HomeMy WebLinkAboutA-015-LIFE-SAFETY-RATED-FRAMING-TYP-DTLS-Rev.011T MAX STUD WALL STUD INSULATION CONTROL JOINT 5/8" TYPE "X" GYP. BOARD (2) LAVERS OF 5/8" TYPE "X" GYP. BOARD. DRYWALL CONTROL JOINTS IN 1-HR RATED GYPSUM PARTITIONS BASIS OF DESIGN'. WHI-647-3024 112" CONTROL JOINT (2) LAYERS OF 5/8" TYPE "X" GYP. BOARD (2) LAVERS OF 5/8" TYPE "X" GYP. BOARD. DRYWALL CONTROL JOINTS IN 2-HR RATED GYPSUM PARTITIONS BASIS OF DESIGN'. WHI-651-0318.1 NOTES: IN ALL RATED PARTITIONS AND/OR SMOKE PARTITIONS, THE SURFACE AREA OF INDIVIDUAL METALLIC OUTLET OR SWITCH BOXES SHALL NOT EXCEED 16 SQUARE INCHES. THE AGGREGATE SURFACE AREA OF THE BOXES SHALL NOT EXCEED 100 SQUARE INCHES PER 100 SQUARE FEET. BOXES WHICH EXCEED THESE STANDARDS SHALL BE RECESSED AS SHOWN IN RECESSED METAL WALL. BOXES LOCATED ON OPPOSITE SIDES OF RATED AND/OR SMOKE PARTITIONS SHALL BE SEPERATED BY A HORIZONTAL DISTANCE OF 24 INCHES MINIMUM, IRREGARDLESS OF THE VERTICAL SEPERATION OF THE BOXES. SEAL BOXES TIGHT TO GYPSUM BOARD W/ DRYWALL JOINT COMPOUND (1/8- MAX. JOINT BETWEEN BOX AND ALL LAVERS OF DRYWALL). TWO 12) LAVERS TYPE 'X"GYP. BOARD MAXIMUM 16 SO. INCH OPENING IN FOR 2-HOUR RATED FIRE OR 2-HOUR FIRE/SMOKE RATED WALL. FIRE AND SMOKE WALL (ONLY ONE (1) LAVER EACH SIDE AT 1-HOUR RATED FIRE OR 1-HOUR SMOKE WALL). SEE WALL SYMBOLS LEGEND ON INDEX SHEET. RATED WALL ELECTRICAL BACK BOXES CONTRACTOR TO IDENTIFY RATED WALLS ABOVE THE CEILING BY PAINTING IN X TALL LETTERS THE REQUIRED FIRE OR SMOKE RATING OF THE WALL. SPACE TEXT AT iT-0"O.C. DOWN LENGTH OF RATED WALL. `__F ---- l 1- HOUR RATED WALL 11- HOUR RATED WALL �I L LJ LIGHT OTYPICAL FRAMING DTL. O TYP. WALL ASSEMBLY STENCILING 11 10 3/8' = 1'-0" METAL STUD FRAMING 16" O.C. BATT INSULATION AS SPECIFIED. 5/8" TYPE "X" GYP. BOARD AS REQUIRED. MUD AND TAPE JOINTS AS REQUIRED. BASIS OF DESIGN:1-HR WALL. UL 465 OR UL V438 RATED WALL OUTSIDE CORNER ® TYPICAL FRAMING DTL. �) TYPICAL FRAMING DTL, ROOF OR FLOOR ASSEMBLY EXTEND ALL LAYERS OF GYP. BOARD TIGHT TO WITHIN III DECK FLUTES AND SEAL TIGHT TO DECK 5/8" TYPE "X" GYP. BOARD EACH SIDE -MUD AND TAPE DRYWALL JOINTS ABOVE CEILING FULL HEIGHT BOTH SIDES OF WALL (TYP.) EXTEND ALL LAYERS OF GYP. BOARD TIGHT TO WITHIN 1/4" OF DECK FLUTES AND SEAL TIGHT TO DECK - METAL STUDS AT 16" O.C. MAX INFILL SOLID W/ BATT INSULATION NON -RATED WALL PARALLEL TO DECKING n TYPICAL FRAMING DTL, RELEASED FOR CONSTRUCTION Subject to compliance with all regulations of State and Local Codes City of Cannel �PRNGIDJol ROOF OR FLOOR —{= ASSEMBLY tTs r-:-- EXTEND ALL LAYERS OF III I' EXTEND ALL LAYERS OF GYP. BOARD TIGHT TO GYP. BOARD TIGHT TO WITHIN 1/4" OF DECK WITHIN 114" OF DECK FLUTES AND SEAL TIGHT FLUTES AND SEAL TIGHT TO DECK WITH APPROVED TO DECK WITH APPROVED FIRESTOP MATERIAL FIRESTOP MATERIAL ONE OR TWO LAVERS OF 5/8' TYPE IV GYP. BOARD EACH SIDE -MUD AND TAPE METAL STUDS AT 16" DRYWALL JOINTS ABOVE O.C. MAX INFILL SOLID CEILING FULL HEIGHT BOTH W/ BATT INSULATION SIDES OF WALL (TYP.) RATED AND/OR SMOKE WALL PARALLEL TO DECKING NOTE: CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF ALL NEW DUCTWORK LOCATIONS TO AVOID CONFLICTS WITH RATED ASSEMBLIES WHERE POSSIBLE. CONSULT WITH ARCHITECT PRIOR TO INSTALLATION OF NEW DUCTWORK IN CONFLICT WITH WALL FRAMING. FLOOR OR ROOF _ _ _ _ FLOOR OR ROOF �_ ° _ _ ASSEMBLY T ASSEMBLY TI CUT GYP. BOARD TO FIT CUT GYP. BOARD TO FIT SUPPORT BATT WITHIN 1l4" OF DECK FLU TE$ WITHIN 1/4" OF DECK FLUTES INSULATION AT TOP OF AND SEAL TIGHT TO DECK AS WALLAS REQUIRED. SEAL WITH APPROVED FIRESTOP MATERIAL — HANGER RODS AS REQUIRED INSULATED DUCT SEE MECHANICAL 2 1/2" C-H STUD SHAFT WALL SYSTEM BY USG. SHAFT WALL RATING TO MATCH WALL RATING I STOP STUD WALL AS TIGHT REQUIRED BELOW. SEE CODE TO DUCT AS POSSIBLE PLAN FOR WALL RATINGS — — NOTE OFF -SET WALL WILL OCCUR WHEN MECHANICAL DUCT AND WALLS RUN PARALLEL. TYPE GYP. BOARD EACH SIDE - MUD AND TAPE DRYWALL JOINTS NOTE: LINERS PANELS AND GYPSUM WALLBOARD ABOVE CEILING FULL HEIGHT BOTH PANELS IN SHAFTWALL SYSTEM SHALL BE SUPPLIED SIDES OF WALL (TYP.) ADD LAYERS OF PER SHAFT WALL MNF. RECOMMENDATIONS. GYP. AS REQUIRED FOR WALL RATING. CONSULT WITH MNF. FOR MORE INFO. SEE CODE PLAN. NOTE:SHAFT WALL FRAMING SHALL BE SUPPLIED AND INSTALLED AS RECOMMENDED BY MNF. PER. REQUIRED SPANS. CONSULT WITH MNF. FOR MORE INFORMATION. RATED OFFSET WALL AT EXISTING DUCT INTERRUPTION TYPICAL FRAMING DTL. 1" = 1'-0" METAL STUD FRAMING 16" O.C. BATT INSULATION AS SPECIFIED. OF 5/8" TYPE "X" ff7LAYER(S) OARD AS REQUIRED. PER WALL RATING. MUD AND TAPE JOINTS AS REQUIRED. WALL INTERSECTION AT RATED WALL ®= FIRE PRIORITY PARTITION PRIORITY LEGEND 2-HR FIRE AND SMOKE WALL - HIGHEST 2-HR FIRE WALL - PRIORITY2 2-HR SHAFT WALL - PRIORITY 3 1-HR FIRE AND SMOKE WALL - PRIORITY4 1-HR FIRE WALL - PRIORITY5 SMOKE TIGHT WALL - PRIORITY NON RATED WALL - PRIORITY 7 BASIS OF DESIGN:1-HR WALL - UL 465 OR UL V438 2-HR WALL - UL 411 OR UL V438 TYPICAL FRAMING DTL. 11 =11-0n HANGER RODS AS REQUIRED INSULATED DUCT SEE METAL STUDS AT MECHANICAL Ll 16" O.C. MAX 3-5/8" MIN. METAL STUD AT - EACH VERTICAL STUD i Ig WALL AS STOP STUD ' TIGHT TO DUCT AS POSSIBLE SIT TYPE "X" GYP. BOARD EACH SIDE -MUD AND TAPE DRYWALL JOINTS ABOVE NOTE: CEILING FULL HEIGHT BOTH OFF -SET WALL WILL OCCUR WHEN SIDES OF WALL (TYP.) MECHANICAL DUCT AND WALLS RUN PARALLEL. NON -RATED OFFSET WALL AT EXISTING DUCT INTERRUPTION 5/8" TVPE"X" GYPSUM BOARD PER WALL RATING. SEE CODE REVIEW PLAN FOR MORE INFORMATION. METAL STUD RUNNER ATTACHED TO FLOOR WITH ANCHORS @ 2'-0" O.C. MAX. 1/4' MAX. GAP TOLERANCE (TYP.) FLOOR ASSEMBLY SEE BUILDING SECTION FOR MORE INFORMATIO RATED WALL SEAL AT FLOOR TYPICAL FRAMING DTL. 3" = 1'-0" METAL STUD FRAMING 16" O.C. W/ BATT INSULATION (TYP.) TALL GYP. BOARD OVER FIRESTOP 'ER FIRESTOP MNF. SPECIFICATION 15TENERS BEHIND FIRESTOP SEAL. �P/ BOTTOM TRACK FIRESTOP SEAL BYAPPROVED MANUFACTURE. INSTALL HORIZONTAL STUD TOP AND BOTTOM OF PATCH AREA II II F� FASTEN THE DRYWALL INTO METAL STUD FRAMING i FACE OF DRYWALL PATCH DUST BE FLUSH WITH FACE OF ADJACENT WALL TAPE, MUD, AND SAND JOINTS BETWEEN NEW PATCH AND EXISTING WALL FIRE STOP JOINT BETWEEN 'IDRYWALL AND PIPING METAL STUDS @ 16" O.C. II OPENINGS OVER 3" CIA. GENERAL NOTES A r/ 1>� IF GAP AROUND PENETRATION IS G114"OR LESS, PACK AND SEAL WITH APPROVED FIRESTOP SEALANT I( )� IF GAP AROUND PENETRATION IS GREATER THAN 114",PACK TIGHTLY WITH THERMAFIBER SAFING INSULATION OR APPROVED FIREPROOFING MATERIAL, AND APPLY PATCH AS SHOWN RATED AND/OR SMOKE WALLS PATCHING AND SEALING PENETRATIONS OTYPICAL FRAMING DTL. 911= 1,-On O NOTE: IF DUCT IS TO BE INSULATED, DO NOT RUN DUCT INSULATION THROUGH THE WALL FLARE DUCT INSULATION ONTO FACE OF WALL AROUND DUCT ON BOTH SIDES OF WALL, All SEAL DUCT INSULATION TO FACE OF WALL WITH INSULATION MASTIC. WHEN DIMENSION EXCEEDS 16" MAX 16" MAX T INSTALL CRIPPLE STUD IN CORNER. (TYP.) HORIZ. METAL STUD ATTACH TO VERT. STUD Lti VERT. METAL STUDS II AT IT O.C. MAX. SAFING INSULATION UPPL ETU N DUC PACKED TIGHTLY ii RGERT TVPIC WALLS D GATL II I II ATTACHED vy TO VERTAL U NER STUDS. TO VERT. STUDS. —IF Ti II II I PENETRATION RECTANGULAR DUCT PENETRATION RATED AND/OR SMOKE WALL DUCT PENETRATION TYPICAL FRAMING DTL. RATED INTERIOR WALL. SEE LIFE SAFETY PLAN EXTERIOR WALL CLADDING — 5/W TYPE "X" GYPSUM BOARD STUD FRAMING @ IT O.C. MAX. BATT INSULATION AS SPECIFIED RATED INTERIOR WALL INTERSECTING NO- RATED EXTERIOR WALL TYPICAL FRAMING DTL. 1" = 1'-0" MKM architecture + design 119 West Wayne Streat FOIt Wayne, Indiana 46802 p 260.422.0783 f MOA264561 www.MKMicesian.cum Na AftIf286aB1 67ATEOF HIS, Plert THE PROPERTY OF MKIM ARCHITECTURE �N AMID WERE CREATED AND DEVELOPED FOR USE ON AMID IN CONNECTION MH THIS SPECIFIC PROJECT WINE OF THE IDENS DESIGNS ARRANGEMENTS OR PLARIS SHUMAL BE USED BY OR DISCLOSED TO ANY PERSON, FIRM OR CORPORATION FOR ANN PURPOSE WHATSOEVER MHI THE WRITER PERMISSION Of WIN ARCHITECTURE I DESHUN THE OMER SHALL BE PERMITTED TO RETAIN COPIES FOR INFORMAKTION AND lanamal IN CONNECTION NTH THIS PROJECT ARMED DIMENSIONS ON THESE DRAWINGS SHALL HAND PRECEDENCE OVER SCALE DIMENSIONS ADD THIS OFFICE MUST BE NOTIFIED OF ANY VARIATIONFROMTHEDIMENABONSANDCONDITHOME SHOM BY THESE DRAININGS SHOP DRAINAGE MUST BE WMI� TO THIS OFFICE FOR REAM BEFORE PROGREDING WITH FARRICATION ARMS INSTALLATION THE WORK SHOM ON THIS DOCUMENT, AND THE CORRESPONDING sPOPUrcimi INTERFACES SMITH WORK SHOWN ON OTHER DOCUMENTS KILUDING MRK To BE PERFORMED BY OTHER CONTRACTORS OR SUBCONTRACTORS EACH CONTRACTOR OF SUBCONTRACTOR $HALL BE FAMILIAR WIN THE WORK OF OTHER CONTRACTORS OR SUBSCONTRACTORS WHETHER OR NOT SHUM ON THIS DOCUMENT WHICH IMPACTS THE WORK IMPACTS THE MAN SHOM HERFUN AND SHALL DOMINATE SUCH BORK SO AS TO SEE IN St. Vincent Carmel Hospital Carmel Pharmacy 797 800 13500 N Meridian Street REVISION DRAMING Cown_wTS: LIFE SAFETY/RATED FRAMING TYP DTLS ISSOEWTE'. PROJECT NO. 04/26/2019 MKM'. 17107 ASCENSION'. W286 DRAwwG NO. A-015 DATE: 09/04/19