0P 30 M COOLER L L-YOGNSPIN 31 201 1033 1573 540 20A-0P 32 R R-KIDS RM L L-STRENGTH 33 20A-1P' 960 1320 360 20A-iP 34 R RiNINDOWS L L-SIGN 35 20A11P 300 B40 MID 20A11P 36 R R-WINDOWS S SPARE 37 20A IP 0 1500 1500 40A-3P 38 M EWH (3#8 & 1#10 GRD, V C) S SPARE 39 20AAP 0 3000 3000 40 S SPARE 41 20A-lP 0 1500 1500 42 8853 8136 9167 TOTAL VA PER PHASE CONNECTED LOAD DEMAND FACTOR DEMANDLOAD L LIGHTING & SIGN 3.44 kVA 1.0 3.44 kVA R RECEPTACLES 7.38 WA 1.0(FISRT I OKVA)+0.5(REST) 7.38 <VA M MOTOR/EQUIPMENT 15.336 kVA 1.0 15.336 KVA AC AIR CONDITIONING 0.0 kVA 1.0 0.0 kVA H ELECTRIC HEAT 0.0 kVA 1.0 0.0 KVA TOTAL CONNECTED LOAD: 26.156 kVA TOTAL DEMAND LOAD: 26.156 kVA TOTAL DEMAND CURRENT: 72.6 AMPS (208V,30) GENERALPANELBOARD NOTES: 1. PROVIDE A TYPED PANELBOARD DIRECTORY. PANEL NOTE: 1. # - INDICATES A LOCKOUT DEVICE ON THE CIRCUIT BREAKER MOTOR EQUIPMENT SCHEDULE REMARKS HP SOURCE OF VOLTAGE CIRCUIT E.C.-ELECTRICAL CONTRACTOR ELECTRICAL OR POWERAND AND BREAKER/ CIRCUITS WIRE CONDUIT TAG kW/kVA PROTECTION PHASE FUSE M.C.- MECHANICAL CONTRACTOR T.C.- TEMPERATURE CONTROL CONTRACTOR RTU 1 ip 897 KVA PANEL TP-Bib-HV ggOV,3❑ 4NEW (1,3,5) 3#8& 1#10 GRD 1' VFD/DISCONNECT FURNISHED BY M.C. AND INSTALLED AND WIRED BY THE E.C. BREAKER RTU 19.667 KVA 460V,3❑ NEW 70A,3P (7,9,11) 1-1/4 VFD/DISCONNECT FURNISHED BY M.C. TPPB 6EHV BREAKER 1# GRD AND INSTALLED AND WIRED BY THE E.C. NEW RTU 3 19887 KVA PANEL TP4316-HV 4BOV,3E 70A,3P (2,4,6) 3#4& 1#-BGRD 1-1/4' VFD/DISCONNECT FURNISHED BY M.C. AND AND E.C. BREAKER INSTALLED WIRED BY THE TEF 1 1/4 HP PANEL TP-Bib-LV 120V.1E 201 10 2#12& 1#12 GRD 3/4^ E.C. TO PROVIDE A 20A,1P WEATHER PROOF TOGGLE DISCONNECT SWITCH BREAKER SP-NGA spin • strength • yoga FOXFIELD CONSTRUCTION LTD. �p�,l iC�LL�]i u�axass�ruaa¢ VIRTUAL ENERGY SOLUTIONS 6252 W 59th STREET, CHICAGO, IL 60638 312.583.7023 W W W.VESCHICAGO.COM #AA26003751 _ > N mCD U (p L rM W C r � U � _ Q U� m r E r � LID � U r ``p0111 11PI)JI'S 77 '4 �� 74;Q�GTST q`Fo . PE11600637 '? STATE OF i ,¢ VES project number: 190301 sheet title: ELECTRICAL SCHEDULES AND RISER DIAGRAMS sheet numbed ° 2 3 E601 ® 2018 Virtual Energy Solutions, Inc.