HomeMy WebLinkAboutP005 - PLUMBING SPECIFICATIONSr 1. Hard coppertube, ASTM B 88, Type L; wrought -copper, solder -joint fittings; and brazed joints. G. Aboveground domestic water piping, NPS 2 and smaller, shall be the following: 1. Galvanized -steel pipe and nipples; galvanized, gray -iron threaded fiffings; and threaded joints. 2. Hand copper tube, ASTM B 88, Type L ASTM B 88, Type M; cast- or wrought -copper, solderjoint fittings; and soldered joint. H. Aboveground domestic water piping, NPS 2-1/2 to NPS 4, shall be the following: 1. Had copper to be, ASTM B 88, Type L copper, solderjoint fittings; and soldered joints. I. Aboveground, combined domestic waterservice and fire -service -main piping, NPS 6 to NPS 12, shall be the following: 1. Plain -end, ductile -iron pipe; grorved int, ductile -iron -pipe appurtenances; and grooved joints. END OF SECTION 221116 SECTION 221119 - DOMESTIC WATER PIPING SPECIALTIES PART 1 -GENERAL 1.1 SUMMARY A. Section Includes: 1. Vacuum breakers. 2. Backflow P reventers. 3. Water pressure -reducing valves. P 9 4. Balancing valves. 5. Temperature -actuated, water mixing valves. 6. Stainers. 7. Hose blobs. 8. Wall hydrants. 9. Drain valves. 10. Water -hammer arresters. B. Related Requirements: 1. Section 220519 "Meters and Gages for Plumbing Piping" for thermometers, pressure gages, and flaw meters in domestic water piping. 2. Section 221116"Domestic Water Piping" for water meters. 1.2 ACTIONSUBMITTALS A. Product Data: For each type of product. 1.3 CLOSEOUT SUBMITTALS A. Operation and maintenance data. PART2-PRODUCTS 2.1 GENERAL REQUIREMENTS FOR PIPING SPECIALTIES A. Potable -water piping and components shall complywith NSF 61 Annex G and NSF 14. 2.2 PERFORMANCE REQUIREMENTS A. Minimum Working Pressure for Domestic Water Piping Specialties: 125 psig unless otherwise indicated. 2.3 VACUUM BREAKERS A. Pipe -Applied, Atmospheric -Type Vacuum Breakers: 1. Standard ASSE 1001. 2. Size: NPS 1/4 to NPS 3, as required to match connected piping. 3. Body: Bronze. 4. Inlet and Outlet Connections: Threaded. 5. Finish: Chrome plated. B. Hose -Connection Vacuum Breakers: 1. Standard: ASSE 1011. 2. Body: Bronze, nonremovable, with manual Bain. 3. Outlet Connection: Garden -hose threaded complying with ASME B1.20.7. 4. Finish: Chrome or nickel plated. 2.4 BACKFLOW PREVENTERS A. Intermediate Atmospheric -Vent Backflow Preventem: 1. Standard: ASSE 1012. 2. Operation: Continuous -pressure applications. 3. Size: NPS 1/2. 4. Body: Bronze. 5. End Connections: Union, solder joint. 6. Finish: Chrome plated. B. Reduced -Pressure -Principle Backflow Preventers: 1. Standard ASSE 1013. 2. Operation: Continuous -pressure applications. 3. Pressure Loss: 12 psig maximum, through middle third of flow range. 4. Body: Bronze for NPS 2 and smaller, cast iron with interior lining that complies with AW WA C550 or that is FDA approved for NPS 2-1/2 and larger. 5. End Connections: Threaded for NPS 2 and smaller, flanged for NPS 2-1/2 and larger. 6. Configuration: Designed for horizontal, stmight4h rough flow. 7. Accessories: a. Valves NPS 2 and Smaller: Ball type with threaded ends on inlet and outet. b. Valves NPS 2-1/2 and Larger: Outside -screw and yoke -gate type with flanged ends on inlet and outlet. C. Air -Gap Fitting: ASME At 12.1.2, matching backflow-preventer connection. C. Double-Check,Backflow-Prevention Assemblies: 1. Standard ASSE 1015. 2. Operation: Continuous-pressum applications unless otherwise indicated. 3. Pressure Loss: 5 psig maximum, through middle third of flow range. 4. Body: Bronze for NPS 2 and smaller, cast iron with interior lining that complies with AWWA C550 or that is FDA approved for NPS 2-1/2 and larger. 5. End Connections: Threaded for NPS 2 and smaller, flanged for NPS 2-1/2 and larger. 6. Configuration: Designed for horizontal, stmight4h rough flow. 7. Accessories: a. Valves NPS 2 and Smaller: Ball type with threaded ends on inlet and outlet. b. Valves NPS 2-1/2 and Larger: Outside -screw and yoke -gate type with flanged ends on inlet and outlet. 2.5 WATER PRESSURE -REDUCING VALVES A. Water Regulators: 1. Manufacturers: Subject to compliance with requirements, provide protlucts by one of the following: a. Apollo Valves; Condemn Industries, Inc. b. Watts; a Wafts Water Technologies company. RELEASED FOR CONSTRUCTION Subject to compliance with all regulations mof 150 psig. of State and Local Codes eat iron with interior lining that complies with City of Camel 'S2-1/2 and NPS 3. DATE: 08/23/19 5. Valves for Booster Heater Water Supply: Include integral bypass. 6. End Connections: Threaded for NPS 2 and smaller, flanged for NPS 2-1/2 and NPS 3. 2.6 BALANCING VALVES A. Memory -Stop Balancing Valves: 1. Manufacturers: Subject to compliance with requirements, provide products by one of the following: a. Apollo Valves; Conbmco Industries, Inc. b. Hammond Valve. C. Milwaukee Valve Company. d. NIBCO INC. 2. Standard: MSS SPA 10 fortwo-piece, copperalloy ball valves. 3. Pressure Rating: 4001 minimum CWP. 4. Size: NPS 2 or smaller. 5. Body: Copper alloy. 6. Pod: Standard or full pod. 7. Ball: Chrome-platetl bass. 8. Seats and Seals: Replaceable. 9. End Connections: Soltlerjoint or threaded. 10. Handle: VinN-covered steel with memory -setting device. 2.7 TEMPERATURE -ACTUATED, WATER MIXING VALVES A. Water -Temperature Limiting Devices: 1. Manufacturers: Subject to compliance with requirements, provide products by one of the following: a. Apollo Valves' Conlomco Industries Inc. b. Armstrong International, Inc. c. Leonard Valve Company. J. TACO Comfort Solutions, Inc. e. Watts; a Watts Water Technologies company. f. Zorn Industries, LLC. 2. Standard ASSE 1017. 3. Pressure Rating: 125 prig. 4. Type: Thermostatically controlled, water mixing valve. 5. Material: Bronze hotly with corrosion -resistant interior components. 6. Connections: Threaded inlets and outlet. 7. Accessories: Check stops on hot- and coltl-water supplies, and adjustable, temperatu%-control handle. 8. Tempered -Water Selling: 105 F. 9. Valve Finish: Chrome plated. B. Primary, Thermostatic, Water Mixing Valves: 1. Manufacturers: Subject to compliance with requirements, provide products by one of the following: a. Apollo Valves; Conbmco Industries, Inc. b. Armstrong International, Inc. c. Zorn Industries, LLC. 2. Standard: ASSE 1017. 3. Pressure Rating: 125 psigminimum unless otherwise indicated. 4. Type: Exposed -mounted, thermostatically controlled, water mixing valve. 5. Material: Bronze body with corrosion -resistant interior components. 6. Connections: Threaded inlets and outlet. 7. Accessories: Manual temperature control, check stops on not-andcold-water supplies, and adjustable, temperature -control handle. B. Tempered -Water Setting: 105 F. 9. Valve Finish: Chrome plated. 10. Piping Finish: Chrome plated. 2.8 STRAINERS FOR DOMESTIC WATER PIPING A. Y-Pattern Strainers: 1. Pressure Rating: 125 psig minimum unless otherwise indicated. 2. Body: Bronze for NPS 2 and smaller; cast iron with interior lining that complies with AW WA C550 or that is FDA approved, epoxy waled and for NPS 2-1/2 and larger. 3. End Connections: Threaded for NPS 2 and smaller, flanged for NPS 2-1/2 and larger. 4. Screen: Stainless steel with round per oations unless otherwise indicated. 5. Drain: Factory -installed, hose -end tlmin valve. 2.9 HOSE BIBBS A. Hose Bibbs: 1. Standard ASME A112.18.1 forsediment faucets. 2. Body Material: Bronze. 3. Seat: Bronze, replaceable. 4. Supply Connections: NPS 1/2 or NPS 3/4 threaded orsolderjoint inlet. 5. Outlet Connection: Garden -hose thread complying with ASME B1.20.7. 6. Pressure Rating: 125 psig. 7. Vacuum Breaker: Integral orfield-installation, nonremovable, dminable, hose -connection vacuum breaker complying with ASSE 1011. 8. Finish for Equipment Rooms: Rough bronze, or chrome or nickel plated. 9. Finish for Service Areas: Rough bronze. 10. Finish for Finished Rooms: Chrome or nickel plated. 11. Operation for Equipment Rooms: Wheel handle or operating key. 12. Operation for Service Areas: Wheel handle. 13. Operation for Finished Rooms: Operating key. 14. Include operating key with each operating -key hose bibb. 15. Include integral wall flange with each chrome -or mckel-platetl hose bibb. 2.10 WALL HYDRANTS A. Nonfreeze Wall Hydrants: 1. Standard: ASME A112.21.3M for exposed -outlet, seg-draining wall hydrants. 2. Pressure Rating: 125 psig. 3. Operation: Loose key. 4. Casing and Opeabng Rod: Of length required to match wall thickness. Include wall clamp. 5. Inlet: NPS 314 or NPS 1. 6. Outlet: Concealed, with integral vacuum breaker and garden -hose thread complying with ASME 31.20.7. 7. Box: Deep, flush mounted with cover. B. Box and Cover Finish: Polished nickel bronze. 9. Outlet: Exposed, with integral vacuum breaker and gaden-hose thread complying with ASME 31.20.7. 10. Nozzle and Wall -Plate Finish: Polished nickel bronze. 11. Operating Keysi Two with each wall hydrant. 2.11 DRAIN VALVES A. Ball -Valve -Type, Hose -End Drain Valves: 1. Standard MSS SP-110 for standard -port, two-piece ball valves. 2. Pressure Rating: 4001 minimum CWP. 3. Size: NPS 3/4. 4. Body: Copper alloy. 5. Ball: Chrome -plated bass. 6. Seats and Seals: Replaceable. 7. Handle: Vinyl -covered steel. 8. Inlet: Threaded or solder joint. 9. Outlet: Threaded, shod nipple with garden -hose thread complying with ASME 31.20.7 and cap with brass chain. 2.12 WATER -HAMMER ARRESTERS A. Water -Hammer Arresters: 1. Manufacturers: Subject to compliance with requirements, provide products by one of the following: a. Jay R. Smith Mfg. Co. It. MIFAB, Inc. C. Wafts; a Wafts Water Technologies company. J. Zorn Industries, LLC. 2. Standard: ASSE 1010 or PDI-W H 2O1. 3. Type: Capper tube with piston. 4. Size: ASSE 1010, Sizes AA and A through F, or PDI-WH 2O1, Sizes A through F. PART 3-EXECUTION 3.1 INSTALLATION A. Install backflow preventers in each water supply to mechanical equipment and systems and to other equipment and water systems that may be sources of contamination. Comply with authorities having jurisdiction. 1. Locate bacidlow preventers in same room as connected equipment or system. 2. Install drain for backflow pmventem with atmospheric -vent drain connection with air -gap filling, fixed air -gap fifting, or equivalent positive pipe separation of at least two pipe diametem in Pain piping and pipe -to -floor drain. Locate air -gap device attached to or under backflow pmventer. Simple air breaks are unacceptable for this application. 3. Do not install bypass piping around backflow preventers. B. Install water regulators with inlet and outlet shutoff valves and bypass with memory -stop balancing valve. Install pressure gages on inlet and outlet. C. Install balancing valves in locations where they can easily be adjusted. D. Install temperature -actuated, water mixing valves with check stops or shutoff valves on inlets and with shutoff valve on outlet. E. Install Y-pattern strainers for water on supply side of each control valve water pressure -reducing valve solenoid valve and pump. F. Set nonfreeze, nondmining-type post hydrants in concrete or pavement. G. Set freeze -resistant yard hydrants with riser pipe in concrete or pavement. Do not encase canister in concrete. H. Install water -hammer arresters in water piping according to PDI-W H 2O1. 3.2 CONNECTIONS A. Comply with requirements for ground equipment in Section 260526 "Grounding and Bonding for Electrical Systems." B. Fire -retardant -treated -wood blocking is specified in Section 260519 "Low -Voltage Electrical Power Conductors and Cables" for electrical connections. 3.3 FIELD QUALITY CONTROL A. Perform the following tests and inspections: 1. Test each pressure vacuum breaker retluced-pressure-principle backflow preventer double-check, backflow-prevention assembly and double-check, detector -assembly backflow preventer according to authorities having jurisdiction and the device's reference standard. B. Domestic water piping specialties will be considered defective if they do not pass tests and inspections. C. Prepare test and inspection reports. 3.4 ADJUSTING A. Set field -adjustable pressure set points of water pressure -reducing valves. B. Set field -adjustable flow set points of balancing valves. C. Set field -adjustable temperature set points of temperature -actuated, water mixing valves. END OF SECTION 221119 SECTION 221123 - DOMESTIC WATER PUMPS PART1-GENERAL 1.1 SUMMARY A. Section Includes: 1. Horizontally mounted, in -line, chose -coupled centrifugal pumps. 1.2 ACTION SUBMITTALS A. Product Data: For each type of product indicated. 1.3 CLOSEOUT SUBMITTALS A. Operation and maintenance data. 1.4 QUALITYASSURANCE A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. B. ILL Compliance: Comply with ILL 778 for motor -operated water pumps. PART2-PRODUCTS 2.1 HORIZONTALLY MOUNTED, IN -LINE, CLOSE -COUPLED CENTRIFUGAL PUMPS A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Bell B Gassed; a Xylem brand. 2. TACO Comfort Solutions, Inc. B. Description: Factory -assembled and -tested, in -line, single -stage, close -coupled, overhung -impeller contrifugal pumps designed for installation with pump and motor shaft mounted horizontal. C. Pump Construction: 1. Casing: Radially split with threaded companion -flange connections for pumps with NPS 2 pipe connections and flanged connections for pumps with NPS 2-1/2 pipe connections. 2. Impeller Statically and dynamically balanced, closed, and keyed to shaft. 3. Shaft and Shaft Sleeve: Steel shaft with deflector, with wpperalloy shaft sleeve. Include water Slinger on shaft between motor and seal. 4. Seal: Mechanical, with carbon -steel rotating ring, stainless -steel spring, ceramic seat, and rubber bellows and gasket. 5. Bearings: Oil -lubricated; bronzejournal or ball type. 6. Shoff Coupling: Flexible, capable of absorbing torsional vibration and shaft misalignment. D. Motor: Single speed, with grease -lubricated ball bearings; and resiliently or rigidly mounted to pump casing. E. Capacities and Characteristics: 1. Casing Material: Bronze. 2. Impeller Material: ASTM B 584, cast bronze or stainless steel. 3. Minimum Working Pressum: 175 psig. 4. Maximum Continuous Operating Temperature: 225 deg F. 5. Pump Control: Thermostat. 6. Electrical Characteristics: a. Volts: 120. b. Phases: Single. C. Heitz: 60. 2.2 MOTORS A. Comply with NEMA designation, temperature rating, service factor, enclosure type, and efficiency requirements for motors specified in Section 220513 "Common Motor Requirements for Plumbl rig Equ 1pment" 1. Motor Sizes: Minimum size as indicated. If not indicated, large enough so driven load will not require motor to operate in service factor range above 1.0. 2.3 CONTROLS A. Thermostats: Electric; adjustable for control of hot-water circulation pump. 1. Type: Water -immersion temperature sensor, for installation in piping. 2. Range: 65 to 200 deg F. 3. Enclosure: NEMA 250, Type 4X. 4. Operation of Pump: On or off. 5. Transformer : Provide if required. 6. Settings: Brad pump at 105 deg F and stop pump at 120 deg F. PART 3-EXECUTION 3.1 PUMP INSTALLATION A. Install horizontally mounted, in -line, close -coupled centrifugal pumps with shaft horizontal. B. Install continuous -thread hanger rods and spring hangers of size required to support 9 P 9 9 9 PP pump weight. 1. Coco with requirements for vibration isolation devices specified in Section 220648.13 PYP "Vibration Controls for Plumbing Piping and Equipment" Fabricate bracket or support as required. 2. Comply with requirements for hangers and supports specified in Section 220529 "Hangers and Supports for Plumbing Piping and Equipment" C. Install thermostats in hot-water return piping. 3.2 CONNECTIONS A. Comply with requirements for piping specified in Section 221116 "Domestic Water Piping." Drawings indicate general arrangement of piping, fittings, and specialties. B. Install piping adjacent to pumps to allow service and maintenance. C. Connect domestic water piping to pumps. Install suction and discharge piping equal to or greater than size of pump nozzles. 1. Install flexible connectors adjacent to pumps in suction and discharge piping of the following pumps: a. Horizontally mounted, in -line, close -coupled centrifugal pumps. b. Comply with requirements for flexible connectors specified in Section 221116 "Domestic Water Piping." 2. Install shutoff valve and strainer on suction side of each pump, and check, shutoff, and throttling valves on discharge side of each pump. Install valves same size as connected piping. Comply with requirements for valves specified in Section 220523.12 "Ball Valves for Plumbing Piping," Section 220523.13 "Butterfly Valves for Plumbing Piping," Section 220523.14 "Check Valves for Plumbing Piping," and Section 220523.15 "Gate Valves for Plumbing Piping," and comply with requirements for stainers specified in Section 221119 "Domestic Water Piping Specialties! 3. Install pressure gage at suction of each pump and pressure gage at discharge of each pump. Install at integral pressure -gage tappings where provided or install pressuregage connectors in suction and discharge piping around pumps. Comply with requirements for pressure gages and snubbers specified in Section 220519 "Meters and Gages for Plumbing Piping." D. Con nect thermostats to four cops that they control. 3.3 ADJUSTING A. Adjust domestic rater pumps to function smoothly, and lubricate as recommended by manufacturer. B. Adjust initial temperature set points. C. Set field -adjustable switches and circuit -breaker trip ranges as indicated. END OF SECTION 221123 SECTION 221316 -SANITARY WASTE AND VENT PIPING PART1-GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipe, tube, and fittings. 2. Specialty pipe fittings. 1.2 ACTION SUBMITTALS A. Product Data: For each type of product. PART 2-PRODUCTS 2.1 PERFORMANCE REQUIREMENTS A. Components and installation shall be capable of withstanding the following minimum working pressure unless otherwise indicated: 1. Soil, Waste, and Vent Piping: 10-foot head of water. 2.2 PIPING MATERIALS A. Piping materials shall bear label, stamp, or other markings of specified testing agency. B. Comply with requirements in "Piping Schedule" Article for applications of pipe, tube, fitting materials, and joining methods for specific services, service locations, and pipe sizes. 2.3 HUB -AND -SPIGOT, CAST-IRON SOIL PIPE AND FITTINGS A. Pipe and Fittings: ASTM A 74, Service class. B. Gaskets: ASTM C 564, rubber. C. Calking Materials: ASTM B 29, pum lead and oakum or hemp fiber. 2.4 COPPER TUBE AND FITTINGS A. Copper Type DWV Tube: ASTM B 306, drainage tube, drawn temper. B. Copper Drainage Fittings: ASME B16.23, cast copper or ASME B16.29, wrought copper, solder -joint fittings. C. Copper Pressure Fittings: 1. Copper Fittings: ASME B16.19,cast-copperalloy or ASME B16.22, wrought- copper, solderjoint fittings. Furnish wrought -copper fittings if indicated. 2. Copper Unions: MSS SP-123, copper -alloy, hexagonal -stock body with ball-and-socket, metal -to -metal seating surfaces, and solderjoint or threaded ends. D. Copper Flanges: ASME B16.24, Class 150, cast copper with solderjoint end. 1. Flange Gasket Materials: ASME B16.21, full -face, flat, nonmetallic, asbestos -free, 1/8-inch maximum thickness unless thickness or specific material is indicated. 2. Flange Bolts and Nuts: ASME B18.2.1, carbon steel unless otherwise indicated. E. Solder: ASTM B 32, lead free with ASTM B 813, water-flushable flux. PART 3-EXECUTION 3.1 PIPING INSTALLATION A. Dmwing plans, schematics, and diagrams indicate general location and arrangement of piping systems. 1. Indicated locations and arrangements were used to size pipe and calculate friction loss, expansion, pump sizing, and other design considerations. 2. Install piping as indicated unless deviations to layout are approved on coordination drawings. B. Install piping in concealed locations unless otherwise indicated and except in equipment rooms and service areas. C. Install piping indicated to be exposed and piping in equipment moms and service areas at right angles or parallel to building walls. Diagonal runs are prohibited unless specifically indicated otherwise. D. Install piping above accessible ceilings to allow sufficient space for ceiling panel removal. E. Install piping to permit valve servicing. F. Install piping at indicated slopes. G. Install piping free of sags and bends. H. Install fittings for changes in direction and branch connections. I. Install piping to allow application of insulation. J. Make changes in direction for soil and waste drainage and vent piping using appropriate branches, bends, and long -sweep bends. 1. Sanitary tees and short -sweep 1/4 bends may be used on vertical stacks if change in direction of flow is from horizontal to vertical. 2. Use long -turn, double Y-branch and 1/8-bend fittings if two fixtures are installed back to back or side by side with common Bain pipe. a. Straight tees, elbows, and crosses may be used on vent lines. 3. Do not change direction of flow more than 90 degrees. 4. Use proper size of standard increasers and retlucem if pipes of different sizes are connected. a. Reducing size of waste piping in direction of flow is prohibitetl. K. Lay buried building waste piping beginning at low point of each system. 1. Install time to grades and alignment indicated, with unbroken continuity of invert. Place hub ends of piping upstream. 2. Install required gaskets according to manufacturer's written instructions for use of lubricants, cements, and other installation requirements. 3. Maintain swab in piping and pull past each joint as completed. L. Install soil and waste and vent piping at the following minimum slopes unless otherwise indicated: 1. Building Sanitary Waste: 2 percent downward in direction of flow for piping NPS 3 and smaller; 2 percent downward in direction of flow for piping NPS 4 and larger. 2. Horizontal Sanitary Waste Piping: 2 percent downward in direction of flow. 3. Vent Piping: 1 percent down toward vertical fixture vent or toward vent stack. M. Install cast-iron soil piping according to CISPI's "Cast Iron Soil Pipe and Fittings Handbook," Chapter IV, "Installation of Cast Iron Soil Pipe and Fittings." N. Install aboveground copper tubing according to CDAs "Copper Tube Handbook." O. Do not enclose, cover, or put piping into operation until it is inspected and approved by authorities having jurisdiction. P. Install sleeves for piping penetrations of walls, ceilings, and floors. 1. Comply with requirements for sleeves specified in Section 220517 "Sleeves and Sleeve Seals for Plumbing Piping." Q. Install sleeve seals for piping penetrations of concrete walls and slabs. 1. Comply with requirements for sleeve seals specified in Section 220517 "Sleeves and Sleeve Seals for Plumbing Piping." R. Install escutcheons for piping penetrations of walls, ceilings, and floors. 1. Comply with requirements for escutcheons specified in Section 220518 "Escutcheons for Plumbing Piping." 3.2 JOINT CONSTRUCTION A. Join Indi-and-spigot,cast-iron soil piping with gasket joints accoding to CISP I's "Cast Iron Soil Pipe and Fittings Handbook" for compression joints. B. Join copper tube and fittings with soldered joints according to ASTM B 828. Use ASTM B 813, water-flushable, lead-free flux and ASTM B 32, lead -free -alloy solder. 3.3 HANGER AND SUPPORT INSTALLATION A. Comply with requirements for pipe hanger and support devices and installation specified in Section 220548.13 "Vibration Controls for Plumbing Piping and Equipment" 1. Install carbon -steel pipe hangers for horizontal piping in noncorrosive environments. 2. Install stainless -steel pipe hangers for horizontal piping in corrosive environments. 3. Install carbon -steel pipe support clamps for vertical piping in noncorrosive environments. 4. Install stainless -steel pipe support clamps for vertical piping in corrosive environments. 5. Vertical Piping: MSS Type 8 or Type 42, clamps. 6. Install individual, straight, horizontal piping inns: a. 100 Feet and Less: MSS Type 1, adjustable, steel clevis hangers. b. Longer Than 100 Feet: MSS Type 43, adjustable roller hangers. C. Longer Than 100 Feet if Indicated: MSS Type 49, spring cushion rolls. 7. Multiple, Straight, Horizontal Piping Runs 100 Feet or Longer: MSS Type 44, pipe rolls. Support pipe rolls on trapeze. 8. Base of Vertical Piping: MSS Type 52, spring hangem. B. Support horizontal piping and tubing within 12 inches of each fitting and coupling. C. Support vertical piping and tubing at base and at each floor. D. Rod diameter may be mtlucetl one size for double -rod hangers, with 3/8-inch minimum rods. E. Install hangem for ces moron soil piping with the following maximum horizontal spacing and minimum rotl diameters: 1. NPS 1-1/2 and NPS 2: 60 inches with 3/8-inch rod. 2. NPS 3:60 inches with 1/2-inch rod. 3. NPS 4 and NPS 5: 60 inches with 5/8-inch red. 4. NPS 6 and NPS 8:60 inches with 3/4-inch red. 5. NPS 10 and NPS 12: 60 inches with 7/8-inch red. 6. Spacing for 10-foot lengths may be increased to 10 feet. Spacing forfittings is limited to 60inches. F. Install supports for vertical cast-iron soil piping every 15 feet. G. Install hangers for steel piping with the fallowing maximum horizontal sparing and minimum rotl tliameters: 1. NPS 1-1/4: 84 inches with 3/8-inch rod. 2. NPS 1-1/2: 108 inches with 318-inch rotl. 3. NPS 2: 10 feet with 3/8-inch rod. 4. NPS 2-12: 11 feet with 1/2-inch rod. 5. NPS 3: 12 feet with 1/2-inch rod. 6. NPS 4 and NPS 5: 12 feet with 5/8-inch rotl. 7. NPS 6 and NPS 8: 12 feet with 3/4-inch rotl. 8. NPS 10 and NPS 12: 12 feet with 7/8-inch rotl. H. Install supports for vertical steel piping every 15 feet. I. Install hangers for stainless -steel piping with the following maximum horizontal spacing and minimum rod diameters: 1. NPS 2: 84 inches with 3/8-inch rotl. 2. NPS 3:96 inches with 1/2-inch rotl. 3. NPS 4: 108 inches with 1/2-inch rotl. 4. NPS 6: 10 feet with 5/8-inch rod. J. Install supports for vertical stainless -steel piping every 10 feet. SP-NGA spin a strength • yoga FOXFIELD CONSTRUCTION I.M. rxsaaxas msoev¢ s �aenaaa VIRTUAL ENERGY SOLUTIONS 33 E. OGDEN AVE. SUITE 304 LA GRANGE IL, 60525 312.683.7023 W W W.VESCHICAGO.COM #AA26003751 7 i N (0 m C) 0 Q U � (D V ry� W (Z Z ICU W Q� a _� U Cf) C M � U r PEIISO0637 '? STATE OF J ,R Dare VES project number: 190301 sheet title: PLUMBING SPECIFICATIONS sheet number: P005 © 2018 Virtual Energy Solutions, Inc.