PANEL CIRCUIT LEGEND
NW4 = RiNW4
NW5=RiNWS
E1 = E1NW-1
SHEET GENERAL NOTES:
A. REFERTO SHEETEOOO FOR ELECTRICAL
SYMBOLS, ABBREVIATIONS AND NOTES.
B. COORDINATE MOUNTING HEIGHTS OF ALL
DEVICES WITH EQUIPMENT PRIOR TO ROUGH -
IN.
KEYNOTES:
1. CONNECT TO EXISTING 20A-3P BREAKER IN
EXISTING PANEL P1SW-1 LOCATED IN
SOUTHWEST ELECTRICAL ROOM. REFER TO
SHEET E401.A FOR PANEL LOCATION.
2. CONNECT TO CONTROL BOX. CONTROL BOX
FURNISHED BY OTHERS; INSTALLED BY
ELECTRICAL CONTRACTOR. PROVIDE
CONNECTION FROM CONTROL BOX TO
DISPOSER AND SOLENOID VALVE.
3. CUT CONCRETE FLOOR AND ROUTE CONDUIT
TO NEAREST WALL AND UP TO ABOVE CEILING.
PATCH FLOOR. COORDINATE LOCATION OF
DEVICE WITH KITCHEN EQUIPMENT.
4. FEED PANEL FROM 40OA DISCONNECT ON
EXISTING BUS DUCT IN ELECTRICAL ROOM 114
WITH 4#500KCM, 1#3G, 4" CONDUIT. REFER TO
SHEET E401.A FOR BUS DUCT LOCATION.
5. FEED PANEL FROM EXISTING 150A
DISCONNECT ON EXISTING BUS DUCT IN
ELECTRICAL ROOM 114 WITH 4#1/0, 1#6, 2"
CONDUIT. REFER TO SHEET E401.A FOR BUS
DUCT LOCATION.
6. OVERHEAD SECURITY GRILLE. COORDINATE
LOCATION OF MOTOR PRIOR TO ROUGH -IN.
7. MOUNT DISCONNECT NEAR MOTOR FOR
OVERHEAD SECURITY GRILLE.
8. 3-POSITION SWITCH FURNISHED WITH
SECURITY GRILLE, INSTALLED BY ELECTRICAL
CONTRACTOR.
9. EFER TO CAPTIVEAIRE DRAWINGS FOR
ADDITIONAL INSTRUCTIONS AND
REQUIREMENTS OF EXHAUST FAN AND MUA
CONNECTIONS AND CONTROLS WITH HOOD.
*I M EG � KEYSTONE XIING SUITE INDIMMOUS, IN Zia
'RG "gNwiI pfiva4l'a
GEICO
so
O
EI?OAN
®■
STRUCTUREPOINT
7260 SM1adeland Smtion I Intllanapolis, Indiana M256
TEL 317.547.5560 1 FU31].543.02]0
www.an ctumpoim.00m
8900 KEYSTONE XING PH: 317.848.5045
SUITE 210 FAX 317.844.2201
INDIANAPOLIS, IN www.imegeorp.com
46240
GEICO CORPORATE
FIRST FLOOR
RENOVATION PHASE 3
101 W. 103RD ST.
INDIANAPOLIS, IN 46290
No.
11400159
STATE OF
066/1144/19
D BY
ISSUANCEINDEX
DATE:
06/14/19
PROJECT PHASE:
CONSTRUCTION DOCUMENTS
PHASE 3
REVISION SCHEDULE
NO. I DESCRIPTION I DATE
Project Number 18002480.01
ENLARGED KITCHEN
POWER PLAN
DATE: 09/24/19
LIED CVRIP RESERVES FROFAIEfARY RIGHTS. INCLUDING CCVYRIGHTS. TO THIS
DRAWING AND THE DATA SHOWN TIERI SAID DRAWING PNddi DATA ME
THE IXCLUSNE PRWERTY GF MEG CO RP AND $HALL NOT 6E USED OR
REPRODUCED FOR MY OTHER PROJECT WITHOUT THE E%PRESS WRITTEN
PPRII AND PARTCPATION Of II.EG CORP. 020I811 EGCORP.
REFERENCE SCALE IN INCHES
E601