HomeMy WebLinkAboutA-015-LIFE-SAFETY-RATED-FRAMING-TYP-DTLS-Rev.011T MAX STUD WALL
STUD INSULATION
CONTROL JOINT
5/8" TYPE "X" GYP. BOARD
(2) LAVERS OF 5/8" TYPE "X" GYP. BOARD.
DRYWALL CONTROL JOINTS IN 1-HR RATED GYPSUM PARTITIONS
BASIS OF DESIGN'. WHI-647-3024
112"
CONTROL JOINT
(2) LAYERS OF 5/8" TYPE "X" GYP. BOARD
(2) LAVERS OF 5/8" TYPE "X" GYP. BOARD.
DRYWALL CONTROL JOINTS IN 2-HR RATED GYPSUM PARTITIONS
BASIS OF DESIGN'. WHI-651-0318.1
NOTES:
IN ALL RATED PARTITIONS AND/OR SMOKE PARTITIONS, THE SURFACE AREA OF INDIVIDUAL
METALLIC OUTLET OR SWITCH BOXES SHALL NOT EXCEED 16 SQUARE INCHES. THE AGGREGATE
SURFACE AREA OF THE BOXES SHALL NOT EXCEED 100 SQUARE INCHES PER 100 SQUARE FEET.
BOXES WHICH EXCEED THESE STANDARDS SHALL BE RECESSED AS SHOWN IN RECESSED METAL
WALL.
BOXES LOCATED ON OPPOSITE SIDES OF RATED AND/OR SMOKE PARTITIONS SHALL BE
SEPERATED BY A HORIZONTAL DISTANCE OF 24 INCHES MINIMUM, IRREGARDLESS OF THE
VERTICAL SEPERATION OF THE BOXES.
SEAL BOXES TIGHT TO
GYPSUM BOARD W/
DRYWALL JOINT
COMPOUND (1/8- MAX.
JOINT BETWEEN BOX AND
ALL LAVERS OF DRYWALL).
TWO 12) LAVERS TYPE 'X"GYP. BOARD MAXIMUM 16 SO. INCH OPENING IN
FOR 2-HOUR RATED FIRE OR 2-HOUR FIRE/SMOKE RATED WALL.
FIRE AND SMOKE WALL (ONLY ONE (1)
LAVER EACH SIDE AT 1-HOUR RATED
FIRE OR 1-HOUR SMOKE WALL). SEE
WALL SYMBOLS LEGEND ON INDEX SHEET.
RATED WALL ELECTRICAL BACK BOXES
CONTRACTOR TO IDENTIFY RATED WALLS ABOVE THE CEILING
BY PAINTING IN X TALL LETTERS THE REQUIRED FIRE OR SMOKE
RATING OF THE WALL. SPACE TEXT AT iT-0"O.C. DOWN LENGTH
OF RATED WALL.
`__F ---- l
1- HOUR RATED WALL 11- HOUR RATED WALL �I
L LJ
LIGHT
OTYPICAL FRAMING DTL. O TYP. WALL ASSEMBLY STENCILING
11 10 3/8' = 1'-0"
METAL STUD FRAMING 16" O.C.
BATT INSULATION
AS SPECIFIED.
5/8" TYPE "X" GYP.
BOARD AS REQUIRED.
MUD AND TAPE
JOINTS AS REQUIRED.
BASIS OF DESIGN:1-HR WALL. UL 465 OR UL V438
RATED WALL OUTSIDE CORNER
® TYPICAL FRAMING DTL. �) TYPICAL FRAMING DTL,
ROOF OR FLOOR
ASSEMBLY
EXTEND ALL LAYERS OF
GYP. BOARD TIGHT TO
WITHIN III DECK
FLUTES AND SEAL TIGHT
TO DECK
5/8" TYPE "X" GYP. BOARD EACH
SIDE -MUD AND TAPE DRYWALL
JOINTS ABOVE CEILING FULL
HEIGHT BOTH SIDES OF WALL
(TYP.)
EXTEND ALL LAYERS OF
GYP. BOARD TIGHT TO
WITHIN 1/4" OF DECK
FLUTES AND SEAL TIGHT
TO DECK
- METAL STUDS AT 16" O.C.
MAX INFILL SOLID W/ BATT
INSULATION
NON -RATED WALL PARALLEL TO DECKING
n TYPICAL FRAMING DTL,
RELEASED FOR CONSTRUCTION
Subject to compliance with all regulations
of State and Local Codes
City of Cannel
�PRNGIDJol
ROOF OR FLOOR —{=
ASSEMBLY tTs r-:--
EXTEND ALL LAYERS OF III I' EXTEND ALL LAYERS OF
GYP. BOARD TIGHT TO GYP. BOARD TIGHT TO
WITHIN 1/4" OF DECK WITHIN 114" OF DECK
FLUTES AND SEAL TIGHT FLUTES AND SEAL TIGHT
TO DECK WITH APPROVED TO DECK WITH APPROVED
FIRESTOP MATERIAL FIRESTOP MATERIAL
ONE OR TWO LAVERS OF
5/8' TYPE IV GYP. BOARD
EACH SIDE -MUD AND TAPE METAL STUDS AT 16"
DRYWALL JOINTS ABOVE O.C. MAX INFILL SOLID
CEILING FULL HEIGHT BOTH W/ BATT INSULATION
SIDES OF WALL (TYP.)
RATED AND/OR SMOKE WALL PARALLEL TO DECKING
NOTE: CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF
ALL NEW DUCTWORK LOCATIONS TO AVOID CONFLICTS WITH RATED
ASSEMBLIES WHERE POSSIBLE. CONSULT WITH ARCHITECT PRIOR TO
INSTALLATION OF NEW DUCTWORK IN CONFLICT WITH WALL FRAMING.
FLOOR OR ROOF _ _ _ _ FLOOR OR ROOF �_ ° _ _
ASSEMBLY T ASSEMBLY TI
CUT GYP. BOARD TO FIT CUT GYP. BOARD TO FIT SUPPORT BATT
WITHIN 1l4" OF DECK FLU TE$ WITHIN 1/4" OF DECK FLUTES INSULATION AT TOP OF
AND SEAL TIGHT TO DECK AS WALLAS REQUIRED.
SEAL WITH APPROVED
FIRESTOP MATERIAL
— HANGER RODS AS
REQUIRED
INSULATED DUCT SEE
MECHANICAL
2 1/2" C-H STUD SHAFT WALL
SYSTEM BY USG. SHAFT WALL
RATING TO MATCH WALL RATING
I
STOP STUD WALL AS TIGHT
REQUIRED BELOW. SEE CODE
TO DUCT AS POSSIBLE
PLAN FOR WALL RATINGS
—
—
NOTE OFF -SET WALL WILL OCCUR WHEN
MECHANICAL DUCT AND WALLS RUN PARALLEL.
TYPE GYP. BOARD EACH SIDE -
MUD AND TAPE DRYWALL JOINTS
NOTE: LINERS PANELS AND GYPSUM WALLBOARD
ABOVE CEILING FULL HEIGHT BOTH
PANELS IN SHAFTWALL SYSTEM SHALL BE SUPPLIED
SIDES OF WALL (TYP.) ADD LAYERS OF
PER SHAFT WALL MNF. RECOMMENDATIONS.
GYP. AS REQUIRED FOR WALL RATING.
CONSULT WITH MNF. FOR MORE INFO.
SEE CODE PLAN.
NOTE:SHAFT WALL FRAMING SHALL BE SUPPLIED AND
INSTALLED AS RECOMMENDED BY MNF. PER. REQUIRED
SPANS. CONSULT WITH MNF. FOR MORE INFORMATION.
RATED OFFSET WALL
AT EXISTING DUCT INTERRUPTION
TYPICAL FRAMING DTL.
1" = 1'-0"
METAL STUD FRAMING 16" O.C.
BATT INSULATION
AS SPECIFIED.
OF 5/8" TYPE "X"
ff7LAYER(S)
OARD AS REQUIRED.
PER WALL RATING.
MUD AND TAPE
JOINTS AS REQUIRED.
WALL INTERSECTION AT RATED WALL
®= FIRE PRIORITY
PARTITION PRIORITY LEGEND
2-HR FIRE AND SMOKE WALL
- HIGHEST
2-HR FIRE WALL
- PRIORITY2
2-HR SHAFT WALL
- PRIORITY 3
1-HR FIRE AND SMOKE WALL
- PRIORITY4
1-HR FIRE WALL
- PRIORITY5
SMOKE TIGHT WALL
- PRIORITY
NON RATED WALL
- PRIORITY 7
BASIS OF DESIGN:1-HR WALL - UL 465 OR UL V438
2-HR WALL - UL 411 OR UL V438
TYPICAL FRAMING DTL.
11 =11-0n
HANGER RODS AS
REQUIRED
INSULATED DUCT SEE
METAL STUDS AT
MECHANICAL
Ll
16" O.C. MAX
3-5/8" MIN. METAL STUD AT
-
EACH VERTICAL STUD
i
Ig WALL AS
STOP STUD
' TIGHT TO DUCT AS
POSSIBLE
SIT TYPE "X" GYP. BOARD
EACH SIDE -MUD AND TAPE
DRYWALL JOINTS ABOVE
NOTE:
CEILING FULL HEIGHT BOTH
OFF -SET WALL WILL OCCUR WHEN
SIDES OF WALL (TYP.)
MECHANICAL DUCT AND WALLS
RUN PARALLEL.
NON -RATED OFFSET WALL AT EXISTING DUCT INTERRUPTION
5/8" TVPE"X" GYPSUM BOARD PER
WALL RATING. SEE CODE REVIEW
PLAN FOR MORE INFORMATION.
METAL STUD RUNNER ATTACHED
TO FLOOR WITH ANCHORS
@ 2'-0" O.C. MAX.
1/4' MAX. GAP TOLERANCE (TYP.)
FLOOR ASSEMBLY SEE BUILDING
SECTION FOR MORE INFORMATIO
RATED WALL SEAL AT FLOOR
TYPICAL FRAMING DTL.
3" = 1'-0"
METAL STUD FRAMING 16" O.C. W/
BATT INSULATION (TYP.)
TALL GYP. BOARD OVER FIRESTOP
'ER FIRESTOP MNF. SPECIFICATION
15TENERS BEHIND FIRESTOP SEAL.
�P/ BOTTOM TRACK FIRESTOP SEAL
BYAPPROVED MANUFACTURE.
INSTALL HORIZONTAL STUD TOP
AND BOTTOM OF PATCH AREA
II
II
F� FASTEN THE DRYWALL INTO
METAL STUD FRAMING
i
FACE OF DRYWALL PATCH
DUST BE FLUSH WITH
FACE OF ADJACENT WALL
TAPE, MUD, AND SAND
JOINTS BETWEEN NEW
PATCH AND EXISTING WALL
FIRE STOP JOINT BETWEEN
'IDRYWALL AND PIPING
METAL STUDS @ 16" O.C.
II
OPENINGS OVER 3" CIA.
GENERAL NOTES
A
r/ 1>� IF GAP AROUND PENETRATION
IS G114"OR LESS, PACK AND SEAL
WITH APPROVED FIRESTOP SEALANT
I( )� IF GAP AROUND PENETRATION
IS GREATER THAN 114",PACK
TIGHTLY WITH THERMAFIBER
SAFING INSULATION OR APPROVED
FIREPROOFING MATERIAL, AND
APPLY PATCH AS SHOWN
RATED AND/OR SMOKE WALLS
PATCHING AND SEALING PENETRATIONS
OTYPICAL FRAMING DTL.
911= 1,-On
O
NOTE:
IF DUCT IS TO BE INSULATED, DO NOT RUN DUCT INSULATION THROUGH THE WALL
FLARE DUCT INSULATION ONTO FACE OF WALL AROUND DUCT ON BOTH SIDES OF
WALL, All SEAL DUCT INSULATION TO FACE OF WALL WITH INSULATION MASTIC.
WHEN DIMENSION EXCEEDS 16" MAX 16" MAX
T INSTALL CRIPPLE STUD
IN CORNER. (TYP.)
HORIZ. METAL STUD
ATTACH TO VERT. STUD Lti
VERT. METAL STUDS II
AT IT O.C. MAX.
SAFING INSULATION UPPL ETU N DUC
PACKED TIGHTLY ii RGERT TVPIC
WALLS D GATL
II I
II
ATTACHED vy
TO VERTAL U NER STUDS.
TO VERT. STUDS. —IF
Ti
II II I
PENETRATION
RECTANGULAR DUCT PENETRATION
RATED AND/OR SMOKE WALL DUCT PENETRATION
TYPICAL FRAMING DTL.
RATED INTERIOR
WALL. SEE LIFE
SAFETY PLAN
EXTERIOR WALL CLADDING
— 5/W TYPE "X" GYPSUM BOARD
STUD FRAMING @ IT O.C. MAX.
BATT INSULATION AS SPECIFIED
RATED INTERIOR WALL INTERSECTING NO- RATED EXTERIOR WALL
TYPICAL FRAMING DTL.
1" = 1'-0"
MKM
architecture + design
119 West Wayne Streat
FOIt Wayne, Indiana 46802
p 260.422.0783
f MOA264561
www.MKMicesian.cum
Na AftIf286aB1
67ATEOF
HIS, Plert
THE PROPERTY OF MKIM ARCHITECTURE �N
AMID WERE CREATED AND DEVELOPED FOR USE ON
AMID IN CONNECTION MH THIS SPECIFIC PROJECT
WINE OF THE IDENS DESIGNS ARRANGEMENTS OR
PLARIS SHUMAL BE USED BY OR DISCLOSED TO ANY
PERSON, FIRM OR CORPORATION FOR ANN
PURPOSE WHATSOEVER MHI THE WRITER
PERMISSION Of WIN ARCHITECTURE I DESHUN
THE OMER SHALL BE PERMITTED TO RETAIN
COPIES FOR INFORMAKTION AND lanamal IN
CONNECTION NTH THIS PROJECT ARMED
DIMENSIONS ON THESE DRAWINGS SHALL HAND
PRECEDENCE OVER SCALE DIMENSIONS
ADD THIS OFFICE MUST BE NOTIFIED OF ANY
VARIATIONFROMTHEDIMENABONSANDCONDITHOME
SHOM BY THESE DRAININGS SHOP DRAINAGE
MUST BE WMI� TO THIS OFFICE FOR REAM
BEFORE PROGREDING WITH FARRICATION ARMS
INSTALLATION THE WORK SHOM ON THIS
DOCUMENT, AND THE CORRESPONDING
sPOPUrcimi INTERFACES SMITH WORK SHOWN
ON OTHER DOCUMENTS KILUDING MRK To BE
PERFORMED BY OTHER CONTRACTORS OR
SUBCONTRACTORS EACH CONTRACTOR OF
SUBCONTRACTOR $HALL BE FAMILIAR WIN THE
WORK OF OTHER CONTRACTORS OR
SUBSCONTRACTORS WHETHER OR NOT SHUM ON
THIS DOCUMENT WHICH IMPACTS THE WORK
IMPACTS THE MAN SHOM HERFUN AND SHALL
DOMINATE SUCH BORK SO AS TO SEE IN
St. Vincent
Carmel Hospital
Carmel Pharmacy 797 800
13500 N Meridian Street
REVISION
DRAMING Cown_wTS:
LIFE SAFETY/RATED
FRAMING TYP DTLS
ISSOEWTE'. PROJECT NO.
04/26/2019 MKM'. 17107
ASCENSION'. W286
DRAwwG NO.
A-015
DATE: 09/04/19