HomeMy WebLinkAboutA-016-INTERIOR-FRAMING-DETAILS-TYPICAL-FIREPROOFING-Rev.0ROOF OR FLOOR
ASSEMBLY
TING SPRAY APPLIED
:IREPROOFING TO BE
PROTECTED DURING
CONSTRUCTION
SPRAY APPLIED
FIREPROOFING PATCH
TO COMPLETELY COVER
THE SUSPENDED
CEILING WIRE CLAMP.
NOTE:
SPRAYAPPLIED FIREPROOFING MUST NOT BE REMOVED TO
ATTACH METAL STUD FRAMING TO BEAMS AND COLUMNS. ROOF OR FLOOR ASSEMBLY
ROOF OR FLOOR ALL ATTACHMENTS MUST BE INSTALLED PRIOR TO THE
ASSEMBLY SPRAVAPPLIED FIREPROOFING.
1/4" MAX. GAP TOLERANCE (TYP.) T�
TING SPRAY APPLIED
:IREPROOFING TO BE
PROTECTED DURING
CONSTRUCTION
SPRAYAPPLIED
FIREPROOFING
PATCH
NOTE:
EXISTING STEEL BEAM (OR JOIST) WITH SPRAY APPLIED
FIREPROOFING (S.A.F.). THE GENERAL CONTRACTOR IS
RESPONSIBLE FOR PATCHING & REPAIRING SPRAY APPLIED
FIREPROOFING THAT IS DAMAGED DURING CONSTRUCTION WHEN
FASTENERS TO BEAMS & JOISTS ARE REMOVED OR ADDED, THE
S.AF. MUST BE PATCHED. THE G.C. MUST MONITOR
SUBCONTRACTORS TO ENSURE THEY DO NOT REMOVE EXCESSIVE
S.AF. DURING CONSTRUCTION WHEN ITEMS ARE ATTACHED TO
BEAMS. EXCESSIVE S.A.F. REMOVAL MUST BE PATCHED.
OFIREPROOFING PATCH DTL.
6 1 1/2" = 1'-0"
THIS DIMENSION VARIES UNLESS
OTHERWISE DIMENSION
NOTED. DIMENSION
WILL BE DETERMINED BY THE WORSE
CONDITION. (IE. LARGEST COLUMN
SO THAT ALL WALLS ARE STRAIGHT
ANDAT90DEG. WITH EACH OTHER
p'-r p'-iR
NOTES:
1. ADDITIONAL LAYER(S) OF GYP. BD.
TO BE CONTINUOUS AROUND COLUMN
WHERE RATED WALL OR RATED FIRE
AND SMOKE WALL ABUTTS COLUMN
OF COLUMN
3. FRAME AS TIGHT TO THE COLUMN AS
POSSIBLE. COLUMNS WITHIN THE SAME
ROOM OR SPACE SHALL BE EQUAL IN
WIDTH AND DEPTH BASED ON THE
LARGEST COLUMN IN THAT AREA
SPRAY APPLIED FIREPROOFING
PER THE UL DESIGN NO.
'2' MIN. METAL STUDS @ 16" O.C.
UNLESS NOTED OTHERWISE
RELEASED FOR CONSTRUCTION LLS BYPASSING OR ABUTTING COLUMNS
Subject to compliance with all regulations -YPICAL FRAMING DTL.
of State and meal Codes
City of Carmel 1=11_0"
�"IDANN�
DATE: 09/04/19
CUT GYP. BOARD TO FIT WITHIN
1/4" OF DECK FLUTES AND SEAL
TIGHT TO DECK
METAL STUD RUNNER ATTACHED
WITH ANCHORS@ 2'-0" O.C. MAX
SEAL TIGHT BY DIMPLING GYP. BD
INTO SPRAY FIREPROOFING
it 1 1 II
METAL STUDS BEYOND (TYP.)
11 1 i1
MAX 6" GYP. BD. CANTILEVER (TVPA I 1 I
NOTE:
GYP. BD. MUST SPAN A MIN. OF (2)
STUDSBEFORE CANTILEVER. WHEN
CANTILEVEREVER OF GYP. BD. EXCEEDS
6", PROVIDE METAL STUD ATTACHED
W/ 20 GA. "Z" CLIPS TO WEB OF BEAM L METAL STUD RUNNER
TO SUPPORT GYP. BD. ATTACH (2)
CLIPS TO BEAM BEFORE APPLYING
SPRAY FIREPROOFING.
SPRAY FIREPROOFING PER U.L. DESIGN NO. '
NON -RATED WALLS PERPENDICULAR TO METAL DECK FLUTES
OTYPICAL FRAMING DTL.
,.=,,_0R
20 GA METAL CLIP ANGLE AT
ROOF /FLOOR ASSEMBLY
16" O.C. ATTACHED TO DECK
BEFORE APPLYING SPRAY
EXTEND SPRAY FIREPROOFING
FIREPROOFING
INTO DECK FLUTES
CUT GYP. BOARD TO FIT
PATCH AND REPAIR
WITHIN 1/4" OF DECK FLUTES
FIREPROOFING AS REQUIRED
AND SEAL TIGHT TO DECK
20 GA. METAL Z-CLIP AT 16" O.C.
(2) 20 GA Z-CLIPS AT EACH STUD
ATTACH TO STEEL BEFORE
ATTACH Z-CLIPS BEFORE
APPLYING SPRAY FIREPROOFING
APPLYING SPRAY FIREPROOFING
METAL STUDS AT 16' O.C. MAX
DIMPLE GYP. BOARD INTO SPRAY
FIREPROOFING - MUD AND TAPE
JOINT BETWEEN BETWEEN SPRAY
METAL STUDS AT 16" O.C. MAX
FIREPROOFING AND 5/8" TYPE "X"
INFILL SOLID W/ BATT INSULATION
GYP. BOARD (TYP.)
518" TYPE "X" GYP. BOARD EACH
SIDE -MUD AND TAPE DRYWALL
JOINTS ABOVE CEILING FULL
HEIGHT BOTH SIDES OF WALL (TYP.)
NON -RATED WALL
INTERRUPTED BY BEAM
TYPICAL
FRAMING DTL.
C
FILL ENTIRE VOID BEHIND
ROOF OR FLOORASSEMBLV
CANTILEVERED GYPSUM BD.
WITH SAVING INSULATIONS
x
114" MAX. GAP TOLERANCE (TYP.)
f
e
CUT GYP. BOARD TO FIT
DECK FLUTES
AND SEALL TIGHT TO DECK
ANDS
--
WITH APPROVED FIRESTOP
MATERIAL II
II II
II II
METAL STUD RUNNER ATTACHED
1
WITH ANCHORS @ 2'-P O.C. MAX
SEAL TIGHT BY DIMPLING GYP. BD.
1
INTO SPRAY FIREPROOFING
tI
METAL STUDS BEYOND (TYP.) _ - _ -
11
MAX.6" GYP. BD. CANTILEVER (TYP.) I
NOTE:
GYP. BD. MUST SPAN MIN. OF (2)
STUDS BEFORE CANTILEVER. WHEN
CANTILEVER GYP. BD. EXCEEDS
6", PROVIDE METAL STUD ATTACHED
W/ 20 GA. "Z" CLIPS TO WEB OF BEAM
METAL STUD RUNNER
TO SUPPORT GYP. BD. ATTACH (2)
CLIPS TO BEAM BEFORE APPLYING
SPRAY FIREPROOFING.
SPRAY FIREPROOFING PER U.L. DESIGN NO.
RATED AND/OR SMOKE WALL PERPENDICULAR TO METAL DECK FLUTES
20 GA METAL CLIP ANGLE AT W
ROOF/FLOOR ASSEMBLY
O.C. ATTACHED TO DECK BEFORE
APPLYING SPRAY FIREPROOFING
EXTEND SPRAY FIREPROOFING
'
INTO DECK FLUTES
CUT GYP. BOARD TO FIT WITHIN 1/4" OF
PATCH AND REPAIR
DECK FLUTES AND SEAL TIGHT TO DECK
FIREPROOFING AS
WITH APPROVED FIRESTOP MATERIAL
REQUIRED
I
(2) 20 GA. Z-CLIPS AT EACH STUD
20 GA. METAL Z-CLIP AT
ATTACH Z-CLIPS BEFORE APPLYING
16"QC. ATTACH TO STEEL
' I SPRAY FIREPROOFING
BEFORE APPLYING SPRAY
-
FIREPROOFING
' -
METAL STUDS AT 16" O.C. MAX.
DIMPLE GYP. BOARD INTO SPRAY
FIREPROOFING -SEAL WITH
METAL STUDS AT 16" O.C. MAX
APPROVED FIRESTOP MATERIAL
INFILL SOLID W/ BATT INSULATION
ONE OR TWO LAYERS OF 518"—'
TYPE "X" GVP BOARD EACH SIDE
- MUD AND TAPE DRYWALL JOINTS
ABOVE CEILING FULL HEIGHT BOTH
SIDES OF WALL (TYP J
RATED AND/OR SMOKE WALL
INTERRUPTED BY BEAM
FLOOR OR ROOF ASSEMBLY —
EXTEND SPRAY FIREPROOFING
INTO FLUTES OF DECK (TYP.)
CUT GYP. BOARD TO FIT �
WITHIN 11T OF DECK FLUTES
PATCH AND REPAIR
AND SEAL TIGHT TO DECK
FIREPROOFING AS REQUIRED
12 OR
LESS DIMPLEGYP. BOARD INTO
ISPRAV
METAL STUDS @ 16" O.C. MAX.
FIREPROOFING
INFILL SOLID W/ BATT INSULATION
MUD AND TAPE JOINT
20 GA. Z-CLIP AT EACH STUD
BETWEEN BETWEEN SPRAY
ATTACH TO BEAM BEFORE
FIREPROOFING AND 518"
APPLYING SPRAY FIREPROOFING
TYPE "X" GYP. BOARD (TYP.)
2-1/2- (MIN.) METAL STUD @
518" TYPE "X" GYP. BOARD
EACH VERTICAL STUD
EACH SIDE -MUD AND TAPE
DRYWALL JOINTS ABOVE
CEILING FULL HEIGHT BOTH
SIDES OF WALL (TYP.)
NON -RATED WALL WITHIN 12"
OF SPRAY FIREPROOF BEAM
OTYPICAL FRAMING DTL.
,.=,,_0R
ROOF/FLOOR ASSEMBLY
--—---————-
FLOOR OR ROOF ASSEMBLY —
EXTEND SPRAY FIREPROOFING
INTO FLUTES OF DECK (TYP.)
CUT GYP. BOARD TO FIT WITHIN 1
1/4" OF DECK FLUTES AND SEAL
TIGHT TO DECK WITH
APPROVED FIRESTOP MATERIAL 12" OR
PATCH AND REPAIR
METAL STUDS @ 16" O.C. MAX LESS
FIREPROOFING AS REQUIRED
INFILL SOLID W/ BATT INSULATION
DIMPLE GYP. BOARD INTO
20 GA. Z-CLIP AT EACH STUD
SPRAY FIREPROOFING -
ATTACH TO BEAM BEFORE
SEAL WITH APPROVED
APPLYING SPRAY FIREPROOFING
Ir\ FIRESTOP MATERIAL
r
-
ONE OR TWO LAVERS OF
2-11T (MIN.) METAL STUD @
5'8" TYPE "X" GYP. BOARD
EACH VERTICAL STUD
EACH SIDE -MUD AND TAPE
DRYWALL JOINTS ABOVE
CEIUNG FULL HEIGHT BOTH
SIDES OF WALL (TYP.)
RATED AND/OR SMOKE WALL WITHIN 12"
OF SPRAY FIREPROOF BEAM
20 GA METAL Z-CLIP AT EXTEND SPRAY FIREPROOFING
i6" O.C. AT TO STEEL INTO DECK FLUTES (TVP.)
BEFORE APPLYING SPRAY
FIREPROOFING PATCH AND REPAIR
FIREPROOFING AS REQUIRED
fd8" TYPE "X" GYP. BOARD EACH DIMPLE GYP. BOARD INTO SPRAY
SIDE -MUD AND TAPE DRYWALL FIREPROOFING -MUD AND TAPE
JOINTS ABOVE CEILING FULL JOINT BETWEEN BETWEEN SPRAY
HEIGHT BOTH SIDES OF WALL (TYP.) FIREPROOFING AND S/8"TYPE 'X'
GYP. BOARD (TYP.)
METAL STUDS AT 16" O.C. MAX
INFILL SOLID W/ BATT INSULATION
NON -RATED WALL UNDER BEAM
TYPICAL
FRAMING DTL.
ROOF/FLOOR ASSEMBLY
20 GA METAL Z-CLIP AT
16" O.C. ATTACH TO STEEL
BEFORE APPLYING SPRAY
FIREPROOFING ���%%%
ONE OR TWO LAYERS OF 518"
TYPE "X" GYP. BOARD EACH
SIDE -MUD AND TAPE DRYWALL
JOINTS ABOVE CEILING FULL
HEIGHT BOTH SIDES OF WALL (TYP.)
EXTEND SPRAY FIREPROOFING
INTO DECK FLUTES (TYP.)
PATCH AND REPAIR
FIREPROOFING AS REQUIRED
DIMPLE GYP. BOARD INTO
SPRAY FIREPROOFING - SEAL
WITH APPROVED FIRESTOP
MATERIAL BOTH SIDES
METAL STUDS AT 16" O.C. MAX
INFILL SOLID W/ BATT INSULATION
RATED AND/OR SMOKE WALL UNDER BEAM
MKM
architecture + design
119 West Wayne street
FOIt Wayne, Indiana 46802
IS 260.422.0783
f MOA2&4%1
www.MKMdesian.cum
iM AftIf286EB1
BTASEOf
IKey FIAT
INDICATED BY THIS DRAWNG ARE OWNED BY, AND
THE PROPERTY OF None ARCHITECTURE , DESIGN
AMID WERE CREATED AND DEVELOPED FOR USE ON
AMID IN CONNECTION MH THIS SPECIFIC PROJECT
WINE OF THE DI DESIGNS ARRANGEMENTS OR
PLANS SHALL BE USED BY OR DJSCUOPRED TO ANY
HANSON, FIRM OR CORPORATION FOR ANY
PURPOSE AFFATANOEwER MHOUT THE WRITTEN
THE OMER SHALL BE PERM17ED TO RETAN
WINES FOR INFORMATION AND REFERENCE IN
CONNECTION NTH THIS PROJECT ARMED
DIMENSIONS ON THESE DRAWNGS SHALL MAE
PRECEDENCE OVER SCALE DIMENSIONS
ADD THIS OFFICE MOST BE NOTIFED OF ANY
VARIATIONFROMTHEDIMENSONSANDCONDITTIONS
SHOWN BY THERE DRAMIGS SHOP THAI
MUST BE MMITTED TO THIS OFFICE FOR REAM
BEFORE PROCESEUNG WITH FABRICATION ANDOR
INSTALLATION THE WORK SICAMS ON THIS
DOCUMENT, AND THE CORRESPONDING
mccirecYnoNs INTERFACES WITH WORK SHOWN
ON OTHER DOCUMENTS INCLUDING MRK To BE
PERFORMED BY OTHER CONTRACTORS OR
SUBCONTRACTORS EACH CONTRACTOR OF
SUBCONTRACTOR $HALL BE FAMEAR WIN THE
WORK OF OTHER CONTRACTORS OR
SUBCONTRACTORS WHETHER OR NOT SHOWN ON
THIS DOCUMENT WHICH IMPACTS THE WORK
IMI THE WORK SHOWN HERSIN AND SHALL
DOMINATE SUCH MISS ED AS TO SE IN
St. Vincent
Carmel Hospital
Carmel Pharmacy 797 800
13500 N Meridian Street
MIS"
DRAWING CONTENTS:
INTERIOR FRAMING
DETAILS/ TYPICAL
FIREPROOFING
INSIDE DATE'. PROJECT NO.
04/26/2019 MKM'. 17107
ASCENSION. W286
DRAWNG NO.
A-016