HomeMy WebLinkAboutE 501ilt411:b1:1�3Q11a 17N71II�VINIIIISNLU31�7MSN1f[N:IIQI:F THESE SPECIFICATIONS, ALL OTHER DOCUMENTS ATTACHED HERETO, ALL ADDENDA ISSUED AND THE ACCOMPANYING PLANS ARE INTENDED TO PROVIDE FOR THE COMPLETE FURNISHING AND INSTALLING OF THE ENTIRE ELECTRICAL SYSTEM. THE WORK SHALL BE DONE IN ACCORDANCE WITH BEST PRACTICE SO AS TO CONTRIBUTE TO EFFICIENCY OF OPERATION AND MINIMUM MAINTENANCE AND SHALL BE INSTALLED WITH PROPER ACCESSIBILITY. THE MATERIALS AND EQUIPMENT, INCLUDING ALL NECESSARY ACCESSORIES, SHALL BE PUT INTO PROPER ADJUSTMENT SO THAT THE COMPONENT PARTS FUNCTION TOGETHER AS A WORKABLE SYSTEM. PROVIDE ALL EQUIPMENT, MATERIALS AND OPERATIONS AS INDICATED EITHER ON THE DRAWINGS OR CONTAINED HEREIN OR AS MAY BE REASONABLY IMPLIED BY EITHER TO ACCOMPLISH COMPLETE ELECTRICAL SYSTEMS. DESCRIPTION OF WORK: PRINCIPAL ITEMS OF WORK INCLUDE, BUT ARE NECESSARILY LIMITED TO THE FOLLOWING: SYSTEM SERVICE VOLTAGE SHALL BE 120/208 VOLT, 3 PHASE, 4 WIRE AND 277/480 VOLT, 3 PHASE, 4 WIRE. FURNISH AND INSTALL DISTRIBUTION PANELS, TRANSFORMERS AND LIGHTING AND RECEPTACLE PANEL BOARDS. FURNISH AND INSTALL ALL WIRING, STARTERS, DISCONNECT SWITCHES, ETC. FOR ALL MECHANICAL EQUIPMENT, INCLUDING CONTROLS AND REQUIRED INTERLOCKING, UNLESS SPECIFICALLY STATED OTHERWISE. FURNISH AND INSTALL ALL CONDUIT BACK BOXES, RECEPTACLES AND FACEPLATES. PROVIDE ALL SUPPORTS REQUIRED FOR THE INSTALLATION OF ELECTRICAL EQUIPMENT. FURNISH AND INSTALL ALL GROUNDING PER N.E.C. INCLUDING BRANCH CIRCUITING. FURNISH AND INSTALL ALL INTERIOR LIGHTING FIXTURES, AUXILIARIES, LAMPS SWITCHES AND FACEPLATES. FURNISH AND INSTALL ALL EXTERIOR LIGHTING FIXTURES, AUXILIARIES, LAMPS, PHOTOCELLS, CONTACTORS AND TIME SWITCHES. FURNISH AND INSTALL LIGHTING MOTION SENSORS. FURNISH AND INSTALL FLUSH BOXES, COVER PLATES AND CONDUIT FOR POWER/DATA/TELEPHONE, COMMUNICATION CABLES BY OTHERS. PROVIDE ARC FLASH LABELING. FURNISH AND INSTALL ALL CONDUIT BACK BOXES FACEPLATES PULL STRING FOR TELEPHONE/DATA SYSTEM, JACKS AND WIRING BY OTHERS. DEFINITIONS: 'PROVIDE' - SHALL MEAN 'FURNISH AND INSTALL AND PLACE IN OPERATION OR 'FURNISH LABOR AND MATERIAL REQUIRED FOR INSTALLATION OF AND PLACE IN OPERATION'. 'CONDUIT' - INCLUDES IN ADDITION TO CONDUIT, ALSO FITTINGS, HANGERS AND OTHER ACCESSORIES WHICH COMPRISE A SYSTEM. INSPECTION OF SITE: THE ELECTRICAL CONTRACTOR SHALL VISIT THE JOB SITE BEFORE HE SUBMITS HIS BID, TO FAMILIARIZE HIMSELF WITH ACTUAL JOB CONDITIONS. GOVERNING AGENCIES: THE CONTRACTOR SHALL BE FULLY INFORMED OF ALL LAWS, ORDINANCES AND CODES, AND SHALL, IN THE PERFORMANCE OF THE CONTRACT, COMPLY WITH ALL APPLICABLE FEDERAL, STATE AND LOCAL REGULATIONS. ANY DEVIATION FROM THE PLANS OR SPECIFICATIONS AND ANY ADDITIONAL WORK NECESSARY TO MEET CODE REQUIREMENTS SHALL BE MADE BY THE CONTRACTOR WITHOUT EXTRA COST TO THE OWNER. ALL WORK SHALL BE EXECUTED AND INSPECTED IN ACCORDANCE WITH THE LATEST APPROVED EDITION OF THE NATIONAL ELECTRIC CODE 2017, THE CODES OF O.S.H.A. AND ALL LOCAL AUTHORITIES HAVING JURISDICTION. SECURE AND PAY FOR ALL PERMITS, FEES, BONDS, INSPECTIONS AND TESTS REQUIRED. UTILITY COMPANY REQUIREMENTS: WORK SHALL BE DONE IN ACCORDANCE WITH THE RULES OF LOCAL UTILITY COMPANIES. THE CONTRACTOR SHALL CHECK WITH EACH UTILITY SUPPLYING SERVICE TO THIS PROJECT AND SHALL DETERMINE FROM THEM ALL EQUIPMENT AND CHARGES WHICH SHALL BE INCLUDED IN HIS PRICE. BARRIER FREE DESIGN: THE CONTRACTOR SHALL REVIEW INSTALLATION REQUIREMENTS FOR CONFORMING TO THE HANDICAPPED BARRIER FREE REGULATIONS AND AMERICAN DISABILITY ACT. IN PARTICULAR, MOUNTING HEIGHTS OF OUTLETS AND ACCESSIBILITY OF CONTROLS ETC. SHALL BE COMPLIED WITH. HANDLING OF MATERIAL AND EQUIPMENT: THE CONTRACTOR SHALL RECEIVE, PROPERLY HOUSE, TRANSPORT AND INSTALL AT PROPER LOCATIONS, EQUIPMENT AND MATERIALS REQUIRED FOR HIS CONTRACT. RESPONSIBILITY FOR CARE AND PROTECTION OF EQUIPMENT, MATERIAL AND WORK PERFORMED AGAINST THEFT, INJURY OR DAMAGE FROM ALL CAUSES REMAINS WITH THE CONTRACTOR UNTIL ACCEPTANCE OF THE PROJECT BY THE OWNER. DAMAGE TO OTHER WORK: THE ELECTRICAL CONTRACTOR WILL BE HELD RESPONSIBLE FOR DAMAGE TO WORK CAUSED BY HIS WORK OR THROUGH THE NEGLECT OF HIS WORKMEN. ALL PATCHING AND REPAIRING OF DAMAGED WORK SHALL BE DONE BY THE GENERAL CONTRACTOR, BUT THE COST OF SAME SHALL BE PAID BY THE CONTRACTOR RESPONSIBLE FOR THE DAMAGE. Cl CORING AND PATCHING: CUTTING, CORE DRILLING, INSERTS AND CONDUIT OR CABLE SLEEVES AND PATCHING REQUIRED IN THE GENERAL CONSTRUCTION FOR COMPLETION OF THE WORK, SPECIFIED HEREIN, SHALL BE FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR. SEAL ALL OPENINGS THROUGH S WITH 3M OR STI FIRE RATED MATERIAL. RELEASED FOR CONSTRUCTION Subject to compliance with all regulations of State and Local Codes e City of Camel ((�� �VTl�tla+nrfiaAAL DATE: \ 08/27/19 CONDUIT INSTALLATION: ALL WORK SHALL BE CONCEALED IN WALLS AND ABOVE CEILINGS IN FINISHED AREAS, UNLESS OTHERWISE NOTED. EXPOSED CONDUIT WHERE REQUIRED SHALL BE INSTALLED PERPENDICULAR OR PARALLEL TO WALLS, CEILINGS AND STRUCTURAL MEMBERS AND COORDINATED WITH MECHANICAL DUCTS, PIPES, LIGHTING FIXTURES AND EQUIPMENT. IN GENERAL, ALL CONDUITS SHALL BE RUN OVERHEAD. DRAWINGS: THE DESIGN DRAWINGS SHOW THE GENERAL ARRANGEMENT AND EXTENT OF THE WORK. THE DRAWINGS ARE DIAGRAMMATIC AND MAY NOT BE DRAWN TO SCALE IN CERTAIN AREAS FOR PURPOSES OF CLARITY AND LEGIBILITY. IT IS INTENDED THAT ALL APPARATUS BE LOCATED SYMMETRICAL WITH ARCHITECTURAL ELEMENTS AND BE INSTALLED TO AVOID OBSTRUCTIONS AND PRESERVE HEADROOM. THE CONTRACTOR SHALL REVIEW THE PLANS OF OTHER TRADES WITH HIS OWN WORK TO AVOID CONFLICTS AND INTERFERENCES; HE SHALL MAKE USE OF ALL SOURCES OF DATA, INCLUDING SHOP DRAWINGS AND DRAWINGS OF EQUIPMENT FURNISHED BY OTHERS. SHOP DRAWINGS: COMPLETE SHOP DRAWINGS FOR ALL ELECTRICAL WORK SHALL BE SUBMITTED TO THE ENGINEER FOR REVIEW BEFORE FABRICATION OF THE WORK. SEVEN (7) COPIES OF SHOP DRAWINGS SHALL BE SUBMITTED ON ALL ITEMS OF ELECTRICAL EQUIPMENT, PANELS, LIGHT FIXTURES, FACTORY GENERATED MOTION SENSOR LAYOUT, SPECIALTIES, ETC. RECORD DRAWINGS: CONTRACTOR SHALL PREPARE AND MAINTAIN ACCURATE RECORD DRAWINGS OF ALL UNDERGROUND AND CONCEALED WORK AND SHALL SUBMIT THESE DRAWINGS TO OWNER UPON FINAL ACCEPTANCE OF THE WORK OR UPON OWNER'S REQUEST. :Q9;U71:/.11[9;�7/M7[NNIiiY;E1 COORDINATE WORK WITH OTHER TRADES TO AVOID INTERFERENCES AND PRESENT A NEAT APPEARANCE. INTERFERENCES AS A RESULT FROM POOR COORDINATION WILL NOT BE CONSIDERED AS EXTRA WORK. ruX;I14;IX:la�: ALL MINOR DEVIATIONS REQUIRED DUE TO INTERFERENCES WITH THE WORK OF OTHERS SHALL BE MADE BY ELECTRICAL CONTRACTOR AT NO ADDITIONAL COST VERIFY LOCATIONS OF EXISTING SYSTEMS AND BUILDING STRUCTURAL SYSTEMS IN THE PROJECT AREA FOR CONNECTIONS TO SAME AND TO AVOID POSSIBLE INTERFERENCES. SUPPORTS: PROVIDE ALL SUPPORTS, FRAMING, ETC., FOR THE PROPER INSTALLATION OF CONDUIT, TRANSFORMERS, ELECTRICAL EQUIPMENT, LIGHTING FIXTURES, ETC. CONNECTIONS TO ELECTRICAL EQUIPMENT: MOTORS LIGHTING FIXTURES PACKAGE PANELS ETC., SHALL BE MADE IN ACCORDANCE WITH SHOP DRAWINGS AND ROUGH -IN MEASUREMENTS FURNISHED BY THE MANUFACTURERS OF THE PARTICULAR EQUIPMENT FURNISHED. ANY AND ALL ADDITIONAL CONNECTIONS NOT SHOWN ON THE PLANS, BUT CALLED FOR BY THE EQUIPMENT MANUFACTURER'S SHOP DRAWINGS OR REQUIRED FOR THE SUCCESSFUL OPERATION OF THE PARTICULAR EQUIPMENT FURNISHED, SHALL BE INSTALLED BY THE CONTRACTOR AS PART OF HIS CONTRACT WITH NO ADDITIONAL CHARGE. PAINTING: ALL FACTORY FINISHED EQUIPMENT SHALL BE CLEANED AT COMPLETION OF JOB. EQUIPMENT SHOWING RUST OR MARS SHALL BE GIVEN ONE COAT OF ENAMEL PAINT. COLOR AS SELECTED BY THE OWNER OR SHALL MATCH ORIGINAL FINISH. ACCESS TO EQUIPMENT: ALL CONTROL DEVICES, EQUIPMENT, ETC., SHALL BE SO LOCATED SO AS TO PROVIDE FOR EASY ACCESS OF OPERATION, REPAIRS AND MAINTENANCE. PROVIDE ACCESS DOORS AS REQUIRED. TESTING: ALL WORK SHALL BE TESTED AND ACCEPTED IN THE PRESENCE OF THE ARCHITECT OR ENGINEER, IF NOT IN WORKING ORDER OR COMPLIANCE, THE CONTRACTOR SHALL PROMPTLY CORRECT SAME AND MAKE GOOD TO CONFORM TO SPECIFICATIONS. EACH RECEPTACLE SHALL BE CHECKED FOR POLARITY, OPENS, GROUNDS, ETC., USING AN APPROVED RECEPTACLE TESTER, HUBBELL /5200 OR EQUAL PERFORM ALL TESTS REQUIRED BY STATE, CITY, COUNTY AND/OR OTHER AGENCIES HAVING JURISDICTION. AFTER ALL ELECTRICAL WORK HAS BEEN COMPLETED, THE CONTRACTOR SHALL DEMONSTRATE TO THE ARCHITECT OR ENGINEER THAT THE ENTIRE INSTALLATION IS IN WORKING ORDER. ANY DEFECTIVE WORK OR EQUIPMENT, OR ANY WORK THAT IS NOT IN COMPLIANCE WITH THE SPECIFICATIONS, SHALL BE PROMPTLY CORRECTED BY THE CONTRACTOR. ;NILI:IR[H32U111:IH7:IR[e AFTER ALL TESTS HAVE BEEN MADE, THE CONTRACTOR SHALL MAKE A THROUGH INSPECTION OF THE PROJECT AND ARRANGE TO HAVE WORK INVOLVED THOROUGHLY CLEANED, ALL RUBBISH REMOVED AND LEAVE ALL WORK IN A SATISFACTORY CONDITION TO THE ARCHITECT OR ENGINEER. DEMOLITION: ELECTRICAL DEMOLITION WORK SHALL INCLUDE: REMOVING AND/OR RELOCATING OF EXISTING PANELS, LIGHTING FIXTURES, RECEPTACLES, WIRE, CONDUIT, BOXES, ETC., AS INDICATED ON THE DRAWINGS. REMOVE ALL CONDUIT, WIRE, HANGERS, CLAMPS, ETC., THAT IS NOT BEING RE -USED UNLESS CONCEALED ABOVE CEILINGS OR IN WALLS, WHICH MAY BE ABANDONED AND LEFT IN PLACE. REMOVE ALL WIRE IN EXISTING CONCEALED ABANDONED CONDUITS. EXISTING CONCEALED CONDUITS (IF APPLICABLE) MAY BE RE -USED FOR NEW WIRING. REMOVE WIRE FROM CONDUITS ENTERING THE FLOOR. CAP CONDUIT FLUSH WITH OR FILL WITH CONCRETE. ALL EXISTING PANELS, LIGHTING FIXTURES, WIRING DEVICES, TELEPHONE OUTLETS, ETC., SHALL REMAIN IN THEIR EXISTING LOCATIONS, UNLESS OTHERWISE NOTED. REMOVE EXISTING WIRING DEVICES, PULL ALL WIRES OUT AND INSTALL A BLANK STAINLESS STEEL COVER PLATE OVER THE EXISTING OUTLET. MAKE CIRCUIT 'SAFE'. REVISE PANEL DIRECTORIES AS REQUIRED TO REFLECT ALL REVISIONS TO EXISTING PANELS. ALL MATERIALS THAT ARE TO BE REMOVED; PANELS, LIGHTING FIXTURES, WIRING DEVICES, CONDUIT, WIRE, ETC., SHALL BECOME THE PROPERTY OF THE CONTRACTOR UNLESS OTHERWISE NOTED ON THE DRAWINGS AND REMOVED FROM THE SITE AND LEGALLY DISPOSED OF. NAMEPLATES: PROVIDE NAMEPLATES ON EACH INDIVIDUAL MOTOR STARTERS PANELS SAFETY SWITCHES, ETC., INDICATING DEVICES CONTROLLED. NAMEPLATES SHALL BE WHITE LAMINATED PLASTIC WITH BLACK SCRIBED LETTERS SECURELY FASTENED TO DEVICE WITH SCREWS. ALL MATERIAL AND WORKMANSHIP SHALL BE GUARANTEED FOR A PERIOD OF ONE YEAR FROM THE DATE OF ACCEPTANCE, AND THE CONTRACTOR SHALL MAKE GOOD ANY DEFECTS WITHIN THAT PERIOD AT NO ADDITIONAL COST TO THE OWNER. MOUNTING HEIGHTS: LIGHTING SWITCHES Al TO CENTERLINE RECEPTACLES 1'-6' TO BOTTOM TELEPHONE/DATA 1'-6' TO BOTTOM WALL TELEPHONE 1'-0' TO CENTERLINE RECEPTACLE PANELS 6'-6' TO TOP MOTOR STARTERS/DISCONNECT 5'-6' TO TOP ALL MOUNTING HEIGHTS TO BE VERIFIED PRIOR TO STARTING WORK. CERTIFICATE OF APPROVAL: WHEN THE JOB IS COMPLETED, THE CONTRACTOR SHALL PROVIDE THE ARCHITECT/ENGINEER WITH CERTIFICATE OF APPROVAL FROM THE LOCAL ELECTRICAL INSPECTION AUTHORITY. THE CONTRACTOR SHALL GIVE THE OWNER A WRITTEN GUARANTEE THAT HE WILL MAKE GOOD, AT HIS OWN EXPENSE, ANY DEFECTS IN MATERIALS OR WORKMANSHIP WHICH MAY DEVELOP WITHIN ONE (1) YEAR FROM THE DATE OF FINAL ACCEPTANCE. ELECTRICAL - BASIC MATERIALS MATERIALS: MATERIALS SHALL BE NEW AND BEAR THE U.L. LABEL OR LISTING, WHEREVER STANDARDS HAVE BEEN ESTABLISHED. ALL EQUIPMENT OF THE SAME OR SIMILAR SYSTEMS SHALL BE OF THE SAME MANUFACTURER. CONDUIT, CONDUIT SHALL BE MC, THINWALL (EMT) R.G.S. OR PVC. CONDUIT INSTALLED IN OR UNDER SHALL BE Si MINIMUM, R.G.S. OR PVC. CONDUIT INSTALLED IN FINISHED AREAS SHALL BE CONCEALED. FLEXIBLE METAL CONDUIT WITH GROUND WIRE SHALL BE USED FOR FINAL CONNECTION TO LIGHTING FIXTURES, TRANSFORMERS, MOTORS, ETC., 1/2' MINIMUM. MC CABLE MAY BE USED IN PARTITION WALL OR ABOVE ACCESSIBLE CEILINGS. NO PVC CONDUIT WILL ALLOW IN BUILDING. ALL CONDUITS TURNING UP O BE ALLOWED B LD D FROM UNDERGROUND SHALL BE STEEL ELLS. EXPANSION: PROVIDE EXPANSION FITTINGS IN ALL CONDUIT RUNS THAT CROSS BUILDING EXPANSION JOINTS. CONDUIT SLEEVES: PROVIDE CONDUIT SLEEVES WHERE CONDUITS PASS THIRD FLOORS, WALLS, ETC. AS REQUIRED. ALL VOIDS BETWEEN SLEEVES OR HOLES AND CONDUITS PASSING THIRD SHALL BE FIRESTOPPED. 3M, Sri SPECSEAL 100 FIRE STOP SEALANT OR EQUAL. FIRE STOPPING: SEAL ALL OPENING WHERE NONMETALLIC SHEATHED CABLES, TELEPHONE AND CONDUITS PASS THIRD JOISTS, WALLS, S ETC. TO PREVENT PASSAGE OF FIRE, SMOKE, TOXIC GASSES AND WATER. SEALANT SHALL BE LATEX BASED HIGH SOLIDS FIRE STOP COMPOUND. SEALANT SHALL ADHERE WELL TO ALL SURFACES AND MAY BE APPLIED USING A STANDARD CAULK GUN OR PUTTY KNIFE. SEALANT SHALL BE SPECIFIED TECHNOLOGIES INC. (STI) JLC100. WIRING: FEEDERS SHALL BE TYPE 'THW' OR 'XHHW'. BRANCH CIRCUIT WIRING SHALL BE TYPE *THWN/THHN, /12 MINIMUM. ALL WIRE SHALL BE COPPER, HAVE 600 VOLT INSULATION, /8 WIRE AND LARGER SHALL BE STRANDED. ALL WIRE INSULATION TO BE COLOR CODED. PROVIDE SEPARATE NEUTRAL AND GROUND WIRE FOR EACH RECEPTACLE CIRCUIT FOR COMPUTER EQUIPMENT. ARC FLASH LABELS: THIS CONTRACTOR SHALL PROVIDE ARC FLASH LABELS IN ACCORDANCE WITH THE LATEST APPROVED EDITION OF THE N.E.C. 2017. TRANSFORMER: STEP DOWN TRANSFORMER SHALL BE DRY TYPE, 150' DEGREES C. RISE, 480V., 3 PHASE, 3 WIRE, PRIMARY 120/2081 3 PHASE, 4 WIRE, SECONDARY. TRANSFORMER TO BE MOUNTED ON VIBRATION ISOLATORS. 4-2-1/2% TAPS 2 ABOVE AND 2 BELOW NORMAL. SQUARED, SIEMENS, CUTLER HAMMER, G.E. OR EQUAL. GROUND TRANSFORMER TO BUILDING GROUND. TRANSFORMERS, OTHER THAN CLASS 2 OR CLASS 3 TRANSFORMERS, SHALL HAVE A DISCONNECTING MEANS LOCATED EITHER IN SIGHT OF THE TRANSFORMER OR IN A REMOTE LOCATION. WHERE LOCATED IN A REMOTE LOCATION, THE DISCONNECTING MEANS SHALL BE LOCKABLE IN ACCORDANCE WITH 110.25, AND ITS LOCATION SHALL BE MARKED ON THE TRANSFORMER (PER NEC 2017 SECTION 450.14). RECEPTACLE PANELS: PANELS SHALL BE 120/208 VOLT, 3 PHASE, 4 WIRE, WITH BOLT -ON CIRCUIT BREAKERS RATED 10,000 A.I.C. MINIMUM, COPPER BUS, DOOR -INDOOR COVER PLATE, SQUARE On 'NOOD' OR AS NOTED. PROVIDE TYPEWRITTEN DIRECTORY INDICATING EACH ITEM SERVED. LOAD CENTERS ARE NOT ACCEPTABLE. CONDUIT STUBS: ALL FLUSH PANELS TO HAVE TWO (2) 1'C STUBBED TO CEILING SPACE FOR FUTURE. DISCONNECT SWITCHES: DISCONNECT SWITCHES SHALL BE 250 VOLT OR 600 VOLT HEAVY DUTY, FUSED OR NON -FUSED AS INDICATED, IN A NEMA I ENCLOSURE. DISCONNECT SWITCHES INSTALLED OUTDOORS SHALL BE IN A NEMA 31? ENCLOSURE. SQUARE D 3110 SERIES OR AS NOTED. SINGLE PHASE MOTOR STARTERS SHALL HAVE MANUAL TOGGLE SWITCH WITH THERMAL OVERLOADS, FLUSH MOUNTED WITH PILOT LIGHT, SQUARE D, CLASS 2510, CUTLER HAMMER, G.E., OR SIEMENS I.T.E. SINGLE PHASE MOTOR STARTERS WITH AUTO -OFF -HAND SPOT SELECTOR SWITCH, SHALL BE FLUSH MOUNTED WITH PILOT LIGHT. SQUARE D CLASS 2510-FF71P CUTLER HAMMER, C.E. OR SIEMENS I.T.E. THREE PHASE MOTOR STARTERS SHALL BE MAGNETIC TYPE, WITH FUSED CONTROL TRANSFORMER WITH 3 OVERLOADS, HAND-OFF AUTO SWITCH, AUXILIARY CONTACTS AND PILOT LIGHT AS REQUIRED, SQUARE D, CLASS 8536, CUTLER HAMMER, G.E., OR SIEMENS I.T.E. COMBINATION THREE PHASE MOTOR STARTERS SHALL BE THE SAME AS ABOVE EXCEPT WITH FUSED DISCONNECT AND CLASS R FUSES. FUSES: 601 AMPERE AND LARGER SHALL BE PROTECTED BY CURRENT LIMITING BUSSMANN HI -CAP TIME DELAY FUSES KRP-C, 250 VOLT OR 480 VOLT. 0 TO 600 AMPERE SHALL BE PROTECTED BY CURRENT UNITING BUSSMANN LOW -PEAK DUAL ELEMENT FUSES LBN/LPS, 250 VOLT OR 480 VOLTS. MOTOR CIRCUITS SHALL BE PROTECTED BY BUSSMANN LOW -PEAK DUAL -ELEMENT FUSES LPN/LPS, 250 VOLT OR 480 VOLTS. CIRCUIT BREAKER PANELS SHALL BE PROTECTED BY BUSSMANN LOW -PEAK DUAL -ELEMENT FUSES LPN/LBS, 250 VOLT OR 480 VOLTS. GROUNDING: PROVIDE SEPARATE GROUND WIRE FOR ALL MOTORS, RECEPTACLES AND FEEDERS. CABINETS, MOTOR FRAMES, STARTERS, CONDUIT SYSTEMS, PANELS, ETC., SHALL BE GROUNDED IN ACCORDANCE WITH THE LATEST N.E.C. AND LOCAL CODES AS ADOPTED BY THE AUTHORITY HAVING JURISDICTION. SWITCHES: SWITCHES SHALL BE 20A., 120/277V., 1 POLE, 3 AND 4 WAY AS INDICATED, HUBBELL /1221 SERIES OR EQUAL COLOR TO BE WHITE OR AS SELECTED BY ARCHITECT. DIMMER SWITCHES: LOW VOLTAGE DIMMER SWITCHES SHALL INTERFACE WITH OCCUPANCY SENSORS AND POWER PACKS. DIMMER SWITCHES SHALL BE RATED 0-10VDC UNLESS OTHERWISE NOTED, SOLID STATE, U.I. LISTED. PROVIDE EXTERNAL DIMMED POWER PACK RELAY AS REQUIRED PER MANUFACTURER. VERIFY MANUFACTURER DE -RATING REQUIREMENTS IF GANGED WITH OTHER DIMMER SWITCHES. MOTION SENSORS: CEILING MOUNTED MOTION SENSORS AND SWITCH PACKS (POWER PACKS) ARE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO REVIEW MANUFACTURER'S INSTALLATION INSTRUCTIONS PRIOR TO ROUGH -IN. CONTRACTOR SHALL PROVIDE MANUFACTURERS FACTORY GENERATED DEVICE LAYOUT AS PART OF SHOP DRAWING SUBMITTALS. (SENSOR SWITCH, GREENGATE, WATT STOPPER, LUTRON OR LEVITON). ELECTRICAL CONTRACTOR SHALL VERIFY AND COORDINATE MOTION SENSOR LOCATIONS WITH LIGHTING LAYOUT, MECHANICAL EQUIPMENT LAYOUT, ETC PRIOR TO ROUGH -IN INCLUDING FURNITURE LAY -OUT. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF THE NUMBER OF SWITCH PACKS NEEDED. ONE SWITCH PACK PER CIRCUIT. MAXIMUM OF FIVE SENSORS PER SWITCH PACK. MULTIPLE CIRCUITS MAY BE CONTROLLED BY ON SENSOR BY USING ADDITIONAL SWITCH PACKS. MAXIMUM OF TEN SWITCH PACKS PER SENSOR. ELECTRICAL CONTRACTOR SHALL FOLLOW MANUFACTURER'S RECOMMENDATION OF FINAL DEVICE LOCATIONS, COVERAGE, FREQUENCY, QUANTITY AND VERIFY CIRCUITS WITH RESPECT TO SWITCH PACK NEEDED IN THE FIELD PER MANUFACTURER OF CHOICE. TO PREVENT FALSE ACTIVATION, CEILING MOUNTED SENSORS SHALL BE MOUNTED AWAY FROM THE PATH OF STRONG AIR TURBULENCE, A MINIMUM OF FOUR FEET FOR STANDARD SENSITIVITY AND SIX FEET FOR MAXIMUM SENSITIVITY. ELECTRICAL CONTRACTOR SHALL FIELD ADJUST EACH AREAS MOTION SENSOR'S TIME DELAY FROM 15 SECONDS TO 30 MINUTES PER OWNER'S DIRECTION. PRIOR TO INSTALLATION OF MOTION SENSORS, ELECTRICAL CONTRACTOR SHALL MEET WITH OWNER TO DETERMINE EACH AREAS TIME DELAY SETTING. RECEPTACLES: RECEPTACLES SHALL BE SPECIFICATION GRADE DUPLEX, GROUNDING TYPE 20A., 125V., WHITE FINISH, HUBBELL ;E5362-W OR EQUAL. SPECIAL PURPOSE RECEPTACLES 30A., 40A., 50A., 2P. OR 3P., ETC., SHALL BE SPECIFICATION GRADE, HUBBELL, COOPER WIRING DEVICES, PASS & SEYMOUR, OR LEVITON. G.F.I. RECEPTACLES SHALL BE SPECIFICATION GRADE DUPLEX GROUNDING TYPE, 20A., 1251 HUBBELL /GF5362-WA, COOPER WIRING DEVICES, PASS & SEYMOUR OR LEVITON. WEATHERPROOF CFI RECEPTACLES SHALL BE OUTDOOR RATED AND HAVE WHILE -IN -USE POLYCARBONATE WEATHERPROOF COVER . THE ENCLOSURE SHALL HAVE CORD PORTS CAPABLE OF ALLOWING AN ELECTRICAL CORD TO PASS THROUGH WHEN COVER IS CLOSED, TAYMAC /20310 OR EQUAL WALL PLATES: WALL PLATES FOR SWITCHES, RECEPTACLES AND TELEPHONE OUTLETS SHALL BE HIGH -IMPACT SMOOTH NYLON OR SUPER STAINLESS STEEL, ANSI 302, HUBBELL P1 SERIES OR #97000 SERIES OR EQUAL. SPECIAL PLATES AS NECESSARY. WEATHERPROOF RECEPTACLES SHALL HAVE CAST GASKET COVERPLATE HUBBELL i5206WO OR EQUAL OUTLETS: OUTLET BOXES FOR CONCEALED WORK SHALL BE PRESSED STEEL BOXES, GALVANIZED, /12 GAUGE. CEILING BOXES SHALL BE 4' ROUND OR OCTAGONAL WALL OUTLET BOXES SHALL BE 4' SQUARE BY 1-1/2' DEEP, SINGLE GANG FOR WIRING DEVICES. CTOH 11111 5M ROUND NON-METAWC FLOOR BOX FOR POWER/TELEPHONE/DATA. FLOOR BOX SHALL BE 6' DEEP WITH TWO 1' SIZE HUB AND TWO 3/4' SIZE HUB. PROVIDE ADAPTER RINGS, LOW VOLTAGE DIVIDER, BRASS MULTI -SERVICE COVER WITH DUPLEX FLAP WITH (2) 1/2' DIAMETER LOW VOLTAGE FEED THROUGH HOLES AND (1) 20A 125V RECEPTACLE, HUBBELL #5362. CONTRACTOR SHALL VERIFY FLOOR TYPE PRIOR TO ROUGH -IN. HUBEl PFB1-PFBAIA-PFBTIA-SF39253A-S5016. (COLOR/FINISH SELECTED BY ARCHITECT). ROUND SINGLE -SERVICE NON-METALLIC FLUSH FLOOR BOX WITH BRASS COVER ROUND NON-METAWC FLOOR BOX FOR POWER ONLY. FLOOR BOX SHALL BE 6' DEEP WITH TWO 1' SIZE HUB AND TWO 3/4' SIZE HUB. PROVIDE ADAPTER RINGS, BRASS SINGLE -SERVICE COVER WITH DUPLEX FLAP AND (1) 20A 125V RECEPTACLE, HUBBELL 15362. CONTRACTOR SHALL VERIFY FLOOR TYPE PRIOR TO ROUGH -IN. HUBBELL PFBI-PFBAIA-SA3925-S5016. (COLOR/FINISH SELECTED BY ARCHITECT). TIME SWITCHES: TIME SWITCHES SHALL BE 7-DAY, ELECTRONIC, 4 CIRCUIT, RATED 20A PER POLE, INTERMATIC ET70415CR, PARAGON OR FORK. LIGHTING FIXTURES: (REFER TO OGHTING FIXTURE SCHEDULE) ALL FIXTURES SHALL BE U.L. LISTED. ALL FIXTURES INSTALLED OUTSIDE SHALL HAVE DAMP LOCATION LABEL 1EM: LUMINAIRE SHALL MAINTAIN 70% LUMEN OUTPUT (L70) FOR A MINIMUM OF 50,000 HOURS. DRIVER SHALL HAVE A RATED LIFE OF 50.000 HOURS, MINIMUM. LUMEN OUTPUT SHALL NOT DEPRECIATE MORE THAN 20% AFTER 10,000 HOURS OF USE. DRIVER AND LEDS SHALL BE FURNISHED FROM A SINGLE MANUFACTURER TO ENSURE COMPATIBILITY. WIRING CONNECTIONS TO LED DRIVERS SHALL UTILIZE POLARIZED QUICK - DISCONNECTS FOR FIELD MAINTENANCE. THE LED LUMINAIRE SHALL CARRY A LIMITED 5-YEAR WARRANTY MINIMUM FOR LED LIGHT ENGINES)/BOARD ARRAY, AND DRIVER(S). LIGHTING PHOTOCONTROL• PHOTOCONTROL SHALL BE RATED 2000 WATTS AT 120 VOLT AND 3600 WATTS AT 277 VOLT. INTERMATIC BK4121M AND /K4123C, OR FORK. CONTROL: PROVIDE ALL CONTACTORS, TIME SWITCHES AND PHOTOCELL FOR A COMPLETE OUTSIDE LIGHTING SYSTEM. PHOTOCELL TURNS LIGHTING 'ON, TIME CLOCK TURNS LIGHTING 'OFF'. TELEPHONE/DATA (CONDUIT QNLY1: TYPICAL OUTLET SHALL BE A DOUBLE GANG BOX WITH SINGLE GANG FACEPLATE AND 1' MINIMUM CONDUIT TERMINATING ABOVE AN ACCESSIBLE CEILING (LAY -IN) Al JOIST SPACE WHERE NO CEILING IS PRESENT. PROVIDE ALL CONDUITS, FITTINGS, NYLON BUSHINGS, PULL WIRE, BACK BOXES, ETC. PROVIDE BLANK COVER PLATES ON UN -USED BOXES. OWNER WILL PROVIDE ALL CABLING, EQUIPMENT AND JACKS. COVERING M/E/P DESIGN �G��O RTER OO! No. f innnroia 07/18/19 `e d � e� ULL s V a° L Q w 'co wa o - n `mm my Ory ma TDGArchitects.com Automotive O V CV v a J Z D 0 E W OU LU''00 4-7 Q W aT CO IY O U a U � CL W = O Z Q W_ Q W Do W (D j J W Y CO '� aJZQoczi 0 W Oil LO O o — W LNI — a 2 OvU aE�lm ReWelon Sch Date ill 03/28/19 Final Review EAM Eegikeers, Inc Eledncal and Mechanical Consulting Engineers 400 S.ON Woodward Site 100, Birmingham Ml 48009 Phone 24 528 7 Fax 24 28.1542 www.eam engine entneers.cown Job No.: 423-18041 V J � Z is O <6 U s /C�A./) L L L.L rap U U IOR g= ~ LLI ^f p` W FLU V J 12 Project Number 18-840w01 Drawing Number E 501