HomeMy WebLinkAboutA121 Reflected Ceiling PlanLEGEND
NEW OR RELOCATED EXISTING TO REMAIN
LIGHT FIXTURE, 2'x4',
LED
LIGHT FIXTURE, 2'x2',
LED
0
LIGHT FIXTURE, I'x4',
LED
o
LIGHT FIXTURE, I'x4',
LED
LIGHT FIXTURE
TRACK
RECESSED LIGHT
FIXTURE
DIRECTIONAL RECESSED
LIGHT FIXTURE
WALL SCONCE LIGHT
FIXTURE
®
LIGHT FIXTURE,
PENDANT
NIL
NIGHT LIGHT
LIGHT FIXTURE, 2'x4',
FLUORESCENT, PARABOLIC
LIGHT FIXTURE, 2'x2'
FLUORESCENT, PARABOLIC
0 LIGHT FIXTURE, 1'x4',
FLUORESCENT, PARABOLIC
o LIGHT FIXTURE, I'x4',
FLUORESCENT, INDIRECT
LIGHT FIXTURE,
TRACK
0 RECESSED LIGHT
FIXTURE
XP WAILSCONCELIGHT
FIXTURE
® LIGHT FIXTURE,
PENDANT
®
EXIT LIGHT FIXTURE
®
EXIT LIGHT FIXTURE
EMERGENCY LIGHT FIXTURE
EMERGENCY LIGHT FIXTURE
LIGHT SWITCH
3 LIGHT SWITCH, 3-WAY
ND LIGHT SWITCH, DIMMER
p SWITCH, PROJECTOR
SCREEN
IG SWITCH, GARBAGE
DISPOSAL (ABOVE
COUNTERTOP(
*NE SWITCH, EXHAUST FAN
/—� LIGHTCIRCUIT
CEILING GRID,
SUSPENDED, 2'x2'
GYPSUM BOARD CEILING
EXPOSED TO DECK
LIGHT SWITCH
3 LIGHT SWITCH, 3-WAY
t LIGHT SWITCH, DIMMER
pp
SWITCH, PROJECTOR
SCREEN
G
SWITCH, GARBAGE
DISPOSAL
xE SWITCH, EXHAUST FAN
UGHTCIRCUIT
GYPSUM BOARD CEILING
RELOCATED DIFFUSER,
®
DIFFUSER,
LAY-1 N, 2'x2'
LAY-1 N, 2'x2'
—
RELOCATED DIFFUSER,
®
DIFFUSER,
LAY -IN, 1'X4
LAY-IN, 1 At
RELOCATED DIFFUSER,
m
DIFFUSER,
LAY IN, 4"x4'
LAY IN, 4"x4'
®
EXHAUST FAN, 2'x2'
EXHAUST FAN,
NOTE: IF IN GOOD CONDITION, EXISTING H.V.A.C. DEVICES AND CEILING TILES
SALVAGED FROM DEMOLITION CAN BE SUBSTITUTED FOR NEW. NO NEW
HVAC DUCTWORK IS TO BE INSTALLED PER THIS SHEET.
RELEASED FOR CONSTRUCTION
Subject to compliance with all regulations
of State and Local Codes
City of Camel
DATE: 08/23/19
GENERAL NOTES
I. PROVIDE N EW BUILDING STANDARD CEILING GRID AND TILE UNLESS
OTHERWISE NOTED. PROVIDE NEW 2X2 CEILING GRID TO MATCH
EXISTING CORRIDOR HEIGHT. TILES ARE 2x2 ACOUSTICAL LAY IN
TILES. REPAIR ANY DAMAGED GRID AND REPLACE ANY DAMAGED
TILES WITH NEW TO MATCH EXISTING.
2. PROVIDE LIKE CEILING TI LES IN INDIVIDUAL ROOMS WHERE POSSIBLE
TO CREATE UNIFORM LOOK.
3. PROVIDE EMERGENCY LIGHTING IN TENANT SPACE AS REQUIRED PER
NEMAANDIBC. LIGHTS CONNECTED TO AN EMERGENCY POWER
SOURCE ARE REQUIRED IF THE SPACE CONTAINS 50 PERSONS OR
MORE, FIXTURES SHOWN ON PLAN ARE FOR REFERENCE ONLY, IN
RECEPTION AREAS, CONFERENCE ROOMS AND OTHER HIGH PROFILE
AREAS WITHIN SUITE, ALL LOCATIONS OF SUCH DEVICES MUST BE
APPROVED BY SDI OR TENANT PRIOR TO INSTALLATION. FAILURE TO
DO SO MAY RESULT IN CONTRACTOR RELOCATING THESE ITEMS AT
THEIR EXPENSE.
4. LAYOUT SHOWN IS INTENDED TO MEET ASHRAE 90.1 STANDARDS.
ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR COMPLIANT
INSTALLATION. IF ADJUSTMENT IS REQUIRED TO MEET ASHRAE 90.1,
CONTRACTOR MUST NOTIFY SDI, OVER 50% OF THE LIGHTING WILL
BE REPLACED WITH NEW, SO ASHRAE WATTAGE REQUIREMENTS WILL
NEED TO BE MET.
5. ALL NEW SWITCHES TO BE OCCUPANCY SENSORS, PROVIDE COMBO
UNIT WITH BOTH ULTRASONIC AND INFRARED TECHNOLOGY WITH
ONE BUTTON OVERRIDE. OCCUPANCY SENSORS ARE TO BE
LOCATED SUCH THAT OCCUPANCY WITHIN ANY PORTION OF
INCLUDED AREA IS DETECTED, PROVIDE CEILING MOUNTED
OCCUPANCY SENSORS IN OPEN AREAS AS REQUIRED.
6. NEW DEVICES AND FACE PLATES TO BE WHITE. WHERE POSSIBLE,
GANG MULTIPLE SWITCHES TO ACCOMMODATE MULTISWITCHPLATE
WHEN SWITCHES ARE SHOWN ADJACENT ON PLAN.
7. ELECTRICAL WORK IS LIMITED TO A DESIGN -BUILD SCOPE AND IS
OUTLINED IN THESE DRAWINGS. ALL ELECTRICAL WORK IS LIMITED TO
ADDITIONS OR RELOCATIONS OF ELECTRICAL OUTLET DEVICES AND
LIGHTING THAT DO NOT EXCEED THE CAPACITY OF THE EXISTING
ELECTRICAL SERVICE IN THE BUILDING. ELECTRICAL CONTRACTOR IS
TO NOTIFY APPLICABLE PARTIES IF ADDITIONAL WORK IS REQUIRED
SO THAT ADDITIONAL PLANS CAN BE FILED AND MUST COMPLY WITH
ALL APPLICABLE CODES.
® AREA NOT IN CONTRACT
❑ AREA OF WORK
MECHANICAL NOTES
wmiiiiiiiiiiiiiim
MECHANICAL W OR IS LIMITED TO A DESIGNBUILDSCOPE AND 6
OUTLINED IN THESE DRAWINGS. NO NEW MAIN MECHANICAL
APPLIANCES OR MAIN EQUIPMENT ARE BEING PROVIDED. ALL
MECHANICAL WORK IS LIMITED TO RELOCATION OF DIFFUSERS AND
FLEX DUCT PER NEW WALL LAYOUT. NO NEW HARD DUCTWORK OR
EQUIPMENT IS BEING ADDED; MECHANICAL CONTRACTOR IS TO
NOTIFY APPLICABLE PARTIES IF ADDITIONAL WORK IS REQUIRED SO
THAT ADDITIONAL PLANS CAN BE FILED AND MUST COMPLY WITH THE
NDIANA MECHANICAL CODE AND ALL OTHER APPLICABLE CODES,
2. HVAC LAYOUT TO BE APPROVED PRIOR TO WORK BEING COMPLETED.
FILTERS MUST BE CHANGED AT CLOSE OF PROJECT AND ALL
THERMOSTATS MUST BE CALIBRATED AND AIR BALANCED, PROVIDE
REPORT TO OWNER.
PLAN NOTES
R01 BUILDING STANDARD HVAC TO BE PROVIDED IN SERVER ROOM
UNLESS NOTED OTHERWISE.
REFLECTED CEILING PLAN
0 2' 4' 8' 16'
THIS DRAWING, AND THE IDEAS,
DESIGNS AND CONCEPTS CONTAINED
HEREIN, ARE THE EXCLUSIVE
INTELLECTUAL PROPERTY OF SCHOTT
DESIGN, INC., AND ARE NOT TO BE
USED OR REPRODUCED IN WHOLE, OR
IN PART, WITHOUT THE WRRTEN
CONSENT OF SCH07 DESIGN.
CNI
co
C)
Q
WC4-
I. LLJ
O S 2
1
V=J
Y •
Z�~
Q � Q
Z 0
aaa� Q
JpLu
Z
REVISIONS
MAR=RI"ON
PROJECT NUMBER
2019.150
DRAWN BY
NP
4TH FLOOR
REFLECTED
CEILING PLAN
>N Al21