HomeMy WebLinkAboutEnergy code (as designed)IECC 2009 Performance Compliance
Property
122 SHOSHONE DR
CARMEL, IN 46032
Model: CUSTOM
Community: MACKAY RESIDENCE
MACKAY (AS DESIGNED)
MACKAY RESIDENCE
Organization
TSI Energy Solutions
❑evin Sielschott
Builder
SIGMA BUILDERS, LLC
Design
Heating
Cooling
Water Heating
SubTotal - Used to determine compliance
Lights &Appliances
Onsite generation
Total
405.3
R402.4.1.2
402.5
402.5
403.2.2
Mandatory Checldist
R4052
Inspection Status
Results are projected
Annual Energy Cost
IECC 2009 Performance
$1,277
$169
$179
$1,625
$764
$0
$2,389
Requirements
Performanoe-based compliance passes by 2.5%
Air Leakage Testing
Area -weighted average fenestration SHGC
Area -weighted average fenestration U-Factor
Duct Testing
Mandatory code requirements that are not
checked by Ekotrope must be met.
Duct Insulation
C-M,
Energy Solutions
As Designed
$1.255
$149
$179
$1,584
$764
so
$2,348
Air sealing is 5.00 ACH at 50 Pa. It must not exceed 7.00 ACH at 50 Pa.
Design exceeds requirements for IECC 2009 Performance compliance by 2.5%.
As a 3rd party extension of the code jurisdiction utilizing these reports, I certify that this energy code compliance document has been created in accordance with the requirements of
Chapter 4 of the adopted International Energy Conservation Code based on Climate Zone 5. If rating is Projected, I certify thatthe building design described herein is consistent with
the building plans, specifications, and other calculations submitted with the permit application. If rating is Confirmed, I certify that the address referenced above has been
inspected/tested and thatthe mandatary provisions of the IECC have been installed to meet or exceed the intentof the IECC or will be verified as such by another party.
Name: Devin Sielschott
Organization: TSI Energy Solutions
Signature:
Date: 815119 at 10:41 AM
Ekotrope RATER -Version 3.1.1.2227
IECC 2009 Performance compliance results calculated using Ekotrope RATER's energy and code complianceaIgo rithm.
Ekotrope RATER is a RESNET Accredited H ERS Rating Tool. All results are based on data entered by Ekotrope users.
Ekotropedisclaims all liabilityforthe information shown on this report.
122 SHOSHONE DR
CARMEL, IN 46032
Builder: SIGMA BUILDERS, LLC
L 'f
Ceiling Attic, R-38
Above Grade Walls R-15
Foundation Walls R-10
Framed Floor N/A
Slab R-0.0 Perimeter, R-0.0 Under
Infiltration 5 ACH50
Window U-Value: 0.3. SHGC: 0.25
Building Features
Duct Supply R-6.0, Return R-6.0
Duct Leakage to Outside 192 CFM a@ 25Pa (5.841100 s.f.)
Total Duct Leakage 256.0 CFM @ 25Pa
Heating Furnace • Natural Gas • 92.1 AFUE
Cooling Air Conditioner • Electric • 13 SEER
Water Heating Water Heater • Natural Gas • 0.64 Energy Factor
As a 3rd party extension of the code jurisdiction utilizing these reports, I certify that this energy code compliance document has been created in accordance with the requirements of
Chapter 4 of the adopted International Energy Conservation Code based on Climate Zone 5. If rating is Projected. I certify that the building design described herein is consistent with the
building plans, specifications, and other calculations submitted with the permit application. If rating is Confirmed, I certify that the address referenced above has been inspectedltested and
that the mandatory provisions of the IECC have been installed to meet or exceed the intentof the IECC or will be verified as such by another party.
Name: Sevin Sielschott
Organization: TSI Energy Solutions
Signature:
Date:
8l5f19 at 10:41 AM
Ekotrope RATER - Version 3.1.1.2227
20091ECC compliance resuits calculated using Ekotrope RATER's energy and code compliance algorithm-
Ekotrope RATER is a RESNET Accredited HERS Rating Tool. All results are based on data erd.ered by Ekotrope users.
Ekotrope disclaims all liability for the information shown on this report.
Energy Code Inspection Checklist
Property organization
122 SHOSHONE DR TSI Energy Solutions
CARMEL, IN 46032 ❑evin Sielschott
Model: CUSTOM
Community: MACKAY RESIDENCE Builder
SIGMA BUILDERS, LLC
MACKAY (AS DESIGNED)
MACKAY RESIDENCE
General Building Information
Conditioned Area (sq ft) 3,289
Conditioned Volume (cubic ft) 33,088
Insulated Shell Area (sq ft) 8,178
Inspection Status
Results are projected
C-M,
Energy Solutions
The building energy model in Ekotrope reflects the building assemblies and energy features listed below. Sometimes energy
features will change in the field from what has been modeled. The inspection process should identify any changes and ensure
that the home continues to meet the applicable energy code.
Slab
] Name: BSMT(1,174 s.f., 115 ft. exterior perimeter)
R-0 perimeter insulation, R-0 under slab insulation.
]l Name: CRAWL(941 s.f., 123 ft. exterior perimeter)
R-0 perimeter insulation, R-0 under slab insulation.
Framed Floor
None Present
Foundation Wall
Name: UNFIN (Exterior Perimeter [ft]: 38, Height Above Grade [ft]: 1, Depth Below Grade [ft]: 8)
R: 5.00
Feet from top of wal I to top of i nsulation: 0.8, Feet from top of wall to bottom of insulation: 0
Name: FIN (Exterior Perim ete r [ft]: 77: Height Above Grade [ft]: 1, Depth Below Grade [ft]: 8)
R: 16.275
Fully insulated (top to bottom)
Name: CRAWL/GARAGE (Exterior Perimeter [ft]: 80, Height Above Grade [ft]: 1, Depth Below Grade [ft]: 2)
R: 10.00
Fully insulated (top to bottom)
] Name: CRAWLIGARAGE (Exterior Perimeter [ft]: 43, Height Above Grade [ft]: 1, Depth Below Grade [ft]: 2)
R: 10.00
Fully insulated (top to bottom) 1
Energy Code Inspection Checklist
7'SI Energy Solutions
Property Organization Inspection Status
122 SHOSHONE DR TSI Energy Solutions Results are projected
CARMEL, IN 46032 ❑evin Sielschott
Model: CUSTOM
Community: MACKAY RESIDENCE Builder
SIGMA BUILDERS, LLC
MACKAY (AS DESIGNED)
MACKAY RESIDENCE
Above Grade Wall
Name: CONDIAMB (1,755 s.f.)
R-0 continuous insulation, R-15 cavity insulation
Insulation Grade: I
Name: CONDIGAR (387 s.f.)
R-0 continuous insulation, R-15 cavity insulation
Insulation Grade: I
Name: CONDIATTIC (164 s.f.)
R-0 continuous insulation, R-15 cavity insulation
Insulation Grade: I
Rim Joist
* Name: C0NDIAMB (195 s.f.)
R: 11.691
Name: CONDIGARAGE (43 s.f.)
R: 11.691
Roof
El Name: MAIN (2,115 s.f.)
R-27.55 continuous insulation, R-10.15 cavity insulation
Insulation Grade: I
Opaque Door
Name: FRONT (24 s.f.)
U: 0.182
Name: GARAGE (24 s.f.)
U: 0.182
Glazing
2
Energy Code Inspection Checklist
7'SI Energy Solutions
Property Organization Inspection Status
122 SHOSHONE DR TSI Energy Solutions Results are projected
CARMEL, IN 46032 ❑evin Sielschott
Model: CUSTOM
Community: MACKAY RESIDENCE Builder
SIGMA BUILDERS, LLC
MACKAY (AS DESIGNED)
MACKAY RESIDENCE
E] Name: FRONT (64 s.f.), U: 0.300, SHGC: 0.25, Orientation: SOUTH—EAST
Name: BACK (150 s.f. ), U: 0.300, SHGC: 0.25, Orientation: NORTH—WEST
Name: GD (24 s.f.), U: 0.300, SHGC: 0.25, Orientation: NORTH—WEST
El Name: BSMT (16 s.f.), U: 0.300, SHGC: 0.25, Orientation: NORTH—WEST
E] Name: RIGHT (18 s.f.), U: 0.300, SHGC: 0.25, Orientation: NORTH—EAST
jl Name: LEFT BSMT (18 s.f.), U: 0.300, SHGC: 0.25, Orientation: NORTH—EAST
Skylight
None Present
Mechanical Ventilation
None Present
Mechanical Equipment
FURNACE 1 • Natural Gas • 100% Heating Load @ 92.1 AFUE
El AC 1 • Electric • 100% Cooling Load @ 13 SEER
F1 Water Heating • Natural Gas • 100% Hot Water Load @ 0.64 Energy Factor
Air Leakage Control
Test Status: Blower -door tested
House is air -sealed as to achieve 2,757 CFM50 (5.00 ACH50) or less at final blower -door test.
Infiltration Requirements for IECC in Climate Zone 5
2009 IECC Infiltration limit for the design home is 7 ACH50.
2012 IECC Infiltration limit for the design home is 3 ACH50. 3
2015 IECC Infiltration limit for the design home is 3 ACH50.
Energy Code Inspection Checklist
Property organization
122 SHOSHONE DR TSI Energy Solutions
CARMEL, IN 46032 ❑evin Sielschott
Model: CUSTOM
Community: MACKAY RESIDENCE Builder
SIGMA BUILDERS, LLC
MACKAY (AS DESIGNED)
MACKAY RESIDENCE
Duct Leakage
Duct System 1
Inspection Status
Results are projected
NOT entirely within conditioned space, testing required
Leakage to Outside specified as: 192 CFM @ 25Pa (5.841 100 s.f.)
Total Duct Leakage specified as 256.0 CFM @ 25Pa (Post -Construction)
Duct Leakage Code Requirements for IECC
2009 IECC:
Postconstruction Leakage Test: Duct Leakage to Outdoors <= 8 CFM25/ 100 sq ft CFA.
Rough in Test with AHU: Total Duct Leakage -�= 6 CFM251100 sq ft CFA.
Rough in Test without AHU: Total Duct Leakage — 4 CFM251100 sq ft CFA.
2012 IECC and 2015 IECC Prescriptive Path:
Postconstruction Leakage Test: Total Duct Leakage <= 4 CFM25 1100 sq ft CFA.
Rough in Test with AHU: Total Duct Leakage <= 4 CFM25 1100 sq ft CFA.
Rough in Test without AHU: Total Duct Leakage <= 3 CFM25 1100 sq ft CFA.
2015 Performance Path (Cost Compliance):
CTSI
Energy Solutions
Leakage testing is required UNLESS all ducts and air handlers are located entirely within the thermal envelope.
There is no pass/fail threshold for duct leakage on the performance path.
Project Notes
Building Summary
Properly
Organization
122SHOSHONEDR
TSI Energy Solutions
CARMEL. IN46032
Devin Sielschott
Model: CUSTOM
Community: MACKAY RESIDENCE
Suilder
SIGMA BUILDERS, LLC
MACKAY (AS DESIGNED)
MACKAY R ES I D E NC E
General Building Information
Number Of Bedrooms 3
Number Of Floors
1
Conditioned Floor Area [sq. ft.]
3,289
Unconditioned, attached garage?
Yes
Conditioned Volume [cu. ft.]
33,088
Total Units in Building
1
Residence Type
Single family detached
Floor Number
Model
CUSTOM
Community
MACKAY RESIDENCE
Climate Zone
5A
Inspection Status
Results are projected
C-M,
Energy Solutions
Foundation Wall
Name Library Type
CRAWLIGARAGE R-10 Draped, Full
Height Above Grade
1
Depth Below Grade
2
Perimeter
43
Location
Exposed Exterior
Enclosing
Conditioned Space
CRAWLIGARAGE R-10 Draped. Full
1
2
80
Exposed Exterior
Conditioned Space
FIN R 5 Ext, R-13 FIN G1
1
8
77
Exposed Exterior
Conditioned Space
UNFIN R-5 Ext GRADE
1
8
38
Exposed Exterior
Conditioned Space
Foundation Wall Library List
Name Feet From Wall Top To
Feet From Wall Top To
Is Fully Insulated
Continuous R-value
Cavity RWalue
Effective Insulation R-
Continuous Insulation
Continuous Insulation
value
Top
Bottom
R-10 Draped, Full N,'A
NJA
Yes
NIA
NIA
10.00
R-5 Ext GRADE as
0
No
NIA
NIA
5.00
R5 Ext, R-13 FIN G1 WA
NIA
Yes
NIA
NIA
16.275
Sla V
Name Library Type Perimeter Floor Grade Carpet R Exposed Surface Area Location Enclosing
Masonry Area
BSMT Uninsulated 115 Below Grade 0 0 1,174.0 f12 Exposed Exterior Conditioned
Space
CRAWL Uninsulated 123 Below Grade 0 0 941.0 fl' Exposed Exterior Conditioned
Space
1
Building Summary
C-M
Energy Solutions
Properly Organization Inspection Status
122SHOSHONEDR TSI Energy Solutions Results are projected
CARMEL. IN46032 Devin Sielschott
Model: CUSTOM
Community: MACKAY RESIDENCE Builder
SIGMA BUILDERS, LLC
MACKAY (AS DESIGNED)
MACKAY R ES I D E NC E
ibrary List
Name Wall Construction slab Completer Underslab Perimeter Perimeter Thermal Break Effective R-value
Type Insulated . Insulation Width [ft] Insulation Depth [ftJ Insulation R Value
Uninsulated Wood Frame? Other No ❑ 0 ❑ No ❑.0❑
Framed Floor I
Framed Floor Library List
Rim Joist
Name
CONDIAMB
CON DIGARAG E
Rim Joist Library List
Name
Wa
None Present
None Present
Library Type
G1 R-15, OSB
Surface Area
195.❑ fts
G1 R-15, OSB 43.0 fts
G" F.-1�- 11.691
Location
Exposed Exterior
Unconditioned. attached garage
Surface Area Location
CONDIAMB
G1 R-15 BATT. OSB
Medium
1,755.0 ft'
Exposed Exterior
CONDIATTIC
Gl R-15 BATT. OSB
Medium
164.0 ft'
Attic
4
Building Summary
Properly
122 SHOSHONE DR
CARMEL. IN 46032
Model : CUSTOM
Community: MACKAY RESIDENCE
MACKAY (AS DESIGNED)
MACKAY R ES I D E NC E
Name
CONDIGAR GI R-15 Gar Walls
Organization
TSI Energy Solutions
Devin Sielschott
Suilder
SIGMA BUILDERS, LLC
Library type
Wall Library List
Name Effective R-value
G1 R 15 BATT, OS 13.423
G1 R-15 Gar Walls 11.972
Glazing
C-M
Energy Solutions
Inspection Status
Results are projected
Surface Color Surface Area Location
Medium 387.0 fts Unconditioned, attached garage
Name
Librarytype Wall
Assignment
Foundation Wall Overhang
Depth Overhang
Ft To Overhand
Ft To
Orientation
Surface Area
Assignment
Tbp
ottom
BACK
U-.30, SHGG25
COND+AMB
0
0
0
Northwest
150.0 fts
BSMT
U-.30, SHGG25
UNFIN
0
0
0
Northwest
16.0 R2
FRONT
U-.30, SHGG25
COND+AMB
0
0
0
Southeast
64.0 R2
GD
U-.30, SHGC-25
COND+AMB
❑
0
0
Northwest
24.0 ftz
LEFT BSMT
U-.30, SHGC-25
UNFIN
❑
0
0
Northeast
18.0 fts
RIGHT
U-.30, SHGC-25
COND+AMB
❑
0
0
Northeast
18.0 fts
Glazing Library List
Name Shgc U-factol
U-.30, SHGC-.2�- 025 0.300
Skylight
None Present
Q
Building Summary
Properly Organization
122SHOSHONEDR TSI Energy Solutions
CARMEL. IN46032 Devin Sielschoft
Model: CUSTOM
Community: MACKAY RESIDENCE Suilder
SIGMA BUILDERS, LLC
MACKAY (AS DESIGNED)
MACKAY R ES I D E NC E
kylight Library List
None Present
Opaque Door
i
Name
FRONT Fiberglass/Steel CONDIAMB 0.9 0.75 Medium 24.0 fts Exposed Exterior
Door
GARAGE Fiberglass/Steel COND+GAR G9 0.75 Medium 24.0 fts Exposed Exterior
Door
Inspection Status
Results are projected
C-M,
Energy Solutions
Opaque Door Library List
Name Effective Ufiactor
IFiberg lasslSteel Door 0.182
Roof Insulation mrMIEW
Name Library Type Attic Exterior Area Clay or Concrete Roof
P11 Tiles
MAIN R-3BBIGwn, GR1 2,115 No
Roof Insulation Library List qq
Name Has Radiant Barrier
IR-38 Blown, GR1 Na
Surface Color Surface Area Location
Effective R-yalue
38268
Whole House Infiltration
Infiltration Measurement Type Sheller Class
5ACH at 50 Pa BIGwer--door tested 4
Medium 2,115.0 fts Attic
4
Building Summary
Properly
Organization
122SHOSHONEDR
TSI Energy Solutions
CARMEL. IN46032
Devin Sielschott
Model: CUSTOM
Cornmunity: MACKAY RESIDENCE
Suilder
SIGMA BUILDERS, LLC
MACKAY (AS DESIGNED)
MACKAY R ES I D E NC E
Mechanical Ventilation
None Present
Lightic
% Interior F
75
Onsite Generation
D
None Present
Onsite Generation Library List
None Present
Solar Generation
Solar Generation Library List
None Present
None Present
75
Inspection Status
Results are projected
0
C-M,
Energy Solutions
75
D
7
r�
Building Summary
Properly Organization Inspection Status
122SHOSHONEDR TSI Energy Solutions Results are projected
CARMEL. IN46032 Devin Sielschott
Model: CUSTOM
Community: MACKAY RESIDENCE Suilder
SIGMA BUILDERS, LLC
MACKAY (AS DESIGNED)
MACKAY R ES I D E NC E
onditioning Equipment
Name Library Type Heating Percent Load Cooling Percent Load
AC 1 CA13NA042 0% 100%
IFURNACE 1 912SA6012OS24 100% 0%
IWater Heating RG1 PV50S'N 0% 0%
1
Equipment Type: 912SA6012OS24
Fuel Type
Natural Gas
Distribution Type
Forced Air
Motor Type
PSG (Single Speed)
Heating Efficiency
92.1 AFUE
Heating Capacity [kBtulh]
112
Use default EAE
No
EAE [kWh]
1,247
Equipment Type: CA13NA042
Fuel Type
Electric
Distribution Type
Forced Air
Motor Type
PSG (Single Speed)
Cooling Efficiency
13 SEER
Cooling Capacity [kBtulh]
40
Equipment Type: RG1 PV50S*N
Fuel Type
Natural Gas
Distribution Type
Hydronic Delivery
Hot Water Efficiency
0.64 Energy Factor
Tank Capacity (gal-)
50
Hot Water Capacity [kBtulh]
40
Recovery Efficiency
0.80
C-M,
Energy Solutions
Percent Load
❑%
❑%
100 %
Locanan
Conditioned Space
Conditioned Space
Conditioned Space
Building Summary
Properly
122 SHOSHONE DR
CARMEL. IN 46032
Model: CUSTOM
Community: MACKAY RESIDENCE
MACKAY (AS DESIGNED)
MACKAY R ES I D E NC E
stributivn System
Distribution Type
Heating Equipment
Cooling Equipment
Sq. Feet Served
# Return Grilles
Supply Duct R Value
Return Duct R Value
Supply Duct Area [ftJ
Return Duct Area [ft2]
Lea kageto Outdoors
Total Leakage
Total Leakage Duct Test Conditions
Use Default Flaw Rate
Duct 1
Duct Location
Percent Supply Area
Percent Return Area
Duct 2
Duct Location
Percent Supply Area
Percent Return Area
Duct 3
Duct Location
Percent Supply Area
Percent Return Area
Duct 4
Duct Location
Percent Supply Area
Percent Return Area
Duct 5
Duct Location
Percent Supply Area
Percent Return Area
Duct 6
Duct Location
Percent Supply Area
Percent Return Area
Ceiling Fan
Has Ceiling Fan
Cfm Per Watt
Organization
TSI Energy Solutions
Devin Sielschol
Suilder
SIGMA BUILDERS, LLC
Forced Air
FURNACE 1
AC 1
3280
3
6
6
888.03
493.35
192 CFM @ 25Pa (5.841 100 s-t)
256
Post -Construction
Yes
Conditioned Space
5❑
50
Attic (well vented, under insulation)
5❑
5❑
Conditioned Space
0
Conditioned Space
Conditioned Space
0
Conditioned Space
0
No
1❑❑
Inspection Status
Results are projected
C-M,
Energy Solutions
7
Building Summary
Properly
122 SHOSHONE DR
CARMEL. IN 46032
Model: CUSTOM
Community: MACKAY RESIDENCE
MACKAY (AS DESIGNED)
MACKAY R ES I D E NC E
Water Fixture Type
Use Default Hot Water Pipe Length
Hot Water Pipe Length [ft]
At Least R3 Pipe Insulation?
Hot Water Recirculation System?
Recirculation System Pipe Loop Length [ft]
Drain Water Heat Recovery?
Clothes Dryer
Fuel Type
Cef
Field Utilization
Clothes Washer
Label Energy Rating
Electric Rate
Annual Gas Cost
Gas Rate
Capacity
I met
Appliances and Controls
Programmable thermostat?
Dishwasher Size
Dishwasher Efficiency
Range/Oven Fuel
Convection Oven?
Induction Range?
Refrigerator Consumption
Organization
TSI Energy Solutions
Devin Sielschol
Suilder
SIGMA BUILDERS, LLC
Standard
No
60
No
No
34
No
Electric
2.617
Timer Controls
704 kWh/Year
$0-081kWh
$23.00
$0-581Therm
2.874
❑.33053
Yes
Standard
270 kWh
Electric
No
No
715 kWh/Year
Inspection Status
Results are projected
C-M,
Energy Solutions