HomeMy WebLinkAboutA-010-BASEMENT-FLOOR-CODE-REVIEW-PLAN-Rev.0CODE - LIFE SAFETY NOTES
LIFE SAFETY CODE REVIEW: NFPA 101. 12TH EDITION.2012
THIS SHEET SHALL BE PRINTED IN COLOR
\AA
7
CHAPTER 18- NEW HEALTHCARE OCCUPANCIES'.
CHAPTER 19- EXISTING HEALTHCARE OCCUPANCIES.
'EXTENT OF NEW CONSTRUCTION NOTED ON PLAN.
ARRANGEMENT OF MEANS OF EGRESS:
18.2.5.2 / 19.2.5.2 DEAD-END CORRIDORS SHALL NOT EXCEED 39 FT. (NOTE IBC RESTRICTS TO 29)
182.5.3119.2.5.3 COMMON PATH OF TRAVEL. COMMON PATH OF TRAVEL SHALL NOT EXCEED 10OFT. (19.2.5.3
RESERVED).
182.5.4 / 19.25.4 INTERVENING ROOMS OR SPACES. EVERY CORRIDOR SHALL PROVIDE ACCESS TO NOT LESS
THAN TWO APPROVED EXITS IN ACCORDANCE WITH SECTION 7.4 AND 7.5 WITHOUT PASSING THROUGH ANY
INTERVENING ROOMS OR SPACES OTHER THAN CORRIDORS OR LOBBIES.
182ZZA / 19.2.5.5.1 SLEEPING ROOMS OF MORE THAN 100D BE SHALL HAVE NOT LESS THAN TWO EXIT ACCESS
DOORS REMOTELY LOCATED FROM EACH OTHER.
182.5.5.2 / 19.2.5.5.2 NON -SLEEPING ROOMS OF MORE THAN 2,500 SF SHALL HAVE NOT LESS THAN TWO EXIT
ACCESS DOORS REMOTELY LOCATED FROM EACH OTHER.
182.5.6.1 / 19.2.5.6.1 EVERY HABITABLE ROOM SHALL HAVE AN EXIT ACCESS DOOR LEADING DIRECTLY TO AN
EXIT ACCESS CORRIDOR UNLESS OTHERWISE PROVIDED IN 18/192.5.6.2, 18119.2.5.6.3, AND 18119. 2.5.6A.
182.5.6.4 / 19.2.5.6.4 ROOMS WITHIN SUITES COMPLYING WITH 18119.2.5.7 SHALL NOT BE REQUIRED TO HAVE AN
EXIT ACCESS DOOR LEADING DIRECTLY TO AN EXIT ACCESS CORRIDOR.
SUITES:
18.2.5.7.1.1 / 19.2.5.7.1.1 SUITE PERMISSION. SUITES COMPLYING WITH18/19.2.5.7 SHALL BE PERMITTED TO BE
USED TO MEET THE CORRIDOR ACCESS REQUIREMENTS OF 18/19.2.5.6.
182.5.7.12' SUITE SEPARATION. SUITES SHALL BE SEPARATED FROM THE REMAINDER OF THE BUILDING, AND
FROM OTHER SUITES BY WALLS AND DOORS MEETING THE REQUIREMENTS OF 18.3.6.2 THROUGH 18.3.6.5.
'A18.2.5.7.1.2 TWO OR MORE CONTIGUOUS SUITES WITH AN AGGREGATE AREA NOT EXCEEDING THE SUITE SIZE
LIMITATIONS OF 18.2.5.7.2.3 AND 18.2.5.7.3.3 ARE PERMITTED TO BE CONSIDERED A SINGLE SUITE, SO AS NOT TO
REQUIRE SEPARATION FROM EACH OTHER.
19.2.5.7.1.2' SUITE SEPARATION. SORES SHALL BE SEPARATED FROM THE REMAINDER OF THE BUILDING, AND
FROM OTHER SORES, BY ONE OF THE FOLLOWING
(1) WALLS AND DOORS MEETING THE REQUIREMENTS OF 19.2.3.6.2 THROUGH 19.2.3.6.5
(2) EXISTING APPROVED BARRIERS AND DOORS THAT LIMIT THE TRANSFER OF SMOKE.
'A19.5.5.7.1.2 TWO OR MORE CONTIGUOUS SORES WITH AN AGGREGATE AREA NOT EXCEEDING THE SUITE SIZE
LIMITATION OF 19.2.5.7.2.3 AND 19.2.5.7.3.3 ARE PERMITTED TO BE CONSIDERED A SINGLE SUITE, SO AS NOT TO
REQUIRE SEPARATION FROM EACH OTHER. THE INTENT OF 19.2.5.7.1.2(2) IS TO CONTINUE TO PERMIT SUITES
19.3.8.2.4 EVEN THOUGH SPRINKLER PROTECTION IS NOT PROVIDED.
18119.2.5.7.1.3 SURE HAZARDOUS CONTENTS AREAS.
(A) INTERVENING ROOMS SHALL NOT BE HAZARDOUSAS DEFINED BY 18.32.
(B) HAZARDOUS AREAS WITHIN A SUITE $HALL BE SEPARATED FROM THE REMAINDER OF THE SUITE IN
ACCORDANCE WITH 18119.3.2.1, UNLESS OTHERWISE PROVIDED IN 18/19.2&T1.3(C), OR M2. &T1.3(D).
(C) HAZARDOUS AREAS WITHIN A SURE SHALL NOT BE REQUIRED TO BE SEPARATED FROM THE
REMAINDER OF THE SUITE WHERE COMPLYING WITH ALL OF THE FOLLOWING:
18119(C)(1) THE SUITE IS PRIMARILY A HAZARDOUS AREA.
181 THE SUITE IS PROTECTED BY AN APPROVED AUTOMATIC SMOKE DECTECTION SYSTEM IN
ACCORDANCE WITH SECTION 9.6
18(C)(3) / 19(C)(2) THE SUITE IS SEPARATED FROM THE REST OF THE HEALTHCARE FACILITY AS
REQUIRED FORA HAZARDOUS ARE BY 18/19.3.2.1.
19(D) SPACES CONTAINING STERILE SURGICAL MATERIALS LIMBED TO A ONE -DAY SUPPLY IN OPERATING
SUITES OR SIMILAR SPACES THAT ARE SPRINKLERED IN ACCORDANCE WITH 19.3.5.7 SHALL BE
PERMITTED TO BE OPEN TO THE REMAINDER OF THE SUITE WITHOUT SEPARATION.
182.51.3 PATIENT CARE NON -SLEEPING SUITES. NON -SLEEPING SUITES SHALL BE IN ACCORDANCE WITH
THE FOLLOWING:
(1) NON -SLEEPING SORES FOR PATIENT CARE SHALL COMPLY WITH THE PROVISIONOF 18119.25.7.3.1
THROUGH 18/19.2.5.7.3.4.
2 NON -SLEEPING SUITRES NOT FOR PATIENT CARE SHALL COMPLY WRH THE PROVISIONS OF
18'18
19.2.5.7.4.
18119.2.5.7.3.1: PATIENT CARE NON -SLEEPING SURE ARRANGEMENT
(A) OCCUPANTS OF HABITABLE ROOMS WITHIN NON -SLEEPING SUITES SHALL HAVE EXIT ACCESS TO A
CORRIDOR COMPLYING WITH 18/19.3.6 OR TO A HORIZONTAL EXIT, DIRECTLY FROM THE SUITE.
(B) WHERE TWO OR MORE EXIT ACCESS DOORS ARE REQUIRED FROM THE SUITE BY 18119.2.5.5.2, ONE OF
THE EXIT ACCESS DOORS SHALL BE PERMITTED TO BE DIRECTLY TO AN EXIT STAIR, EXIT PASSAGE, OR
EXIT DOOR TO THE EXTERIOR.
181192.5.7.3.2 PATIENT CARE NON -SLEEPING SURE NUMBER OF MEANS OF EGRESS.
(A) SLEEPING SUITES OF MORE THAN 2500 SF SHALL HAVE NOT LESS THAN TWO EXIT ACCESS DOORS
REMOTELY LOCATED FROM EACH OTHER.
(B) ONE MEANS OF EGRESS FRO THE SUITE SHALL BE DIRECTLY TO A CORRIDOR COMPLYING WITH
18119.3.6.
(C)' FOR SUITES REQUIRING TWO MEANS OF EGRESS, ONE MEANS OF EGRESS FROM THE SURE SHALL
BE PERMITTED TO BE INTO ANOTHER SUITE, PROVIDED THAT THE SEPARATION BETWEEN SUITES
COMPLIES WITH THE CORRIDOR REQUIREMENTS OF 18119.3.6.2 THROUGH 18119.3.6.5
A18119.2.5.7.3.2.(C) WHERE THE SECOND EXIT ACCESS FOR A SLEEPING SUITE IS THROUGH AN ADJACENT
SUITE, IT IS THE INTENT THAT THE ADJACENT SUITE NOT BE CONSIDERED AN INTERVENING ROOM.
18119.2.5.7.3.3 PATIENT CARE NON -SLEEPING SUITE MAXIMUM SIZE. NON -SLEEPING SERIES SHALL NOT EXCEED
10000 SF.
181192.5.7.3A PATIENT CARE NON -SLEEPING SUITE TRAVEL DISTANCE
(A) THE TRAVEL DISTANCE WITHIN A NON -SLEEPING SURE TO AN EXIT ACCESS DOOR FROM THAT SUITE
SHALL NOT EXCEED 100 Fr.
18(B) TRAVEL DISTANCE BETWEEN ANY POINT IN A NON -SLEEPING SUITE AND AN EXIT SHALL NOT
EXCEED 2(AFT.
19(B) TRAVEL DISTANCE BETWEEN ANY POINT IN A NON -SLEEPING SUITE AND AN EXIT SHALL NOT
EXCEED THE FOLLOWING:
19(1) 150 FT IF THE BUILDING IS NOT PROTECTED THROUGHOUT BY AN APPROVED ELECTRICALLY
SUPERVISED SPRINKLER SYSTEM COMPLYING WITH 19.&&T
19(2) WO FT IF THE BUILDING IS PROTECTED THROUGHOUT BVAN APPROVED ELECTRICALLY
SUPERVISED SPRINKLER SYSTEM COMPLYING WITH 19.1&T
181192.5.7A NON -PATIENT -CARE SUITE.
THE EGRESS PROVISIONS FOR NON -PATIENT -CARE SUITES SHALL BE IN ACCORDANCE THE PRIMARY USE AND
OCCUPANCY OF THE SPACE.
TRAVEL DISTANCES:
182.6.2.1: THE TRAVEL DISTANCE BETWEEN ANY POINT IN A ROOM AND AN EXIT SHALL NOT EXCEED 20D FT.
192.6.2A: THE TRAVEL DISTANCE BETWEEN ANY POINT IN A ROOM AND AN EXIT SHALL NOT EXCEED 150 FT,
UNLESS OTHERWISE PERMITTED BY 19.2.6.2.4.
192.6.2.2: THE MAXIMUM TRAVEL DISTANCE SPECIFIED IN 19.2.6.2.1 SHALL BE PERMITTED TO BE INCREASED BY
50 FT (15M) IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER
SYSTEM IN ACCORDANCE WITH 19.3.5.7.
18119.2.6.2.3: THE TRAVEL DISTANCE BETWEEN ANY POINT IN A HEALTHCARE SLEEPING ROOM AND AN EXIT
ACCESS DOOR IN THAT ROOM SHALL NOT EXCEED 50 FT.
18119.2.6.2A: THE TRAVEL DISTANCE WTHIN SUITES SHALL BE IN ACCORDANCE WITH 18/19.2.5.7.
PROTECTION FROM HAZARDS:
18.3.21': HAZARDOUSAREAS. ANY HAZARDOUS AREA SHALL BE PROTECTED IN ACCORDANCE WITH SECTION
8.7, AND THE AREAS DESCRIBED IN TABLE 18.3.2.1 SHALL BE PROTECTED AS INDICATED.
A18.3.2.1 PROVISIONS FOR THE ENCLOSURE OF ROOMS USED FOR CHARGING LINEN CHUTES OR FOR ROOMS
INTO THESE CHUTES EMPTY ARE PROVIDED IN SECTION 9.5.
19.3.21: HAZARDOUS AREAS. ANY HAZARDOUS AREAS SHALL BE SAFEGUARDED BY A FIRE BARRIER
HAVING A 1-HOUR FIRE RESISTANCE RATING OR SHALL BE PROVIDED WITH AN AUTOMATIC EXTINGUISHING
SYSTEM IN ACCORDANCE WITH 8.7A1
19.3.21A AN AUTOMATIC EXTINGUISHING SYSTEM, WHERE USED IN HAZARDOUS AREAS, SHALL BE PERMITTED
TO BE IN ACCORDANCE WITH 19.3.5.9.
19.3.21.2 WHERE THE SPRINKLER OPTION OF 19.32AIS USED, THE AREAS SHALL BE SEPARATED FROM OTHER
SPACES BY SMOKE PARTITIONS IN ACCORDANCE WITH SECTION 8A.
19.3.2.1.5 HAZARDOUS AREAS SHALL INCLUDE, BUT SHALL NOT BE RESTRICTED TO, THE FOLLOWING:
(1) BOILER AND FUEL -FIRED ROOMS.
(2) CENTRAL / BULK LAUNDRIES LARGER THAN 100SF.
(3) PAINT SHOPS.
(4) REPAIR SHOPS.
(5) ROOMS WITH SOILED LINEN IN VOLUME EXCEEDING 64 GALLONS.
(6) ROOMS WITH COLLECTED TRASH IN VOLUME EXCEEDING 64 GALLLONS.
(7) ROOMS OR SPACES LARGER THAN 50SF, INCLUDING REPAIR SHOPS, USED FOR STORAGE OF
COMBUSTIBLE SUPPLIES AND EQUIPMENT IN QUANTITIES DEEMED HAZARDOUS BY THE AUTHORITY
HAVING JURISDICTION
(8) LABORATORIES EMPLOYING FLAMMABLE OR COMBUSTIBLE MATERIALS IN QUANTITIES LESS THAN
THOSE THAT WOULD BE CONSIDERED A SEVERE HAZARD.
SUBDIVISION OF BUILDING SPACES:
18.3.7.1: BUILDINGS CONTAINING HEALTHCARE FACILITIES SHALL BE SUBDIVIDED BY SMOKE BARRIERS(SEE
18.2A.3), UNLESS OTHERWISE PERMITTED BY 18.3.7.2, AS FOLLOWS:
(1) TO DIVIDE EVERY STORY USED BY INPATIENTS FOR SLEEPING OR TREATMENT INTO NOT LESS THAN
TWO SMOKE COMPARTMENTS.
(2) TO DIVIDE EVERY STORY HAVING AN OCCUPANT LOAD OF 50 OR MORE PERSONS, REGARDLESS OF
USE, INTO NOT LESS THAN TWO SMOKE COMPARTMENTS.
(3) TO LIMIT THE THE SIZE OF EACH SMOKE COMPARTMENT REQUIRED BY 1&1T 1(1) AND (2) TO AN AREA
NOT EXCEEDING 22,500 SF UNLESS THE AREA IS AN ATRIUM SEPARATED IN ACCORDANCE WITH 8.6.7, IN
WHICH CASE NO LIMITATION IN SIZE IS REQUIRED.
(4) TO LIMIT THE TRAVEL DISTANCE FROM ANY POINT TO REACH A DOOR IN THE REQUIRED SMOKE
BARRIER TO A DISTANCE NOT EXCEEDING 200 FT.
19.3.7.1: SMOKE BARRIERS SHALL BE PROVIDED TO DIVIDE EVERY STORY USED FOR SLEEPING ROOMS FOR
MORE THAN 30 PATIENTS INTO NOT LESS THAN TWO SMOKE COMPARTMENTS (SEE 19.2A.4), AND THE
FOLLOWING SHALL APPLY:
(1) THE SIZE OF ANY SUCH SMOKE COMPARTMENT SHALL NOT EXCEED 22,500 BE, AND THE TRAVEL
DISTANCE FROM ANY POINT TO REACH A DOOR IN THE REQUIRED SMOKE BARRIER SHALL NOT EXCEED
200 Fr. (6e0cN
Mn.
GTH NOR WIDTH OF THE SMOKE COMPARTMENT EXCEEDS150 ET, THE
RELEASED FOR CONSTRUCTION ED IN ACCORDANCE TO 8.6.7 SHALLOT BE LIMITED SMOKE BARRIER DOOR SHALL NOT BE IN SIZE
Subject to compliance with all regulations
at State and Local Codes
City of Carried (�
�V10IGIC u•A1al�LL
THE FLOOR SLAB OF THE HOSPITAL IS TWO HOUR FIRE BARRIER. ALL PENETRATIONS THROUGH THE
SLAB MUST BE FIRE STOPPED TO MEET THE TWO HOUR FIRE BARRIER REQUIREMENT. VERIFY WITH FACIILTY
MANAGMENT ON TYPE OF FIRE STOPPING MANUFACTURER PRODUCTS THAT ARE USED WITHIN THE FACILITY.
SMOKE COMPARTMENT- MAX ALLOWABLE SIZE 22,500 SF. 18.3.7A
CONSTRUCTION OF CORRIDOR WALLS 18.3.6.2.1 - 18.3.6.2.3
(A.18.3.6.2)... AN ARCHITECTURAL, EXPOSED, SUSPENDED -GRID ACOUSTICAL TILE CEILING WITH PENTRATING
ITEMS, SUCH AS SPRINKLER PIPING AND SPRINKLERS; DUCTED HVAC SUPPLY AND RETURN -AIR DIFFUSERS;
SPEAKERS; AND RECESSED LIGHTING FIXTURES, IS CAPABLE OF LIMITING THE TRANSFER OF SMOKE. CORRIDOR
WALLS SHALL BE PERMITTED TO TERMINATE AT THE CEILING WHERE THE CEILING IS CONSTRUCTED TO LIMIT
THE TRANSFER OF SMOKE. NO FIRE RESISTANCE RATING IS REQUIRED FOR CORRIDOR WALLS. CORRIDOR
WALLS SHALL FORM A BARRIER TO LIMIT THE TRANSFER OF SMOKE.
A.18.3.6.2.3 WHILE A CORRIDOR WALL IS REQUIRED TO FORM A BARRIER TO LIMIT THE TRANSFER OF SMOKE,
SUCH A BARRIER IS NOT REQUIRED TO BE EITHER A SMOKE BARRIER OR A SMOKE PARTITION - TWO TERMS FOR
WHICH SPECIFIC CODE DEFINITIONS AND REQUIREMENTS APPLY.
CONSTRUCTION OF CORRIDOR WALLS. 19.3.6.2.1 - 19.3.6.2A
CORRIDOR WALLS SHALL BE CONTINUOUS FROM THE FLOOR TO THE UNDERSIDE OF THE FLOOR OR ROOF DECK
ABOVE; THROUGH ANY CONCEALED SPACES, SUCH AS THOSE ABOVE SUSPENDED CEILINGS; AND THROUGH
INTERSTITIAL STRUCTURAL AND MECHANICAL SPACES, UNLESS OTHERWISE PERMITTED BY 19.3.6.2.4 THROUGH
19.3.6.2.8. CORRIDOR WALL SHALL HAVE A MINIMUM 112-HOUR FIRE RESISTANCE RATING. (A.19.3.6.2.2 THE
INTENT OF THE MINIMUM 1/2-HOUR FIRE RESISTANCE RATING FOR CORRIDOR PARTITIONS IS TO REQUIRE A
NOMINAL FIRE RATING, PARTICULARLY WHERE THE FIRE RATING OF EXISTING PARTITIONS CANNOT BE
DOCUMENTED...) CORRIDOR WALLS SHALL FORM A BARRIER TO LIMIT THE TRANSFER OF SMOKE. A19.3.6.2.3 THE
PURPOSE OF EXTENDING A CORRIDOR WALL ABOVE THE LAY -IN CEILING OR THROUGH A CONCEALED SPACE IS
TO PROVIDE A BARRIER TO LIMIT THE PASSAGE OF SMOKE. SUCH A BARRIER IS NOT REQUIRED TO BE EITHER A
SMOKE BARRIER OR A SMOKE PARTITION - TWO TERMS FOR WHICH SPECIFIC CODE DEFINITIONS AND
REQUIREMENTS APPLY...
IN SMOKE COMPARTMENTS PROTECTED THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER
SYSTEM IN ACCORDANCE WITH 19.3.5.7, A CORRIDOR SHALL BE PERMITTED TO BE SEPARATED FROM ALL OTHER
AREAS BY NON -FIRE -RATED PARTITIONS AND SHALL BE PERMITTED TO TERMINATE AT THE CEILING WHERE THE
CEILING IS CONSTRUCTED TO LIMIT THE TRANSFER OF SMOKE.
8.3.4.1 EVERY OPENING IN A FIRE BARRIER SHALL BE PROTECTED TO LIMIT THE SPREAD OF FIRE AND RESTRICT
THE MOVEMENT OF SMOKE FROM ONE SIDE OF THE FIRE BARRIER TO THE OTHER. THE FIRE PROTECTION
RATING FOR OPENING PROTECTIVES IN ACCORDANCE WITH TABLE 8.3A.2, EXCEPT AS OTHERWISE PERMITTED
IN 8.3A.3 OR 8.3AA
A.8A.1 ALTHOUGH A SMOKE PARTITION IS INTENDED TO LIMIT THE FREE MOVEMENT OF SMOKE, Fr IS NOT
INTENDED TO PROVIDE AN AREA THAT WOULD BE FREE OF SMOKE.
8.4.2 CONTINUITY. SMOKE PARTITIONS SHALL COMPLY WITH THE FOLLOWING:
1. THEY SHALL EXTEND FROM THE FLOOR TO THE UNDERSIDE OF THE FLOOR OR ROOF ABOVE,..
2. THEY SHALL BE PERMITTED TO EXTEND FROM THE FLOOR TO THE UNDERSIDE OF A MONOLITHIC OR
SUSPENDED CEILING SYSTEM WHERE ALL THE FOLLOWING CONDITIONS ARE MET:
A. THE CEILING FORMS CONTINUOUS MEMBRANE.
B. ASMOKE-TIGHT JOINT IS PROVIDED BETWEEN THE TOP OF THE SMOKE PARTITION AND THE BOTTOM
OF THE SUSPENDED CEILING.
C. THE SPACE ABOVE THE CEILING IS NOT USED AS A PLENUM.
3. SMOKE PARTITIONS ENCLOSING HAZARDOUS AREAS SHALL BE PERMITTED TO TERMINATE AT THE
UNDERSIDE OF A MONOLITHIC OR SUSPENDED CEILING SYSTEM WHERE ALL OF THE FOLLOWING
CONDITIONS ARE MET:
A. THE CEILING FORMS CONTINUOUS MEMBRANE,
B. A SMOKE -TIGHT JOINT IS PROVIDED BETWEEN THE TOP OF THE SMOKE PARTITION AND THE BOTTOM
OF THE SUSPENDED CEILING.
C. WHERE THE SPACE ABOVE THE CEILING IS USED AS A PLENUM, RETURN GRILLES FROM THE
HAZARDOUS AREA INTO THE PLENUMS ARE NOT PERMITTED.
8.4.3.5 DOORS SHALL BE SELF -CLOSING OR AUTOMATIC -CLOSING IN ACCORDANCE WITH 7.2A S.
8.5.2 CONTINU ITV. 8.5.2.1 SMOKE BARRIERS REQUIRED BY THIS CODE SHALL BE CONTINUOUS FROM AN
OUTSIDE WALL TO AN OUTSIDE WALL FROM A FLOOR TO A FLOOR, OR FROM ASMOKE BARRIER TO A SMOKE
BARRIER OR A COMBINATION THEREOF.
8.5.2.2 SMOKE BARRIERS SHALL BE CONTINUOUS THROUGH ALL CONCEALED SPACES, SUCH AS THOSE FOUND
ABOVE CEILING, INCLUDING INTERSTITIAL SPACES.
THE MINIMUM FIRE RESISTANCE RATING FOR THE ENCLOSURE OF FLOOR OPENINGS SHALL BE AS FOLLOWS
(SEE 7A 3.2.1 FOR ENCLOSURE OF EXIT$):
(1) ENCLOSURES CONNECTING FOUR OR MORE STORIES IN NEW CONSTRUCTION - 2-HOUR FIRE
BARRIERS
(2) OTHER ENCLOSURES IN NEW CONSTRUCTION - 1-HOUR FIRE BARRIERS
(3) EXISTING ENCLOSLURES IN EXISTING BUILDINGS - 112-HOUR FIRE BARRIERS
8.7 SPECIAL HAZARD PROTECTION
8.7.1 GENERAL. 8.7.1.1' PROTECTION FROM ANY AREA HAVING A DEGREE OF HAZARD GREATER THAN THAT
NORMAL TO THE GENERAL OCCUPANCY OF THE BUILDING OR STRUCTURE SHALL BE PROVIDED BY ONE OF THE
FOLLOWING MEANS:
(1) ENCLOSING THE AREA WITH A FIRE BARRIER WITHOUT WINDOWS THAT HAS A 1-HOUR FIRE
RESISTANCE RATING IN ACCORDANCE WITH SECTION 8.3.
(2) PROTECTING THE AREA WITH AUTOMATIC EXTINGUISHING SYTEMS IN ACCORDANCE WITH SECTION
9.7.
(3) APPLYING BOTH 8.7A A(1) AND (2) WHERE THE HAZARD IS SEVERE OR WHERE OTHERWISE SPECIFIED
BYCHAPTERS 11 THROUGH43.
A.8.7.1.1 AREAS REQUIRING SPECIAL HAZARD PROTECTION INCLUDE, BUT ARE NOT LIMITED TO, AREAS SUCH AS
THOSE USED FOR STORAGE OF COMBUSTIBLES OR FLAMMABLES, AREAS HOUSING HEAT PRODUCING
APPLIANCES, OR AREAS USED FOR MAINTENANCE PURPOSES.
8.7.1.2 IN NEW CONSTRUCTION, WHERE PROTECTION IS PROVIDED WITH AUTOMATIC EXTINGUISHING SYSTEMS
WITHOUT FIRE -RESISTIVE SEPARATION, THE SPACE PROTECTED SHALL BE ENCLOSED WITH SMOKE PARTITIONS
IN ACCORDANCE WITH SECTION 8A, UNLESS OTHERWISE PERMITTED BY ONE OF THE FOLLOWING CONDITIONS:
(1) WHERE MERCANTILE OCCUPANCY GENERAL STORAGE AREAS AND STOCKROOMS ARE PROTECTED
BY AUTOMATIC SPRINKLERS IN ACCORDANCE WITH SECTION 9.7
(2) WHERE HAZARDOUS AREAS IN INDUSTRIAL OCCPANCIES ARE PROTECTED BYAUTOMATIO
EXTINGUISHING SYSTEMS IN ACCORDANCE WITH 40.3.2.
(3) WHERE HAZARDOUS AREAS IN DETENTION AND CORRECTIONAL OCCUPANCIES ARE PROTECTED BY
AUTOMATIC SPRINKLERS IN ACCORDANCE WITH 22.3.2.
BUILDING CODE
CODE REVIEW NOTES
BUILDING CODES. 2014INDIANA BUILDING CODE (20121BC WITH INDIANA AMEMDMENTS).
2012 NFPA 101 LIFE SAFETY CODE, 12TH ED.
20D1 EDITION GUIDELINES FOR DESIGN AND CONSTRUCTION OF HOSPITALS AND
HEALTHCARE FACILITIES.
TABLE 601 THE CONSTRUCTION TYPE IS II
PER TABLE 503 THE GROUP 1-2 OCCUPANCY CAN BE UNLIMITED IN HEIGHT AND AREA.
FM GLOBAL NOTES
FM GLOBAL
1. FMDS0100-SAFEGUARDS DURING CONSTRUCTION, ALTERATION, AND DEMOLITION
2. FMDS02DO - INSTALLATION GUIDELINES FOR AUTOMATIC SPRINKLERS
3. FMDS0326 - FIRE PROTECTION WATER DEMAND FOR NON -STORAGE SPRINKLERED
PROPERTIES
RATED WALL LEGEND
1 - HOUR FIRE WALL
— 2 - HOUR FIRE WALL
—3-HOURE FIRE WALL
— 4-HOUR FIRE WALL
1 - HOUR SMOKE BARRIER
---"--- SMOKE PARTTION
EGRESS PATH - TOTAL LENGTH
EXIT ROUTE DISTANCE
TRAVEL DISTANCE 10T- 11"
BASEMENT REFERENCE FLOOR PLAN
1112" = r-n"
NORTH
BASEMENT LIFE SAFETY PLAN
NORTH
MKM
architecture + design
119 West Wayne Street
Fqt Wayne, Indiana 46802
p 260.422.0783
f MOA284%1
www.MKMdesian.com
iM AftIf280EB1
BTATEOF
"Fin:
THE PROPERTY OF MKM ARCHITECTURE ♦ DESIGN,
ANDWERE CREATEDAND DEVELOPED FOR USE ON,
AMID IN CONNECTION WTH THIS SPECIFIC PROJECT
NONE OF THE IDEAS, DESIGNS. ARRµGEMEH130R
RARE SHALL BE USED BY OR DISCLOSED TO AIR
PERSON, FIRM OR CORPORATION FOR ANY
PURPOSE WHATSOEVER LWTHOUT THE WHITEN
PERMISSION OF MNM ARCHITECTURE • C N.
THE OMER SHOT BE PERM17ED TO RETAIN
COPIES FOR INFORMATION AND REFERnICE IN
CONNECTION NTH THIS PROJECT NEUTRON
DIMENSIONS ON THESE DRAMNGS SMILE HAVE
PRECEDENCE OVER SCALE DIMENSIONS.
AHD THIS OFFICE MUST BE NOTIFIED OF ANY
VARIATIONFRONTHEDIMENABONSANDCONDITTONS
SHOWN BY THESE DRAwNGS. SHOP DRAINAGE
MUST BE yJOMITTEL TO THIS OFFICE FOR REAM
BEFORE PROFFEDING WITH FABRICATION ARMS
INSTALLATION. THE WORK SHOKM ON THIS
DOCUMENT, AND THE CORRESPONDING
SFECIFILATOHs, INTERFACES NRH NORK BROAD
ON OTHER DOCUMENTS INCLUDING VARK To BE
PERFORMED BY OTHER CONTRACTORS OR
SUBCONTRACTORS. EACH CONTRACTOR OR
SUBCONTRACTOR SHALL BE FAMILIAR M11 THE
WORK OF OTHER CONTRACTORS OR
SUBCONTRACTORS, WHETHER OR NOT SHOWN ON
THIS DOCUMENT WHICH IMPACTS THE NOR
IMPACTS THE WORK SHOWN HEBFJN AND SHALL
COORDINATE SUCH WORK SO AS TO EF IN
COMPUAHCEWTHTHEINTNTOMLTHEPROFCT
DOCUMENTS.
St. Vincent
Carmel Hospital
Carmel Pharmacy 797 800
13500 N Meridian Street
REVISION
DRAWING CONTENTS:
BASEMENT FLOOR
CODE REVIEW PLAN
ISSUE DATE'. PROJECT NO.
04/26/2019 MKM'. 17107
ASCENSION W286
DRAWING NO.
A-010
DATE: 09/04/19