HomeMy WebLinkAboutE600-ELECTRICAL-RISER,-SCHEDULES,-AND-DETAILS-Rev.0LA
RELEASED FOR CONSTRUCTION
LIGHT FIXTURE SCHEDULE
NOTE: SEE SPECIFICATION SECTION 260923, 260933, 260936, 265100, 265561, 265600, 265668 FOR ADDITIONAL INFORMATION REGARDING LIGHTING FIXTURES AND INSTALLATION REQUIREMENTS. PROVIDE OPTIONS AND
ACCESSORIES BY THE REFERENCED COLUMN TITLED "REMARKS". MANUFACTURERS LISTED SHALL MEET ALL REQUIREMENTS AND FEATURES INDICATED.
FIXTURE DIMENSIONS
LAMP DATA
x
�
x
�
x
FIXTURE
o
z
O
COLOR
DELIVERED
MANUFACTURER CATALOG
TYPE
3
�
Ill
M
DIA
DESCRIPTION
VOLTAGE
WATTAGE
TYPE
TEMP
LUMENS
SERIES
ACCESSORIES/OPTIONS
Lf
24'
48'
6'
0-0'
CLEANROOM TROFFER
120V
45W
LED
3500K
5700
FAIL-SAFE - CUM,
MINIMUM 90 CRI, WET LOCATION LISTED, SEALED
KURTZON - EL,
AND GASKETED, ISO 7 MINIMUM RATING
KENALL -CSEDI
L2
24'
48'
6'
0-0'
CLEANROOM TROFFER
120V
72W
LED
3500K
BBDD
FAIL-SAFE -CUA,
MINIMUM 90 CRI, WET LOCATION LISTED, SEALED
KURTZON-EL,
AND GASKETED, ISO 7 MINIMUM RATING
KENALL-CSEDI
VARIABLE FREQUENCY CONTROLLER SCHEDULE
EQUIPMENT DATA
CIRCUIT BREAKER
BYPASS
CONTROLLER
NEMA
DESIGNATION
LOAD
SERVED
LOCATION
HP
FLA
VOLTAGE
PHASE
FRAME
SIZE
TRIP SIZE
TYPE
NEMA
SIZE
ENCLOSU
RE
COMMENTS
VFC-EKF15A
EXF-15A
hECH ROOM
2
3.4
480
3
30
15
NNR
00
TYPE)
VFC-EXF15B
EXF-15B
NECH ROOM
1.5
3.0
480
3
30
15
NNR
00
TYl'E7
Branch Panel: BLC3
Location: PHARMACYBWO069
Supplied From:
Mountino: Recessed
Enclosure Type: Type 1
General Panel Comments:
1. EXISTING PANELBOARD AND CIRCUIT BREAKERS.
Voles
Phase:
Wire:
Ground:
1201208 Wye
3
4
YES
Branch: CRITICAL
&I.C. Raltnu: 10K
Main Type: MCB
Main RaBnu: 100 A
Circuit
Number
Circuit Description
Trip
Poles
A
B
C
Poles
Trip
Circuit Description
Circuit
Number
1
EXISTING CIRCUIT
20A
1
0.0
0.0
1
20A
EXISTING CIRCUIT
2
3
EXISTING CIRCUIT
20A
1
0.0
0.0
1
20A
EXISTING CIRCUIT
4
5
EXISTING CIRCUIT
20A
1
0.0
0.0
1
20A
EXISTING CIRCUIT
6
7
EXISTING CIRCUIT
20A
1
0.0
0.0
1
20A
EXISTING CIRCUIT
8
9
EXISTING CIRCUIT
20A
1
0.0
0.0
1
20A
EXISTING CIRCUIT
10
11
EXISTING CIRCUIT
20A
1
0.0
0.0
1
20A
EXISTING CIRCUIT
12
13
EXISTING CIRCUIT
20A
1
0.0
0.0
1
20A
EXISTING CIRCUIT
14
15
EXISTING CIRCUIT
20A
1
0.0
0.0
1
20A
EXISTING CIRCUIT
16
17
BWO074,76,77,83-RECEPS
20A
1
0.2
0.0
1
20A
EXISTINGCIRCUIT
18
19
BW 0083 -FREEZER
20A
1
0.4
0.0
1
20A
EXISTING CIRCUIT
20
21
BWO076-NMTHHOW
20A
1
0.4
0.0
1
20A
EXISTING CIRCUIT
22
23
EXISTING CIRCUIT
20A
1
0.0
0.0
1
20A
EXISTING CIRCUIT
24
25
EXISTING CIRCUIT
20A
1
0.0
0.0
1
20A
EXISTING CIRCUIT
26
27
EXISTING CIRCUIT
20A
1
0.0
0.0
1
20A
EXISTING CIRCUIT
28
29
EXISTING CIRCUIT
20A
1
0.0
0.0
1
20A
EXISTING CIRCUIT
30
31
EXISTING CIRCUIT
20A
1
0.0
0.0
1
20A
SPARE
32
33
EXISTING CIRCUIT
20A
1
0.0
0.0
1
20A
EXISTING CIRCUIT
34
35
EXISTING CIRCUIT
20A
1
0.0
0.0
1
20A
SPARE
36
37
SPARE
20A
1
0.0
0.0
1
20A
EXISTING CIRCUIT
38
39
EXISTING CIRCUIT
20A
1
0.0
0.0
1
20A
EXISTING CIRCUIT
40
47
EXISTING CIRCUIT
20A
1
0.0
0.0
1
20A
EXISTING CIRCUIT
42
Total
Load:
0.4 kVA
0.4
IVA
0.2 kVA
Total Connected Load...
Total Connected Load (Amps):
1.0 kVA
2.8 A
Remarks:
LAY -IN CEILING T-BAR
LAY -IN CEILING TILE
ATTACH OCTAGON
BOX TO THE FIXTURE
HANGER
4-OCTAGON 112'
WORKBOX
ROMEX CONNECTOR
OCCUPANCY SENSOR
ATTACH SENSOR TO
OCTAGON BOX. CENTER IN
THE CEILING TOLE.
NOTE:
LOW VOLTAGE CABLES SHALL BE SUPPORTED TO BE OFF OF THE CEILING GRID AND CEILING TILE.
SUPPORT CABLES TO THE BUILDING STRUCTURE UTILIZING VELCRO OR CABLE TIES.
�\ OCCUPANCY SENSOR MOUNTING DETAIL
NO SCALE
SNAP ON FDGUREI
BOX HANGER
LAY -IN CEILING T-BAR
ATTACH FIXTURE HANGER
TO CEILING GRID.
VARIABLE
FREQUENCY
CONTROLLER
BYPASS
CONTACTOR
BYPASS CONTACTOR
ENCLOSURE
NON -FUSED SAFETY SWITCH WITH
AUXILIARY INTERLOCK
SIEMENS-ALLIS
MARQ MCC
MCC -A
480V
FED FROM BHE1
BACNET
EXF-15A EXF-15B
617
AHU-7
RECIRCULATION
PUMPAHU-6
AHU6 SUPPLY FAN 1
AHU6 SUPPLY FAN 2
SPARE
AHU4 SUPPLY FAN 1
HRU-1
AM-FL01
2BLE
AHU4 SUPPLY FAN 2
lAM-FL01
FAN NO 31
SPARE
AHUIRELIEF
AHU4 RELIEF FAN
SPARE
5% LINE REACTOR
CIRCUIT BREAKER
WITH DOOR
INTERLOCK
ISOLATION
CONTACTOR
5\ VARIABLE FREQUENCY CONTROLLER SCHEMATIC
No SCALE
i1 MCC -A ELEVATION
NOSCALE
CADDY SCREW GL
METAL STUDS
GENERALNOTES
A. REFER TO SHEET E001 FOR ELECTRICAL SYMBOLS AND ADDITIONAL GEN ERAL NOTES.
PLAN NOTES
Ill
PROVIDE NEW DUAL CIRCUIT BREAKER FEEDER UNIT IN MCC FOR NEW EXHAUST
FANS. BOTH CIRCUIT BREAKERS SHALL BE 480Vf3P115A. REFER TO RISER AND
BEVATI ON ON SHEET E600.
617
DISCONNECT AND REM GIVE EXISTING BUCKET IN MCC AT THIS LOCATION. PROVID E
NEW 0UAL CIRCUIT BREAKER FEEDER UNIT IN MCC FOR NEW EXHAUST FANS. BOTH
CIRCUIT BREAKERS SHALL BE 480Vf3P115A.
MECHANICAL ROOM,
3-C72, M12 CND, 3M' C
I
I
I
EXISTINGMCC 1uR EXF-15A
480Vf3P fill VFC VFC 2HP
MCC -A
BOX MOUNTING BRACKET
NOTE:
1, FOR METAL STUD WALL CONSTRUCTION ONLY.
2. EITHER CADDY SCREW GUN BRACKET OR BOX MOUNTING
BRACKET MAY BE USED AS STUD-TOSTUD SUPPORTS
WALL BOX INSTALLATION DETAIL - DOUBLE MOUNT
NO SCALE
3412, N12 GND, 3I4' C
1.5HP
_ SECOND FLOOR
FIRST FLOOR
BASEMENT
i1 NEW ELECTRICAL RISER
NO SCALE
COMBINATION BEAM CLAMI
CONDUIT HANGER OR EQU....--,..
NOTE: FOR STEEL STRUCTURAL SYSTEM
AND SMALLER CONDUIT SUPPORT DETAIL - STEEL BEAM
SMALLER CONDUIT SUPPORT DETAIL - STEEL BEAM
NO SCALE
MKM
architecture design
119 West Wayne Street
Fort Wayne, Indiana 46802
p 260.422.0783
1260.426.4561
www.MKMdesion.eom
PE10606505
STATE Or
BSAettelmalures
9365 DoucGoal s, Raw Sum 330
Goal 78IN fx 17.819.
Ph 317.819.7878 Tx 317.819.7288
K" Pan:
TIE PROPERTY OF MKM ARCHITECTURE. DESIGN,
AHD WERE CREATEDPHO DEVELOPED FOR USE ON,
AHD IN CONNECTION WITH THIS SPECIFIC PROJECT
HONE OF THE IDEAS DESIGNS, ARRANGEMENTS OR
PUNS SHALL BE USED By OR DISCLOSED TO ANY
PERSON, FIRM OR CORPORUION FOR ANY
PURPOSE WHATSOEVER MHOMT THE WRITTEN
PERMISSION OF PIKE ARCHITECTURE , reSpN.
THE OWNER SHALL BE PERMITTED TO RETAIN
COPIES FOR INFORMATION AND REFERENCE IN
CONNECTION NTH THIS PROJECT WRITTEN
DIMENSIONS ON THESE oMWTNGS SHALL HAVE
PRECEDENCE OVER SCALE DIMENSIONS.
AND THIS OFFICE MUST BE NOTIFIED OF ANY
SHVARIATION FROM ME DIMENSIONS AND CONDITIONS
OWN BY THESE DWNNGS. SHOP DRAWIGS
MOST SE SUBMITTED TO THIS OFFICE FOR REVIEW
BEFORE PROCEEDING NTH FABRICATION ANDSOR
INSTALLATION. ME WORK SHOWN ON THIS
DOCUMENT AND THE CORRESPONDING
SPECIFICANg15, INTERFACES WRH WORK SHOWN
ON OTHER OCCUMENTS INCLUDING WORK TO BE
PERFORMED BY OTHER CONTRACTORS OR
SUBCONTRACTORS. EACH CONTRACTOR OR
SUBCONTRACTOR SH L1 BE FAMBWR NTH THE
WORK of OTHER CONTRACTORS OR
sOBcomRACTws. WHETHER OR NOT SHOWN ON
THIS DOCUMENT, WHICH IMPACTS THE WORK
IMPACTS THE WORK SHOWN HEREON AND SH 11
COORDINATE SUCH WORK SO AS TO BE IN
COMPLIANCE NTH THE INTENTOF ALLTHE PROJECT
DOCUMENTS.
O
1rv�^ J
z
w
U
V)
St. Vincent
Carmel Hospital
Carmel Pharmacy 797 800
13500 N Meridian Street
REVISION
CHINNING CONTENTS:
ELECTRICAL RISER,
SCHEDULES, AND DETAILS
Subject to compliance with all regulations
of State and Local Codes
City of Camel
�N;1Lv�law�,pMS�
DATE: 09/04/19
SSUE DATE: PROJECT NO.
0426/2019 BSA: 17107
ASCENSION: 30286
DRAWING NO
E600