HomeMy WebLinkAboutA-010-BASEMENT-FLOOR-CODE-REVIEW-PLAN-Rev.0CODE - LIFE SAFETY NOTES LIFE SAFETY CODE REVIEW: NFPA 101. 12TH EDITION.2012 THIS SHEET SHALL BE PRINTED IN COLOR \AA 7 CHAPTER 18- NEW HEALTHCARE OCCUPANCIES'. CHAPTER 19- EXISTING HEALTHCARE OCCUPANCIES. 'EXTENT OF NEW CONSTRUCTION NOTED ON PLAN. ARRANGEMENT OF MEANS OF EGRESS: 18.2.5.2 / 19.2.5.2 DEAD-END CORRIDORS SHALL NOT EXCEED 39 FT. (NOTE IBC RESTRICTS TO 29) 182.5.3119.2.5.3 COMMON PATH OF TRAVEL. COMMON PATH OF TRAVEL SHALL NOT EXCEED 10OFT. (19.2.5.3 RESERVED). 182.5.4 / 19.25.4 INTERVENING ROOMS OR SPACES. EVERY CORRIDOR SHALL PROVIDE ACCESS TO NOT LESS THAN TWO APPROVED EXITS IN ACCORDANCE WITH SECTION 7.4 AND 7.5 WITHOUT PASSING THROUGH ANY INTERVENING ROOMS OR SPACES OTHER THAN CORRIDORS OR LOBBIES. 182ZZA / 19.2.5.5.1 SLEEPING ROOMS OF MORE THAN 100D BE SHALL HAVE NOT LESS THAN TWO EXIT ACCESS DOORS REMOTELY LOCATED FROM EACH OTHER. 182.5.5.2 / 19.2.5.5.2 NON -SLEEPING ROOMS OF MORE THAN 2,500 SF SHALL HAVE NOT LESS THAN TWO EXIT ACCESS DOORS REMOTELY LOCATED FROM EACH OTHER. 182.5.6.1 / 19.2.5.6.1 EVERY HABITABLE ROOM SHALL HAVE AN EXIT ACCESS DOOR LEADING DIRECTLY TO AN EXIT ACCESS CORRIDOR UNLESS OTHERWISE PROVIDED IN 18/192.5.6.2, 18119.2.5.6.3, AND 18119. 2.5.6A. 182.5.6.4 / 19.2.5.6.4 ROOMS WITHIN SUITES COMPLYING WITH 18119.2.5.7 SHALL NOT BE REQUIRED TO HAVE AN EXIT ACCESS DOOR LEADING DIRECTLY TO AN EXIT ACCESS CORRIDOR. SUITES: 18.2.5.7.1.1 / 19.2.5.7.1.1 SUITE PERMISSION. SUITES COMPLYING WITH18/19.2.5.7 SHALL BE PERMITTED TO BE USED TO MEET THE CORRIDOR ACCESS REQUIREMENTS OF 18/19.2.5.6. 182.5.7.12' SUITE SEPARATION. SUITES SHALL BE SEPARATED FROM THE REMAINDER OF THE BUILDING, AND FROM OTHER SUITES BY WALLS AND DOORS MEETING THE REQUIREMENTS OF 18.3.6.2 THROUGH 18.3.6.5. 'A18.2.5.7.1.2 TWO OR MORE CONTIGUOUS SUITES WITH AN AGGREGATE AREA NOT EXCEEDING THE SUITE SIZE LIMITATIONS OF 18.2.5.7.2.3 AND 18.2.5.7.3.3 ARE PERMITTED TO BE CONSIDERED A SINGLE SUITE, SO AS NOT TO REQUIRE SEPARATION FROM EACH OTHER. 19.2.5.7.1.2' SUITE SEPARATION. SORES SHALL BE SEPARATED FROM THE REMAINDER OF THE BUILDING, AND FROM OTHER SORES, BY ONE OF THE FOLLOWING (1) WALLS AND DOORS MEETING THE REQUIREMENTS OF 19.2.3.6.2 THROUGH 19.2.3.6.5 (2) EXISTING APPROVED BARRIERS AND DOORS THAT LIMIT THE TRANSFER OF SMOKE. 'A19.5.5.7.1.2 TWO OR MORE CONTIGUOUS SORES WITH AN AGGREGATE AREA NOT EXCEEDING THE SUITE SIZE LIMITATION OF 19.2.5.7.2.3 AND 19.2.5.7.3.3 ARE PERMITTED TO BE CONSIDERED A SINGLE SUITE, SO AS NOT TO REQUIRE SEPARATION FROM EACH OTHER. THE INTENT OF 19.2.5.7.1.2(2) IS TO CONTINUE TO PERMIT SUITES 19.3.8.2.4 EVEN THOUGH SPRINKLER PROTECTION IS NOT PROVIDED. 18119.2.5.7.1.3 SURE HAZARDOUS CONTENTS AREAS. (A) INTERVENING ROOMS SHALL NOT BE HAZARDOUSAS DEFINED BY 18.32. (B) HAZARDOUS AREAS WITHIN A SUITE $HALL BE SEPARATED FROM THE REMAINDER OF THE SUITE IN ACCORDANCE WITH 18119.3.2.1, UNLESS OTHERWISE PROVIDED IN 18/19.2&T1.3(C), OR M2. &T1.3(D). (C) HAZARDOUS AREAS WITHIN A SURE SHALL NOT BE REQUIRED TO BE SEPARATED FROM THE REMAINDER OF THE SUITE WHERE COMPLYING WITH ALL OF THE FOLLOWING: 18119(C)(1) THE SUITE IS PRIMARILY A HAZARDOUS AREA. 181 THE SUITE IS PROTECTED BY AN APPROVED AUTOMATIC SMOKE DECTECTION SYSTEM IN ACCORDANCE WITH SECTION 9.6 18(C)(3) / 19(C)(2) THE SUITE IS SEPARATED FROM THE REST OF THE HEALTHCARE FACILITY AS REQUIRED FORA HAZARDOUS ARE BY 18/19.3.2.1. 19(D) SPACES CONTAINING STERILE SURGICAL MATERIALS LIMBED TO A ONE -DAY SUPPLY IN OPERATING SUITES OR SIMILAR SPACES THAT ARE SPRINKLERED IN ACCORDANCE WITH 19.3.5.7 SHALL BE PERMITTED TO BE OPEN TO THE REMAINDER OF THE SUITE WITHOUT SEPARATION. 182.51.3 PATIENT CARE NON -SLEEPING SUITES. NON -SLEEPING SUITES SHALL BE IN ACCORDANCE WITH THE FOLLOWING: (1) NON -SLEEPING SORES FOR PATIENT CARE SHALL COMPLY WITH THE PROVISIONOF 18119.25.7.3.1 THROUGH 18/19.2.5.7.3.4. 2 NON -SLEEPING SUITRES NOT FOR PATIENT CARE SHALL COMPLY WRH THE PROVISIONS OF 18'18 19.2.5.7.4. 18119.2.5.7.3.1: PATIENT CARE NON -SLEEPING SURE ARRANGEMENT (A) OCCUPANTS OF HABITABLE ROOMS WITHIN NON -SLEEPING SUITES SHALL HAVE EXIT ACCESS TO A CORRIDOR COMPLYING WITH 18/19.3.6 OR TO A HORIZONTAL EXIT, DIRECTLY FROM THE SUITE. (B) WHERE TWO OR MORE EXIT ACCESS DOORS ARE REQUIRED FROM THE SUITE BY 18119.2.5.5.2, ONE OF THE EXIT ACCESS DOORS SHALL BE PERMITTED TO BE DIRECTLY TO AN EXIT STAIR, EXIT PASSAGE, OR EXIT DOOR TO THE EXTERIOR. 181192.5.7.3.2 PATIENT CARE NON -SLEEPING SURE NUMBER OF MEANS OF EGRESS. (A) SLEEPING SUITES OF MORE THAN 2500 SF SHALL HAVE NOT LESS THAN TWO EXIT ACCESS DOORS REMOTELY LOCATED FROM EACH OTHER. (B) ONE MEANS OF EGRESS FRO THE SUITE SHALL BE DIRECTLY TO A CORRIDOR COMPLYING WITH 18119.3.6. (C)' FOR SUITES REQUIRING TWO MEANS OF EGRESS, ONE MEANS OF EGRESS FROM THE SURE SHALL BE PERMITTED TO BE INTO ANOTHER SUITE, PROVIDED THAT THE SEPARATION BETWEEN SUITES COMPLIES WITH THE CORRIDOR REQUIREMENTS OF 18119.3.6.2 THROUGH 18119.3.6.5 A18119.2.5.7.3.2.(C) WHERE THE SECOND EXIT ACCESS FOR A SLEEPING SUITE IS THROUGH AN ADJACENT SUITE, IT IS THE INTENT THAT THE ADJACENT SUITE NOT BE CONSIDERED AN INTERVENING ROOM. 18119.2.5.7.3.3 PATIENT CARE NON -SLEEPING SUITE MAXIMUM SIZE. NON -SLEEPING SERIES SHALL NOT EXCEED 10000 SF. 181192.5.7.3A PATIENT CARE NON -SLEEPING SUITE TRAVEL DISTANCE (A) THE TRAVEL DISTANCE WITHIN A NON -SLEEPING SURE TO AN EXIT ACCESS DOOR FROM THAT SUITE SHALL NOT EXCEED 100 Fr. 18(B) TRAVEL DISTANCE BETWEEN ANY POINT IN A NON -SLEEPING SUITE AND AN EXIT SHALL NOT EXCEED 2(AFT. 19(B) TRAVEL DISTANCE BETWEEN ANY POINT IN A NON -SLEEPING SUITE AND AN EXIT SHALL NOT EXCEED THE FOLLOWING: 19(1) 150 FT IF THE BUILDING IS NOT PROTECTED THROUGHOUT BY AN APPROVED ELECTRICALLY SUPERVISED SPRINKLER SYSTEM COMPLYING WITH 19.&&T 19(2) WO FT IF THE BUILDING IS PROTECTED THROUGHOUT BVAN APPROVED ELECTRICALLY SUPERVISED SPRINKLER SYSTEM COMPLYING WITH 19.1&T 181192.5.7A NON -PATIENT -CARE SUITE. THE EGRESS PROVISIONS FOR NON -PATIENT -CARE SUITES SHALL BE IN ACCORDANCE THE PRIMARY USE AND OCCUPANCY OF THE SPACE. TRAVEL DISTANCES: 182.6.2.1: THE TRAVEL DISTANCE BETWEEN ANY POINT IN A ROOM AND AN EXIT SHALL NOT EXCEED 20D FT. 192.6.2A: THE TRAVEL DISTANCE BETWEEN ANY POINT IN A ROOM AND AN EXIT SHALL NOT EXCEED 150 FT, UNLESS OTHERWISE PERMITTED BY 19.2.6.2.4. 192.6.2.2: THE MAXIMUM TRAVEL DISTANCE SPECIFIED IN 19.2.6.2.1 SHALL BE PERMITTED TO BE INCREASED BY 50 FT (15M) IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH 19.3.5.7. 18119.2.6.2.3: THE TRAVEL DISTANCE BETWEEN ANY POINT IN A HEALTHCARE SLEEPING ROOM AND AN EXIT ACCESS DOOR IN THAT ROOM SHALL NOT EXCEED 50 FT. 18119.2.6.2A: THE TRAVEL DISTANCE WTHIN SUITES SHALL BE IN ACCORDANCE WITH 18/19.2.5.7. PROTECTION FROM HAZARDS: 18.3.21': HAZARDOUSAREAS. ANY HAZARDOUS AREA SHALL BE PROTECTED IN ACCORDANCE WITH SECTION 8.7, AND THE AREAS DESCRIBED IN TABLE 18.3.2.1 SHALL BE PROTECTED AS INDICATED. A18.3.2.1 PROVISIONS FOR THE ENCLOSURE OF ROOMS USED FOR CHARGING LINEN CHUTES OR FOR ROOMS INTO THESE CHUTES EMPTY ARE PROVIDED IN SECTION 9.5. 19.3.21: HAZARDOUS AREAS. ANY HAZARDOUS AREAS SHALL BE SAFEGUARDED BY A FIRE BARRIER HAVING A 1-HOUR FIRE RESISTANCE RATING OR SHALL BE PROVIDED WITH AN AUTOMATIC EXTINGUISHING SYSTEM IN ACCORDANCE WITH 8.7A1 19.3.21A AN AUTOMATIC EXTINGUISHING SYSTEM, WHERE USED IN HAZARDOUS AREAS, SHALL BE PERMITTED TO BE IN ACCORDANCE WITH 19.3.5.9. 19.3.21.2 WHERE THE SPRINKLER OPTION OF 19.32AIS USED, THE AREAS SHALL BE SEPARATED FROM OTHER SPACES BY SMOKE PARTITIONS IN ACCORDANCE WITH SECTION 8A. 19.3.2.1.5 HAZARDOUS AREAS SHALL INCLUDE, BUT SHALL NOT BE RESTRICTED TO, THE FOLLOWING: (1) BOILER AND FUEL -FIRED ROOMS. (2) CENTRAL / BULK LAUNDRIES LARGER THAN 100SF. (3) PAINT SHOPS. (4) REPAIR SHOPS. (5) ROOMS WITH SOILED LINEN IN VOLUME EXCEEDING 64 GALLONS. (6) ROOMS WITH COLLECTED TRASH IN VOLUME EXCEEDING 64 GALLLONS. (7) ROOMS OR SPACES LARGER THAN 50SF, INCLUDING REPAIR SHOPS, USED FOR STORAGE OF COMBUSTIBLE SUPPLIES AND EQUIPMENT IN QUANTITIES DEEMED HAZARDOUS BY THE AUTHORITY HAVING JURISDICTION (8) LABORATORIES EMPLOYING FLAMMABLE OR COMBUSTIBLE MATERIALS IN QUANTITIES LESS THAN THOSE THAT WOULD BE CONSIDERED A SEVERE HAZARD. SUBDIVISION OF BUILDING SPACES: 18.3.7.1: BUILDINGS CONTAINING HEALTHCARE FACILITIES SHALL BE SUBDIVIDED BY SMOKE BARRIERS(SEE 18.2A.3), UNLESS OTHERWISE PERMITTED BY 18.3.7.2, AS FOLLOWS: (1) TO DIVIDE EVERY STORY USED BY INPATIENTS FOR SLEEPING OR TREATMENT INTO NOT LESS THAN TWO SMOKE COMPARTMENTS. (2) TO DIVIDE EVERY STORY HAVING AN OCCUPANT LOAD OF 50 OR MORE PERSONS, REGARDLESS OF USE, INTO NOT LESS THAN TWO SMOKE COMPARTMENTS. (3) TO LIMIT THE THE SIZE OF EACH SMOKE COMPARTMENT REQUIRED BY 1&1T 1(1) AND (2) TO AN AREA NOT EXCEEDING 22,500 SF UNLESS THE AREA IS AN ATRIUM SEPARATED IN ACCORDANCE WITH 8.6.7, IN WHICH CASE NO LIMITATION IN SIZE IS REQUIRED. (4) TO LIMIT THE TRAVEL DISTANCE FROM ANY POINT TO REACH A DOOR IN THE REQUIRED SMOKE BARRIER TO A DISTANCE NOT EXCEEDING 200 FT. 19.3.7.1: SMOKE BARRIERS SHALL BE PROVIDED TO DIVIDE EVERY STORY USED FOR SLEEPING ROOMS FOR MORE THAN 30 PATIENTS INTO NOT LESS THAN TWO SMOKE COMPARTMENTS (SEE 19.2A.4), AND THE FOLLOWING SHALL APPLY: (1) THE SIZE OF ANY SUCH SMOKE COMPARTMENT SHALL NOT EXCEED 22,500 BE, AND THE TRAVEL DISTANCE FROM ANY POINT TO REACH A DOOR IN THE REQUIRED SMOKE BARRIER SHALL NOT EXCEED 200 Fr. (6e0cN Mn. GTH NOR WIDTH OF THE SMOKE COMPARTMENT EXCEEDS150 ET, THE RELEASED FOR CONSTRUCTION ED IN ACCORDANCE TO 8.6.7 SHALLOT BE LIMITED SMOKE BARRIER DOOR SHALL NOT BE IN SIZE Subject to compliance with all regulations at State and Local Codes City of Carried (� �V10IGIC u•A1al�LL THE FLOOR SLAB OF THE HOSPITAL IS TWO HOUR FIRE BARRIER. ALL PENETRATIONS THROUGH THE SLAB MUST BE FIRE STOPPED TO MEET THE TWO HOUR FIRE BARRIER REQUIREMENT. VERIFY WITH FACIILTY MANAGMENT ON TYPE OF FIRE STOPPING MANUFACTURER PRODUCTS THAT ARE USED WITHIN THE FACILITY. SMOKE COMPARTMENT- MAX ALLOWABLE SIZE 22,500 SF. 18.3.7A CONSTRUCTION OF CORRIDOR WALLS 18.3.6.2.1 - 18.3.6.2.3 (A.18.3.6.2)... AN ARCHITECTURAL, EXPOSED, SUSPENDED -GRID ACOUSTICAL TILE CEILING WITH PENTRATING ITEMS, SUCH AS SPRINKLER PIPING AND SPRINKLERS; DUCTED HVAC SUPPLY AND RETURN -AIR DIFFUSERS; SPEAKERS; AND RECESSED LIGHTING FIXTURES, IS CAPABLE OF LIMITING THE TRANSFER OF SMOKE. CORRIDOR WALLS SHALL BE PERMITTED TO TERMINATE AT THE CEILING WHERE THE CEILING IS CONSTRUCTED TO LIMIT THE TRANSFER OF SMOKE. NO FIRE RESISTANCE RATING IS REQUIRED FOR CORRIDOR WALLS. CORRIDOR WALLS SHALL FORM A BARRIER TO LIMIT THE TRANSFER OF SMOKE. A.18.3.6.2.3 WHILE A CORRIDOR WALL IS REQUIRED TO FORM A BARRIER TO LIMIT THE TRANSFER OF SMOKE, SUCH A BARRIER IS NOT REQUIRED TO BE EITHER A SMOKE BARRIER OR A SMOKE PARTITION - TWO TERMS FOR WHICH SPECIFIC CODE DEFINITIONS AND REQUIREMENTS APPLY. CONSTRUCTION OF CORRIDOR WALLS. 19.3.6.2.1 - 19.3.6.2A CORRIDOR WALLS SHALL BE CONTINUOUS FROM THE FLOOR TO THE UNDERSIDE OF THE FLOOR OR ROOF DECK ABOVE; THROUGH ANY CONCEALED SPACES, SUCH AS THOSE ABOVE SUSPENDED CEILINGS; AND THROUGH INTERSTITIAL STRUCTURAL AND MECHANICAL SPACES, UNLESS OTHERWISE PERMITTED BY 19.3.6.2.4 THROUGH 19.3.6.2.8. CORRIDOR WALL SHALL HAVE A MINIMUM 112-HOUR FIRE RESISTANCE RATING. (A.19.3.6.2.2 THE INTENT OF THE MINIMUM 1/2-HOUR FIRE RESISTANCE RATING FOR CORRIDOR PARTITIONS IS TO REQUIRE A NOMINAL FIRE RATING, PARTICULARLY WHERE THE FIRE RATING OF EXISTING PARTITIONS CANNOT BE DOCUMENTED...) CORRIDOR WALLS SHALL FORM A BARRIER TO LIMIT THE TRANSFER OF SMOKE. A19.3.6.2.3 THE PURPOSE OF EXTENDING A CORRIDOR WALL ABOVE THE LAY -IN CEILING OR THROUGH A CONCEALED SPACE IS TO PROVIDE A BARRIER TO LIMIT THE PASSAGE OF SMOKE. SUCH A BARRIER IS NOT REQUIRED TO BE EITHER A SMOKE BARRIER OR A SMOKE PARTITION - TWO TERMS FOR WHICH SPECIFIC CODE DEFINITIONS AND REQUIREMENTS APPLY... IN SMOKE COMPARTMENTS PROTECTED THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH 19.3.5.7, A CORRIDOR SHALL BE PERMITTED TO BE SEPARATED FROM ALL OTHER AREAS BY NON -FIRE -RATED PARTITIONS AND SHALL BE PERMITTED TO TERMINATE AT THE CEILING WHERE THE CEILING IS CONSTRUCTED TO LIMIT THE TRANSFER OF SMOKE. 8.3.4.1 EVERY OPENING IN A FIRE BARRIER SHALL BE PROTECTED TO LIMIT THE SPREAD OF FIRE AND RESTRICT THE MOVEMENT OF SMOKE FROM ONE SIDE OF THE FIRE BARRIER TO THE OTHER. THE FIRE PROTECTION RATING FOR OPENING PROTECTIVES IN ACCORDANCE WITH TABLE 8.3A.2, EXCEPT AS OTHERWISE PERMITTED IN 8.3A.3 OR 8.3AA A.8A.1 ALTHOUGH A SMOKE PARTITION IS INTENDED TO LIMIT THE FREE MOVEMENT OF SMOKE, Fr IS NOT INTENDED TO PROVIDE AN AREA THAT WOULD BE FREE OF SMOKE. 8.4.2 CONTINUITY. SMOKE PARTITIONS SHALL COMPLY WITH THE FOLLOWING: 1. THEY SHALL EXTEND FROM THE FLOOR TO THE UNDERSIDE OF THE FLOOR OR ROOF ABOVE,.. 2. THEY SHALL BE PERMITTED TO EXTEND FROM THE FLOOR TO THE UNDERSIDE OF A MONOLITHIC OR SUSPENDED CEILING SYSTEM WHERE ALL THE FOLLOWING CONDITIONS ARE MET: A. THE CEILING FORMS CONTINUOUS MEMBRANE. B. ASMOKE-TIGHT JOINT IS PROVIDED BETWEEN THE TOP OF THE SMOKE PARTITION AND THE BOTTOM OF THE SUSPENDED CEILING. C. THE SPACE ABOVE THE CEILING IS NOT USED AS A PLENUM. 3. SMOKE PARTITIONS ENCLOSING HAZARDOUS AREAS SHALL BE PERMITTED TO TERMINATE AT THE UNDERSIDE OF A MONOLITHIC OR SUSPENDED CEILING SYSTEM WHERE ALL OF THE FOLLOWING CONDITIONS ARE MET: A. THE CEILING FORMS CONTINUOUS MEMBRANE, B. A SMOKE -TIGHT JOINT IS PROVIDED BETWEEN THE TOP OF THE SMOKE PARTITION AND THE BOTTOM OF THE SUSPENDED CEILING. C. WHERE THE SPACE ABOVE THE CEILING IS USED AS A PLENUM, RETURN GRILLES FROM THE HAZARDOUS AREA INTO THE PLENUMS ARE NOT PERMITTED. 8.4.3.5 DOORS SHALL BE SELF -CLOSING OR AUTOMATIC -CLOSING IN ACCORDANCE WITH 7.2A S. 8.5.2 CONTINU ITV. 8.5.2.1 SMOKE BARRIERS REQUIRED BY THIS CODE SHALL BE CONTINUOUS FROM AN OUTSIDE WALL TO AN OUTSIDE WALL FROM A FLOOR TO A FLOOR, OR FROM ASMOKE BARRIER TO A SMOKE BARRIER OR A COMBINATION THEREOF. 8.5.2.2 SMOKE BARRIERS SHALL BE CONTINUOUS THROUGH ALL CONCEALED SPACES, SUCH AS THOSE FOUND ABOVE CEILING, INCLUDING INTERSTITIAL SPACES. THE MINIMUM FIRE RESISTANCE RATING FOR THE ENCLOSURE OF FLOOR OPENINGS SHALL BE AS FOLLOWS (SEE 7A 3.2.1 FOR ENCLOSURE OF EXIT$): (1) ENCLOSURES CONNECTING FOUR OR MORE STORIES IN NEW CONSTRUCTION - 2-HOUR FIRE BARRIERS (2) OTHER ENCLOSURES IN NEW CONSTRUCTION - 1-HOUR FIRE BARRIERS (3) EXISTING ENCLOSLURES IN EXISTING BUILDINGS - 112-HOUR FIRE BARRIERS 8.7 SPECIAL HAZARD PROTECTION 8.7.1 GENERAL. 8.7.1.1' PROTECTION FROM ANY AREA HAVING A DEGREE OF HAZARD GREATER THAN THAT NORMAL TO THE GENERAL OCCUPANCY OF THE BUILDING OR STRUCTURE SHALL BE PROVIDED BY ONE OF THE FOLLOWING MEANS: (1) ENCLOSING THE AREA WITH A FIRE BARRIER WITHOUT WINDOWS THAT HAS A 1-HOUR FIRE RESISTANCE RATING IN ACCORDANCE WITH SECTION 8.3. (2) PROTECTING THE AREA WITH AUTOMATIC EXTINGUISHING SYTEMS IN ACCORDANCE WITH SECTION 9.7. (3) APPLYING BOTH 8.7A A(1) AND (2) WHERE THE HAZARD IS SEVERE OR WHERE OTHERWISE SPECIFIED BYCHAPTERS 11 THROUGH43. A.8.7.1.1 AREAS REQUIRING SPECIAL HAZARD PROTECTION INCLUDE, BUT ARE NOT LIMITED TO, AREAS SUCH AS THOSE USED FOR STORAGE OF COMBUSTIBLES OR FLAMMABLES, AREAS HOUSING HEAT PRODUCING APPLIANCES, OR AREAS USED FOR MAINTENANCE PURPOSES. 8.7.1.2 IN NEW CONSTRUCTION, WHERE PROTECTION IS PROVIDED WITH AUTOMATIC EXTINGUISHING SYSTEMS WITHOUT FIRE -RESISTIVE SEPARATION, THE SPACE PROTECTED SHALL BE ENCLOSED WITH SMOKE PARTITIONS IN ACCORDANCE WITH SECTION 8A, UNLESS OTHERWISE PERMITTED BY ONE OF THE FOLLOWING CONDITIONS: (1) WHERE MERCANTILE OCCUPANCY GENERAL STORAGE AREAS AND STOCKROOMS ARE PROTECTED BY AUTOMATIC SPRINKLERS IN ACCORDANCE WITH SECTION 9.7 (2) WHERE HAZARDOUS AREAS IN INDUSTRIAL OCCPANCIES ARE PROTECTED BYAUTOMATIO EXTINGUISHING SYSTEMS IN ACCORDANCE WITH 40.3.2. (3) WHERE HAZARDOUS AREAS IN DETENTION AND CORRECTIONAL OCCUPANCIES ARE PROTECTED BY AUTOMATIC SPRINKLERS IN ACCORDANCE WITH 22.3.2. BUILDING CODE CODE REVIEW NOTES BUILDING CODES. 2014INDIANA BUILDING CODE (20121BC WITH INDIANA AMEMDMENTS). 2012 NFPA 101 LIFE SAFETY CODE, 12TH ED. 20D1 EDITION GUIDELINES FOR DESIGN AND CONSTRUCTION OF HOSPITALS AND HEALTHCARE FACILITIES. TABLE 601 THE CONSTRUCTION TYPE IS II PER TABLE 503 THE GROUP 1-2 OCCUPANCY CAN BE UNLIMITED IN HEIGHT AND AREA. FM GLOBAL NOTES FM GLOBAL 1. FMDS0100-SAFEGUARDS DURING CONSTRUCTION, ALTERATION, AND DEMOLITION 2. FMDS02DO - INSTALLATION GUIDELINES FOR AUTOMATIC SPRINKLERS 3. FMDS0326 - FIRE PROTECTION WATER DEMAND FOR NON -STORAGE SPRINKLERED PROPERTIES RATED WALL LEGEND 1 - HOUR FIRE WALL — 2 - HOUR FIRE WALL —3-HOURE FIRE WALL — 4-HOUR FIRE WALL 1 - HOUR SMOKE BARRIER ---"--- SMOKE PARTTION EGRESS PATH - TOTAL LENGTH EXIT ROUTE DISTANCE TRAVEL DISTANCE 10T- 11" BASEMENT REFERENCE FLOOR PLAN 1112" = r-n" NORTH BASEMENT LIFE SAFETY PLAN NORTH MKM architecture + design 119 West Wayne Street Fqt Wayne, Indiana 46802 p 260.422.0783 f MOA284%1 www.MKMdesian.com iM AftIf280EB1 BTATEOF "Fin: THE PROPERTY OF MKM ARCHITECTURE ♦ DESIGN, ANDWERE CREATEDAND DEVELOPED FOR USE ON, AMID IN CONNECTION WTH THIS SPECIFIC PROJECT NONE OF THE IDEAS, DESIGNS. ARRµGEMEH130R RARE SHALL BE USED BY OR DISCLOSED TO AIR PERSON, FIRM OR CORPORATION FOR ANY PURPOSE WHATSOEVER LWTHOUT THE WHITEN PERMISSION OF MNM ARCHITECTURE • C N. THE OMER SHOT BE PERM17ED TO RETAIN COPIES FOR INFORMATION AND REFERnICE IN CONNECTION NTH THIS PROJECT NEUTRON DIMENSIONS ON THESE DRAMNGS SMILE HAVE PRECEDENCE OVER SCALE DIMENSIONS. AHD THIS OFFICE MUST BE NOTIFIED OF ANY VARIATIONFRONTHEDIMENABONSANDCONDITTONS SHOWN BY THESE DRAwNGS. SHOP DRAINAGE MUST BE yJOMITTEL TO THIS OFFICE FOR REAM BEFORE PROFFEDING WITH FABRICATION ARMS INSTALLATION. THE WORK SHOKM ON THIS DOCUMENT, AND THE CORRESPONDING SFECIFILATOHs, INTERFACES NRH NORK BROAD ON OTHER DOCUMENTS INCLUDING VARK To BE PERFORMED BY OTHER CONTRACTORS OR SUBCONTRACTORS. EACH CONTRACTOR OR SUBCONTRACTOR SHALL BE FAMILIAR M11 THE WORK OF OTHER CONTRACTORS OR SUBCONTRACTORS, WHETHER OR NOT SHOWN ON THIS DOCUMENT WHICH IMPACTS THE NOR IMPACTS THE WORK SHOWN HEBFJN AND SHALL COORDINATE SUCH WORK SO AS TO EF IN COMPUAHCEWTHTHEINTNTOMLTHEPROFCT DOCUMENTS. St. Vincent Carmel Hospital Carmel Pharmacy 797 800 13500 N Meridian Street REVISION DRAWING CONTENTS: BASEMENT FLOOR CODE REVIEW PLAN ISSUE DATE'. PROJECT NO. 04/26/2019 MKM'. 17107 ASCENSION W286 DRAWING NO. A-010 DATE: 09/04/19