HomeMy WebLinkAboutA-016-INTERIOR-FRAMING-DETAILS-TYPICAL-FIREPROOFING-Rev.0ROOF OR FLOOR ASSEMBLY TING SPRAY APPLIED :IREPROOFING TO BE PROTECTED DURING CONSTRUCTION SPRAY APPLIED FIREPROOFING PATCH TO COMPLETELY COVER THE SUSPENDED CEILING WIRE CLAMP. NOTE: SPRAYAPPLIED FIREPROOFING MUST NOT BE REMOVED TO ATTACH METAL STUD FRAMING TO BEAMS AND COLUMNS. ROOF OR FLOOR ASSEMBLY ROOF OR FLOOR ALL ATTACHMENTS MUST BE INSTALLED PRIOR TO THE ASSEMBLY SPRAVAPPLIED FIREPROOFING. 1/4" MAX. GAP TOLERANCE (TYP.) T� TING SPRAY APPLIED :IREPROOFING TO BE PROTECTED DURING CONSTRUCTION SPRAYAPPLIED FIREPROOFING PATCH NOTE: EXISTING STEEL BEAM (OR JOIST) WITH SPRAY APPLIED FIREPROOFING (S.A.F.). THE GENERAL CONTRACTOR IS RESPONSIBLE FOR PATCHING & REPAIRING SPRAY APPLIED FIREPROOFING THAT IS DAMAGED DURING CONSTRUCTION WHEN FASTENERS TO BEAMS & JOISTS ARE REMOVED OR ADDED, THE S.AF. MUST BE PATCHED. THE G.C. MUST MONITOR SUBCONTRACTORS TO ENSURE THEY DO NOT REMOVE EXCESSIVE S.AF. DURING CONSTRUCTION WHEN ITEMS ARE ATTACHED TO BEAMS. EXCESSIVE S.A.F. REMOVAL MUST BE PATCHED. OFIREPROOFING PATCH DTL. 6 1 1/2" = 1'-0" THIS DIMENSION VARIES UNLESS OTHERWISE DIMENSION NOTED. DIMENSION WILL BE DETERMINED BY THE WORSE CONDITION. (IE. LARGEST COLUMN SO THAT ALL WALLS ARE STRAIGHT ANDAT90DEG. WITH EACH OTHER p'-r p'-iR NOTES: 1. ADDITIONAL LAYER(S) OF GYP. BD. TO BE CONTINUOUS AROUND COLUMN WHERE RATED WALL OR RATED FIRE AND SMOKE WALL ABUTTS COLUMN OF COLUMN 3. FRAME AS TIGHT TO THE COLUMN AS POSSIBLE. COLUMNS WITHIN THE SAME ROOM OR SPACE SHALL BE EQUAL IN WIDTH AND DEPTH BASED ON THE LARGEST COLUMN IN THAT AREA SPRAY APPLIED FIREPROOFING PER THE UL DESIGN NO. '2' MIN. METAL STUDS @ 16" O.C. UNLESS NOTED OTHERWISE RELEASED FOR CONSTRUCTION LLS BYPASSING OR ABUTTING COLUMNS Subject to compliance with all regulations -YPICAL FRAMING DTL. of State and meal Codes City of Carmel 1=11_0" �"IDANN� DATE: 09/04/19 CUT GYP. BOARD TO FIT WITHIN 1/4" OF DECK FLUTES AND SEAL TIGHT TO DECK METAL STUD RUNNER ATTACHED WITH ANCHORS@ 2'-0" O.C. MAX SEAL TIGHT BY DIMPLING GYP. BD INTO SPRAY FIREPROOFING it 1 1 II METAL STUDS BEYOND (TYP.) 11 1 i1 MAX 6" GYP. BD. CANTILEVER (TVPA I 1 I NOTE: GYP. BD. MUST SPAN A MIN. OF (2) STUDSBEFORE CANTILEVER. WHEN CANTILEVEREVER OF GYP. BD. EXCEEDS 6", PROVIDE METAL STUD ATTACHED W/ 20 GA. "Z" CLIPS TO WEB OF BEAM L METAL STUD RUNNER TO SUPPORT GYP. BD. ATTACH (2) CLIPS TO BEAM BEFORE APPLYING SPRAY FIREPROOFING. SPRAY FIREPROOFING PER U.L. DESIGN NO. ' NON -RATED WALLS PERPENDICULAR TO METAL DECK FLUTES OTYPICAL FRAMING DTL. ,.=,,_0R 20 GA METAL CLIP ANGLE AT ROOF /FLOOR ASSEMBLY 16" O.C. ATTACHED TO DECK BEFORE APPLYING SPRAY EXTEND SPRAY FIREPROOFING FIREPROOFING INTO DECK FLUTES CUT GYP. BOARD TO FIT PATCH AND REPAIR WITHIN 1/4" OF DECK FLUTES FIREPROOFING AS REQUIRED AND SEAL TIGHT TO DECK 20 GA. METAL Z-CLIP AT 16" O.C. (2) 20 GA Z-CLIPS AT EACH STUD ATTACH TO STEEL BEFORE ATTACH Z-CLIPS BEFORE APPLYING SPRAY FIREPROOFING APPLYING SPRAY FIREPROOFING METAL STUDS AT 16' O.C. MAX DIMPLE GYP. BOARD INTO SPRAY FIREPROOFING - MUD AND TAPE JOINT BETWEEN BETWEEN SPRAY METAL STUDS AT 16" O.C. MAX FIREPROOFING AND 5/8" TYPE "X" INFILL SOLID W/ BATT INSULATION GYP. BOARD (TYP.) 518" TYPE "X" GYP. BOARD EACH SIDE -MUD AND TAPE DRYWALL JOINTS ABOVE CEILING FULL HEIGHT BOTH SIDES OF WALL (TYP.) NON -RATED WALL INTERRUPTED BY BEAM TYPICAL FRAMING DTL. C FILL ENTIRE VOID BEHIND ROOF OR FLOORASSEMBLV CANTILEVERED GYPSUM BD. WITH SAVING INSULATIONS x 114" MAX. GAP TOLERANCE (TYP.) f e CUT GYP. BOARD TO FIT DECK FLUTES AND SEALL TIGHT TO DECK ANDS -- WITH APPROVED FIRESTOP MATERIAL II II II II II METAL STUD RUNNER ATTACHED 1 WITH ANCHORS @ 2'-P O.C. MAX SEAL TIGHT BY DIMPLING GYP. BD. 1 INTO SPRAY FIREPROOFING tI METAL STUDS BEYOND (TYP.) _ - _ - 11 MAX.6" GYP. BD. CANTILEVER (TYP.) I NOTE: GYP. BD. MUST SPAN MIN. OF (2) STUDS BEFORE CANTILEVER. WHEN CANTILEVER GYP. BD. EXCEEDS 6", PROVIDE METAL STUD ATTACHED W/ 20 GA. "Z" CLIPS TO WEB OF BEAM METAL STUD RUNNER TO SUPPORT GYP. BD. ATTACH (2) CLIPS TO BEAM BEFORE APPLYING SPRAY FIREPROOFING. SPRAY FIREPROOFING PER U.L. DESIGN NO. RATED AND/OR SMOKE WALL PERPENDICULAR TO METAL DECK FLUTES 20 GA METAL CLIP ANGLE AT W ROOF/FLOOR ASSEMBLY O.C. ATTACHED TO DECK BEFORE APPLYING SPRAY FIREPROOFING EXTEND SPRAY FIREPROOFING ' INTO DECK FLUTES CUT GYP. BOARD TO FIT WITHIN 1/4" OF PATCH AND REPAIR DECK FLUTES AND SEAL TIGHT TO DECK FIREPROOFING AS WITH APPROVED FIRESTOP MATERIAL REQUIRED I (2) 20 GA. Z-CLIPS AT EACH STUD 20 GA. METAL Z-CLIP AT ATTACH Z-CLIPS BEFORE APPLYING 16"QC. ATTACH TO STEEL ' I SPRAY FIREPROOFING BEFORE APPLYING SPRAY - FIREPROOFING ' - METAL STUDS AT 16" O.C. MAX. DIMPLE GYP. BOARD INTO SPRAY FIREPROOFING -SEAL WITH METAL STUDS AT 16" O.C. MAX APPROVED FIRESTOP MATERIAL INFILL SOLID W/ BATT INSULATION ONE OR TWO LAYERS OF 518"—' TYPE "X" GVP BOARD EACH SIDE - MUD AND TAPE DRYWALL JOINTS ABOVE CEILING FULL HEIGHT BOTH SIDES OF WALL (TYP J RATED AND/OR SMOKE WALL INTERRUPTED BY BEAM FLOOR OR ROOF ASSEMBLY — EXTEND SPRAY FIREPROOFING INTO FLUTES OF DECK (TYP.) CUT GYP. BOARD TO FIT � WITHIN 11T OF DECK FLUTES PATCH AND REPAIR AND SEAL TIGHT TO DECK FIREPROOFING AS REQUIRED 12 OR LESS DIMPLEGYP. BOARD INTO ISPRAV METAL STUDS @ 16" O.C. MAX. FIREPROOFING INFILL SOLID W/ BATT INSULATION MUD AND TAPE JOINT 20 GA. Z-CLIP AT EACH STUD BETWEEN BETWEEN SPRAY ATTACH TO BEAM BEFORE FIREPROOFING AND 518" APPLYING SPRAY FIREPROOFING TYPE "X" GYP. BOARD (TYP.) 2-1/2- (MIN.) METAL STUD @ 518" TYPE "X" GYP. BOARD EACH VERTICAL STUD EACH SIDE -MUD AND TAPE DRYWALL JOINTS ABOVE CEILING FULL HEIGHT BOTH SIDES OF WALL (TYP.) NON -RATED WALL WITHIN 12" OF SPRAY FIREPROOF BEAM OTYPICAL FRAMING DTL. ,.=,,_0R ROOF/FLOOR ASSEMBLY --—---————- FLOOR OR ROOF ASSEMBLY — EXTEND SPRAY FIREPROOFING INTO FLUTES OF DECK (TYP.) CUT GYP. BOARD TO FIT WITHIN 1 1/4" OF DECK FLUTES AND SEAL TIGHT TO DECK WITH APPROVED FIRESTOP MATERIAL 12" OR PATCH AND REPAIR METAL STUDS @ 16" O.C. MAX LESS FIREPROOFING AS REQUIRED INFILL SOLID W/ BATT INSULATION DIMPLE GYP. BOARD INTO 20 GA. Z-CLIP AT EACH STUD SPRAY FIREPROOFING - ATTACH TO BEAM BEFORE SEAL WITH APPROVED APPLYING SPRAY FIREPROOFING Ir\ FIRESTOP MATERIAL r - ONE OR TWO LAVERS OF 2-11T (MIN.) METAL STUD @ 5'8" TYPE "X" GYP. BOARD EACH VERTICAL STUD EACH SIDE -MUD AND TAPE DRYWALL JOINTS ABOVE CEIUNG FULL HEIGHT BOTH SIDES OF WALL (TYP.) RATED AND/OR SMOKE WALL WITHIN 12" OF SPRAY FIREPROOF BEAM 20 GA METAL Z-CLIP AT EXTEND SPRAY FIREPROOFING i6" O.C. AT TO STEEL INTO DECK FLUTES (TVP.) BEFORE APPLYING SPRAY FIREPROOFING PATCH AND REPAIR FIREPROOFING AS REQUIRED fd8" TYPE "X" GYP. BOARD EACH DIMPLE GYP. BOARD INTO SPRAY SIDE -MUD AND TAPE DRYWALL FIREPROOFING -MUD AND TAPE JOINTS ABOVE CEILING FULL JOINT BETWEEN BETWEEN SPRAY HEIGHT BOTH SIDES OF WALL (TYP.) FIREPROOFING AND S/8"TYPE 'X' GYP. BOARD (TYP.) METAL STUDS AT 16" O.C. MAX INFILL SOLID W/ BATT INSULATION NON -RATED WALL UNDER BEAM TYPICAL FRAMING DTL. ROOF/FLOOR ASSEMBLY 20 GA METAL Z-CLIP AT 16" O.C. ATTACH TO STEEL BEFORE APPLYING SPRAY FIREPROOFING ���%%% ONE OR TWO LAYERS OF 518" TYPE "X" GYP. BOARD EACH SIDE -MUD AND TAPE DRYWALL JOINTS ABOVE CEILING FULL HEIGHT BOTH SIDES OF WALL (TYP.) EXTEND SPRAY FIREPROOFING INTO DECK FLUTES (TYP.) PATCH AND REPAIR FIREPROOFING AS REQUIRED DIMPLE GYP. BOARD INTO SPRAY FIREPROOFING - SEAL WITH APPROVED FIRESTOP MATERIAL BOTH SIDES METAL STUDS AT 16" O.C. MAX INFILL SOLID W/ BATT INSULATION RATED AND/OR SMOKE WALL UNDER BEAM MKM architecture + design 119 West Wayne street FOIt Wayne, Indiana 46802 IS 260.422.0783 f MOA2&4%1 www.MKMdesian.cum iM AftIf286EB1 BTASEOf IKey FIAT INDICATED BY THIS DRAWNG ARE OWNED BY, AND THE PROPERTY OF None ARCHITECTURE , DESIGN AMID WERE CREATED AND DEVELOPED FOR USE ON AMID IN CONNECTION MH THIS SPECIFIC PROJECT WINE OF THE DI DESIGNS ARRANGEMENTS OR PLANS SHALL BE USED BY OR DJSCUOPRED TO ANY HANSON, FIRM OR CORPORATION FOR ANY PURPOSE AFFATANOEwER MHOUT THE WRITTEN THE OMER SHALL BE PERM17ED TO RETAN WINES FOR INFORMATION AND REFERENCE IN CONNECTION NTH THIS PROJECT ARMED DIMENSIONS ON THESE DRAWNGS SHALL MAE PRECEDENCE OVER SCALE DIMENSIONS ADD THIS OFFICE MOST BE NOTIFED OF ANY VARIATIONFROMTHEDIMENSONSANDCONDITTIONS SHOWN BY THERE DRAMIGS SHOP THAI MUST BE MMITTED TO THIS OFFICE FOR REAM BEFORE PROCESEUNG WITH FABRICATION ANDOR INSTALLATION THE WORK SICAMS ON THIS DOCUMENT, AND THE CORRESPONDING mccirecYnoNs INTERFACES WITH WORK SHOWN ON OTHER DOCUMENTS INCLUDING MRK To BE PERFORMED BY OTHER CONTRACTORS OR SUBCONTRACTORS EACH CONTRACTOR OF SUBCONTRACTOR $HALL BE FAMEAR WIN THE WORK OF OTHER CONTRACTORS OR SUBCONTRACTORS WHETHER OR NOT SHOWN ON THIS DOCUMENT WHICH IMPACTS THE WORK IMI THE WORK SHOWN HERSIN AND SHALL DOMINATE SUCH MISS ED AS TO SE IN St. Vincent Carmel Hospital Carmel Pharmacy 797 800 13500 N Meridian Street MIS" DRAWING CONTENTS: INTERIOR FRAMING DETAILS/ TYPICAL FIREPROOFING INSIDE DATE'. PROJECT NO. 04/26/2019 MKM'. 17107 ASCENSION. W286 DRAWNG NO. A-016