HomeMy WebLinkAboutE000 ELECTRICAL COVERSHEETELECTRICAL SYMBOL LIST
SYMBOL:
TAG:
SPEC E TI N:
DESCRIPTION:
GB
GB
260526
GROUND BUS
IBT
IBT
260526
INTERSYSTEM BONDING TERMINATION
E
E
ECONN
260533
ELECTRICAL CONNECTION
J
JB
260533
JUNCTION BOX
®
FB-1
262726
FLOOR BOX- DUPLEX RECEPTACLE
so
FB-2
262726
FLOOR BOX- DUAL COMPARTMENT
NMI
FB-3
262726
FLOOR BOX - MULTISERVICE
®BV
FB4
262726
FLOOR -SERVICE FITTING
®RI
RI -TECH
260533
TECHNOLOGY ROUGH -IN
RI
v
RI-TECH-W
260533
TECHNOLOGY ROUGH -IN, MOUNTED+54"AFF
WM-#
260535
MULTI OUTLET SYSTEM
®
WW-#
260535
ELECTRICAL WIREWAY wI DEVICES SHOWN
PB
PB
260916
MOMENTARY PUSHBUTTON OPERATOR
a
PANEL'###'
262416
PANELBOARD- RECESS MOUNT
0
PANEL'###'
262416
PANELBOARD- SURFACE MOUNT
01
MX4NMS-#/FCS-#
262419
MANUAL SWITCH/STARTER/COMBINATION
STARTER
®
TR-#
262200
TRANSFORMER
01
BCS-#
262500
BUSS PLUG- COMBINATION STARTER
0
BP-#
262500
BUSS PLUG -CIRCUIT BREAKER
�I
BFP-#
262500
BUSS PLUG- FUSIBLE DISCONNECT
RECREC=DUP
262726
DUPLEX RECEPTACLE, 125V
REC-DUP-GFI
262726
DUPLEX GFI RECEPTACLE, 125V
REC-DUP-PED
260533
RECEPTACLE -PEDESTAL STYLE
Wag
REC-DUP-WP
262726
DUPLEX GFI WEATHERPROOF RECEPTACLE 125V
U�
REC-USB
262726
DUPLEX RECEPTACLE, USB CHARGING
Q
RECSIM-52OR
262726
SIMPLEX RECEPTACLE, 12W
♦
RECSIM-53OR
262726
RECEPTACLE, 125V
RECSIM-62OR
262726
RECEPTACLE, 6-20R, 25W
RECSIM-63OR
262726
RECEPTACLE, 6-30R, 25W
im
RECSIM-65OR
262726
RECEPTACLE, 6-50R, 25W
RECSIM-72OR
262726
RECEPTACLE, 7-20R, 277V
RECSIM-73OR
262726
RECEPTACLE, 7-30R, 277V
so
RECSIM-75OR
262726
RECEPTACLE, 7-50R, 277V
REC-SIM-142OR
262726
RECEPTACLE, 14-20R, 1251250V
REC-SIM-143OR
262726
RECEPTACLE, 14-30R, 125/25W
REC-SIM-145OR
3111,
262726
RECEPTACLE, 14-50R, 125/25W
REC-SIM-146OR
=40
262726
RECEPTACLE, 14-60R, 125/25W
REC-SIM-152OR
-18
262726
RECEPTACLE, 15-20R, 2501 3PH
REC-SIM-153OR
=@
262726
RECEPTACLE, 15-30R, 2501 3PH
REC-SIM-155OR
am
262726
RECEPTACLE, 15-50R, 25OV, 3PH
REC-SIM-156OR
-0I
262726
RECEPTACLE, 15-60R, 25OV, 3PH
61
REC-SIM-L52OR
262726
RECEPTACLE, LOCKING TYPE, LS-20R, 125V
_16)I
REC-SIM-L53OR
262726
RECEPTACLE, LOCKING TYPE, LS-30R, 125V
-Ell
REC-SIM-L62OR
262726
RECEPTACLE, LOCKING L6-20R, 250V
_ffiI
REC-SIM-L63OR
262726
RECEPTACLE, LOCKING L6-30R, 250V
-9I
REC-SIM-L72OR
262726
RECEPTACLE, LOCKING L7-20R, 277V
♦1
REC-SIM-L73OR
262726
RECEPTACLE, LOCKING L7-30R, 277V
61
RECSI
262726
RECEPTACLE, LOCKING L14-20R, 1251250V
REC-SIM-L143OR
�I
262726
RECEPTACLE, LOCKING L14-30R, 125/250V
RECREC-SI�
�I
262726
RECEPTACLE, LOCKING L15-20R, 25OV, 3PH
RECREC-SI�
262726
RECEPTACLE, LOCKING L15-30R, 250V, 3PH
RECSI
9*I
262726
RECEPTACLE, L16-30R, 48OV, 3PH
RECSI
-DI
262726
RECEPTACLE, LOCKING L21-20R, 120/208V, 3PH
RECSIM-L213OR
�I
262726
RECEPTACLE, LOCKING L21-30R, 120/208V, 3PH
REC-QUAD
262726
QUAD RECEPTACLE, 12W
ap
REC-QUAD-GFI
262726
QUAD GFI RECEPTACLE, 125V
REC-QUAD-USB
26 27 26
QUAD RECEPTACLE, USB 125V
U*
WaN
REC-0UAD-WP
262726
QUAD GFIWEATHERPROOF RECEPTACLE, 125V
REC-PEDQUAD
260533
RECEPTACLE - PEDESTALSTYLE
REC-FB-#
®
262726
FLOOR BOX - POKE THRU, 125V
#
REC-PP#
262723
POWER POLE
ELECTRICAL EQUIPMENT TAGS
TAG:
DESCRIPTION:
RELATED
SPECIFICATION
BCS-#
BUS PLUG COMBINATION STARTER
262500
BFP-#
BUS PLUG FUSIBLE DISCONNECT
262500
BP-#
BUS PLUG CIRCUIT BREAKER
262500
C=#
GENERAL PURPOSE CONTACTOR
262821
CB-#
CIRCUIT BREAKER, REFER TO DISCONNECT AND STARTER SCHEDULE
261419
CT-#
CABLE TRAY
26 05 36
DP-#
DISTRIBUTION PANEL
262416
DS-#
DISCONNECT SWITCH, REFER TO DISCONNECT AND
262816
STARTER SCHEDULE
DTR-#
TRANSFORMER- DISTRIBUTION TYPE
261219
261213
261221
F#
LUMINAIRE TYPE
265100
FAA-#
FIRE ALARM - ANNUNCIATOR
283100
FAP#
FIRE ALARM -CONTROL PANEL
283100
FB-#
FLOOR BOX
262726
FDS-#
FUSIBLE DISCONNECT SWITCH, REFER TO DISCONNECT AND
262816
STARTER SCHEDULE
LC#
LIGHTING CONTACTOR, REFER TO CONTACTOR SCHEDULE
262831
MS#
MANUAL STARTER, REFER TO DISCONNECT AND STARTER SCHEDULE
262419
MX-#
MANUAL SWITCH, REFER TO DISCONNECTAND STARTER SCHEDULE
262419
NEP-#
FIRE ALARM -EXTENDER PANEL
283100
PP#
POWER POLE
262723
R#
RELAY
260939
REC-#
RECEPTACLE -SPECIAL USE
262726
TC#
TIME SWITCH
260933
TRITE!
TRANSFORMER - DRYTYPE, REFER TO TRANSFORMER SCHEDULE
262200
UPS-#
UNINTERRUPTIBLE POWER SUPPLY
263353
VFD-#
VARIABLE FREQUENCY DRIVE- REFER TO VFD SCHEDULE
262923
WW-#
WIREWAY
260535
RELEASED FOR CONSTRUCTION
Subject to compliance with all regulations
of State and Local Codes
City of Carmel
ELECTRICAL SYMBOL LIST
SYMBOL:
TAG:
SPEC
DESCRIPTION:
SECTION:
S
SW-iP
260933
SWITCH -SINGLE POLE
ST
SW-IP-ADJ
260933
SWITCH - LOCALTIMER- USERADJUSTABLE
SM
SW-1P-M
260933
SWITCH- MOMENTARY CONTACT
S2
SW-2P
260933
SWITCH - TWO POLE
S3
SWSW3W
260933
SWITCH -THREE WAY
S4
SW4W
260933
SWITCH - FOUR WAY
O
SW-D-LED
260933
DIMMER -LED
D3
SW-D3-LED
260933
DIMMER - LED -3-WAV
DO
SWSWOD
260933
DIMMER- WALL DIMMER OCCUPANCY SENSOR
LS
SW-LS
260933
DAYLIGHT LEVEL SENSOR
LS
SW-LS-3Z
260933
DAYLIGHT LEVEL SENSOR-3 ZONE
3
LS
SW-LS-D
260933
DAYLIGHT LEVEL SENSOR-1 ZONE DIMMING
0
LS
SW-LS-D-3Z
260933
DAYLIGHT LEVEL SENSOR-3 ZONE DIMMING
30
QD
SW-OC-D
260933
OCCUPANCY SENSOR - DUAL TECHNOLOGY
OC
SW-OC-D-W
260933
OCCUPANCY SENSOR - DUAL
D
TECHNOLOGY -WALL MOUNTED
SO
SW-OC-P-O
260933
SWITCH- OCCUPANCY SENSOR WALL SWITCH
S02
SW-OC-P-02
260933
SWITCH- OCCUPANCY SENSOR AND DUAL
SWITCH
SW
SW
260933
WALL CONTROL STATION
#B
SW-DCS
260933
DIMMER CONTROL STATION
LCS
SW-LCS
260933
DIMMER CONTROL STATION WITH FADERS
O
CB-#
262816
CIRCUIT BREAKER - SURFACE MOUNTED
II
CB-#
262816
CIRCUIT BREAKER - FLUSH MOUNTED
DS-#
F#
262816
265100
DISCONNECT
LINEAR LUMINAIRES
0
F#
265100
TROFFER
F#
265100
WALL SCONCE LUMINAIRE
O
F#
265100
DOWNLIGHTLUMINAIRE
<O
F#
2651 00
AIMABLE OR WALL WASH LUMINAIRE
F#
265100
INDUSTRIAL LUMINAIRE
11
F#
265100
WALL BRACKET LUMINAIRE
®
X#
265100
SINGLE FACE EXIT SIGN
®
X#
265100
DOUBLE FACE EXIT SIGN
ELECTRICAL SYMBOL LIST
SYMBOL:
TAG:
SPEC
DESCRIPTION:
p
FAFA100
283100
FIRE ALARM CONTROL PANEL
SD
FA120
283100
FIRE ALARM SMOKE DETECTOR - CEILING
MOUNTED
SD
FA122
283100
FIRE ALARM DUCT SMOKE DETECTOR
0
FA l30
2831 00
FIRE ALARM MANUAL PULL STATION
OFA140
2831 00
FIRE ALARM HEAT DETECTOR
MM
FA160
283100
FIRE ALARM ADDRESSABLE MONITOR MODULE
AR
FA161
283100
FIRE ALARM ADDRESSABLE RELAY
Vi V3
VS
al
FA200
283100
FIRE ALARM VISUAL NOTIFICATION
V7 VH
DEVICE - WALL MOUNTED
V3,
WeVi
V7 VH
FA=201
283100
FIRE ALARM VISUAL NOTIFICATION
DEVICE - CEILING MOUNTED
AQ
FA=210
283100
FIRE ALARM AUDIO NOTIFICATION DEVICE -
WALL MOUNTED
Al A3
FA211
283100
FIRE ALARM AUDIO/VISUAL NOTIFICATION
A7 AH
DEVICE - WALL MOUNTED
AS
AO
FA230
283100
FIRE ALARM AUDIO NOTIFICATION
DEVICE - CEILING MOUNTED
Ai A3
FA231
283100
FIRE ALARM AUDIO/VISUAL NOTIFICATION
mAS
AT AH
DEVICE - CEILING MOUNTED
RI
FA241
283100
FIRE ALARM REMOTE INDICATOR
FS
FAFA=260
2831 00
FIRE ALARM FLOW SWITCH TO MONITOR FIRE
PROTECTION SYSTEM
es
FAFA261
283100
FIRE ALARM MONITOR SWITCH TO
MONITOR FIRE PROTECTION SYSTEM
DH
FA270
283100
FIRE ALARM ELECTROMAGNETIC DOOR
HOLD DEVICE
HD
HD
ARCH
HAND DRYER
pp
PP
ARCH
PUSH PAD
THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, LIGHTING, POWER, AND SYSTEMS.
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD
SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND
REPORT ANY CONFLICTS BEFORE PROCEEDING.
2. NOT ALL EXISTING EQUIPMENT LUMINAIRES AND CONDUITARE SHOWN. VERIFY EXISTING
CONDITIONS AND REPORT ANY CONFLICTS WITH NEW WORK BEFORE STARTING WORK.
3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR CABLE TRAY, BUSWAYAND CONDUITS
BEFORE FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING
FIELD CONDITIONS.
4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF HISHER WORK
AND SHALL NOTIFY THE GENERAL CONTRACTOR PRIOR TO BIDDING IF OTHER UTILITIES ARE
REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO HISIHER AREA OF
WORK.
5. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR CUTTING, REMOVAL AND PATCHING OF
ROOFS, WALLS, AND FLOORS ASSOCIATED WITH WORK BY ALL CONTRACTORS.
CONTRACTORS SHALL NOTIFY THE GC OF AFFECTED AREAS PRIOR TO BIDDING.
6. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF
CEILINGS, CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL
CONTRACTORS. NOTIFY THE GENERAL CONTRACTOR OF AFFECTED AREAS PRIOR TO
BIDDING.
7. WHERE EXISTING ELECTRICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT W ITH NEW
EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER
ARRANGE NEW EQUIPMENT, CONDUIT, OR DUCTWORK IN SUCH A FASHION THAT IT DOES
NOT CONFLICT W ITH EXISTING SYSTEMS, OR REWORK EXISTING ELECTRICAL SYSTEMS TO
ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
ELECTRICAL ABBREVIATION KEY
ABBR:
DESCRIPTION:
AFF
ABOVE FINISHED FLOOR
C
CONDUIT
GFI
GROUND FAULT INTERRUPTER
N.C.
NORMALLYCLOSED
NIC
NOT IN CONTRACT
N.O.
NORMALLY OPEN
SV
SOLENOID VALVE
TYP
TYPICAL
UNO
UNLESS NOTED OTHERWISE
LUMINAIRE
SYMBOL
KEY
SYMBOL:
DESCRIPTION:
0
NORMAL BRANCH LUMINAIRE
® ®
EMERGENCY LIFE SAFETY BRANCH LUMINAIRE
UNSW ITCHED FOR NIGHT LIGHT, UNLESS NOTED'SE'
VIEW KEY
NAME LEVEL NAME C VINDICATES NOTE USED TO DESCRIBE
V 10'-0"HEIGHT ABOVE ADDITIONAL INFORMATION ABOUT
PROJECTO'-O" WORK REQUIRED, SPECIFICTOTHE
SHEET AND/OR DETAIL
INDICATES DIRECTION OF TRUE NORTH
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
" VI W NAME
PLAN OR DETAIL SCALE
NORS�
INDICATES SIMILAR DETAIL
SIM
REFERENCED IN MULTIPLE LOCATIONS
DETAIL REFERRED TO BY SECTION CUT
1
M101 SHEET DETAIL IS LOCATED ON
INDICATES SIMILAR DETAIL
Sim
REFERENCED IN MULTIPLE LOCATIONS
DETAIL REFERRED TO BY ELEVATION
4
S Tloi� SHEET DETAIL IS LOCATED ON
LINE TYPE KEY:
NEW WORK BY THIS CONTRACTOR
(DARK SOLID LINE)
— — — NEW WORK UNDERFLOOR OR UNDERGROUND BY THIS CONTRACTOR
(DARK LONG DASHED LINE)
NEW WORK BY OTHERS AND/OR EXISTING TO REMAIN
(LIGHT SOLID LINE) — — — — — — —
EXISTING TO BE REMOVED BY THIS CONTRACTOR
(DARK SHORT DASHED LINE)
ELECTRICAL GENERAL NOTES:
1. ###W# INDICATES ELECTRICAL EQUIPMENT DEFINED IN ELECTRICAL SCHEDULES OR
SPECIFICATION. REFER TO DRAWINGS CONTAINING ELECTRICAL SCHEDULES. PERMANENT
NAMEPLATE SHALL MATCH FINAL EQUIPMENT NOMENCLATURE, NOT ELECTRICAL
EQUIPMENT TAG NAME, REFER TO SPECIFICATIONS.
2. "NL" INDICATES LUMINAIRE IS UNSW ITCHED FOR NIGHT LIGHT.
3. "SE" INDICATES LUMINAIRE IS SWITCHED/CONTROLLED DURING NORMAL OPERATION AND
OPERATES FROM EMERGENCY CIRCUIT UPON LOSS OF POWER.
4. SHADED LUMINAIRE OR DEVICE INDICATES LUMINAIRE OR DEVICE IS CONNECTED TO AN
EMERGENCY CIRCUIT.
LUMINAIRE KEY:
F1 = FIXTURE TAG
1 -CIRCUIT NUMBER
LUMINAIRE a= SWITCH DESIGNATION
NL= SUBSCRIPT (IF APPLICABLE)
'IF LABEL IS ORIENTED HORIZONTALLYA SLASH WILL SEPARATE THIS
INFORMATION. EX: F1 111 a I NL
DEVICE KEY:
DEVICE1r A= MOUNTING (IF APPLICABLE)
1 = CIRCUIT NUMBER
'IF LABEL IS ORIENTED HORIZONTALLYA SLASH WILL SEPARATE THIS
INFORMATION. EX: A / 1
ELECTRICAL MOUNTING SUBSCRIPT KEY
A MOUNT AT+6" TO CENTERLINE ABOVE COUNTER OR BACKSPLASH
C MOUNTATCEILING
H MOUNT ORIENTED HORIZONTALLY
L MOUNT IN CASEWORK
M MOUNT IN MODULAR FURNITURE
R MOUNT IN SURFACE RACEWAY
4RXet1014 101il&tf_l4W_AiMilIil101*3
1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE ADA STANDARDS FOR
ACCESSIBLE DESIGN. REFER TO THE ADA GUIDELINES FOR ALL CONFIGURATION DETAILS
ON THIS PAGE FOR ADDITIONAL INFORMATION.
2. CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT IDENTIFICATION. CIRCUITING SHALL AGREE
WITH NUMBERING ON THE PANEL PROVIDED. COMMON NEUTRALS MAY NOT BE USED FOR
BRANCH CIRCUITS. BALANCE THE LOAD ON PANELAS EVENLY AS POSSIBLE BETWEEN
EACH PHASE.
3. CIRCUITS SERVING EMERGENCYAND EXIT LUMINAIRES WILL BE RUN IN A SEPARATE
RACEWAY FROM ALL OTHER CIRCUITS.
4. FLUSH MOUNTALL LIGHTING CONTROL DEVICES AT+46" FROM FLOOR(CENTERLINE
DIMENSION), EXCEPT WHERE OTHERWISE NOTED. DEVICES MAY BE SURFACE MOUNTED
WHEN CONDUIT IS SPECIFIED EXPOSED.
5. FLUSH MOUNTALL DUPLEX RECEPTACLES AND TECHNOLOGY OUTLETS AT+18" FROM
FLOOR(CENTERUNE DIMENSION), EXCEPT WHERE OTHERWISE NOTED. RECEPTACLES AND
OUTLETS MAY BE SURFACE MOUNTED WHEN CONDUIT IS SPECIFIED EXPOSED.
6. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALL
BE TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OF
THROUGH -PENETRATION FIRESTOPS.
7. CONNECTION FOR ELECTRIC WATER COOLERS (EWC) SHALL BE A JUNCTION BOX
CONCEALED BEHIND WATER COOLERACCESS PLATE OR BE A GFI RECEPTACLE LOCATED
DIRECTLY BELOW AND CENTERED ON EWC. CONTRACTOR SHALL VERIFY TYPE OF EWC TO
BE INSTALLED.
8. MOUNT ALL FIRE ALARM PULL STATIONS AT+42" FROM FLOOR(CENTERLINE DIMENSION)
EXCEPT WHERE OTHERWISE NOTED.
9. INSTALL ALL WALL MOUNTED FIRE ALARM NOTIFICATION DEVICES AT 90" ABOVE FINISHED
FLOOR OR 6" BELOW THE CEILING, WHICHEVER IS LOWER, EXCEPT WHERE OTHERWISE
NOTED. HEIGHT SHALL BE MEASURED TO THE TOP OF THE DEVICE.
10. CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL CEILING MOUNTED DEVICES AND
EQUIPMENT W ITH LUMINAIRES, SPRINKLER, AND CEILING DIFFUSERS. CENTER ALL DEVICES
IN CEILING TILE PATTERN. SMOKE DETECTORS AND OCCUPANCYNACANCY SENSORS
SHALL BE LOCATED NO CLOSER THAN 3 FEET TO AN AIR SUPPLY DIFFUSER OR RETURN
GRILLE.
11. CONTRACTOR SHALL VERIFY ALL FURNITURE, MODULAR FURNITURE, AND EQUIPMENT
LOCATIONS WITH ARCHITECTURAL PLANS, ELEVATIONS, AND REVIEWED SHOP DRAWINGS.
PRIOR TO MAKING THE ACTUAL ELECTRICAL INSTALLATION, THIS CONTRACTOR SHALL
ADJUST RECEPTACLES, OUTLETS, OR CONNECTION LOCATIONS TO ACCOMMODATE
FURNITURE AND/OR EQUIPMENT.
12. ELECTRICAL AND TECHNOLOGY EQUIPMENT SHALL BE MOUNTED TO AVOID IMPEDANCE OF,
OPERATION OF, AND/OR ACCESS TO ELECTRICAL AND MECHANICAL EQUIPMENT. ALL
MOUNTING OF ELECTRICAL AND TELECOMMUNICATIONS EQUIPMENT, ON EQUIPMENT
SUPPLIED BY ANOTHER CONTRACTOR, SHALL BE APPROVED IN ADVANCE BY THE OTHER
CONTRACTOR.
13. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OPENINGS REQUIRED IN WALLS. ALL
OPENINGS SHALL BE REPAIRED TO MATCH EXISTING BY A QUALIFIED CONTRACTOR AT THE
EXPENSE OF THIS CONTRACTOR. ALL CONDUITS THROUGH WALLS SHALL BE GROUTED OR
SEALED INTO OPENINGS.
14. ALL W ELDING SHALL BE ACCORDING TO AMERICAN WELDING SOCIETY STANDARDS.
CONTRACTOR SHALL FURNISH TO THE ARCHITECT/ENGINEER CERTIFICATES QUALIFYING
EACH WELDER, PRIOR TO START OF WORK. THE ARCHITECT/ENGINEER RESERVES THE
RIGHT TO REQUIRE QUALIFYING DEMONSTRATION, AT THE CONTRACTOR'S EXPENSE, OF
ANY WELDERS ASSIGNED TO THE JOB.
15. CONTRACTOR SHALL REMOVE AND REINSTALL ALL CEILING TILES AS REQUIRED FOR THE
EXECUTION OF ELECTRICAL WORK. CONTRACTOR SHALL REPLACE CEILING TILES WITH
IDENTICAL MATERIAL WHERE DAMAGED BY THIS CONTRACTOR.
16. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY
AUDIONISUAL, AND OTHER ELECTRICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING
MOUNTED DEVICES, OTHER THAN SPRINKLERS.
NMEGMEG CORIP RESERVES FROPMEETARY TER
DRAWINGAND THE DATA SHMN RE
THE EAC-USIVE PROPERT`( OF NEED REPRODUCED MR ANYOTHER PROJECT �=��:� UDING DRAWING ANIALL NOT BE THE EAPRESS �°COMP
n
OAMERICAN
M■ STRUCTUREPOINT
INC
7260 smeelane Srman I Imlanapom, Indiana M236
TEL 317.M7.MM I RUX317.343.0270
wxw.WumnspoimspFl
*IMEG
8900 KEYSTONE XING PH: 317.848.5045
SUITE 210 FAX 317.844.2201
INDIANAPOLIS, IN www.imegeorp.com
46240
GEICO CORPORATE
FIRST FLOOR
RENOVATION PHASE 3
101 W. 103RD ST.
INDIANAPOLIS, IN 46290
4 No. °
11400159
STATE OF
nnm�ooc(o//o066/ 114/n/ 19
6l
Alin 1
ISSUANCE INDEX
DATE:
06114119
PROJECT PHASE:
CONSTRUCTION DOCUMENTS
PHASE 3
REVISION SCHEDULE
NO. DESCRIPTION DATE
Project Number 18002480.01
ELECTRICAL
COVERSHEET
DATE: 09/24/19
E000