HomeMy WebLinkAboutE-1 Electrical PlansRELEASED FOR CONSTRUCTION
Subject to compliance with all regulations
of State and Local Codes
CiityGF Camnedl
�VT�Vt�B*VAWML
DATE: 09/06/19
ELECTRICAL PLAN NOTES
1, ELECTRICAL CONTRACTOR SHALL REVIEW ALL DRAWINGS OF THIS SET,
2. CONTRACTOR TO VERIFY THAT ALL EQUIPMENT SHOWN AS EXISTING MATCHES THE DESCRIPTIONS AND
SPECIFICATIONS SHOWN ON DRAWINGS AND SCHEDULES. IF DIFFERENT, NOTIFY ARCHITECT/ENGINEER
BEFORE BIDDING, ORDERING, OR PROCEEDING WITH WON(.
3. ELECTRICAL CONTRACTOR SHALL SUPPLY AND INSTALL ALL NEW ELECTRICAL WON( INDICATED.
CONSTRUCTION SHALL BE IN ACCORDANCE WITH DRAWINGS AND APPLICABLE SPECIFICATIONS. IFA
PROBLEM IS ENCOUNTERED IN COMPLYING WITH THIS REQUI REMENT, CONTRACTOR SHALL NOTIFY THE
OWNER OR HIS REPRESENTATIVE AS SOON AS POSSIBLE AFTER DISCOVERY OF THE PROBLEM AND SHALL NOT
PROCEED WITH THAT PORTION OF THE WORK UNTIL OWNER HAS DIRECTED CORRECTIVE ACTION TO BE
TAKEN.
4. ELECTRICAL CONTRACTOR SHALLVISITJOB SITE AND FAMILIARIZE HIMSELF WITH ALL CON DITIONS AFFECTING
ELECTRICAL AND COMMUNICATIONS INSTALLATION AND MAKE PROVISIONS AS TO THE COST THEREOF.
EXISTING CONDITIONS OF ELECTRICAL EQU IPMENT, LIGHT FIXTURES, ETC... THAT ARE PART OF THE FINAL
SYSTEM SHALL BE VERIFIED BY THE CONTRACTOR PRI OR TO SUBMITTING HIS BID.
S. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE 2014 EDITION OF THE NATIONAL ELECTRIC
CODE AND ALL CODES AND ORDINANCES OF THE AUTHORITY HAVING JURISDICTION.
6. DO N OT SCALE THE ELECTRICA L DRAWN GS. REFER TO ARCH ITECTU RAL PLAN S AN D ELEVATI DNS FOR EXACT
LOCATION FOR ALL EQU IPMENT. CONFIRM WITH OWNER'S REPRESENTATIVE.
). ALL ELECTRI CAL N OT REIN G RE U SED MUST BE RE MOVED IN ITS ENTI RETY.
8. ALL CON DU IT IN OR UN DERGROUN D OR INCON CRETE MU ST BE RI GI D GALVAN IZED STEEL.
9. CI ROL IT BREAKERS AN D PANELS TO BE BOLT ON TYPE
10, ALL EQU IPMENT SHALL M APPROVE D BY U L OR OTTE R NATIONALLY RECOGN IZE D TESTING COMPANY.
11. ALL RECEPTACLES SHALL BE GROU N BE D AS REQU I RE D BY NEC 250.146
12. SUBM IT SERVI CE ENTRAN CE EQU IPMENT FOR SEPARATE APP ROVAL.
13. ALL LOW VOLTAGE MUST BE IN CONDUIT TO ABOVE THE DROP CEILING. BRIDAL RINGS OR"J"HOOKS
REQUIRED.
14. THE 2014 EDITI ON OF THE NATI DNAL ELECTRIC CODE WITH LOCAL AMEN DMENTS SHALL RE IN E FFE CT.
15. SEPA RATE PE RMITS ARE REQU I RE D FOR ALL LOW VOLTAGE SUCH AS TE LEP HONE, DATA, THE RMOSTAT,
MUSIC,A0,RMSETC.
16. SEPARATE PERMIT REQUIRED FOR SIGNAGE.
17. PRIOR TO ANY CONSTRUCTION WORK BEGAN ING AN ON SITE MEETING WITH GENERAL CONTRACTORS IS
REQUIRED.
18. ELECTRI CIAN MUST BE ON SITE FOR ALL INSPECTION S.
19, MIN I M U M WI RE SIZE SHIA LL BE#12 AND. EXCLU DING CONTROL WI RIN G. ALL CON DUCTORS SHALL
COPPER AN D UNLESS OTHERWISE NOTED THHN IN SU UTI ON.
20. OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS, PLASTIC AND CAR ALLOY WITH THREADED HUBS
IN WET OR DAMP LOCATIONS, AND SPECIAL ENCLOSURES FOR OTHER CLASSIFIED AREAS,
21. IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF CON ARUCTI ON. THE
CONTRACTOR 15 EXPECTED TO FUND ISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL SYSTEM AND
PROVI BE ALL REQU IRE VENTS NECESSARY FOR EQUIPMENT TO BE PLACED IN PROPER WORKING ORDER.
22. ELECTRI CAL SYSTE M SHALL M COMPLETE AN D E FFECTIVE LY G FOLD DE D AS REQU I RE D BY THE 2014 E DITI ON
OF THE IN F.C. OR LOCAL CODES.
23, ALL MATE PALS SHALL BE N EW AN D BEAR UN DE RWRITE RS' DBE LS WHE RE APPLICABLE.
24. ALL WORK SHALL BE PE RFORME D BY A LI DEN SE D ELECTRI CAL CONTRACTOR IN A F I RST CLASS WORKMA N LI KE
MANNER. THE COMPLETED SYSTEM SHALL BE FULLY OPERATIVE AND ACCEPTED BY ENGINEER/ARCHITECT.
25, ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH THE PROGRESS OF
CONSTRUCTION.
26. ELECTRICAL CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROMDEFECTSFOR
A PERIOD OF NOT LESS THAN ONE YEAR FROM DATE THAT CERTIFICATE OF OCCUPANCY IS ISSUED.
WARRANTY SHALL BE PROVIDED IN WRITING.
22. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE AND SHALL INCLUDE
REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED
THEREBY.
28. ALL REQU IRED INSU RANCE SHALL BE PROVIDED FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY
DAMAGE FOR THE DU RATION OF THE WORK.
29. CONTRACTOR SHALL PAY FOR ALL PERMITS, FEES INSPECTI DNS AN D TESTIN G. CONTRACTOR TO OBTAIN
PERMIT AND APPROVED SUBMITTALS PRIOR TO BEGINNING WORK OR ORDERING EQUIPMENT.
30. THE ELECTRI CAL INSTALLATI ON S HALL MEET ALL STAN DARD REQU I REMENTS OF POWE R AN D TE LEPHONE
COMPANIES.
31. CONTRACTOR SHALL COORDINATE WITH MECHANICAL DRAWINGS AN D FROM DE ALL NECESSARY CONTROL
WIRING.
32, ALL CI RCU IT BREAKE RS FEE DING MECHAN ICA L EQU IPMENT SHALL BE HACR TYPE CI RCU IT BREAKERS.
33. PROVI BE AN D IN STALL CON DU IT, CON DUCTORS, PU LL WIRES, BOXES, COVER PLATES, DEVI CES, ETC. FOR ALL
OUTLETS AS INDICATED.
34, MATE RIALS, PRODU CTS, AN D EQU IPMENT, IN CJ DIN G ALL COMPON DINTS THE ROOF, SHIA LL BE NEW AND
SUCH AS APPEAR ON THE UL LIST OF APPROVED ITEMS AND SHALL MEET OR EXCEED THE REQUIREMENTS OF
N.E.C. NEMA, AN D IECE.
35, CONTRACTOR SHALL SU BY IT SHOP DRAWN GS OR CUT SHEETS OF LI GHTING FIXTU RES, SWITCHES AND
OTHER ELECTRICAL ITEMS FOR APPROVAL BY ENGINEER/ARCH ITER.
36, ELECTRI CAL CONTRACTOR SHALL BE RESPONSIBLE FOR A LL CUTTIN G, PATCH ING AN D FI RE D CAU LKING
REQU IRED OF HIS WORK.
37. ELECTRICAL CONTRACTOR SHALL LABEL ALL PANELS W/TYPE WRITTEN DIRECTORIES.
38, ALL ELECTRI CAL AN D COM MUN ICATION S OUTLETS TO M AT 19- A.F.F. UN LESS N OTE D OTHERWISE, AND
VERTICALLY MOUNTED.
39. ALL LIGHTSWITCHES TO RE AT 42"AF.F.
40, ALL ELECTRICAL WIRING SHALLBE THE RESPONSIBILITY OFTHE ELECTRICAL CONTRACTOR.%ELECTRICAL
WIRING FOR WAC SYSTEM INCLUDING CONTROLS, THERMOSTATS, POWER, ETC.SHALLBETHE
RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR.
41, BREAKER ANDPANELS--ALLCURRENT CARRYING BUSSESSHALLBE COPPER. ALLGROUNDBUS MRS SHALLBE
COPPER. PANEL BOARD ENCLOSU RES SHALL BE FURNISHED WITHOUT PRE PUNCHED CONCENTRIC HOLES.
A.I.C. RATINGS SHALL BE AS INDICATED ON PANEL BOARD SCHEDULES.
42, DISCONNECT SWITCHES SHALL BEHP. RATED, GENERAL DUTY, QUICK -MAKE, QUICKLaREAK ENCLOSURES AS
REQUIREDBYEXPOSURI
43. MOTOR STARTERS SHALL HE MANUAL OR MAGNETIC, WITH OVERLOAD RELAYS IN EACH HOT LEG.
44, THE TERM 'PROVIDE " USED IN THE CONSTRUCTION DOCUMENTS AND SPECIFICATIONS INDICATES THE
CONTRACT SHALL FURNISH AND INSTALL.
45. CONTRACTOR SHALL CONFIRM WITH ANY AND ALL REQUIREMENTS SUCH AS WGSIZERESTRICTI ONS,
CONDUIT ENTRY, TRANSFORMER SIZE, SCHEDU LED DOWNTIME FOR OWNERS CONFIRMATION, ETC. ANY
CONFLICTS SHALL BE BROUGHT TO ATTENTION OF THE ENGINEER BEFORE PROCEEDING WITH ANY WORK.
46. VOLTAGE DROP FOR ALL BRANCH CONDUCTORS SHALL NOT EXCEED 3%. WHERE VOLTAGE DROP EXCEEDS 3%,
CONTRACTOR SHALL INCREASE SIZE OF CONDUCTORS.
42. CONTRACTOR SHALL PROVIDE GFI TYPE BREAKER FOR ALL EXTERIOR 120V CIRCUITS OR GFI PROTECTION--
W R THE WHOLE CIRCUIT.
49, GAS PIPING SHALL BE BONDED.
49. ELECTRICAL CONTRACTOR SHALL COORDINATE SERVICE ENTRY WITH SERVICE PROVIDER PRIOR TO
CETERMIN ING EXACT LOCATION OF THE METER BOX IN ORDER TO AVOID DISCREPANCIES BETWEEN
DRAWINGS ANDIOB CONDITIONS.
50. ALL OUTDOOR EQUIPMENT SHALL BE WEATHERPROOF.
51. CONSTRUCTION"AS BUILT" DRAWINGS AND DOCUMENTS SHALL BE PROVIDED TO THE OWNER WITHIN 30
DAYS AFTER THE DATE OF ACCEPTANCE.
52. OPERATION MANUALS AND MAINTENANCE MANUALS SHALL BE PROVIDED TO THE BUILDING OWNER.
53. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING, PATCHING AND FIRE CAULKING
REQUIRED OF HIS WORK.
54. ABSOWTELYNO FLEXIBLE CONDUIT ISPERM17ED IN DEMISINGWALLS. FLEXIBLE CONDUIT ISPERM17ED
FOR SHORT FINAL CONNECTIONS ONLY ("'OR LESS).
55. EXPOSED CONDUIT SHALL BE INSTALLED IN STRAIGHT LINES, PARALLEL OR IN RIGHT ANGLES TO THE SLIDING
STRUCTURE. DO NOT LOOP EXCESS FLEXIBLE CONDUIT IN CEILING SPACE OR WALL CAVITY. NO CON DUIT TO
BE SUPPORTED FROM THE ROOF DECK.
56. CABLE TYPES AC AND MN CABLES ARE NOT ACCEPTABLE. TYPE MC CABLE, ELECTRIC METALLIC TUBING (EMT)
AND RIGID GALVANIZED CONDUIT ARE PERMITTED.
57, ALL EQUIPMENT, DEVICES AND FIXTU RES SHALL M GROUN DED IN COMPLIANCE WITH NEC AND UL
REQUIREMENTS.
58. ALL PANELS TO RE UL LABELED WITH BOLT- ON TYPE CIRCUIT BREAKERS.
59, 7-DAY 24-HOUR TIME CLOCK IS REQUIRED TO CONTROL STOREFRONT ENTRY LIGHTS, SHOW WIN DOW LIGHTS,
SHOW WINDOW RECEPTACLES AND STOREFRONT SIGNAGE. ILLUMINATED STOREFRONT SIGNS MUST
REMAIN LIT DURING ALL MALL BUSINESS HOU R5.
60, TENANT IS REQUIRED TO MAKE AFIELD SURVEY OF THE EXISTING ELECTRICAL SERVICE TO ENSU RE THAT THE
TOTAL CONNECTED LOAD DOES NOT EXCEED THE ELECTRIC SERVICE. ANY/ALL MODIFICATIONS OR UPGRADES
NEEDED ARE SUBJECT TO LANDLORD'S PRIOR APPROVAL AND WILL BE COMPLETED BY TENANT/TENANT'S GC
ATTENANT'SSOIEEXPENSE.
61. ALL ELECTRICAL PANELS TORE MOUNTED ON PLYWOOD BACKER BOARD.
62. PANELPHASE LOADSTO BE BALANCED WITHIN 10%.
63. ELECTRICAL PANELS MAY NOT BE RECESSED IN DEMISING PARTITIONS. SURFACE MOUNT OR FULL FUR OUT
WALL TO ACHIEVE FLUSH FINAL APPEARANCE.
64. COORDINATE ALL CONCRETE TRENCHING/CORING TO ENSURE THAT ANY UNDER SLAB UTILITIES, ETC. ARE
NOT DAMAGED DURING FLOOR CUT. ANY DAMAGE TO BE REPAIRED AT TENANT'S EXPENSE. PRIOR
APPROVAL AN D COORDINATION WITH PROPERTY MANAGEMENT IS REQUIRED FOR ALL CONCRETE CUTTING.
65. CONFIRM ELECTRICAL METER REQUIREMENTS WITH MALL OPERATIONS.
SCOPE OF WORK
USING EXISTING (2) 200 AM P, 120/208Y-30 ELECTRICAL SERVICE PROVIDE ALL NECESSARY
EQUIPMENT AND ALL WIRING FOR RESTAURANT BU ILDOUT INCLUDING WIRING OF ALL KITCHEN
EQUIPMENT. ALL LIGHTING IS EXISTING TO REMAIN.
COORDINATE WITH G.C. FOR LOW VOLTAGE WIRING,
ELEGTHIGALLEGEND
SYMBOL
DESCRIPTION
EXHAUSTFAN
COMBINATION EXHAUST FAN/LIGHT (REFER TO MECHANICAL PLANS)
5
SPEAKERS @ CEILING
OO
JUNCTION BOX
®
CEILING MOUNTED SMOKE DETECTOR I IOV., INTERCONNECTED W/ BATT.
BACKUP. SMOKE DETECTOR SHALL COMPLY WITH NFPA 72, AND FBC 906.2.
2)
BATTERY BACK UP EXIT LIGHT
29
BATTERY BACK UP EMERGENCY LIGHT
WALL SWITCH (SINGLE, DOUBLE,)
WALL SWITCH 3 WAY, 4 WA
WALL SWITCH(TIMER)
DIMMER WALL SWITCH
OCCUPANCY SENSOR WALL SWITCH
SINGLE RECEPTACLE
DUPLEX RECEPTACLE
DUPLEX RECEPTACLE, 46" TO AFT AT KITCHEN, BATHS AND TOPS
HALF SWITCHED DUPLEX RECEPTACLE
®
230 VOLT RECEPTACLE
QUADRUPLEX RECEPTACLE
FLOOR MOUNTED. FLUSH DUPLEX RECEPTACLE
FLOOR MOUNTED. FLUSH QUAD. RECEPTACLE
ELECTRICAL PANEL
CDJ
DISCONNECT SWITCH
ELECTRIC METER
Z
TELEVISION OUTLET
TELEPHONE OUTLET
TELEPHONE/DATA OUTLET
DATA OUTLET
FLOOR MTD. FLUSH TELEPHONE/DATA OUTLET
ABBREVIATIONS:
ABOVE FINISH FL0iA.F.F. BELOW COUNTET=BC
COUNTER TOP LEVEL=C PUSH BUTFON=RE
GROUND FAULT INTERRUPTER= GFCI UNDER CABINET=UC
VERIFYPRIORTOINSTALI=VH VAPOR PRJOF=VP
WEATHER PROOF= WP SALVAGED =S
GENERAL LIGHTING NOTES
A. WHE RE LIG HT FIXTU RE IS FOLLOWE D BY"NL", TH IS FIXTU R E IS DESIG NATED AS A N IGHT
LIGHT AN D SHALL BE CON IN ECTED TO AN U NSWITCH ED HOT CONDUCTOR.
B. UPPERCASE LETTER N EXT TO LIG HT FIXTU R E DEN OTES FIXTU R E TYPE AN D LOWERCASE
LETTER DENOTES SWITCHING SCHEME.
C. ALL EM E RG ENCY FIXTU RES SHALL BE CON N ECTED TO AN U NSWITCH ED HOT CON DU CTOR
T.G.C. SHALL VERIFY THE EXISTING ELECTRICAL RISER
AND ALL ELECTRICAL REQUIREMENTS OF EXISTING AND
NEW MECHANICAL EQUIPMENT (III ETC.). INFORMATION
SHOWN ON PANEL RISER AND SCHEDULE IS FOR
REFERENCE ONLY. T.G.C. SHALL ADJUST WIRE SIZE,
BREAKER SIZE, DISCONNECT SWITCH, ETC., AS
REQUIRED PER MANUFACTURER'S SPECIFICATIONS.
I MOP I
F-- POD -7 1 1W2D8
MOUNTED
TRANSFORMER I
I T I m
2-#8THHN 2-#12 THHN
+1-#8 GAD +1-#12 GAD
IN�'COND. j CON Ep
WIF WIC ATl}1 flN-2 GLYCOL HEF7 REFER TO MUA-1
(N) (I ILL IE) (E) 30NF DOD SHOP 30NF
DflA'MNGS
I I
T_._
I l i i l 2-#12THHN
VVH
I l j i j +INS COND.D M)VE
N) EXTERIOR SIGN SOFT S MACHINES
S
i l i l
T. _-
I i l i i �E%ISTING----
__ __ __ J I
PONEL"A" JE -- -- -� I
J J
t 30
IF
__
200AMP ___ ___ _ ______MOB THE j TO HOOD 3-$10 THHN120808V CLOCK +1-#10 GAD
�IN t COND.
EXISTING L- jib.-.-.-.
_______J 2-012 THIN RELAY TO SHUT DOWN
+ GAD ELECTRICAL
EXISTING INkOO D. EQUIPMENT UNDERPOWER HOOD
ALL FEEDERS ARE COPPER UNLESS OTHERWISE NOTED
ELECTRICAL RISER SCALE 7
N.T.S.
E0
cv
o I� E
�M e
o I N3r
�J ¢
t>
E
PROJECT
W
O
M Ln
1�
U�
w M
V Ir�TI
W
M �y
I\
REVISIONS DATES:
PRC%BOIkFiS�AL
O`%QJG..Q...�......JJ
tNO.PE10200dOT} [t p
piJF`SS/ONAX-gyp:
ERJCENGELLPEpI@gM%
REgBTEREDENGJNEER
STATEOFTNDDiNA
ISSUE DATE: 03.01.19
PROJECT#: 282C.1268C1
DRAWN BY: ED
CHECKED BY: AK
ELECTRICAL RISER,
PANELS,NOTES,
LEGEND &
SCHEDULE
E-1