Loading...
HomeMy WebLinkAbout2. THYSSENKRUPP SUBMITTAL - APPROVEDELEVATOR SUBMITTAL PACKAGE Date Submitted: JUNE 06, 2019 For Project: SPECIFIED LIGHTING TKE Job Number: 140-1200-02B Elevator(s): 1 (SIMPLEX) Located At: 101 CARMEL DRIVE CARMEL, IN 46032 Company (Mail To): PETERSON CONSTRUCTION 7132 ZIONSVILLE ROAD INDIANAPOLIS, IN 46268 GC Phone: Attention: GEORGE BILANSKY PRELIMINARY DRAWINGS FOR APPROVAL INSTRUCTIONS Failure to complete the Contractor Verification Sheet and Approve drawings WILL result in delay of fabrication and shipping of equipment. Q Check ALL hoistway dimensions, elevator travel (floor to floor heights), pit depth, clear over-head, machine room dimensions and entrance wall thickness. Mark-up drawings accordingly, and remit with necessary approval (i.e: approved or approved as noted) to the Local ThyssenKrupp Elevator Office. Q Complete all information on the Contractor Verification Sheet. Q Provide a firm on-site date to the Local ThyssenKrupp Representative. Any previously quoted manufacturing lead-times for material delivery, shall begin the date of receipt by ThyssenKrupp of ALL approvals, confirmations, and a fully executed subcontract agreement. The installation start date cannot be any earlier than the delivery of the material to the site and the completion of all items shown on the Pre-Installation Checklist sent to you in this submittal package. INFORMATION "ALL DEPICTIONS, DIMENSIONS, MEASUREMENTS AND ALL OTHER INFORMATION CONTAINED IN THESE DRAWINGS ARE FOR ILLUSTRATION PURPOSES ONLY. THE CONSTRUCTION MANAGER AND/OR GENERAL CONTRACTOR BEARS FULL RESPONSIBILITY TO PROPERLY BUILD THE NECESSARY HOISTWAYS, CONTROL-ROOMS, AND/OR MACHINE-ROOMS TO ACCOMMODATE THE ELEVATOR EQUIPMENT PURCHASED." IN NO EVENT WILL THYSSENKRUPP ELEVATOR CORPORATION BE LIABLE FOR ANY INCIDENTAL, CONSEQUENTIAL, OR INDIRECT DAMAGES (INCLUDING BUT NOT LIMITED TO, DAMAGES FOR LOSS OF PROFITS, DELAY, BUSINESS INTERRUPTION,) ARISING OUT OF THE USE OF THESE DRAWINGS, THE INABILITY TO USE THESE DRAWINGS (INCLUDING ANY INFORMATION CONTAINED THEREIN), OR ANY TRANSACTIONS RELATED TO THE USE OF THESE DRAWINGS. BECAUSE SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF LIABILITY FOR CONSEQUENTIAL OR INCIDENTAL DAMAGES, THE ABOVE LIMITATION MAY NOT APPLY TO YOU. IN SUCH STATES, THYSSENKRUPP ELEVATOR CORPORATION'S LIABILITY IS LIMITED TO THE GREATEST EXTENT PERMITTED BY LAW. REMITTANCE INFORMATION: PLEASE REMIT ELECTRONIC COPY OF ALL CONFIRMATIONS AND APPROVALS TO: TO: RICK WILHITE EMAIL: PHONE: 317-595-1125 PACKAGE CONTENT: Contractor Verification Sheet Instruction and Information Sheet Approval/Approved Sheet Layout Sheet Entrance Sheet(s) - The enclosed submittals are in compliance with conditions of ThyssenKrupp Elevator's subcontract or supplying and installing materials and or systems for the project referenced above. - Enclosed drawings are for approval purposes only and not to be used for construction. CONTACT INFORMATION: Sales Representative: RICK WILHITE Construction Superintendent: BRAD BOLTON Project Manager: 317-595-1125 317-595-1125 317-595-1125 General Contractor Owner Job-Site Pre-Installation Checklist (See G.C. Site Binder) TKE-Instruction-Information / [Border] TKE-Instruction-Information Email this PDF CONTRACTOR VERIFICATION SHEET ELEVATOR DESIGNATION:FACTORY JOB NUMBER: REQUIRED CAB INFORMATION:REQUIRED POWER CONFIRMATION:REQUIRED ENTRANCE INFORMATION: APPROVED BY:____________________________________________________________ DATE: _______________ FAILURE TO FULLY COMPLETE THIS SHEET MAY RESULT IN DELAY OF SCHEDULE WE REQUIRE THAT THE FOLLOWING POWER INFORMATION BE CONFIRMED: BUILDING POWER: _________________________________ Q CONFIRMED STARTING TYPE: _________________________ Q CORRECTED: VOLTS: _______ PHASE: _______ CYCLES: _______ MAIN EGRESS/ FIRE RECALL @ FLOOR MARKED: DESCRIPTION OF YOUR CAB FEATURES: <VLT><PH><CYC> <MAINEGRESS> FEATURES FOR YOUR FIXTURES: OILVerificationSheet <APPROVALSHEETSIGNATURE><APPROVALSHEETDATE> In an effort to meet your expectations concerning schedule for the project, we are requesting material delivery/start dates based on the availability or anticipated completion of the items listed in the thyssenkrupp site binder. Note: Prior to the delivery of material and the start of installation, all items on the pre start check list inside the thyssenkrupp elevator site binder must be completed. Requested Elevator Material Delivery/Start Date: ____ / ____ / _____ (Delivery of all remaining material, less any early shipment) The General Contractor agrees to assume responsibility of the equipment the day of arrival from the factory on date mentioned above. Adequate ingress and egress to this area must also be provided along with a dumpster or area for disposing of packaging material. Any relocation of the equipment as directed by the contractor/owner after its initial delivery will be at others (not thyssenkrupp elevators) expense. If the site conditions are not in place at the time of elevator delivery, the equipment will be stored per the rates established in the contract and the thyssenkrupp elevator proposal. At such time the site becomes ready for delivery/starting the elevator installation, thyssenkrupp will need payment of any outstanding invoices inclusive of storage costs accrued before delivery/mobilization and in the thyssenkrupp elevator proposal for storage fees. EMERGENCY POWER VERIFICATION: MATERIAL RELEASE FORM: <MNT><DAY><YR> Q CUSTOMER APPROVAL BOX (THESE ITEMS MUST BE CONFIRMED BEFORE THE ELEVATOR WILL BE MANUFACTURED) CONFIRMED AS SHOWN ON SECTION VIEW CORRECTED: _________________________ CONFIRMED AS SHOWN ON SECTION VIEW CORRECTED: _________________________ CONFIRMED AS SHOWN ON SECTION VIEW CORRECTED: _________________________ CLEAR OVERHEAD: HOISTWAY SIZE: HAND OF DOOR: PIT DEPTH: FIRE SERVICE LOCATION: PRIMARY SERVICE AT FLOOR: ___________ ALTERNATE SERVIC E AT FLOOR: __________ CONFIRMED AS SHOWN ON SECTION VIEW CORRECTED: _________________________ CONFIRMED AS SHOWN ON SECTION VIEW CORRECTED: _________________________ NET TRAVEL:Q Q Q QQ <NETTRAVELCORRECTED> <PITDEPTHCORRECTED> <DOORHANDCORRECTED> <CLROVERHEADCORRECTED> <HWYSIZECORRECTED> QQ Q Q QQ 1 208 VOLTS A.C., 3 PHASE, 60 CYCLES SOLID STATE STARTING CAB TYPE:APPLIED PANEL REVEALS:#4 STAINLESS STEEL CAB CEILING:6-9 LED FIXTURES IN METAL PAN CEILING CEILING FINISH: #4 STAINLESS STEEL CAB DOOR:#4 STAINLESS STEEL CAR SILLS: ALUMINUM CAB HANDRAIL(S):(3) 1 1/2" CYLINDRICAL HANDRAIL(S) FINISH: #4 STAINLESS STEEL CAB PROTECTION: PAD BUTTONS PROVIDED. (1) PADS CAB FLOORING: FINISH FLOOR WEIGHT (3/8" MAX. THICKNESS) = 111 LBS. BY OTHERS CAB PANEL COLOR:<NONSTDPLAM> IS EMERGENCY OPERATION ON BUILDING GENERATOR POWER REQUIRED? YES NO IF YES, HOW MANY ELEVATORS WILL BE CAPABLE OF RUNNING AT THE SAME TIME WHILE ON EMERGENCY POWER ? _________ IF NOT, IS TKE BATTERY BACK-UP OPERATION NECESSARY? YES NO FOR MR AND CR VERSIONS OF CONTROLLERS ELECTRICAL CONTRACTOR MUST PROVIDE: - AUXILIARY CONTACTS IN THE DISCONNECT. - IF EMERGENCY POWER IS PROVIDED, THEN EPNP CONTACTS FOR CO NTROLLER ARE REQUIRED. NOTE: IF CONTROLLER IS JAMB MOUNTED THEN THE AUXILIARY CONTACTS ARE INCLUDED WITH THE DISCONNECT IN THE CONTROLLER. SEE LOCAL Thyssenkrupp FIELD REPRESENTATIVE FOR MORE INFORMATION. <QTYELEV> Q Q Q Q FLOORING TYPE: Q VCT Q CARPET Q OTHER, COMPLETE BELOW: 1. FINISH FLOOR HEIGHT (INCLUDES THE HEIGHT OF THE SETTING BED AND FLOORING) IS _______________________. 2. CONTACT LOCAL BRANCH FOR LOCAL MAXIMUM FLOORING HEIGHT LIMITS. * IF FINISHES ARE NOT FROM TKE COLOR BROCHURE, ADDITIONAL CHARGES WILL APPLY. <FLOORINGWEIGHT> Ƒ PLEASE REVIEW ALL BOX DIMENSIONS ( 0'-0" ) AND ALL DATA CHECK BOXES INDICATED BY . DISTANCE OF MACHINE ROOM TO HOISTWAY. MACHINE ROOM WIDTH. MACHINE ROOM LENGTH. DOOR SWING. DOOR LOCATION. LOCATION OF DISCONNECTS. REVIEW ITEMS IN MACHINE ROOM: Q Q Q Q Q Q Q SUMP PIT LOCATIONENTRANCE WALL DETAIL MASONRY WALL TYPE FRAME DRYWALL TYPE FRAME Elevator Entrance Frame Elevator Entrance Frame Elevator Entrance Frame"X""X""X" * X = Wall thickness COMBINATION DRYWALL/ MASONARY TYPE FRAMEŹŹŹŹŹŹŹŹŹ 1 FLOOR MARKING:WALL TYPE:WALL THICKNESS (X):ENTRANCE DOOR FINISH:ENTRANCE FRAME FINISH: 2 <WALLTYPE><WALLTHK>#4 STAINLESS STEEL #4 STAINLESS STEEL 1 <WALLTYPE><WALLTHK>#4 STAINLESS STEEL #4 STAINLESS STEEL B <WALLTYPE><WALLTHK>#4 STAINLESS STEEL #4 STAINLESS STEEL PUSH BUTTON ILLUMINATION COLOR: BLUE 1' 0 - 5/8" 1' 0 - 5/8" 1' 0 - 5/8" 3 STAIRWELLSPLASTIC LAMINATED Combo Combo Combo 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 X LVT - - FORMICA BELOW - LVT 3/8" TOTAL FORMICA TERRIL PLEX FINISH ( 2297-PX ) 5mm THICK = .19685 " FOR PANELS IN CAB 07/30/2019 PIT PLANELEVATION VIEW AA THIS DRAWING AND ALL INFORMATION THEREON IS THE PROPRIETARY PROPERTY OF THYSSENKRUPP ELEVATOR AND MUST NOT BE MADE PUBLIC OR COPIED. THIS DRAWING IS LOANED SUBJECT TO RETURN ON DEMAND AND IS NOT TO BE USED DIRECTLY OR INDIRECTLY, IN ANY MANNER DETRIMENTAL TO THE INTEREST OF THYSSENKRUPP ELEVATOR. FOR: SPECIFIED LIGHTING ADDRESS: 101 CARMEL DRIVE CITY: CARMEL, IN 46032 4 OF 7 DATE A SHEETJOB NUMBER 6/6/2019 REVDRAWN RW 140-1200-02B FRONT FRONT HOISTWAY PLAN SECTION[RH-CO] - STDHYD OF TARGET HOLES = TARGET HOLE GUIDE RAILSTO OF TARGET EDGE OF PLATFORM FACE OF RAIL 1 1/2" 1 13/16" S S SS 7'-6 5/8"SŹ ŹŹŹ ŹF2 F1 OMEGA RAIL Ź ŹŹSUMP PIT SIZE TO BE DETERMINED BY GENERAL CONTRACTOR 5" PIT LADDER ŹŹ ŹƔ LIGHTING (MINIMUM 200LUX/19FT. CANDLES) AND SWITCH, CONVENIENCE OUTLETS WITH GFCI PROTECTION PER NEC. LIGHTING IS REQUIRED AT THE PIT LEVEL. Ɣ A LIGHT SWITCH LOCATED 4'-0" ABOVE BOTTOM LANDING NEXT TO THE TOP RUNG OF THE LADDER. Ɣ A PLUMB AND PROPERLY VENTED HOISTWAY BUILT ACCORDING TO CODE AND SIZES SHOWN. Ɣ ADEQUATE SUPPORT FOR JACK, GUIDE RAIL BRACKETS, AND BUFFERS (FOR REACTIONS SHOWN) Ɣ HOISTWAY BARRICADES AND ALL CUTTING AND PATCHING TO INSTALL HOISTWAY ENTRANCES, SILLS, HALL FIXTURES, OIL, AND ELECTRIC LINES. Ɣ ENTRANCE WALL WITH LINTELS MUST BE PROVIDED AFTER ENTRANCE FRAMES ARE SET OR LEAVE A ROUGH OPENING 15" WIDER AND 15" HIGHER THAN THE FRAME OPENING. SEE INSTALLATION PROCEDURES FOR FRAME-TO-WALL INTERFACE DETAILS TO ENSURE CONFORMANCE WITH THE LABELED ENTRANCE INTERFACE CONSTRUCTION. Ɣ PIT LADDER PER CAR (ACCORDING TO CODE) NOTE: MUST BE CLEAR OF ALL ELEVATOR EQUIPMENT. Ɣ PIT LADDER LOCATION TO BE CONFIRMED BY THYSSENKRUPP ELEVATOR SUPERINTENDENT. Ɣ POCKETS IN CORRIDOR WALL FOR HALL FIXTURES. NOTE: MUST BE LOCATED AS DIRECTED BY ELEVATOR CONTRACTOR Ɣ SMOKE SENSORS (AS REQUIRED) Ɣ ELEVATOR MEETS ASME A17.1 2007 CODE. Ɣ AN 8" X 8" BLOCK OUT IS REQUIRED IN THE HOISTWAY WALL. LOCATION TO BE DETERMINED BY THYSSENKRUPP ELEVATOR SUPERINTENDENT. Ɣ SUMP PIT OR DRAIN AS REQUIRED BY LOCAL CODE BY GENERAL CONTRACTOR. BY OTHERS THE FOLLOWING CONDITIONS MUST BE MET BEFORE INSTALLATION IS COMPLETED AND ARE NOT INCLUDED IN THE ELEVATOR CONTRACT GENERAL DATA 7'-8" BETWEEN CENTERLINE OF JACKS 1'-0"4'-2"4'-2"3'-0 3/4"2 3/4"2 3/4" 8'-4" HOISTWAY WIDTH 7'-10 1/2" BACK TO BACK RAILS 7'-3" DISTANCE BETWEEN RAILS 5'-9"HOISTWAY DEPTHSRAILSSJACKSS CAR 3'-6" CLR. OPENING3'-11" 6'-0" ROUGH OPENING @ TYP. FLR. 2'-4" 8"8" 2" 6'-8" MIN. CLEAR INSIDE 6 1/4"1 3/4"5'-1"PLATFORM DEPTH4'-3"MIN. CLEAR INSIDE2" 7'-0" PLATFORM WIDTH4'-0 3/4" SAFETY BEAM 2 1/2"OIL LINE2"4'-0"REFUGE SPACE8'-8" TOP OF CABIN FULL TOP OVER TRAVEL12'-8"CLEAR OVERHEAD7'-4"CEILING HEIGHT7'-11"OVERALL CAB HEIGHT9'-5"UNDER CROSSHEAD22'-0"NET TRAVEL8'-3" ROUGH OPENING HEIGHT7'-0" CLEAR OPENING HEIGHT4'-0"PIT DEPTH4'-0" MIN.PIT LADDER@ FLOORS B,1,2REAR OF HOISTWAYFRONT OF HOISTWAY11" N (4") S JACK (TYP) SELECTORƔ SAFETY BEAM REQUIRED PER OSHA 1926 502 PROVIDED AND INSTALLED BY OTHERS, AS DIRECTED BY THYSSENKRUPP FIELD OFFICE DESIGN LOAD = (STATIC, NOT IMPACT)5,000 LBS 3" HYDRAULIC ELEVATOR CONTRACT DATA TYPE:ELEVATOR DESIGNATION: NOTE A: OIL PIPE LINES AND FITTINGS SHALL BE PROPERLY SUPPORTED TO RELIEVE STRAIN. NOTE B: ALL REACTIONS INCLUDE ALLOWANCE FOR IMPACT. NOTE C: THYSSENKRUPP ELEVATOR TO BE NOTIFIED OF ANY CHANGE TO ELEVATOR HOISTWAY OR MACHINE ROOM DESIGN. NOTE D: ELEVATOR DESIGN & FABRICATION BASED ON ESTIMATED CAB WEIGHT SHOWN. LAYOUT APPROVAL WILL BE CONSTRUED AS FINAL CAR WEIGHT, UNLESS OTHERWISE NOTIFIED. SPEED:CAPACITY: CAR ENCLOSURE:DOOR HAND: PLATFORM THICKNESS:FINISHED FLOOR: CAR WEIGHT: TELEPHONE:PIT LADDER: POWER UNIT:POWER SUPPLY: STARTING:OPERATION: GLOJ:GLOPU: OVER TRAVEL:BOTTOM:TOP: JACK MODEL:PLUNGER WEIGHT: PLUNGER WALL THK: BETWEEN PIT FLOOR & CAR BOLSTER ON COMPRESSED BUFFER: PLUNGER O.D: NET AREA: BOTTOM CAR RUNBY: CAR BUFFER STROKE:EST. WORKING PRESS: (QTY) SPRING(S) #:TOTAL SPRING(S) CAPACITY: CAR FRAME S = I = A =A = I = S =S = I = R = RAIL FORCES F1 F2 SEISMIC RAIL FORCES ZONE: CAR STATION FEATURES: CAR RIDING LANTERN: PUSH BUTTON MARKINGS: F1 =F2 = FORMED CROSSHEAD FORMED BOLSTER FORMED STILE UPPER:LOWER: UPPER:LOWER: JACK REACTION (EA.):CAR BUFFER REACTION: PLUNGER LENGTH:UPPER:LOWER: CYLINDER LENGTH:CYLINDER O.D:WALL THK: endura 25 A 1 150 FPM UP / 150 FPM DOWN 2,500 LBS TKAP RIGHT FRONT 3 3/8"BY OTHERS 2,491.00 LBS BY ELEVATOR COMPANY BY ELEVATOR COMPANY EP-125, 30 HP 208 V 3 Phase 60 Cycles SOLID STATE STARTING TAC32 4,991 LBS 5,586 LBS 9"8 1/2" 2.5T TWIN/TELE 595.00 LBS 13'-7 5/8"13'-2 7/16" 0.375"0.25" 2.5"3.75" 13'-2 7/8"5"1/4" 15.904 SQ.IN. 6" 2 1/2"386 PSI (1) 780CB1 15,223 LBS 3.27 9.82 1.85 7GA x 6" x 2 1/2" 5.67 23.39 2.40 7GA x 8 1/4" x 2 3/4" 1.38 2.17 1.01 10GA 405 LBS 231 LBS N/A N/A Signa 4 Fixtures, T2 Buttons, Alarm Button, Telephone, Position Indicator B, 1, 2 Car Operating Panel 2'-3 7/8" 5,908.00 LBS 14,632.00 LBS "PLEASE REFERENCE ASME A17.1 (2.2.2) FOR SUMP PIT REQUIREMENTS" PLAN HWY FRONT 5 OF 7 140-1200-02B 6/6/2019RWA DATEJOB NUMBER SHEETDRAWNREV THIS DRAWING AND ALL INFORMATION THEREON IS THE PROPRIETARY PROPERTY OF THYSSENKRUPP ELEVATOR AND MUST NOT BE MADE PUBLIC OR COPIED. THIS DRAWING IS LOANED SUBJECT TO RETURN ON DEMAND AND IS NOT TO BE USED DIRECTLY OR INDIRECTLY, IN ANY MANNER DETRIMENTAL TO THE INTEREST OF THYSSENKRUPP ELEVATOR. FOR: SPECIFIED LIGHTING ADDRESS: 101 CARMEL DRIVE CITY: CARMEL, IN 46032 FOR ELEVATOR:1 IF A CUT STARTER RAIL IS CALLED FOR IN THE STACK, CONFIRM THE NUMBER OF SPLICES PRIOR TO CUTTING 5'-9"HOISTWAY DEPTH8'-4" HOISTWAY WIDTH 4'-0 3/4"³WHERE DISTANCE BETWEEN FLOORS EXCEEDS THE MAXIMUM BRACKET SPAN, BRACKET SUPPORT MUST BE PROVIDED MIDWAY. BRACKET SUPPORT WILL NEED TO BE SUPPLIED BY OTHERS TO ALLOW FOR RAIL ATTACHMENT. INSIDE SUPPORT SHALL NOT BE RECESSED BEHIND WALL SYSTEM AND SHALL NOT BE PROUD BY MORE THAN 1/4´ AT ANY POINT. COORDINATE WITH TKE SUPPORT/OPERATIONS MANAGER´ SRAILS6'-0" ROUGH OPENING WIDTH 2"4'-0 3/4"SAFETY BEAM8'-3" ROUGH OPENING HEIGHT BRACKET LOCATION DIMENSIONS RAIL SECTION DIMENSIONS 4'-0" PIT DEPTH 12'-8" CLEAR OVERHEAD FRONT OF HOISTWAY REAR OF HOISTWAY 22'-0" NET TRAVEL RAIL STACK SECTION VIEW RAILS AND BRACKETS - TOTAL QUANTITY RAILS BRACKETS QTY: SPAN: (5) 16 FT SPLICES:4 LEFT HAND RIGHT HAND 4 4 8"8" 6'-5 1/2" RAIL 16'-0" RAIL 16'-0" RAIL 11'-6"1'-3"10'-8"1'-3"8'-10"1'-3"2'-9" B12 CAR RAIL LINE LENGTH QUANTITY (6) LENGTH QUANTITY 16'-0"4 6'-5 1/2"2 FLOOR TO FLOOR TRAVEL FLOOR TO FLOOR TRAVEL 1-2 11'-11" B-1 10'-1" NET TRAVEL 22'-0" CAR RAIL LINE BRACKETS AND INSERT LOCATIONS REQ. AT : LOCATION DESCRIPTION 15'-9"MAX. UNSUPPORTED RAIL BRACKET SPACING 11'-6"ABOVE TOP FLOOR 1'-3"BELOW B,1-2 TYPICAL SURFACE MOUNTING DETAILS AT ALL FLOOR LOCATIONS TYP TYP TYP 22" BRACKET O.A. 16" 30" DRYWALL INSERT. BOLT TO WO OD BEAM SUPPORT (INSERT) PROVIDED BY TKE, INSTALLED BY G.C. MOUNT FLUSH WITH WALL. 30 X 6" STEEL PLATE WELDED TO TUBE STEEL PROVIDED AND INSTALLED BY G.C. MO UNT FLUSH WITH WALL. 30 X 6" STEEL PLATE WELDED TO TUBE STEEL PROVIDED AND INSTALLED BY G.C. MOUNT FLUSH WITH WALL. 30 X 6" STEEL PLATE WELDED TO STEEL PROVIDED AND INSTALLED BY G.C. MOUNT FLUSH WITH WALL. INSERT INSTALLED BY G .C. MOUNT FLUSH WITH WALL & GROUT SOLID ALL AROUND. INSERT INSTALLED BY G .C. MOUNT FLUSH WITH WALL & GROUT SOLID ALL AROUND. 22" BRACKET O.A.22" BRACKET O.A.22" BRACKET O.A.22" BRACKET O.A.22" BRACKET O.A. 16"16" MACHINE ROOM PLAN VIEW MINIMUM MACHINE ROOM CEILING HEIGHT = 7'-6" 6 OF 7 140-1200-02B 6/6/2019RWA DATEJOB NUMBER SHEETDRAWNREV THIS DRAWING AND ALL INFORMATION THEREON IS THE PROPRIETARY PROPERTY OF THYSSENKRUPP ELEVATOR AND MUST NOT BE MADE PUBLIC OR COPIED. THIS DRAWING IS LOANED SUBJECT TO RETURN ON DEMAND AND IS NOT TO BE USED DIRECTLY OR INDIRECTLY, IN ANY MANNER DETRIMENTAL TO THE INTEREST OF THYSSENKRUPP ELEVATOR. FOR: SPECIFIED LIGHTING ADDRESS: 101 CARMEL DRIVE CITY: CARMEL, IN 46032 3'-6" CLEARANCE 1'-6"ELEV: 1 3'-6"CLEARANCEELEVATOR DESIGNATOR: 16'-6"MACHINE ROOM DEPTH5'-0" MACHINE ROOM WIDTH 3'-6" DOOR WIDTH Ɣ BASED ON THIS INFORMATION, WE REQUIRE ELECTRICAL FEEDERS AND FUSED DISCONNECTS SIZED PER THE FOLLOWING INFORMATION LISTED IN THE POWER FEEDER TABLE. Ɣ GENERAL CONTRACTOR MUST FORWARD POWER REQUIREMENTS TO THE ELECTRICAL CONTRACTOR. NOTE: ALSO, A FOURTH WIRE OF SAME SIZE AS THREE PHASE WIRES IS REQUIRED FOR GROUNDING PURPOSES TO MINIMIZE ELECTRICAL NOISE INTERFERENCE. THE GROUNDING WIRE MUST BE CONNECTED TO THE BUILDING ELECTRICAL SYSTEM GROUND. Ɣ A MEANS TO AUTOMATICALLY DISCONNECT THE MAIN LINE PER POWER SUPPLY TO THE ELEVATOR PRIOR TO THE APPLICATION OF WATER IN THE ELEVATOR HOISTWAY WILL BE FURNISHED BY THE ELECTRICAL CONTRACTOR THIS MEANS SHALL NOT BE SELF RESETTING. Ɣ DEDICATED 120 VOLT, 15 AMP SERVICE, ALONG WITH TELEPHONE CIRCUIT WHEN REQUIRED TO TERMINALS OF EACH REQUIRED CONTROLLER (AS LOCATED ON PLAN VIEW) FOR THE FOLLOWING: - CAR LIGHT AND ALARM CIRCUIT WITH GFCI PROTECTION PER NEC. - GROUP CONTROL WHEN REQUIRED. NOTE: IF STANDBY POWER IS SUPPLIED TO ELEVATOR, CAR LIGHT AND ALARM CIRCUIT AND GROUP CONTROL SERVICE MUST BE STANDBY POWER BACKED. Ɣ PIPING WITH PULL STRING FROM HOISTWAY TO ELEVATOR MONITORING PANELS BY OTHERS. Ɣ PROVIDE A TRANSFER SWITCH CONTACT THAT IS CLOSED WHEN NORMAL POWER IS PRESENT AND IS OPEN ON EMERGENCY POWER. Ɣ PROVIDE A POWER TRANSFER WARNING CONTACT THAT CLOSES 20 SECONDS PRIOR TO TRANSFER IN EITHER DIRECTION AND IT OPENS WHEN TRANSFER IS COMPLETE. Ɣ TOTAL FULL LOAD UP SPEED AMPS IS BASED ON 100% OF ELEVATOR CAPACITY, THE VALUE NEEDED FOR EMERGENCY POWER SIZING. Ɣ THE HYDRAULIC MOTORS ARE RATED FOR INTERMITTENT DUTY (SEC. 620-13 AND 430-33). BRANCH CIRCUIT CONDUCTORS CAN BE SIZED FOR AN AMPACITY 90% OF THE MOTORS NAMEPLATE RATING AS DETERMINED BY (SEC. 430-22 [E]) Ɣ LIGHT SWITCH, LIGHTING AND CONVENIENCE OUTLET WITH GFCI PROTECTION PER ASME/CSA B44. Ɣ AN ENCLOSED MACHINE AREA (ACCORDING TO CODE) WITH ADEQUATE LIGHT, HEAT AND VENTILATION (MIN. 50ƒF., MAX. 90ƒF. WITH NON-CONDENSING HUMIDITY OF 10-90%) AND SEALED CONCRETE FLOOR SLAB SURFACE. NOTE: MUST PROVIDE ADEQUATE DOOR SIZE TO ALLOW INSTALLATION OF EQUIPMENT, OR LEAVE WALL OUT UNTIL EQUIPMENT IS IN PLACE. BY OTHERS THE FOLLOWING CONDITIONS MUST BE MET BEFORE INSTALLATION IS COMPLETED AND ARE NOT INCLUDED IN THE ELEVATOR CONTRACT GENERAL DATA ELECTRICAL DATA ELEVATOR DESIGNATOR POWER UNIT WIDTH x DEPTH TANK HEIGHT OIL LINE HEIGHT OIL LINE OUTLET TANK WEIGHT WITH OIL CONTROLLER HEIGHT HYDRAULIC FLUID REQ. POWER UNIT AND CONTROLLER INFORMATION POWER SUPPLY HORSE POWER STARTING A.C. AMPS TOTAL FULL LOAD UP SPEED MOTOR A.C. AMPS RATED A.C. AMPS SHORT CIRCUIT CURRENT RATINGS (AT 600V OR LESS) POWER FEEDER 1 3'-3 3/4" X 2'-10"3'-8 1/8"3'-1 7/8"2"2,250 4'-5"106 208 30 283 136 94.3 5,000 AMPS Ɣ BATTERY OPERATION LOWERING IS PROVIDED, A MECHANICAL AUXILIARY CONTACT SHALL BE INSTALLED ON THE DISCONNECT SWITCH FOR EACH CAR. THE AUXILIARY SHALL BE CONFIGURED AS SPST AT 1A 110VC (MIN). THE AUXILIARY CONTACT SHALL BE OPEN WHEN THE DISCONNECT SWITCH IS IN THE OPEN POSITION. IF A SHUNT TRIP CIRCUIT BREAKER IS PROVIDED, AN AUXILIARY CONTACT SHALL BE INSTALLED ON THE CIRCUIT BREAKER. Ɣ HEAT LOAD IS BASED ON CAR LOADED AT 40% CAPACITY RUNNING AT AN AVERAGE 35% DUTY CYCLE. HEAT LOAD IN MACHINE ROOM DUE TO ELEVATOR EQUIPMENT = 14098 BTU/HR ADJACENT AT FLOOR 1 Ɣ PRIMARY FIRE SERVICE LOCATED AT FLOOR: Ɣ ALTERNATE FIRE SERVICE LOCATION AT FLOOR: 1 ADA PHONE PROVIDED N ELEV.OIL LINE SIZE NOTE 1 2" OIL LINE FROM TANK TO 2" SHUTOFF VALVE. 2" SCH 40 BLACK PIPE, ASTM A-53, TYPE (E) OR (S), GRADE (B) OR EQUIVALENT TO JACK 8'-4" 9'-0"5'-9" ENTRANCE LEFT SIDE VIEWLOBBY SIDEENTRANCE ELEVATION VIEW AT TYPICAL FLOORÎENTRANCE PLAN VIEW LOBBY SIDE A D R2 R1ƔƔ THIS DRAWING AND ALL INFORMATION THEREON IS THE PROPRIETARY PROPERTY OF THYSSENKRUPP ELEVATOR AND MUST NOT BE MADE PUBLIC OR COPIED. THIS DRAWING IS LOANED SUBJECT TO RETURN ON DEMAND AND IS NOT TO BE USED DIRECTLY OR INDIRECTLY, IN ANY MANNER DETRIMENTAL TO THE INTEREST OF THYSSENKRUPP ELEVATOR. FOR: SPECIFIED LIGHTING ADDRESS: 101 CARMEL DRIVE CITY: CARMEL, IN 46032 7 OF 7 DATE A SHEETJOB NUMBER 6/6/2019 REVDRAWN RW 140-1200-02B FEATURES OF ENTRANCES DATA SILL MAXIMUM WHEEL LOADS 625 LBS KEYHOLES TO BE INCLUDED THIS FRAME HAS A WARNOCK HERSEY LABEL OF 2 HOURS DUST COVERS NOT INCLUDED FEATURES OF YOUR ENTRANCES FEATURES FINISH LOCATION DOOR OPEN STRUT BUMPERS:PROVIDED @B,1,2 KICKPLATES:__________@B,1,2 BINDERS:__________@B,1,2 SILL FINISH:ALUMINUM @B,1,2 TOTAL WEIGHT ELEVATOR 1 ELEVATOR CAB AND HALL DOORS 327 LBS NOTE "A": 8" MINIMUM STRUCTURAL SUPPORT FOR SILL INSTALLATION ENTRANCE CHART M721 ENTRANCE: CENTER OPENING AND 1 SPEED = FRAME OPENING + 1'-3" 2 SPEED = FRAME OPENING + 1'-5" ENTRANCE TYPE : M721 FOR ELEVATOR 1 1 SPEED RIGHT HAND FRONT ENTRANCE FOR ELEVATOR 1 FOR ELEVATOR: 1 R2 229 R1 566 DOOR REACTION CASE 1 SEE NOTE "A"5'-0"C/L 4.10.5 28 CFR PART 36CLEAR OPENING HEIGHT (REFER TO DOOR SCHEDULE)CLEAR OPENING HEIGHT + 2" = OVERALL FRAME HEIGHT2"0 3/16"MINIMUM FLOOR TO FLOOR HEIGHT = "SEE ENTRANCE CHART"CLEAR OPENING WIDTH REFER TO DOOR SCHEDULE 2" FRAME 2" FRAME ACTUAL WALL SIZE 0 3/4" ELEVATOR:1 FRONT ENTRANCE SCHEDULE FLOOR WALL TYPE WALL SIZE ACTUAL OA. FRAME "B" DIM. PLEASE REFERENCE THE RAIL STACK SHEET OF THIS PACKAGE FOR BUILDING LANDING MATRIX ENTRANCE DIMS. DIM "B" 2 7'-0" H X 3'-6" W TBD TBD TBD 1 7'-0" H X 3'-6" W TBD TBD TBD B 7'-0" H X 3'-6" W TBD TBD TBD FRONT ENTRANCE HALL FIXTURES ITEM DESCRIPTION FLOOR A HALL STATION TYPICAL D HALL POSITION INDICATOR @1 HALL FIXTURES ARE FOR REPRESENTATION ONLY. FOR ACTUAL LOCATION OF POCKETS FOR HALL FIXTURES, CONTACT ELEVATOR CONTRACTOR. 6'-0" ROUGH OPENING WIDTH 8'-3"ROUGH OPENING HEIGHT NOTES: GENERAL CONTRACTOR RESPONSIBLE FOR HOISTWAY REINFORCING AT FLOOR SLAB BEFORE INSTALLATION OF ENTRANCE FRAMES. MINIMUM OF 4" HIGH X 8" WIDE REINFORCED CONCRETE, REINFORCED OF OPENING REQUIRED FOR ANCHORING SILL SUPPORT ASSEMBLY, REINFORCING TO BE LOCATED WITH RESPECT TO REACTION POINTS, REFERENCE INSTALLATION DRAWINGS ARE AVAILABLE UPON REQUEST. REACTIONS (LBS.) DUE TO LOADS ON DOOR PANELS, APPROX. HORIZONTAL LOADS AND LOCATION TO BUILDINGS SHOWN PER ASME A17.1 PART II, THE SPECIFIED LOADS ARE CONSIDERED IMPACTED. 2" BELOW EACH FLOOR5'-3"2'-1 1/2"