HomeMy WebLinkAbout2. THYSSENKRUPP SUBMITTAL - APPROVEDELEVATOR SUBMITTAL PACKAGE
Date Submitted: JUNE 06, 2019
For Project:
SPECIFIED LIGHTING
TKE Job Number: 140-1200-02B
Elevator(s): 1 (SIMPLEX)
Located At:
101 CARMEL DRIVE
CARMEL, IN 46032
Company (Mail To):
PETERSON CONSTRUCTION
7132 ZIONSVILLE ROAD
INDIANAPOLIS, IN 46268
GC Phone:
Attention:
GEORGE BILANSKY
PRELIMINARY
DRAWINGS
FOR APPROVAL
INSTRUCTIONS
Failure to complete the Contractor Verification Sheet and Approve drawings WILL result in delay of fabrication and shipping of equipment.
Q Check ALL hoistway dimensions, elevator travel (floor to floor heights), pit depth, clear over-head, machine room dimensions and entrance wall thickness. Mark-up drawings accordingly, and remit with necessary approval (i.e: approved or approved as noted) to
the Local ThyssenKrupp Elevator Office.
Q Complete all information on the Contractor Verification Sheet.
Q Provide a firm on-site date to the Local ThyssenKrupp Representative.
Any previously quoted manufacturing lead-times for material delivery, shall begin the date of receipt by ThyssenKrupp of ALL approvals, confirmations, and a fully executed subcontract agreement. The installation start date cannot be any
earlier than the delivery of the material to the site and the completion of all items shown on the Pre-Installation Checklist sent to you in this submittal package.
INFORMATION
"ALL DEPICTIONS, DIMENSIONS, MEASUREMENTS AND ALL OTHER INFORMATION CONTAINED IN THESE DRAWINGS ARE FOR ILLUSTRATION PURPOSES ONLY. THE CONSTRUCTION MANAGER AND/OR GENERAL CONTRACTOR BEARS FULL
RESPONSIBILITY TO PROPERLY BUILD THE NECESSARY HOISTWAYS, CONTROL-ROOMS, AND/OR MACHINE-ROOMS TO ACCOMMODATE THE ELEVATOR EQUIPMENT PURCHASED." IN NO EVENT WILL THYSSENKRUPP ELEVATOR CORPORATION BE
LIABLE FOR ANY INCIDENTAL, CONSEQUENTIAL, OR INDIRECT DAMAGES (INCLUDING BUT NOT LIMITED TO, DAMAGES FOR LOSS OF PROFITS, DELAY, BUSINESS INTERRUPTION,) ARISING OUT OF THE USE OF THESE DRAWINGS, THE INABILITY TO
USE THESE DRAWINGS (INCLUDING ANY INFORMATION CONTAINED THEREIN), OR ANY TRANSACTIONS RELATED TO THE USE OF THESE DRAWINGS. BECAUSE SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF LIABILITY FOR
CONSEQUENTIAL OR INCIDENTAL DAMAGES, THE ABOVE LIMITATION MAY NOT APPLY TO YOU. IN SUCH STATES, THYSSENKRUPP ELEVATOR CORPORATION'S LIABILITY IS LIMITED TO THE GREATEST EXTENT PERMITTED BY LAW.
REMITTANCE INFORMATION:
PLEASE REMIT ELECTRONIC COPY OF ALL CONFIRMATIONS AND APPROVALS TO:
TO: RICK WILHITE
EMAIL:
PHONE: 317-595-1125
PACKAGE CONTENT:
Contractor Verification Sheet
Instruction and Information Sheet
Approval/Approved Sheet
Layout Sheet
Entrance Sheet(s)
- The enclosed submittals are in compliance with conditions of ThyssenKrupp Elevator's subcontract or supplying and installing materials and or systems for the
project referenced above.
- Enclosed drawings are for approval purposes only and not to be used for construction.
CONTACT INFORMATION:
Sales Representative: RICK WILHITE
Construction Superintendent: BRAD BOLTON
Project Manager:
317-595-1125
317-595-1125
317-595-1125
General Contractor Owner Job-Site Pre-Installation Checklist (See G.C. Site Binder)
TKE-Instruction-Information / [Border] TKE-Instruction-Information
Email this PDF
CONTRACTOR VERIFICATION SHEET
ELEVATOR DESIGNATION:FACTORY JOB NUMBER:
REQUIRED CAB INFORMATION:REQUIRED POWER CONFIRMATION:REQUIRED ENTRANCE INFORMATION:
APPROVED BY:____________________________________________________________ DATE: _______________
FAILURE TO FULLY COMPLETE THIS SHEET MAY RESULT IN DELAY OF SCHEDULE
WE REQUIRE THAT THE FOLLOWING POWER INFORMATION BE CONFIRMED:
BUILDING POWER: _________________________________ Q CONFIRMED
STARTING TYPE: _________________________
Q CORRECTED: VOLTS: _______ PHASE: _______ CYCLES: _______
MAIN EGRESS/ FIRE RECALL @ FLOOR MARKED:
DESCRIPTION OF YOUR CAB FEATURES:
<VLT><PH><CYC>
<MAINEGRESS>
FEATURES FOR YOUR FIXTURES:
OILVerificationSheet
<APPROVALSHEETSIGNATURE><APPROVALSHEETDATE>
In an effort to meet your expectations concerning schedule for the project, we are requesting material
delivery/start dates based on the availability or anticipated completion of the items listed in the thyssenkrupp
site binder.
Note: Prior to the delivery of material and the start of installation, all items on the pre start check list inside
the thyssenkrupp elevator site binder must be completed.
Requested Elevator Material Delivery/Start Date: ____ / ____ / _____
(Delivery of all remaining material, less any early shipment)
The General Contractor agrees to assume responsibility of the equipment the day of arrival from the factory
on date mentioned above. Adequate ingress and egress to this area must also be provided along with a
dumpster or area for disposing of packaging material. Any relocation of the equipment as directed by the
contractor/owner after its initial delivery will be at others
(not thyssenkrupp elevators) expense.
If the site conditions are not in place at the time of elevator delivery, the equipment will be stored per the
rates established in the contract and the thyssenkrupp elevator proposal. At such time the site becomes
ready for delivery/starting the elevator installation, thyssenkrupp will need payment of any outstanding
invoices inclusive of storage costs accrued before delivery/mobilization and in the thyssenkrupp elevator
proposal for storage fees.
EMERGENCY POWER VERIFICATION:
MATERIAL RELEASE FORM:
<MNT><DAY><YR>
Q
CUSTOMER APPROVAL BOX
(THESE ITEMS MUST BE CONFIRMED BEFORE THE ELEVATOR WILL BE MANUFACTURED)
CONFIRMED AS SHOWN ON SECTION VIEW
CORRECTED: _________________________
CONFIRMED AS SHOWN ON SECTION VIEW
CORRECTED: _________________________
CONFIRMED AS SHOWN ON SECTION VIEW
CORRECTED: _________________________
CLEAR
OVERHEAD:
HOISTWAY
SIZE:
HAND OF
DOOR:
PIT
DEPTH:
FIRE SERVICE
LOCATION:
PRIMARY SERVICE AT FLOOR: ___________
ALTERNATE SERVIC E AT FLOOR: __________
CONFIRMED AS SHOWN ON SECTION VIEW
CORRECTED: _________________________
CONFIRMED AS SHOWN ON SECTION VIEW
CORRECTED: _________________________
NET
TRAVEL:Q
Q
Q
QQ
<NETTRAVELCORRECTED>
<PITDEPTHCORRECTED>
<DOORHANDCORRECTED>
<CLROVERHEADCORRECTED>
<HWYSIZECORRECTED>
QQ
Q
Q
QQ
1
208 VOLTS A.C., 3 PHASE, 60 CYCLES
SOLID STATE STARTING
CAB TYPE:APPLIED PANEL
REVEALS:#4 STAINLESS STEEL
CAB CEILING:6-9 LED FIXTURES IN METAL PAN CEILING
CEILING FINISH: #4 STAINLESS STEEL
CAB DOOR:#4 STAINLESS STEEL
CAR SILLS: ALUMINUM
CAB HANDRAIL(S):(3) 1 1/2" CYLINDRICAL
HANDRAIL(S) FINISH: #4 STAINLESS STEEL
CAB PROTECTION: PAD BUTTONS PROVIDED. (1) PADS
CAB FLOORING:
FINISH FLOOR WEIGHT (3/8" MAX. THICKNESS) = 111
LBS. BY OTHERS
CAB PANEL COLOR:<NONSTDPLAM>
IS EMERGENCY OPERATION ON BUILDING GENERATOR POWER REQUIRED?
YES NO
IF YES, HOW MANY ELEVATORS WILL BE CAPABLE OF RUNNING AT THE SAME TIME
WHILE ON EMERGENCY POWER ? _________ IF NOT, IS TKE BATTERY BACK-UP OPERATION NECESSARY?
YES NO
FOR MR AND CR VERSIONS OF CONTROLLERS ELECTRICAL CONTRACTOR MUST PROVIDE:
- AUXILIARY CONTACTS IN THE DISCONNECT.
- IF EMERGENCY POWER IS PROVIDED, THEN EPNP CONTACTS FOR CO NTROLLER ARE REQUIRED.
NOTE: IF CONTROLLER IS JAMB MOUNTED THEN THE AUXILIARY CONTACTS ARE INCLUDED WITH THE
DISCONNECT IN THE CONTROLLER. SEE LOCAL Thyssenkrupp FIELD REPRESENTATIVE FOR MORE
INFORMATION.
<QTYELEV>
Q Q
Q Q
FLOORING TYPE: Q VCT Q CARPET Q OTHER, COMPLETE BELOW:
1. FINISH FLOOR HEIGHT (INCLUDES THE HEIGHT OF THE SETTING BED AND
FLOORING) IS _______________________.
2. CONTACT LOCAL BRANCH FOR LOCAL MAXIMUM FLOORING HEIGHT LIMITS.
* IF FINISHES ARE NOT FROM TKE COLOR BROCHURE, ADDITIONAL CHARGES WILL APPLY.
<FLOORINGWEIGHT>
Ƒ PLEASE REVIEW ALL BOX DIMENSIONS ( 0'-0" ) AND ALL DATA CHECK BOXES INDICATED BY .
DISTANCE OF MACHINE ROOM TO HOISTWAY.
MACHINE ROOM WIDTH.
MACHINE ROOM LENGTH.
DOOR SWING.
DOOR LOCATION.
LOCATION OF DISCONNECTS.
REVIEW ITEMS IN MACHINE ROOM:
Q
Q
Q
Q
Q
Q
Q SUMP PIT LOCATIONENTRANCE WALL DETAIL
MASONRY WALL TYPE FRAME
DRYWALL TYPE FRAME
Elevator
Entrance Frame
Elevator
Entrance Frame
Elevator
Entrance Frame"X""X""X"
* X = Wall thickness
COMBINATION DRYWALL/
MASONARY TYPE FRAMEŹŹŹŹŹŹŹŹŹ 1
FLOOR MARKING:WALL TYPE:WALL THICKNESS (X):ENTRANCE DOOR FINISH:ENTRANCE FRAME FINISH:
2 <WALLTYPE><WALLTHK>#4 STAINLESS STEEL #4 STAINLESS STEEL
1 <WALLTYPE><WALLTHK>#4 STAINLESS STEEL #4 STAINLESS STEEL
B <WALLTYPE><WALLTHK>#4 STAINLESS STEEL #4 STAINLESS STEEL
PUSH BUTTON ILLUMINATION COLOR: BLUE
1' 0 - 5/8"
1' 0 - 5/8"
1' 0 - 5/8"
3 STAIRWELLSPLASTIC LAMINATED
Combo
Combo
Combo
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
X
LVT -
- FORMICA BELOW
- LVT 3/8" TOTAL
FORMICA TERRIL PLEX FINISH
( 2297-PX ) 5mm THICK = .19685 "
FOR PANELS IN CAB
07/30/2019
PIT PLANELEVATION VIEW
AA
THIS DRAWING AND ALL INFORMATION THEREON IS THE PROPRIETARY PROPERTY OF
THYSSENKRUPP ELEVATOR AND MUST NOT BE MADE PUBLIC OR COPIED. THIS DRAWING
IS LOANED SUBJECT TO RETURN ON DEMAND AND IS NOT TO BE USED DIRECTLY OR
INDIRECTLY, IN ANY MANNER DETRIMENTAL TO THE INTEREST OF THYSSENKRUPP ELEVATOR.
FOR: SPECIFIED LIGHTING
ADDRESS: 101 CARMEL DRIVE
CITY: CARMEL, IN 46032 4 OF 7
DATE
A
SHEETJOB NUMBER
6/6/2019
REVDRAWN
RW 140-1200-02B
FRONT
FRONT
HOISTWAY PLAN
SECTION[RH-CO] - STDHYD
OF TARGET HOLES =
TARGET HOLE
GUIDE RAILSTO OF TARGET
EDGE OF PLATFORM
FACE OF RAIL
1 1/2"
1 13/16"
S
S SS 7'-6 5/8"SŹ ŹŹŹ ŹF2
F1
OMEGA RAIL
Ź ŹŹSUMP PIT SIZE TO BE
DETERMINED BY
GENERAL CONTRACTOR
5"
PIT LADDER
ŹŹ ŹƔ LIGHTING (MINIMUM 200LUX/19FT. CANDLES) AND SWITCH, CONVENIENCE OUTLETS WITH GFCI PROTECTION PER NEC. LIGHTING IS
REQUIRED AT THE PIT LEVEL.
Ɣ A LIGHT SWITCH LOCATED 4'-0" ABOVE BOTTOM LANDING NEXT TO THE TOP RUNG OF THE LADDER.
Ɣ A PLUMB AND PROPERLY VENTED HOISTWAY BUILT ACCORDING TO CODE AND SIZES SHOWN.
Ɣ ADEQUATE SUPPORT FOR JACK, GUIDE RAIL BRACKETS, AND BUFFERS (FOR REACTIONS SHOWN)
Ɣ HOISTWAY BARRICADES AND ALL CUTTING AND PATCHING TO INSTALL HOISTWAY ENTRANCES, SILLS, HALL FIXTURES, OIL, AND
ELECTRIC LINES.
Ɣ ENTRANCE WALL WITH LINTELS MUST BE PROVIDED AFTER ENTRANCE FRAMES ARE SET OR LEAVE A ROUGH OPENING 15" WIDER AND
15" HIGHER THAN THE FRAME OPENING. SEE INSTALLATION PROCEDURES FOR FRAME-TO-WALL INTERFACE DETAILS TO ENSURE
CONFORMANCE WITH THE LABELED ENTRANCE INTERFACE CONSTRUCTION.
Ɣ PIT LADDER PER CAR (ACCORDING TO CODE) NOTE: MUST BE CLEAR OF ALL ELEVATOR EQUIPMENT.
Ɣ PIT LADDER LOCATION TO BE CONFIRMED BY THYSSENKRUPP ELEVATOR SUPERINTENDENT.
Ɣ POCKETS IN CORRIDOR WALL FOR HALL FIXTURES.
NOTE: MUST BE LOCATED AS DIRECTED BY ELEVATOR CONTRACTOR
Ɣ SMOKE SENSORS (AS REQUIRED)
Ɣ ELEVATOR MEETS ASME A17.1 2007 CODE.
Ɣ AN 8" X 8" BLOCK OUT IS REQUIRED IN THE HOISTWAY WALL. LOCATION TO BE DETERMINED BY THYSSENKRUPP ELEVATOR
SUPERINTENDENT.
Ɣ SUMP PIT OR DRAIN AS REQUIRED BY LOCAL CODE BY GENERAL CONTRACTOR.
BY OTHERS
THE FOLLOWING CONDITIONS MUST BE MET BEFORE INSTALLATION IS COMPLETED AND ARE NOT INCLUDED IN THE ELEVATOR CONTRACT
GENERAL DATA
7'-8"
BETWEEN CENTERLINE OF JACKS 1'-0"4'-2"4'-2"3'-0 3/4"2 3/4"2 3/4"
8'-4"
HOISTWAY WIDTH
7'-10 1/2"
BACK TO BACK RAILS
7'-3"
DISTANCE BETWEEN RAILS
5'-9"HOISTWAY DEPTHSRAILSSJACKSS CAR
3'-6" CLR. OPENING3'-11"
6'-0" ROUGH
OPENING @ TYP. FLR.
2'-4"
8"8"
2"
6'-8"
MIN. CLEAR INSIDE
6 1/4"1 3/4"5'-1"PLATFORM DEPTH4'-3"MIN. CLEAR INSIDE2"
7'-0"
PLATFORM WIDTH4'-0 3/4"
SAFETY BEAM
2 1/2"OIL LINE2"4'-0"REFUGE SPACE8'-8" TOP OF CABIN FULL TOP OVER TRAVEL12'-8"CLEAR OVERHEAD7'-4"CEILING HEIGHT7'-11"OVERALL CAB HEIGHT9'-5"UNDER CROSSHEAD22'-0"NET TRAVEL8'-3" ROUGH OPENING HEIGHT7'-0" CLEAR OPENING HEIGHT4'-0"PIT DEPTH4'-0" MIN.PIT LADDER@ FLOORS
B,1,2REAR OF HOISTWAYFRONT OF HOISTWAY11"
N
(4") S
JACK (TYP) SELECTORƔ SAFETY BEAM REQUIRED PER OSHA 1926 502 PROVIDED AND INSTALLED BY OTHERS, AS DIRECTED BY THYSSENKRUPP FIELD OFFICE
DESIGN LOAD = (STATIC, NOT IMPACT)5,000 LBS
3"
HYDRAULIC ELEVATOR CONTRACT DATA
TYPE:ELEVATOR DESIGNATION:
NOTE A: OIL PIPE LINES AND FITTINGS SHALL BE PROPERLY SUPPORTED TO RELIEVE STRAIN.
NOTE B: ALL REACTIONS INCLUDE ALLOWANCE FOR IMPACT.
NOTE C: THYSSENKRUPP ELEVATOR TO BE NOTIFIED OF ANY CHANGE TO ELEVATOR
HOISTWAY OR MACHINE ROOM DESIGN.
NOTE D: ELEVATOR DESIGN & FABRICATION BASED ON ESTIMATED CAB WEIGHT SHOWN.
LAYOUT APPROVAL WILL BE CONSTRUED AS FINAL CAR WEIGHT, UNLESS OTHERWISE NOTIFIED.
SPEED:CAPACITY:
CAR ENCLOSURE:DOOR HAND:
PLATFORM THICKNESS:FINISHED FLOOR:
CAR WEIGHT:
TELEPHONE:PIT LADDER:
POWER UNIT:POWER SUPPLY:
STARTING:OPERATION:
GLOJ:GLOPU:
OVER TRAVEL:BOTTOM:TOP:
JACK MODEL:PLUNGER WEIGHT:
PLUNGER WALL THK:
BETWEEN PIT FLOOR &
CAR BOLSTER ON
COMPRESSED BUFFER:
PLUNGER O.D:
NET AREA:
BOTTOM CAR RUNBY:
CAR BUFFER STROKE:EST. WORKING PRESS:
(QTY) SPRING(S) #:TOTAL SPRING(S) CAPACITY:
CAR
FRAME
S =
I =
A =A =
I =
S =S =
I =
R =
RAIL FORCES F1 F2 SEISMIC RAIL FORCES ZONE:
CAR STATION FEATURES:
CAR RIDING LANTERN:
PUSH BUTTON MARKINGS:
F1 =F2 =
FORMED
CROSSHEAD
FORMED
BOLSTER
FORMED
STILE
UPPER:LOWER:
UPPER:LOWER:
JACK REACTION (EA.):CAR BUFFER REACTION:
PLUNGER LENGTH:UPPER:LOWER:
CYLINDER LENGTH:CYLINDER O.D:WALL THK:
endura 25 A 1
150 FPM UP / 150 FPM DOWN 2,500 LBS
TKAP RIGHT FRONT
3 3/8"BY OTHERS
2,491.00 LBS
BY ELEVATOR COMPANY BY ELEVATOR COMPANY
EP-125, 30 HP 208 V 3 Phase 60 Cycles
SOLID STATE STARTING TAC32
4,991 LBS 5,586 LBS
9"8 1/2"
2.5T TWIN/TELE 595.00 LBS
13'-7 5/8"13'-2 7/16"
0.375"0.25"
2.5"3.75"
13'-2 7/8"5"1/4"
15.904 SQ.IN.
6"
2 1/2"386 PSI
(1) 780CB1 15,223 LBS
3.27
9.82
1.85 7GA x 6" x 2 1/2"
5.67
23.39
2.40 7GA x 8 1/4" x 2 3/4"
1.38
2.17
1.01 10GA
405 LBS 231 LBS N/A N/A
Signa 4 Fixtures, T2 Buttons, Alarm Button, Telephone, Position
Indicator
B, 1, 2
Car Operating Panel
2'-3 7/8"
5,908.00 LBS 14,632.00 LBS
"PLEASE REFERENCE ASME A17.1 (2.2.2) FOR SUMP PIT REQUIREMENTS"
PLAN HWY FRONT
5 OF 7 140-1200-02B 6/6/2019RWA
DATEJOB NUMBER SHEETDRAWNREV THIS DRAWING AND ALL INFORMATION THEREON IS THE PROPRIETARY PROPERTY OF
THYSSENKRUPP ELEVATOR AND MUST NOT BE MADE PUBLIC OR COPIED. THIS DRAWING
IS LOANED SUBJECT TO RETURN ON DEMAND AND IS NOT TO BE USED DIRECTLY OR
INDIRECTLY, IN ANY MANNER DETRIMENTAL TO THE INTEREST OF THYSSENKRUPP ELEVATOR.
FOR: SPECIFIED LIGHTING
ADDRESS: 101 CARMEL DRIVE
CITY: CARMEL, IN 46032
FOR ELEVATOR:1
IF A CUT STARTER RAIL IS CALLED FOR IN THE STACK,
CONFIRM THE NUMBER OF SPLICES PRIOR TO CUTTING
5'-9"HOISTWAY DEPTH8'-4"
HOISTWAY WIDTH 4'-0 3/4"³WHERE DISTANCE BETWEEN FLOORS EXCEEDS THE MAXIMUM BRACKET SPAN, BRACKET SUPPORT MUST BE
PROVIDED MIDWAY. BRACKET SUPPORT WILL NEED TO BE SUPPLIED BY OTHERS TO ALLOW FOR RAIL
ATTACHMENT. INSIDE SUPPORT SHALL NOT BE RECESSED BEHIND WALL SYSTEM AND SHALL NOT BE PROUD
BY MORE THAN 1/4´ AT ANY POINT. COORDINATE WITH TKE SUPPORT/OPERATIONS MANAGER´
SRAILS6'-0"
ROUGH OPENING WIDTH
2"4'-0 3/4"SAFETY BEAM8'-3" ROUGH
OPENING HEIGHT
BRACKET LOCATION
DIMENSIONS
RAIL SECTION
DIMENSIONS
4'-0"
PIT DEPTH
12'-8" CLEAR OVERHEAD
FRONT OF HOISTWAY
REAR OF HOISTWAY
22'-0" NET TRAVEL
RAIL STACK SECTION VIEW
RAILS AND BRACKETS - TOTAL QUANTITY
RAILS
BRACKETS
QTY:
SPAN:
(5) 16 FT
SPLICES:4
LEFT HAND RIGHT HAND
4 4
8"8"
6'-5 1/2"
RAIL
16'-0"
RAIL
16'-0"
RAIL
11'-6"1'-3"10'-8"1'-3"8'-10"1'-3"2'-9"
B12
CAR RAIL LINE LENGTH QUANTITY (6)
LENGTH QUANTITY
16'-0"4
6'-5 1/2"2
FLOOR TO FLOOR TRAVEL
FLOOR TO FLOOR TRAVEL
1-2 11'-11"
B-1 10'-1"
NET TRAVEL 22'-0"
CAR RAIL LINE BRACKETS AND INSERT LOCATIONS REQ. AT :
LOCATION DESCRIPTION
15'-9"MAX. UNSUPPORTED RAIL BRACKET SPACING
11'-6"ABOVE TOP FLOOR
1'-3"BELOW B,1-2
TYPICAL SURFACE
MOUNTING DETAILS
AT ALL FLOOR LOCATIONS
TYP
TYP
TYP
22" BRACKET O.A.
16"
30" DRYWALL INSERT. BOLT TO WO OD
BEAM SUPPORT (INSERT) PROVIDED
BY TKE, INSTALLED BY G.C.
MOUNT FLUSH WITH WALL.
30 X 6" STEEL PLATE WELDED TO TUBE
STEEL PROVIDED AND INSTALLED
BY G.C. MO UNT FLUSH WITH WALL.
30 X 6" STEEL PLATE WELDED TO TUBE
STEEL PROVIDED AND INSTALLED
BY G.C. MOUNT FLUSH WITH WALL.
30 X 6" STEEL PLATE WELDED TO
STEEL PROVIDED AND INSTALLED
BY G.C. MOUNT FLUSH WITH WALL.
INSERT INSTALLED BY G .C.
MOUNT FLUSH WITH WALL &
GROUT SOLID ALL AROUND.
INSERT INSTALLED BY G .C.
MOUNT FLUSH WITH WALL &
GROUT SOLID ALL AROUND.
22" BRACKET O.A.22" BRACKET O.A.22" BRACKET O.A.22" BRACKET O.A.22" BRACKET O.A.
16"16"
MACHINE ROOM PLAN VIEW
MINIMUM MACHINE ROOM CEILING HEIGHT = 7'-6"
6 OF 7 140-1200-02B 6/6/2019RWA
DATEJOB NUMBER SHEETDRAWNREV THIS DRAWING AND ALL INFORMATION THEREON IS THE PROPRIETARY PROPERTY OF
THYSSENKRUPP ELEVATOR AND MUST NOT BE MADE PUBLIC OR COPIED. THIS DRAWING
IS LOANED SUBJECT TO RETURN ON DEMAND AND IS NOT TO BE USED DIRECTLY OR
INDIRECTLY, IN ANY MANNER DETRIMENTAL TO THE INTEREST OF THYSSENKRUPP ELEVATOR.
FOR: SPECIFIED LIGHTING
ADDRESS: 101 CARMEL DRIVE
CITY: CARMEL, IN 46032
3'-6"
CLEARANCE 1'-6"ELEV: 1
3'-6"CLEARANCEELEVATOR DESIGNATOR: 16'-6"MACHINE ROOM DEPTH5'-0"
MACHINE ROOM WIDTH
3'-6"
DOOR WIDTH
Ɣ BASED ON THIS INFORMATION, WE REQUIRE ELECTRICAL FEEDERS AND FUSED
DISCONNECTS SIZED PER THE FOLLOWING INFORMATION LISTED IN THE POWER
FEEDER TABLE.
Ɣ GENERAL CONTRACTOR MUST FORWARD POWER REQUIREMENTS TO THE
ELECTRICAL CONTRACTOR.
NOTE: ALSO, A FOURTH WIRE OF SAME SIZE AS THREE PHASE WIRES IS
REQUIRED FOR GROUNDING PURPOSES TO MINIMIZE ELECTRICAL NOISE
INTERFERENCE. THE GROUNDING WIRE MUST BE CONNECTED TO THE BUILDING
ELECTRICAL SYSTEM GROUND.
Ɣ A MEANS TO AUTOMATICALLY DISCONNECT THE MAIN LINE PER POWER SUPPLY
TO THE ELEVATOR PRIOR TO THE APPLICATION OF WATER IN THE ELEVATOR
HOISTWAY WILL BE FURNISHED BY THE ELECTRICAL CONTRACTOR THIS MEANS
SHALL NOT BE SELF RESETTING.
Ɣ DEDICATED 120 VOLT, 15 AMP SERVICE, ALONG WITH TELEPHONE CIRCUIT WHEN
REQUIRED TO TERMINALS OF EACH REQUIRED CONTROLLER (AS LOCATED ON
PLAN VIEW) FOR THE FOLLOWING:
- CAR LIGHT AND ALARM CIRCUIT WITH GFCI PROTECTION PER NEC.
- GROUP CONTROL WHEN REQUIRED.
NOTE: IF STANDBY POWER IS SUPPLIED TO ELEVATOR, CAR LIGHT AND ALARM
CIRCUIT AND GROUP CONTROL SERVICE MUST BE STANDBY POWER BACKED.
Ɣ PIPING WITH PULL STRING FROM HOISTWAY TO ELEVATOR MONITORING PANELS
BY OTHERS.
Ɣ PROVIDE A TRANSFER SWITCH CONTACT THAT IS CLOSED WHEN NORMAL POWER
IS PRESENT AND IS OPEN ON EMERGENCY POWER.
Ɣ PROVIDE A POWER TRANSFER WARNING CONTACT THAT CLOSES 20 SECONDS
PRIOR TO TRANSFER IN EITHER DIRECTION AND IT OPENS WHEN TRANSFER IS
COMPLETE.
Ɣ TOTAL FULL LOAD UP SPEED AMPS IS BASED ON 100% OF ELEVATOR CAPACITY,
THE VALUE NEEDED FOR EMERGENCY POWER SIZING.
Ɣ THE HYDRAULIC MOTORS ARE RATED FOR INTERMITTENT DUTY (SEC. 620-13
AND 430-33). BRANCH CIRCUIT CONDUCTORS CAN BE SIZED FOR AN AMPACITY
90% OF THE MOTORS NAMEPLATE RATING AS DETERMINED BY (SEC. 430-22 [E])
Ɣ LIGHT SWITCH, LIGHTING AND CONVENIENCE OUTLET WITH GFCI PROTECTION
PER ASME/CSA B44.
Ɣ AN ENCLOSED MACHINE AREA (ACCORDING TO CODE) WITH ADEQUATE LIGHT,
HEAT AND VENTILATION (MIN. 50F., MAX. 90F. WITH NON-CONDENSING HUMIDITY
OF 10-90%) AND SEALED CONCRETE FLOOR SLAB SURFACE.
NOTE: MUST PROVIDE ADEQUATE DOOR SIZE TO ALLOW INSTALLATION OF
EQUIPMENT, OR LEAVE WALL OUT UNTIL EQUIPMENT IS IN PLACE.
BY OTHERS
THE FOLLOWING CONDITIONS MUST BE MET BEFORE INSTALLATION IS
COMPLETED AND ARE NOT INCLUDED IN THE ELEVATOR CONTRACT
GENERAL DATA
ELECTRICAL DATA
ELEVATOR
DESIGNATOR
POWER UNIT
WIDTH x DEPTH
TANK
HEIGHT
OIL LINE
HEIGHT
OIL LINE
OUTLET
TANK WEIGHT
WITH OIL
CONTROLLER
HEIGHT
HYDRAULIC
FLUID REQ.
POWER UNIT AND CONTROLLER INFORMATION
POWER
SUPPLY
HORSE
POWER
STARTING
A.C. AMPS
TOTAL FULL LOAD
UP SPEED MOTOR
A.C. AMPS
RATED
A.C. AMPS
SHORT CIRCUIT
CURRENT RATINGS
(AT 600V OR LESS)
POWER FEEDER
1 3'-3 3/4" X 2'-10"3'-8 1/8"3'-1 7/8"2"2,250 4'-5"106 208 30 283 136 94.3 5,000 AMPS
Ɣ BATTERY OPERATION LOWERING IS PROVIDED, A MECHANICAL AUXILIARY
CONTACT SHALL BE INSTALLED ON THE DISCONNECT SWITCH FOR EACH CAR.
THE AUXILIARY SHALL BE CONFIGURED AS SPST AT 1A 110VC (MIN). THE AUXILIARY
CONTACT SHALL BE OPEN WHEN THE DISCONNECT SWITCH IS IN THE OPEN
POSITION. IF A SHUNT TRIP CIRCUIT BREAKER IS PROVIDED, AN AUXILIARY
CONTACT SHALL BE INSTALLED ON THE CIRCUIT BREAKER.
Ɣ HEAT LOAD IS BASED ON CAR LOADED AT 40% CAPACITY RUNNING AT AN
AVERAGE 35% DUTY CYCLE.
HEAT LOAD IN MACHINE ROOM DUE TO ELEVATOR EQUIPMENT = 14098 BTU/HR
ADJACENT AT FLOOR 1
Ɣ PRIMARY FIRE SERVICE LOCATED AT FLOOR:
Ɣ ALTERNATE FIRE SERVICE LOCATION AT FLOOR:
1
ADA PHONE PROVIDED
N
ELEV.OIL LINE SIZE NOTE
1
2" OIL LINE FROM TANK TO 2" SHUTOFF VALVE. 2" SCH 40
BLACK PIPE, ASTM A-53, TYPE (E) OR (S), GRADE (B) OR
EQUIVALENT TO JACK
8'-4"
9'-0"5'-9"
ENTRANCE LEFT SIDE VIEWLOBBY SIDEENTRANCE ELEVATION VIEW AT TYPICAL FLOORÎENTRANCE PLAN VIEW
LOBBY SIDE
A
D
R2 R1ƔƔ
THIS DRAWING AND ALL INFORMATION THEREON IS THE PROPRIETARY PROPERTY OF
THYSSENKRUPP ELEVATOR AND MUST NOT BE MADE PUBLIC OR COPIED. THIS DRAWING
IS LOANED SUBJECT TO RETURN ON DEMAND AND IS NOT TO BE USED DIRECTLY OR
INDIRECTLY, IN ANY MANNER DETRIMENTAL TO THE INTEREST OF THYSSENKRUPP ELEVATOR.
FOR: SPECIFIED LIGHTING
ADDRESS: 101 CARMEL DRIVE
CITY: CARMEL, IN 46032 7 OF 7
DATE
A
SHEETJOB NUMBER
6/6/2019
REVDRAWN
RW 140-1200-02B
FEATURES OF ENTRANCES DATA
SILL MAXIMUM WHEEL LOADS 625 LBS
KEYHOLES TO BE INCLUDED
THIS FRAME HAS A WARNOCK HERSEY LABEL OF 2 HOURS
DUST COVERS NOT INCLUDED
FEATURES OF YOUR ENTRANCES
FEATURES FINISH LOCATION
DOOR OPEN STRUT BUMPERS:PROVIDED @B,1,2
KICKPLATES:__________@B,1,2
BINDERS:__________@B,1,2
SILL FINISH:ALUMINUM @B,1,2
TOTAL WEIGHT ELEVATOR 1 ELEVATOR
CAB AND HALL DOORS 327 LBS
NOTE "A":
8" MINIMUM STRUCTURAL
SUPPORT FOR SILL INSTALLATION
ENTRANCE CHART
M721 ENTRANCE:
CENTER OPENING AND 1 SPEED = FRAME OPENING + 1'-3"
2 SPEED = FRAME OPENING + 1'-5"
ENTRANCE TYPE : M721
FOR ELEVATOR 1
1 SPEED
RIGHT HAND FRONT ENTRANCE
FOR ELEVATOR 1
FOR ELEVATOR: 1
R2 229
R1 566
DOOR REACTION
CASE 1
SEE NOTE "A"5'-0"C/L 4.10.5 28 CFR PART 36CLEAR OPENING HEIGHT (REFER TO DOOR SCHEDULE)CLEAR OPENING HEIGHT + 2" = OVERALL FRAME HEIGHT2"0 3/16"MINIMUM FLOOR TO FLOOR HEIGHT = "SEE ENTRANCE CHART"CLEAR OPENING WIDTH
REFER TO DOOR SCHEDULE
2"
FRAME
2"
FRAME
ACTUAL
WALL SIZE
0 3/4"
ELEVATOR:1 FRONT ENTRANCE SCHEDULE
FLOOR WALL TYPE WALL SIZE
ACTUAL OA. FRAME "B" DIM.
PLEASE REFERENCE THE RAIL STACK SHEET OF THIS PACKAGE FOR
BUILDING LANDING MATRIX
ENTRANCE DIMS.
DIM "B"
2 7'-0" H X 3'-6" W TBD TBD TBD
1 7'-0" H X 3'-6" W TBD TBD TBD
B 7'-0" H X 3'-6" W TBD TBD TBD
FRONT ENTRANCE HALL FIXTURES
ITEM DESCRIPTION FLOOR
A HALL STATION TYPICAL
D HALL POSITION INDICATOR @1
HALL FIXTURES ARE FOR REPRESENTATION ONLY. FOR ACTUAL LOCATION OF
POCKETS FOR HALL FIXTURES, CONTACT ELEVATOR CONTRACTOR.
6'-0"
ROUGH OPENING WIDTH
8'-3"ROUGH OPENING HEIGHT NOTES:
GENERAL CONTRACTOR RESPONSIBLE FOR HOISTWAY REINFORCING
AT FLOOR SLAB BEFORE INSTALLATION OF ENTRANCE FRAMES.
MINIMUM OF 4" HIGH X 8" WIDE REINFORCED CONCRETE, REINFORCED
OF OPENING REQUIRED FOR ANCHORING SILL SUPPORT ASSEMBLY,
REINFORCING TO BE LOCATED WITH RESPECT TO REACTION POINTS,
REFERENCE INSTALLATION DRAWINGS ARE AVAILABLE UPON
REQUEST.
REACTIONS (LBS.) DUE TO LOADS ON DOOR PANELS, APPROX.
HORIZONTAL LOADS AND LOCATION TO BUILDINGS SHOWN PER ASME
A17.1 PART II,
THE SPECIFIED LOADS ARE CONSIDERED IMPACTED. 2" BELOW EACH FLOOR5'-3"2'-1 1/2"