Loading...
HomeMy WebLinkAboutM601 - MECHANICAL SCHEDULESr: c 0 a` zz 1= m U m rn c N a rn J U LL r N N O W U VENTILATION SCHEDULE - INDIANA MECHANICAL CODE 2014 NO. NAME USE OF SPACE ORDINANCE FLOORAREA NO. OF OCCUPANTS NO OF WC INTERNATION MECH. CODE REQUIREMENTS ACTUAL CFM PROVIDED SERVED BY REMARKS OACFM PER OCCUPANT OA CFWSF OA SUPPLY AIR CFM EXHAUST AIR CFM SUPPLY (CFM) EXHAUST(CFM) 100 Lobby LOBBY 560 SF 10 0 5 0.06 84 0 1250 1450 RTU-1 101 Men's TOILET ROOM (PUBLIC) 144 SF 0 2 0 0.00 0 150 100 150 TEF-1 102 Women's TOILET ROOM (PUBLIC) 224 SF 0 2 0 0.00 0 150 100 150 TEF-1 103 Utility STORAGE ROOM 139 SF 0 0 0 0.00 0 0 150 0 RTU-1 104 Kids Room CLASSROOM (AGES 5-8) 122 SF 4 0 10 0.12 55 0 150 0 RTU-1 105 SPIN HEALTH CLUB / AEROBICS ROOM 826 SF 20 0 20 0.06 450 0 1425 1325 RTU-2 106 YOGA HEALTH CLUB / AEROBICS ROOM 930 SF 20 0 20 0.06 456 0 1200 1300 RTU-2 107 STRENGTH HEALTH CLUB/WEIGHT ROOM 1411 SF 20 0 20 0.06 485 0 2625 2625 RTU-3 Grand total:8 4356 SF 74 4 1528 300 7000 7000 ROOFTOP UNIT SCHEDULE TAG AIR CFM COOLING SECTION ELECTRIC HEATING UNIT ELECTRICAL DATA BASIS OF DESIGN LOCATION NOMINAL TONS TYPE DISCHARGE DIRECTION ESP N. W.C. CAPACITY NO. CAPACITY EVAP. FAN HP FILTER REFRIGERAN T UNIT WEIGHT MANUFACTURE REMARKS TYPE MARK SUPPLY MIN. OA TOTAL SENSIBLE EAT (DEG.F.) LAT (DEG.F.) COMPRESSORS KW FLA MCA MOCP V PH FI'L R MODEL RTU 1 ROOF 5 CONSTANT DOWN 1750 667 1.00 62.0 44.0 76 64 OF 1 23.4 2.00 MERV 8 R410A 42 44 45 480 3 60 765.00 Carrier 50HC VOLUME RTU 2 ROOF 7.5 CONSTANT DOWN 2625 1000 1.00 94.3 66.2 76 64 OF 2 38.3 1.50 MERV 8 R410A 66 67 70 480 3 60 1197.00 Carrier 50HC VOLUME RTU 3 ROOF 7.5 CONSTANT DOWN 2625 1000 1.00 94.3 66.2 76 64 OF 2 38.3 1.50 MERV 8 R410A 66 67 70 480 3 60 1197.00 Carrier 50HC VOLUME 1. PROVIDE WITH WEATHERPROOF DISCONNECT SWITCH 2. PROVIDE WITH PROGRAMMABLE THERMOSTAT CONTROLS 3. PROVIDE WITH MIN. 24- HIGH ROOF CURB 4. PROVIDE WITH ECONOMIZER 5. PROVIDE WITH 120V CONVENIENCE OUTLET 6. PROVIDE WITH DUCT DETECTOR AND COORDINATE CONNECTION WITH FIRE ALARM CONTRACTOR RELEASED FOR CONSTRUCTION Subject to compliance with all regulations of State and Local Codes e City of Camel ((�� �vm�ilaw�9a1�+L DATE: \\ 08/23/19 EXHAUST FAN SCHEDULE TAG FAN DATA MOTOR DATA DIMENSIONS LxM UNIT WEIGHT BASIS OF DESIGN REMARKS TYPE MARK CFM E.S.P. IN. WC. FAN TYPE RPM DRIVE BHP HP V PH HZ L W H MANUFACTURER MODEL TEF 1 300 0.60 DOWNSLAST 1725 DIRECT 0.08 0.1] 120 1 60 1 24 24 24 1 32.00 GREENHECK G-095-VG DIFFUSER/ REGISTER/ GRILLE SCHEDULE TAG SYSTEM DESCRIPTION FACE SIZE (IN.) NECK SIZES CFM RANGE MOUNITNG TYPE DAMPER MATERIAL/ FINISH MAX. N.C. REMARKS W L NECK DIAMETER NECK WIDTH NECK LENGTH MIN. MAX E-1 Exhaust Air SQUARE PERFORATED 12 12 6 0 135 LAY -IN No WHITE STEEL 30 R-1 Return Air Duct Mounted Diffuser 20 14 0 18 12 701 1000 DUCT Yes WHITE STEEL 30 R-1 Return Air Duct Mounted Diffuser 32 14 0 30 12 1001 1600 DUCT Yes WHITE STEEL 30 S-1 Supply Air Duct Mounted Diffuser 12 6 0 10 4 0 200 DUCT Yes WHITE STEEL 30 S-1 Supply Air Duct Mounted Diffuser 12 8 0 10 6 201 300 DUCT Yes WHITE STEEL 30 S-0 Supply Air Duct Mounted Diffuser 16 8 0 14 6 301 400 DUCT Yes WHITE STEEL 30 S-2 Supply AP SQUARE PLAQUE 12 12 6 76 120 LAY -IN No WHITE STEEL 30 SP-NGA spin • strength • yoga IIIIIIII ii FOXFIELI CONSTRUCTION LTD. oewxas oeasoraa n �anuvaors VIRTUAL kNERGY LUTIONS 6252 W 59th STREET, CHICAGO, IL 60638 312.583.7023 W W W.VESCHICAGO.COM #AA26003751 -0 % (N C0 m t] U �p L rM W C ~ U � Q U U) LO � r U ``pO10 11PE'S 7]'4 o GIST... qy0 l PEI]600637 '? STATE OF i ,¢ VES project number: 190301 sheet title: MECHANICAL SCHEDULES sheet number: M601 02018 Virtual Energy Solutions, Inc.